Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
NECA 305–2001
Standard for
Fire Alarm System
Job Practices
Published by
National Electrical Contractors Association
An American National Standard
NECA 305–2001
Standard for
Fire Alarm System
Job Practices
TM
Published by
National Electrical
Contractors Association
Foreword . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .v
1. Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
1.1 Fire Alarm System Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
2. Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
iii ■
NECA 305 Standard for Fire Alarm System Job Practices
■ iv
(This foreword is not a part of the standard)
Foreword
National Electrical Installation Standards™ are struction. It is the responsibility of users of this stan-
designed to improve communication among speci- dard to comply with state and local electrical codes
fiers, purchasers, and suppliers of electrical construc- when installing electrical products and systems.
tion services. They define a minimum baseline of
quality and workmanship for installing electrical Suggestions for revisions and improvements to this
products and systems. NEIS™ are intended to be ref- standard are welcome. They should be addressed to:
erenced in contract documents for electrical con-
struction projects. The following language is recom- NECA Codes and Standards
mended: 3 Bethesda Metro Center Suite 1100
Bethesda, MD 20814
Fire alarm systems shall be installed, tested and (301) 215-4521 telephone
maintained in accordance with the requirements (301) 215-4500 fax
of NECA 305-2001, Standard for Fire Alarm brooke@necanet.org
System Job Practices (ANSI).
To purchase National Electrical Installation
Standards™, contact the NECA Order Desk at
™
Use of NEIS is voluntary, and the National Electrical
(301) 215-4504 tel, (301) 215-4500 fax, or
Contractors Association assumes no obligation or lia-
orderdesk@necanet.org.
bility to users of this publication. Existence of a stan-
dard shall not preclude any member or non-member
Copyright© 2001, National Electrical Contractors
of NECA from specifying or using alternate con-
Association. All rights reserved. Unauthorized repro-
struction methods permitted by applicable regula-
duction prohibited.
tions.
National Electrical Installation Standards and NEIS are
Everything in this publication is intended to comply trademarks of the National Electrical Contractors
with the editions of the National Fire Alarm Code® Association. National Fire Alarm Code, National Electrical
and the National Electrical Code® (NEC) in effect at Code and NEC are registered trademarks of the National
the time of publication. NEIS™ are not intended to Fire Protection Association, Quincy, Massachusetts.
duplicate the safety requirements of these codes or to
establish regulatory requirements for electrical con- Cover image courtesy of Simplex Grinnell.
v ■
<This page intentionally left blank>
1. Scope
This standard describes fire alarm system job prac- A fire alarm system monitors field wiring and key
tices for installing, testing, and maintaining fire system components for operational readiness. In a
alarm systems. These job practices represent a mini- typical electrical system, a broken wire goes unno-
mum level of quality for fire alarm system installa- ticed until a switch is turned on or a thermostat calls
tions. This standard is intended to define what is for heat or cooling. The fire alarm system monitors
meant by installing equipment in a “neat and work- for broken wires, shorted wires, grounded wires, and
manlike manner” as required by the National failure of key components. Each of these faults gener-
Electrical Code, Article 760. ates a visible and audible trouble signal. The required
fire alarm system functionality makes proper installa-
All information in this publication is intended to tion of the field wiring critical to the successful com-
comply with the following standards. Installers pletion and operation of the system.
should always follow the National Fire Alarm Code,
NFPA 72; the National Electric Code (NEC), NFPA Fire alarm systems interconnect with other systems
70; applicable state and local codes; and manufactur- for the purpose of providing control signals during a
ers’ instructions when installing fire alarm equipment fire emergency. It is sometimes difficult to determine
and systems. where the fire alarm system stops and other systems
start. If a fire alarm system powers the “other sys-
1.1 Fire Alarm System Overview tem,” the “other system” is part of the fire alarm sys-
tem. Example: A fire alarm system can power a
The NFPA definition of a fire alarm system is: “A sys- smoke control system making it part of the fire alarm
tem or portion of a system consisting of components system. Or, a fire alarm system can provide signals
and circuits arranged to monitor and annunciate the (e.g., relay contacts) to a separately listed smoke con-
status of fire alarm or supervisory signal initiating trol system, which is not part of the fire alarm sys-
devices and to initiate appropriate response to those tem. The following paragraph from the NEC pro-
signals.” In order to meet the intent of the definition, vides guidance.
all fire alarm system installations must conform to
National Fire Alarm Code, NFPA 72 requirements. “760-1. Scope
All system components must be listed for use in a fire This article covers the installation of wiring and equip-
alarm system. Additionally, the system must meet ment of fire alarm systems including all circuits con-
local codes and be approved by the authority having trolled and powered by the fire alarm system.
jurisdiction(s). FPN No. 1: Fire alarm systems include fire detection
and alarm notification, guard’s tour, sprinkler water-
Simply put, a fire alarm system detects fire condi- flow, and sprinkler supervisory systems. Circuits con-
tions, notifies building occupants and emergency trolled and powered by the fire alarm system include
response personnel, and provides control functions circuits for the control of building systems safety func-
(elevators, fans, dampers, etc.). However, there is a tions, elevator capture, elevator shutdown, door release,
major difference between fire alarm systems and smoke doors and damper control, fire doors and
most other electrical systems. damper control and fan shutdown, but only where
these circuits are powered by and controlled by the fire
1 ■
NECA 305 Standard for Fire Alarm System Job Practices
Reference Table 1: Fire Alarm Chapter Assignments, 1999 NFPA vs. 1993 & 1994 NFPA
■ 2
2. Definitions
Alarm Signal A signal indicating an emer- Average Ambient The root mean square, A-
gency that requires immediate Sound Level weighted, sound pressure level
action, such as a signal indica- measured over a 24-hour
tive of fire. period.
Alarm Verification A feature of automatic fire Central Station A system or group of systems
Feature detection and alarm systems to Fire Alarm System in which the operations of cir-
reduce unwanted alarms cuits and devices are transmit-
wherein smoke detectors ted automatically to, recorded
report alarm conditions for a in, maintained by, and super-
minimum period of time, or vised from a listed central sta-
confirm alarm conditions tion that has competent and
3 ■
NECA 305 Standard for Fire Alarm System Job Practices
■ 4
Definitions
Evacuation Signal Distinctive signal intended to Fire Safety The fire alarm system compo-
be recognized by the occu- Function Control nent that directly interfaces
pants as requiring evacuation Device with the control system that
of the building. controls the fire safety func-
tion.
Fire Alarm Control See Fire Alarm Control Unit.
Panel (FACP) FACP sometimes appears in Fixed-Temperature A device that responds when
manufacturers literature. Detector its operating element becomes
heated to a predetermined
Fire Alarm Control A system component that level.
Unit (FACU) receives inputs from automatic
and manual fire alarm devices Four-Wire Smoke A smoke detector, which initi-
and might supply power to Detector ates an alarm condition on an
5 ■
NECA 305 Standard for Fire Alarm System Job Practices
IDC (Initiating Device Circuit) Ionization Smoke The principle of using a small
and is powered by a separate Detection amount of radioactive material
power supply circuit. to ionize the air between two
differentially charged electrodes
Gateway A device that is used in the to sense the presence of smoke
transmission of serial data particles. Smoke particles
(digital or analog) from the entering the ionization cham-
fire alarm control unit to other ber decrease the conductance of
building system control units, the air by reducing ion mobili-
equipment, or networks ty. The reduced conductance
and/or from other building signal is processed and used to
system control units to the fire convey an alarm condition
alarm control unit. when it meets preset criteria.
Heat Detector A fire detector that detects Life Safety A type of combination system
either abnormally high tem- Network that transmits fire safety con-
perature or rate of tempera- trol data through gateways to
ture rise, or both. other building system control
units.
Household Fire A system of devices that pro-
Alarm System duces an alarm signal in the Line-Type A device in which detection is
household for the purpose of Detector continuous along a path.
notifying the occupants of the Typical examples are rate-of-
presence of a fire so that they rise pneumatic tubing detectors,
will evacuate the premises. projected beam smoke detec-
tors, and heat-sensitive cable.
Initiating Device A system component that orig-
inates transmission of a Maintenance Repair service, including period-
change-of-state condition, ic inspections and tests, required
such as in a smoke detector, to keep the fire alarm system
manual fire alarm box, or and its component parts in an
supervisory switch. operative condition at all times,
and the replacement of the sys-
IDC (Initiating A circuit to which automatic tem or its components when
Device Circuit) or manual initiating devices they become undependable or
are connected where the signal inoperable for any reason.
received does not identify the
individual device operated. Manual Fire Alarm A manually operated device
Station (Box) used to initiate an alarm signal.
Intermediate Fire A control unit used to provide
Alarm or Fire area fire alarm or area fire Multiple Station A single station alarm capable
Supervisory supervisory service that, where Alarm of being interconnected to one
Control Unit connected to the proprietary or more additional alarms so
fire alarm system, becomes a that the actuation of one caus-
part of that system. es the appropriate alarm signal
to operate in all interconnect-
ed alarms.
■ 6
Definitions
Multiple Station Two or more single station that provides audible, tactile,
Alarm Device alarm devices that can be or visible outputs, or any com-
interconnected so that actua- bination thereof.
tion of one causes all integral
or separate audible alarms to NAC (Notification A circuit or path directly con-
operate; or one single station Appliance Circuit) nected to a notification appli-
alarm device having connec- ance(s).
tions to other detectors or to a
manual fire alarm box. Nuisance Alarm Any alarm caused by mechani-
cal failure, malfunction,
Municipal Fire A system of alarm-initiating improper installation, or lack
Alarm System devices, receiving equipment, of proper maintenance, or any
and connecting circuits (other alarm activated by a cause that
than a public telephone net- cannot be determined.
work) used to transmit alarms
from street locations to the Operating Mode, Audible or visible signaling
public fire service communica- Private only to those persons directly
tions center. concerned with the implemen-
tation and direction of emer-
Noncoded Signal An audible or visible signal gency action initiation and
conveying one discrete bit of procedure in the area protect-
information. ed by the fire alarm system.
Non-power- A fire alarm circuit powered by Operating Mode, Audible or visible signaling to
Limited Fire Alarm a source not more than 600 Public occupants or inhabitants of
Circuit (NPLFA) volts and unlimited current the area protected by the fire
capacity with overcurrent pro- alarm system.
tection provided at the point
of connection to the power Operating System The basic operating system
source. [See NEC, Sections Software software that can be altered
760-21 and 760-23.] only by the equipment manu-
facturer or its authorized rep-
Nonrequired A supplementary fire alarm resentative. Operating system
System system component or group of software is sometimes referred
components that is installed at to as firmware, BIOS, or execu-
the option of the owner, and is tive program.
not installed due to a building
or fire code requirement. Permanent Visible An immediately readable, not
Record (Recording) easily alterable, print, slash, or
Nonrestorable A device in which the sensing punch record of all occur-
Initiating Device element is designed to be rences of status change.
destroyed in the process of
operation. Photoelectric Light The principle of using a light
Obscuration source and a photosensitive
Notification A fire alarm system compo- Smoke Detection sensor onto which the princi-
Appliance nent such as a bell, horn, pal portion of the source emis-
speaker, light, or text display sions is focused. When smoke
7 ■
NECA 305 Standard for Fire Alarm System Job Practices
Photoelectric The principle of using a light Prime Contractor The one company contractual-
Light-Scattering source and a photosensitive ly responsible for providing
Smoke Detection sensor arranged so that the central station services to a
rays from the light source do subscriber as required by
not normally fall onto the NFPA 72. The prime contrac-
photosensitive sensor. When tor can be either a listed cen-
smoke particles enter the light tral station or a listed fire
path, some of the light is scat- alarm service-local company.
tered by reflection and refrac-
tion onto the sensor. The light Projected Beam- A type of photoelectric light
signal is processed and used to Type Detector obscuration smoke detector
convey an alarm condition wherein the beam spans the
when it meets preset criteria. protected area.
Placarded A means to signify that the fire Proprietary An installation of fire alarm
alarm system of a particular Supervising systems that serves contiguous
facility is receiving central sta- Station Fire and noncontiguous properties,
tion service in accordance with Alarm System under one ownership, from a
NFPA 72 by a listed central proprietary supervising station
station or listed fire alarm ser- located at the protected prop-
vice-local company that is part erty, at which trained, compe-
of a systematic follow-up pro- tent personnel are in constant
gram under the control of an attendance. This includes the
independent third party listing proprietary supervising sta-
organization. tion; power supplies; signal-
initiating devices; initiating
Positive Alarm An automatic sequence that device circuits; signal notifica-
Sequence results in an alarm signal, even tion appliances; equipment for
when manually delayed for the automatic, permanent
investigation, unless the system visual recording of signals; and
is reset. equipment for initiating the
operation of emergency build-
Power-Limited A fire alarm circuit powered by ing control services.
Fire Alarm a source that is listed and
Circuit (PLFA) marked as follows: a listed Protected A protected premises system
PLFA or Class 3 transformer; a Premises (Local) that sounds an alarm at the
listed PLFA or Class 3 power Fire Alarm System protected premises as the
■ 8
Definitions
Public Fire Alarm A system of fire alarm initiating Remote A system installed in accor-
Reporting System devices, receiving equipment, Supervising dance with NFPA 72 to trans-
and connecting circuits used to Station Fire mit alarm, supervisory, and
transmit alarms from street Alarm System trouble signals from one or
locations to the communica- more protected premises to a
tions center. remote location where appro-
priate action is taken.
Radiant Energy- A device that detects radiant
Sensing Fire energy (such as ultraviolet, Reset A control function that
Detector visible, or infrared) that is attempts to return a system or
emitted as a product of com- device to its normal, non-
bustion reaction and obeys the alarm state.
laws of optics.
Restorable A device in which the sensing
Rate Compensation A device that responds when Initiating Device element is not ordinarily
Detector the temperature of the air sur- destroyed in the process of
rounding the device reaches a operation, whose restoration
predetermined level, regardless can be manual or automatic.
of the rate of temperature rise.
Shall Indicates a mandatory require-
Rate-of-Rise A device that responds when ment.
Detector the temperature rises at a rate
exceeding a predetermined Should Indicates a recommendation
value. or that which is advised but
not required.
Record Drawings Drawings (as-built) that docu-
ment the location of all Signaling Line A circuit or path between any
devices, appliances, wiring Circuit combination of circuit inter-
sequences, wiring methods, faces, control units, or trans-
and connections of the com- mitters over which multiple
ponents of the fire alarm sys- system input signals or output
tem as installed. signals, or both, are carried.
9 ■
NECA 305 Standard for Fire Alarm System Job Practices
Site-Specific Software that defines the Supervisory Signal An initiating device such as a
Software specific operation and configu- Initiating Device valve supervisory switch, water
ration of a particular system. level indicator, or low air pres-
Typically, it defines the type and sure switch on a dry-pipe
quantity of hardware modules, sprinkler system in which the
customized labels, and specific change of state signals an off-
operating features of a system. normal condition and its
restoration to normal of a fire
Sloping Ceiling A ceiling that has a slope of protection or life safety system;
more than 1 in 8. or a need for action in connec-
tion with guard tours, fire sup-
Smoke Alarm A single or multiple station pression systems or equip-
alarm responsive to smoke. ment, or maintenance features
of related systems.
Smoke Detector A device that detects visible or
invisible particles of combus- Supplementary As used in NFPA 72, supple-
tion. mentary refers to equipment
or operations not required by
Smooth Ceiling A ceiling surface uninterrupted NFPA 72 and designated as
by continuous projections, such by the authority having
such as solid joists, beams, or jurisdiction.
ducts, extending more than 4
in. (100 mm) below the ceiling Tactile Notification A notification appliance that
surface. Appliance alerts by the sense of touch or
vibration.
Spacing A horizontally measured
dimension related to the Textual Audible A notification appliance that
allowable coverage of fire Notification conveys a stream of audible
detectors. Appliance information. An example of a
■ 10
Definitions
11 ■
3. Prepare for Installation
3.1 Receive, Inventory and Store Equipment (1) Factory trained and certified personnel
a) Check received equipment against the packing list (2) National Institute of Certification in
and the job bill of material Engineering Technologies (NICET) fire alarm
level II certified personnel
b) Check equipment for shipping damage
(3) Personnel licensed or certified by state or local
authority
c) Store equipment in a dry, safe place
■ 12
Prepare for Installation
13 ■
4. Install Fire Alarm Control Unit(s)
Fire alarm control units ship in various combinations: h) Remove electronic assemblies and power supplies
using directions supplied by the manufacturer. Note:
a) Enclosures may be shipped separately (no elec- The use of a grounded wrist strap is recommended to
tronic assemblies) for job rough-in. prevent electrostatic damage to electronic components
when removing or /replacing electronic assemblies.
b) Enclosures, control unit doors, and the electronic
assemblies may be individually packaged and shipped i) Carefully wrap and place the covers, internal doors
together in an over-pack. and dead-fronts, and electronic assemblies in the
shipping container.
c) Enclosures may be shipped complete, with the
electronic assemblies installed in the enclosure. j) Store the shipping container in a safe, clean, and
dry location until system field wiring is completed,
4.3 Enclosure Installation and job conditions permit mounting the electronics
and door. The control unit will be reassembled after
The general procedures listed below should be used installation of the system wiring and field devices.
when installing a back box. If the enclosure is shipped
separately, some steps can be omitted. Manufacturers k) Fire alarm control unit enclosures may be
provide specific installation instructions with the fire installed surface, semi-flush, or flush mounted,
alarm control unit or empty enclosure. according to manufacturers’ instructions.
a) Carefully open the shipping container. l) Use the enclosure as a template for marking the
location of the mounting holes.
b) Inventory the contents of the shipping container
to ensure complete shipment of the required materi- m) Mount enclosure so accidental operation or fail-
als. (See packing list.) ure is not caused by vibration or jarring.
c) Remove the fire alarm control unit from the ship- n) The power source for the control unit must be
ping container. between 85% and 110% of nameplate rating (102
■ 14
Install Fire Alarm Control Units
VAC to 132 VAC for 120 VAC rated control unit). b) Some enclosures may be “butted” together, while
o) Connections to light and power service shall be others must be slightly spaced and close-nippled, to
on a dedicated branch circuit(s). assure covers can be opened.
p) Provide mechanical protection for the power sup- c) Observe space reserved for installation of batter-
ply circuits(s) and connections. ies, usually in the bottom of the fire alarm control
unit enclosure. Refer to manufacturers’ instructions.
q) Locate the circuit disconnecting means to accessi-
ble only to authorized personnel.
4.4 Cautions
a) Provide sufficient space from walls and other
equipment so the door can be opened 90º, mini-
mum, or as necessary to install door.
15 ■
5. Install System Wiring
Initiating Devices
Control
Panel
2
3
4
■ 16
Install System Wiring
Figure 1 shows a Class A IDC. The end-of-line c) Where looped raceway systems are provided, sin-
device (resistor) is factory installed, internally. gle conduit/raceway drops to individual devices or
appliances shall be permitted.
Figure 2 shows a Class B NAC. The end-of-line
device connects after the last device on the circuit. d) Where looped raceway systems are provided, sin-
gle conduit/raceway drops to multiple devices or
The following paragraphs, 5.2.1, 5.2.2, and 5.2.3, appliances installed within a single room not exceed-
describe the installation requirements that are in ing 92.9 m2 (1000 ft2) in area shall be permitted. [See
addition to NEC requirements: NFPA 72, paragraph 3-4.2.2.2.]
Control
Panel
17 ■
NECA 305 Standard for Fire Alarm System Job Practices
c) A 2-hour fire-rated stairwell in a building fully system—typically power for the control unit. Non-
sprinklered in accordance with NFPA 13, Standard power-limited, power-limited, and control unit
for the Installation of Sprinkler Systems [See NFPA power circuits are permitted in a common enclosure.
72, paragraph 3-8.4.1.1.4.]
5.3.1 General Requirements (NEC, Article 760,
5.2.3 Fire Command Center remote from Fire Part A)
Alarm Control Unit
a) Install all wiring to meet the requirements of NEC
If the fire command center control equipment is Article 760, unless the NEC conflicts with local code.
remote from the fire alarm control unit, the follow- Local code prevails.
ing requirements shall apply:
b) Identify fire alarm circuits at terminal and junc-
a) The interconnecting wiring shall be provided with tion locations. An excellent practice is to install red
mechanical protection by installing the wiring in covers labeled “Fire Alarm Circuit.”
metal raceway.
c) Support cables by the building structure.
b) The interconnecting wiring shall be provided
with resistance to attack from a fire by routing the d) Install circuits extending beyond one building
wiring through areas whose characteristics are at least according to the requirements of NEC Section 760-7,
equal to the limited-combustible characteristics which refers to Article 225 and Article 800, Parts B,
defined in NFPA 90A, Standard for the Installation of C, and D.
Air Conditioning and Ventilating Systems.
5.3.2 Non-power-limited circuits (NEC, Article
c) If the interconnecting wiring exceeds 30 m (100 760, Part B)
ft), additional resistance to attack from a fire shall be
provided by doing either of the following: a) Non-power-limited circuits shall be installed
using any of the three following methods:
1) Installing the wiring in metal raceway in a 2-
hour fire-rated enclosure 1) Conductors from Table 310-13 installed in
accordance with the requirements of Sections
2) Enclosing the wiring in a 2-hour fire-rated 110-3(b), 300-11(a), 300-17, and other appropri-
cable assembly (circuit integrity cable) and ate articles of Chapter 3 (e.g., Article 331 when
installing the cable in metal raceway [See NFPA installing ENT, Article 348 when installing EMT).
72, paragraph 3-8.4.1.3.3.3.] [See NEC Sections
760-31(f) and 760-71(g) for circuit integrity 2) Conductors from Table 402-5 that are listed in
cable requirements.] Section 760-27(b) installed in raceway.
3) Multiconductor cables described in Section
5.3 Installation Guidelines 760-30 used on circuits operating at less than 150
volts to ground installed in raceway or exposed.
Article 760 of the NEC contains the requirements for
installation of fire alarm system circuits: Non-power- b) Solid or stranded copper conductors must be
limited, and power-limited. These two types of cir- used.
cuits must be installed separate from each other.
That is, do not install non-power-limited and power- c) Install overcurrent protection for each conductor
limited circuits in the same cable or raceway. Power at the point where the conductor receives its supply.
circuit conductors are permitted to be installed in the
same raceway with non-power-limited circuits, where d) Install multiconductor non-power-limited fire
the power circuit is functionally associated with the alarm cables as follows:
■ 18
Install System Wiring
19 ■
6. Install Field Devices
Review the following before installing field devices: d) Figure 5 shows connections to a 4-wire smoke
detector circuit (IDC). Note the relay at the end of
a) Do not “T-tap” detectors. The exception is the power circuit. An end-of-line relay must be con-
addressable detectors on a Class B circuit, if permit- nected at the end of each power circuit.
ted by the manufacturer. Refer to manufacturer’s
Installation Instructions. 6.1 Manual Fire Alarm Station (Box)
6.1.1 Code References
b) Figure 3 shows correct and incorrect termination
methods. NFPA 72 Paragraph 2-8
In Out In Out
In Out
Incorrect Correct — separate incoming and outgoing conductors
Single terminal
Duplicate Duplicate notched clamping plate Duplicate
terminals leads terminals End-of-line
Control unit
resistor
initiating
device D D D D
circuit
Splices
Correct wiring method — two-wire detectors
End-of-line
Control unit resistor
initiating
device D D D D
circuit
Circuit wiring One splice lead Circuit wire bent Circuit wire looped
looped under connected, other back on itself and under terminal;
one terminal taped and not used secured in one notch wire run not broken
Incorrect wiring method — two-wire detectors
Figure 4. Correct and incorrect termination methods on various types of field devices.
Figures 3 and 4 reprinted with permission from NFPA 72-1999, Copyright© 1999, National Fire Alarm Code® Handbook, National Fire Protection
Association, Quincy, MA 02269. The reprinted matieral is not the referenced subject which is represented only by the standard in its entirety.
■ 20
Install Field Devices
End-of-line
Control unit device
initiating D D D D
device
circuit
Outgoing power Power supervisory
supply leads relay
Detector
power
supply
Incoming power D = Detector
supply leads
Illustrates four-wire smoke detector employing a four-wire connecting arrangement. Incoming and outgoing leads or terminals for both initiating
device and power supply connections. Wire run broken at each connection to provide supervision.
6.1.3 Cautions
4 in.
(0.1 m)
Ceiling
a) Do not mount where the manual fire alarm sta-
tion will be hidden from view by obstructions.
4-in.
Acceptable here (0.1-m)
minimum b) Door widths (multiple doors) over 12.2 m (40 ft)
Never here
wide require manual fire alarm stations on each side
12-in.
Top of detector (0.3-m) of the set of doors.
acceptable here
maximum
Figures 5 and 6 reprinted with permission from NFPA 72-1999, Copyright© 1999, National Fire Alarm Code® Handbook, National Fire Protection
Association, Quincy, MA 02269. The reprinted matieral is not the referenced subject which is represented only by the standard in its entirety.
21 ■
NECA 305 Standard for Fire Alarm System Job Practices
Figure 7. Detector placement – air supply and/or return ducts. (Reprinted from NEMA Guide for Proper Use of System Smoke
Detectors by permission of the National Electrical Manufacturers Association.)
hour, beams, joists, and partitions. Determination of
correct spacing is part of system design, and typically
Anywhere in
this area
shown on shop drawings.
3 ft 3 ft
(0.9 m) (0.9 m) d) Mount detectors within 900 mm (3 ft) of the
highest point of a sloped or peaked ceiling (see Figure
8).
■ 22
Install Field Devices
6.3 Beam Smoke Detector b) Avoid mounting in areas where there may be
smoke from kitchens and garages.
6.3.1 Code References
c) Do not mount where hot or cold air blow across
NFPA 72, Paragraph 2-3.4
the beam path. Heaters blowing across the beam
path can distort the beam, causing the signal at the
6.3.2 Installation Guidelines receiver to vary.
a) Mount beam detector transmitter and receiver on
stable surfaces to prevent nuisance or erratic opera- d) Do not mount where the receiver is exposed to
tion due to movement. While mirrors are permitted, sunlight and light from extremely bright sources such
some manufacturers recommend mirrors not be as high-pressure sodium, mercury vapor, and metal
used. Do not pendant-mount the transmitter or halide lights.
receiver (i.e., hang from the ceiling on a length of Air duct
Independent support (unless box is listed
conduit or mount on a pole). for pendant mounting)
Conduit
b) Select mounting positions where the beam path oke
Electrical box Sm tor
will be free of objects, such a lift trucks, which may e t
d esse c
block the beam path (see Figure 9). This figure shows Detector acc
c) Mount on walls and ceilings not subject to build- Figure 11.Product-mounted air duct installation.
ing movement or vibration.
Width Width
up to up to
36 in. 72 in.
(1.8 m)
Tube support hole only for ducts 1/2w 1/4 w 1/4 w
more than 3 ft (0.9 m) wide
Depth
up to
36 in.
Airflow direction 1/2 d (915 mm) 1 /2 d
Duct width
18-in.
(457-mm) (915 mm)
maximum 72 in. (1.8 m) 24 in.
Insert rubber plug (610 mm)
this end of inlet tube.
Detectors One detector
Expected airflow Depth evenly spaced for each full
direction up to 24 in. (610 mm)
36 in. of additional
Return tube (915 mm) 1/ 2 d opening width
slant cut face
oriented downstream 18-in.
Inlet tube of airflow (457-mm)
holes face = Smoke detector in duct maximum
upstream of Do not insert
airflow. rubber plug.
23 ■
NECA 305 Standard for Fire Alarm System Job Practices
6.4 Duct Smoke Detector g) Insert the sampling tubes with the holes of the
inlet tube facing the airstream. For tubes longer than
Review the following before installing duct smoke
3 feet, support internally or pass through the duct. If
detectors:
the tube protrudes through the other side of the
duct, seal the exit hole (see Figure 10).
a) The two types of duct smoke detectors are: A
detector using sampling tubes inserted in the air
h) If the duct smoke detector is an area type,
stream, and a spot-type detector listed for air duct
mounted in the duct, an access door shall be provid-
application. A detector with sampling tubes mounts
ed. [(Ref: NFPA 72-1999, paragraph 2-10.5.3] (See
on supply or return air ducts (see Figure 10). Spot-
Figure 11.)
type detectors are typically mounted above a
dropped ceiling directly in front of the return air
i) Select a mounting location for the detector or
duct, and are also listed for mounting in an air duct
detector sampling tubes at each story prior to the
(see Figures 11 and 12).
connection to a common return and prior to any
recirculation or fresh air inlet connection in the air
b) Duct smoke detectors are not a substitute for
return system. This is usually above a dropped-ceil-
area smoke detectors. The primary purpose of a
ing (see Figure 12).
duct smoke detector is to shut down the fan when
smoke is detected in the air duct.
j) Terminate wiring per shop drawings and manu-
facturer’s literature.
6.4.1 Code References
NFPA 72, Paragraph 2-10 k) Reassemble cover and electronic assemblies, as
NFPA 90A Chapter 4 required.
a) Select a mounting location 6 to 10 duct widths a) Mechanical contractors often install duct smoke
downstream from or prior to an air duct restriction detectors, which must be connected to the fire alarm
or bend. See Cautions. system, if one exists in the building. Coordination
between building trades will assure successful job
b) Select a mounting location for the detector or completion.
detector sampling tubes downstream of the fan and
filters and ahead of any branch connections in the b) It is often impossible to install duct detectors to
supply air duct. meet the 6 to 10 duct widths downstream from or
prior to a duct restriction or bend. In those situa-
c) Remove cover and electronic assemblies, if tions, install the duct smoke detector as far as possible
required, from detector housing. from bends and restrictions. The tests run with the
inclined plane manometer or magnehelic over the
d) For the sampling tube detector, use the detector possible range of air velocities will determine if the
housing, or provided template, to mark the holes for location is correct. See manufacturer’s instructions.
mounting the sampling tubes and housing.
6.5 Heat Detectors (Spot-type)
e) Install the gasket material, if provided or required 6.5.1 Code References
around the drilled holes.
NFPA 72, Paragraph 2-2
f) Mount the detector housing.
■ 24
Install Field Devices
c) Mechanical guards must be listed for use with the b) Protect detector from job site dust and airborne
detector. contamination. Do not install detector until the job-
site is ready for occupancy. Where provided, leave
d) Detectors must be supported independently of shipping cover in place until system acceptance testing.
the attached circuit conductors.
c) Do not recess detectors into the mounting surface.
S b) Pressure
1/2 S
6.6.1 Code References
25 ■
NECA 305 Standard for Fire Alarm System Job Practices
6.6.3 Cautions 2.3 m (90 in.), if possible, and the appliances must be
mounted at least 150 mm (6 in.) below the ceiling.
Coordinate with other trades, as required, when con-
necting to these devices. b) Mechanical guards must be listed for use with the
appliances.
6.7 Supervisory Switches
Sprinkler systems companies normally install sup- c) Appliances must be supported independently of
pression system supervisory devices. This section the attached circuit conductors.
addresses the types of devices connected to the fire
alarm system, not how to install them. There are a d) Mount appliances on electrical boxes, unless
number of different types of supervisory devices, equipped with listed fittings. Manufacturer’s installa-
which when activated provide an “off-normal” signal tion instructions shipped with the appliances detec-
at the fire alarm control unit. Supervisory devices tor will show permitted mounting methods.
may be installed to monitor the following:
6.8.3 Cautions
a) Control valve
a) Appliances used in special environments, such as,
outdoors, high or low temperatures, high humidity,
b) Pressure (air, water, steam)
dusty conditions, and hazardous locations must be
listed for the application.
c) Water level
6.9 Visible Notification Appliances (Strobes)
d) Temperature (water tank, room)
6.9.1 Code References
6.7.1 Code References
NFPA 72. Paragraph 4-4
NFPA 72, Paragraph 2-9
6.9.2 Installation Guidelines
6.7.2 Installation Guidelines
a) Install notification appliances on the ceiling or
a) Terminate fire alarm conductors per shop draw- wall. Where wall-mounted, the lens of the appliance
ings and manufacturer’s literature. should be not less than 2.0 m (80 in.) and not greater
than 2.4 m (96 in.) above the floor. Visible notifica-
6.7.3 Cautions tion appliances listed for ceiling mounting must be
mounted or suspended at or below 9.14 m (30 ft).
b) Coordinate with other trades, as required, when
connecting to these devices. b) Appliances shall be located not more than 4.5 m
(15 ft) from the end of a corridor.
6.8 Audible Notification Appliances (bells,
horns, speakers, chimes) c) Appliances shall be located at a separation of not
greater than 30.0 m (100 ft) in a corridor.
6.8.1 Code References
NFPA 72, Paragraph 4-3 d) Appliances shall be supported independently of
the attached circuit conductors.
6.8.2 Installation Guidelines
e) Mount appliances on electrical boxes, unless
a) Install notification appliances on the ceiling or equipped with listed fittings. Manufacturer’s installa-
wall. Where wall-mounted, appliances shall have tion instructions shipped with the appliance will
their tops above the floor at heights of not less than show permitted mounting methods.
■ 26
Install Field Devices
b) One telephone line (number) and one cellular a) The DACT must be connected to a loop start tele-
telephone connection phone circuit, and not to a ground start telephone
circuit.
c) One telephone line (number) and a one-way
radio system b) The DACT must connect to the phone line ahead
of all phones and switchboard connections.
d) One telephone line (number) equipped with a
derived local channel c) The DACT must disconnect any phone that is off-
hook and seize control of the phone lines.
e) One telephone line (number) and a one-way pri-
vate radio alarm system
27 ■
7. Check System Wiring
7.1 Wiring Test Guidelines Leave this device disconnected. Continue to “halve”
the circuit with the voltage until the stray voltage
a) Make sure all conductors or cables are identified
source is located.
(e.g., tagged) with permanent marking.
7.3 Grounds
b) A properly installed wiring system will have:
1) No stray voltages a) Set the meter to the x10,000 ohms scale. Connect
one of the meter leads to ground. Touch every con-
2) No grounds
ductor with the other meter lead. The resistance
3) No open circuits should read infinity—an open circuit.
4) No short circuits
b) General troubleshooting procedures: The resis-
5) Proper circuit resistance tance measured on one conductor will be near zero,
c) Perform the following tests before terminating the while the other conductor will probably be about
conductors at the FACP. equal to the resistance of the end-of-line device. Go
to a point “electrically” half way to the end of the cir-
d) Check wiring using the following sequence using cuit, as shown on shop drawings. Disconnect both
a volt-ohm meter. The general procedure is to locate the incoming and outgoing leads from the device.
a wiring problem by “halving” the field circuit, until Determine which lead is grounded. Leave the device
it is found. disconnected and insulate the four conductors, indi-
vidually (wire nut or tape). Continue to “halve” the
7.2 Voltage (Stray) circuit with the ground fault until the circuit fault is
located.
a) Set the meter to 300 VAC, or higher. Connect the
meter leads across each pair of conductors. The volt- 7.4 Open Circuits
age should read zero.
a) Set the meter to the proper scale according the
b) Set the meter to 30 VDC or higher. Connect manufacturer’s instructions. The reading will
meter leads across each pair of conductors. Reverse depend on the type of circuit being check and the
the leads and measure for voltage again, unless a cen- value of the end-of-line device. Examples follow.
ter-zero meter or polarity-sensing meter is used. The
voltage should read zero. b) The resistance of each Class B IDC and SLC will
be equal to or a little less than the end-of-line device,
c) General troubleshooting procedure: Use extreme usually between 1,000 ohms and 10,000 ohms,
caution, as the voltage source is probably unknown. depending on the system. If a SLC does not have an
Go to a point electrically half way to the end of the end-of-line device, connect a resistor across the end
circuit (e.g., device 8 out of 16). Disconnect both the of the circuit.
incoming and outgoing leads from the device.
Measure for voltage on both sets of conductors. c) The resistance of a Class B NAC circuit will be
equal to or a little more than the end-of-line device
■ 28
Check System Wiring
29 ■
8. Finish Control Unit Installation
d) Mount door.
f) Apply power.
■ 30
9. Check System Operation
• Make sure there is a smoke detector protecting j) Initiate an alarm from any device in the system.
the control unit. • Alarm sounds.
c) Operate lamp test switch. l) Initiate another alarm from a device on a different
• All indicators on initiating device circuit.
• Alarm resounds.
d) Check for ground fault indication. [Connect a
jumper from an initiating or signaling line circuit m) Reset devices and operate system reset switch.
to ground (conduit, system cabinet, etc.]. • System resets.
• Ground fault indicator on (if applicable). • Trouble indicators activate until alarm silence
e) Operate main breaker to disconnect AC power. switch is returned to normal.
• Make sure the location of breaker is indicated
31 ■
NECA 305 Standard for Fire Alarm System Job Practices
9.3 Field Device Test Preparation k) Re-install the device and reset system.
a) This test normally requires two people: one per-
l) Repeat wiring supervision test for each IDC, SLC,
son at the control unit and the other testing the field
and NAC.
devices. Hand-held radios provide an efficient
means of communication.
9.4.2 Class “B” Wiring
b) The person in the field performs a test. The per- a) Remove an initiating device (pull station, smoke
son at the control unit notifies the person perform- detector, etc.) and open the circuit by disconnect-
ing the test what occurred. Record result. ing one wire (there should be 4 wires connected
to each device on the circuit, except for the end-
c) All devices must be tested for alarm or superviso- of-line device—2 wires and end-of-line device).
ry function and indication verified at the control unit Note: Removing a detector from its base will open
and all remote annunciators. the circuit and cause a trouble signal.
• Audible and visible trouble indicators on.
9.4 Monitoring for Integrity Tests (often
b) Reconnect the wire.
referred to as circuit supervision)
9.4.1 Class “A” Wiring c) Reset the system.
a) Remove an initiating device (pull station, smoke d) Connect one side of the device circuit to ground
detector, etc.) and disconnect both incoming wires using a jumper wire.
(there should be 4 wires connected to the device). • Audible and visible indicators on
• Audible and visible trouble indicators on.
e) Reset the device.
b) Actuate the device.
• Alarms sound. f) Repeat ground test for other side of the device cir-
• Zoning identification verified. cuit.
c) Reset the operated device and system. g) Reinstall the device.
d) Replace those two wires and disconnect the two h) Repeat wiring supervision test for IDC, SLC, and
outgoing wires. NAC.
e) Actuate the device. 9.5 Device Tests
• Alarms sound.
9.5.1 Manual Fire Alarm Boxes (Pull Stations)
f) Reconnect wires,
a) Actuate a pull station.
g) Connect one side of the device circuit to ground • Alarms sound.
using a jumper wire.
• Zoning identification verified.
• Visible and audible signal at control unit
b) Repeat for each manual pull station in the system.
h) Actuate the device.
• Alarms sound.
9.5.2 Smoke Detectors, Spot-type
i) Reset device, if required, and system.
a) Actuate a smoke detector using smoke or aerosol
j) Repeat “ground” test for other side of the device acceptable to the manufacturer. Do not test with
circuit. magnets.
• Alarm sounds.
■ 32
Check System Operation
• Zoning identification verified. b) Repeat for each restorable heat detector in system.
c) Repeat for each non-restorable heat detector in a) Short across the conductors at the end of the heat
system. detector cable.
• Alarm sounds.
9.5.7 Restorable Fixed Temperature Heat • Zoning identification verified.
Detector
b) Repeat for each non-restorable line-type heat
a) Heat test using a hair dryer or approved heat detector in system.
detector tester.
• Alarms sound. 9.5.11 Flame Detectors
• Zoning identification verified. a) Follow the manufacturer’s recommended test
b) Acceptance/Re-acceptance Tests – Repeat tests for methods.
each restorable heat detector in system.
9.5.12 Waterflow Switches
c) Periodic Tests -Test 20% of restorable fixed tem-
a) Open the Inspector’s Test Valve and flow water.
perature heat detectors. Be sure to log which detec-
• Alarms sound within 90 seconds. (Time delay
tors have been tested.
should be as short as possible. Adjust to avoid
possible nuisance alarms due to pressure varia-
9.5.8 Rate of Rise Heat Detector
tions, surges, etc.)
a) Heat test using a hair dryer or approved heat b) Repeat for each waterflow switch in system.
detector tester.
33 ■
NECA 305 Standard for Fire Alarm System Job Practices
9.5.13 Pressure-type Waterflow Device (Alarm) • Non-pressure Tank- supervisory signal is received
when water levels falls 300 mm (12 in.) from the
a) Operate the alarm test bypass connection. required level.
• Alarms sound.
• Restoration of signals is received when water lev-
b) Repeat for each pressure-type waterflow switch in els are returned to normal levels.
system.
9.5.14 High or Low Pressure Switch 9.5.17 Gate Valve Supervisory Switch
(Supervisory) a) Turn valve toward closed position.
a) Operate the switch. • Supervisory signal within two revolutions.
• Supervisory signal is received when pressure b) Turn valve to full open position.
increases or decreases by 70 kPa (10 psi). • Supervisory signal restores.
• Restoration of signal is received when pressure c) Repeat for gate valve supervisory switches in sys-
is back within 70 kPa (10 psi) of required pres- tem.
sure.
b) Repeat for each supervisory pressure switch in 9.5.18 Post Indicator Valve Supervisory Switch
system.
a) Turn valve toward closed position.
• Supervisory signal within two revolutions.
9.5.15 Room Temperature Switch (Supervisory)
b) Turn valve to full open position.
a) Operate the switch. • Supervisory signal restores.
• Supervisory signal is received when tempera-
ture is decreased to 4.4°C (40°F). c) Repeat for all other post indicator supervisory
valves in system.
• Restoration of signal is received when tempera-
ture is returned to above 4.4°C (40°F). 9.5.19 Other Supervisory Switches Type of
b) Repeat for each room temperature switch in sys- Device
tem.
a) Operate device as appropriate.
• Supervisory signal received.
9.5.16 Water Temperature Switch (Supervisory)
b) Return device to normal position.
a) Operate the switch. • Supervisory signal restores.
• Supervisory signal is received when tempera-
ture is decreased to 4.4°C (40°F). c) Repeat for all other supervisory switches in system.
■ 34
Check System Operation
9.5.21 Emergency Voice/Alarm Communications a) Disconnect one telephone line. DACT should
Systems report a trouble condition within 4 minutes.
a) Verify alarm signal in selected areas {fire floor, b) Reconnect first telephone line. System should
floor above, floor below, etc.) return to normal condition.
b) Manually place system in general alarm. c) Disconnect second telephone line. DACT should
report a trouble condition within 4 minutes.
c) Verify alarms sound throughout building.
d) Turn DACT primary power breaker off.
4. Verify each speaker zone for proper operation and
identification. e) Verify trouble condition.
5. Verify evacuation tone signals are 15 dBA above f) Reconnect DACT primary power.
average ambient sound level or 5 dBA above maxi-
mum sound level lasting at least 60 seconds. g) Disconnect DACT secondary power.
35 ■
10. Inspect, Test, and Maintain
10.1 Code References mance. NFPA 72, Table 7-3.1, Visible Inspection
Frequencies, provides the frequency of inspection for
NFPA 72, Chapter 7
the various types of fire alarm equipment.
Note: The Inspection and Testing Form shown in
NFPA 72 as Figure 7-5.2.2 is available from AFAA, P.O
10.5 Testing
Box 951807, Lake Mary, FL 32795-1807.
NFPA 72 requires periodic testing of fire alarm
10.2 General Procedures equipment. NFPA 72, Table 7-3.2, Testing
Frequencies, provides the frequency of tests for the
After acceptance by the authority having jurisdiction,
various types of fire alarm equipment. NFPA 72
the ongoing inspection, testing and maintenance
Table 7-2.2 contains the test methods used in testing
begins. NFPA 72, Chapter 7 contains the require-
the fire alarm system.
ments. Manufacturer’s instructions may provide spe-
cific procedures or test equipment required. Local
10.6 Maintenance
code or other authorities having jurisdiction (insur-
ance, hospital) may have additional requirements. a) Maintain the fire alarm according to manufactur-
er’s instructions.
10.3 Qualifications of Service Personnel
b) Clean the equipment as required by local condi-
NFPA 72, paragraph 7-1.2.2 identifies examples of
tions.
personnel qualified to service fire alarm systems:
10.7 Records (Inspection, Testing, and
1) Factory trained and certified
Maintenance)
2) National Institute for Certification in Engineering a) Retain records until the next test and for 1 year
Technologies fire alarm certified thereafter.
3) International Municipal Signal Association fire b) Make a permanent record of each test that
alarm certified includes the following, plus all applicable informa-
tion requested in NFPA 72, Figure 7-5.2.2. (See 10.1
4) Certified by a state or local authority for availability.)
1) Date
5) Trained and qualified personnel employed by an
2) Test frequency
organization listed by a national testing laboratory
for the servicing of fire alarm systems 3) Name of property
4) Address
10.4 Inspection
5) Name of person performing inspection, main-
NFPA 72 requires periodic visible inspection of fire tenance, tests, or combination thereof, and affili-
alarm equipment. Visible inspections ensure that ation, business address, and telephone number
there are no changes that affect equipment perfor-
■ 36
Inspect, Test, and Maintain
10.8 Cautions
a) Look for changes in building construction during
visible inspections, such as, partitions and high cabi-
nets. Look for relocated furnishing that are obstruct-
ing the use of or obscuring the view of devices and
appliances (e.g., plants placed in front of manual fire
alarm boxes).
37 ■
(This appendix is not part of the standard)
ANSI/NFPA 90A-1999, Standard for the Installation of Air-Conditioning and Ventilating Systems
NECA 101-2000, Standard for Installing Steel Tube (Rigid, IMC, EMT)
NECA/AA 104-2000, Recommended Practice for Installing Aluminum Building Wire and Cable (ANSI)
■ 38
Reference Standards
NECA 202-2001, Recommended Practice for Installing and Maintaining Industrial Heat Tracing Systems (ANSI)
NECA/FOA 301-1997, Standard for Installing and Testing Fiber Optic Cables
NECA 400–1998, Recommended Practice for Installing and Maintaining Switchboards (ANSI)
NECA 402-2000, Recommended Practice for Installing and Maintaining Motor Control Centers (ANSI)
NECA/EGSA 405-2001, Recommended Practice for Installing and Commissioning Interconnected Generation
Systems (ANSI)
NECA/IESNA 500-1998, Recommended Practice for Installing Indoor Commercial Lighting Systems (ANSI)
NECA/IESNA 502-1999, Recommended Practice for Installing Industrial Lighting Systems (ANSI)
NECA/BICSI 568-2001, Standard for Installing Commercial Building Telecommunications Cabling (ANSI)
39 ■
Codes and Standards
Index: NECA 305
10K-1/02 TM
National
Electrical
Installation
Standards
™