Sei sulla pagina 1di 4

INDUSTRY TOPICS

THE BASIS FOR PERFORMING


INSULATION POWER-FACTOR
TESTING ON LARGE CAST-COIL
TRANSFORMERS
B Y B R U CE M . R O CK W E L L , American Electrical Testing, Inc.

This article discusses the industry basis and value of performing


an insulation power-factor test on dry-type transformers,
specifically the cast-coil design. The basis for performing this
test as outlined in the industry standards is discussed. The value
of performing the test based on the transformer application, site
conditions, and customer objectives is presented. The intent is
to provide insight into when it is prudent to apply insulation
power-factor testing to dry-type transformers.
The Institute of Electrical and Electronic Engineers Section 8 of the C57.12.01 standard addresses
(IEEE) publishes a voluntary consensus standard, testing. Specifically, paragraph 8.3 addresses
IEEE Std. C57.12.01 (2015), IEEE Standard for routine, design, and other tests for transformers.
General Requirements for Dry-Type Distribution Dry-type transformer tests are summarized in
and Power Transformers. This standard was Table 16. The insulation power-factor test is
first published in 1979, and its purpose is to listed under “other” tests. The standard implies
provide a basis for establishing performance and that other tests are those that are specified
interchangeability requirements for dry-type individually as deemed appropriate. Thus, the
transformers. This standard describes electrical and standards recognize it is common practice to
mechanical requirements of single- and poly-phase consider insulation power-factor testing for
as well as ventilated, non-ventilated, and sealed dry-type transformers.
dry-type distribution and power transformers or
autotransformers with a voltage of 601 volts or A companion standard to IEEE C57.12.01
higher in the highest voltage winding. This standard is IEEE C57.12.91 (2011), IEEE Standard
applies to all dry-type transformers, including those Test Code for Dry-Type Distribution and
with solid cast and/or resin-encapsulated windings. Power Transformers. This standard provides

THE BASIS FOR PERFORMING INSULATION POWER-FACTOR NETAWORLD • 69


TESTING ON LARGE CAST-COIL TRANSFORMERS
INDUSTRY TOPICS
information regarding procedures for testing power factor over time as a predictor of
dry-type transformers. It identifies that overall insulation quality. Such trend test
transformer requirements and specific test data is helpful in identifying degradation
criteria are not part of this standard but are or verifying insulation quality improvement
contained in appropriate standards such as from drying/cleaning. Such testing is also
IEEE C57.12.01 or in other user-developed helpful in identifying potential issues
specifications. Thus, there is some basis that (insulation voids/carbonization) that may
applications vary, and as such, different testing not be observed externally.
may be applicable for different conditions.
Large (>500 kVA) cast-coil transformers (stand-
Within IEEE Std. C57.12.91, the following alone or unit substation types) are generally
commentary is noted: applied (in lieu of open-wound or encapsulated
types) where additional strength and protection
While the real significance that can be is required. These units are intended for harsh
attached to the insulation power factor of dry- environments and/or outdoor applications
type transformers is still a matter of opinion, and are applied for their superior short-circuit
experience has shown that insulation power strength and short-duration overloads as are
factor is helpful in assessing the probable typically experienced in industrial process
condition of the insulation when good judgment applications.
is used. In interpreting the results of insulation
power-factor test values, the comparative values One noted disadvantage when applying or using
of tests taken at periodic intervals are useful in a cast-coil transformer is that the coefficient
identifying potential problems rather than an of expansion of the epoxy insulation is less
absolute value of insulation than that of the copper (or
power factor. A factory aluminum) windings. If the
insulation-power-factor test transformer is exposed to
THE TEST COMMUNITY
is of value for comparison environmental or operating
with field insulation-power- UNIVERSALLY conditions that create cyclical
factor measurements to assess RECOGNIZES APPLYING expansion and contraction
the probable condition of THE INSULATION by heating and cooling the
the insulation. It has not coils, this can lead to cracking
been feasible to establish POWER-FACTOR TEST of the cast-coil epoxy-resin
standard insulation-power- PERIODICALLY FOR insulation over time.
factor values for dry-type MAINTENANCE AND
transformers because General Electric published
USING THE TREND-TEST a service bulletin titled Test
experience has indicated that
little or no relation exists DATA TO VALIDATE Application Data for Secondary
between insulation power THE QUALITY OF DRY- Substation Transformers. In
factor and the ability of the this test application guide,
TYPE TRANSFORMER the insulation power-factor
transformer to withstand the
prescribed dielectric tests. INSULATION AS AN test is listed as an optional
ESTABLISHED INDUSTRY test; however, it is noted that
Another factor cited for this test is useful for checking
BEST PRACTICE.
the inability to establish a the condition of the insulation.
standard insulation-power- This service guide identifies
factor test value is the that comparative measurements
wide variation in size, type, and quantity made at periodic (i.e., maintenance) intervals
of insulating materials used in large dry- are useful in identifying potential problems
type transformers. However, practice has rather than the absolute test value. Thus, GE
proven the value in trending the insulation is one manufacturer that readily acknowledges

70 • FALL 2016 THE BASIS FOR PERFORMING INSULATION POWER-FACTOR


TESTING ON LARGE CAST-COIL TRANSFORMERS
INDUSTRY TOPICS
the value of using the insulation power-factor 1. Ventilated Dry-Type
test trend data as a maintenance test. • CHL (high-to-low) 2 percent
• CL (low-to-ground) 4 percent
The American National Standards Institute • CH (high-to-ground) 3 percent
(ANSI) publishes the ANSI/NETA MTS,
Standard for Maintenance Testing Specifications 2. Epoxy Encapsulated Dry-Type
for Electrical Power Equipment and Systems, 2015 • CHL 1 percent
edition. • CL 2 percent
• CH 3 percent
The ANSI/NETA MTS-2015 test specifications
identify the insulation power-factor test as It is important to note that CL power factors
a standard (routine) test. Additionally, the as high as 8 percent have been noted in some
specifications identify an insulation power- manufacturers’ transformers, and these levels
factor tip-up test as an option. Industry practice may be considered acceptable. Thus, having
has established the value of performing this trend data is very helpful in monitoring/
additional test when the standard insulation- identifying normal and degraded conditions.
power-factor test results are suspect. Literature published by electrical test instrument
manufacturer Megger Group Ltd. provides
The industry body of knowledge referenced
the following insight: “Higher overall power-
herein provides guidance on transformer
factor results may be expected on dry-type
testing by considering the type of insulation
transformers; however, the majority of test
system: dry-type or liquid-filled. There
results for PF are found to be below 2.0
is some distinction with respect to size.
percent, but can range up to 10 percent.”
Transformers larger than 500 kVA (three-
phase) are generally considered significantly The test community universally recognizes
more critical to business operations. The applying the insulation power-factor test
standards make no distinction with respect periodically for maintenance and using the
to the test specifications based on the various trend-test data to validate the quality of dry-type
types of dry-type insulation system designs transformer insulation as an established industry
such as cast coil, resibloc, vacuum-pressure best practice. This practice is also recommended by
impregnated (VPI), or vacuum-pressure ANSI/NETA as a routine maintenance test.
encapsulated (VPE). Industry standards
further guide the user toward good engineering The insulation power-factor tip-up test is
judgment and apply reasonable economic an additional test recognized in the ANSI/
justification based on additional factors such as NETA MTS-2015 industry standard. This
reliability, criticality, environment, and service- test is performed to further clarify what the
aged conditions. insulation power-factor test results may be
indicating. When performed, this optional
Having data on the frequency and magnitude of
test is useful in evaluating and discriminating
through-faults experienced by a transformer are
whether moisture or corona are present in the
criteria that warrant consideration with respect
insulation system. To perform the tip-up test,
to specifying more or less testing. In facilities
the applied test voltage starts at about 1 kV and
and plant sites that have high available fault
increases in intervals up to 10 kV or the line-to-
currents, and in situations where a transformer
ground rating of the winding insulation. If the
has been subjected to a through-fault, it is
prudent to perform insulation power-factor insulation power-factor does not change as the
testing to verify the insulation quality. test voltage is increased, moisture is suspected
as a probable cause. If the insulation power-
Doble Engineering Company suggests the factor increases as the voltage is increased,
following as acceptable, stand-alone insulation- carbonization of the insulation or ionization in
power-factor test values: voids is a probable cause.-

THE BASIS FOR PERFORMING INSULATION POWER-FACTOR NETAWORLD • 71


TESTING ON LARGE CAST-COIL TRANSFORMERS
INDUSTRY TOPICS
C ONC LUSION
It is reasonable to perform the insulation power- Bruce Rockwell is the Director of
factor test on dry-type transformers, including Engineering for American Electrical
cast-coil designed units. The insulation power- Testing, Inc., Boonton, New Jersey. Bruce
factor test may add two to four hours to the has more than 35 years of engineering and
testing scope; thus, it can be significant in the operations experience spanning industrial
price of the work. It is important to understand
and utility power systems in transmission,
how to prioritize the value of this test with
distribution, substation, generation, and rail transit from low
customer economic expectations.
voltage to 500 kV. He has a Bachelor of Science in Electrical
In some aspects, this is akin to the mindset Engineering from the New Jersey Institute of Technology and
that transformers only need to be tested on an MBA from Monmouth University. Bruce is a licensed
the applied tap setting. However, turn-to- Professional Engineer in 22 states, a licensed Electrical
turn winding shorts are found often enough Contractor in New Jersey, and a New Jersey State-Certified
to justify testing a transformer on all of its
Continuing Education Instructor for electrical contractors.
available tap positions, and time added for this
He is a senior member of IEEE and has been recognized
testing is minimal. Understanding the value of
the test, the added scope/cost, and when it may many times for his contributions to various publications and
provide the best value to the customer are all as a speaker at various electric power industry conferences.
things to consider when specifying testing for Bruce was recently appointed as an alternate to the NEC -
dry-type cast coil transformers. Code Panel 10.

Industrial Electric Testing, Inc.


EC13004105 • 24 Hour Emergency Service
ACCEPTANCE AND MAINTENANCE TESTING AND REPAIR
• Cables • LV/MV Switches • Reclosers
• LV/MV Circuit Breakers • Relays - All Types • Surge Arresters
• Rotating Machinery • Motor Control Centers • Capacitors
• Meters • Grounding Systems • Batteries
• Automatic Transfer Switches • Transformers • Ground Fault Systems
• Switchgear and Switchboard • Insulating Fluids • Equipotential Ground
Assemblies • Thermographic Surveys Testing

CoNSulTING AND ENGINEERING SERvICES


• Load Studies • Harmonic Investigation
• Transient Voltage Recording and Analysis • Replacement of Insulating Fluids
• Electromagnetic Field (EMF) Testing • Power Factor Studies

11321 West Distribution Avenue • Jacksonville, Florida 32256 • (904) 260-8378


201 NW 1st Avenue • Hallandale, Florida 33009 • (954) 456-7020

Potrebbero piacerti anche