Sei sulla pagina 1di 10

by Adam Neville

Core Tests:
Easy to Perform, Not
Easy to Interpret
first place the value of the load in than specified. But there may be
Newtons (or pounds), under which other reasons: the cylinders may
failure by crushing occurs, which is have been incorrectly consoli-
then to be divided by the cross- dated (compacted); they may have
sectional area of the core in square been damaged in transit, subjected
millimeters (or square inches). to freezing at a very early age,
Dividing the first of these by the badly cured, or incorrectly tested;
second gives a number in or the resulting compressive
megapascals (or psi); but does this strength may have been incorrectly
number represent the compressive calculated or recorded.
strength of concrete in the struc- The contractor has reasons to
ture from which the core was cut? suggest that it is the cylinders that
The answer is no. Not only must are unsatisfactory, while the
the number be processed, but the concrete in the structure is as
resulting value of strength also specified. On the other hand, the
must be carefully interpreted. engineer has a professional respon-

M any engineers have the


experience of ordering the
taking of cores. The operation is
Because cores are generally taken
when there is a problem, or sus-
sibility to ensure the structural
adequacy of the concrete, as well
pected problem, with concrete, the as a responsibility to the client (or
not difficult, usually undertaken by situation usually involves two or owner) to ascertain that the
skilled specialist personnel. Once more parties, and they may have quality of concrete corresponds to
cut out of the concrete structure, different views of what is an the price paid.
the cores are sent to a testing appropriate interpretation of the It may also happen that while
laboratory for determination of core test results. the strength of test cylinders is
compressive strength, and some- satisfactory, there are suspicions
times for other tests, generally Why take cores? that the concrete being placed in
petrographic in nature. The deter- The taking of cores most com- the actual structure has segregated
mination of strength is quite monly occurs when the results of or has been inadequately consoli-
similar to the determination of tests on standard test cylinders to dated. This can be resolved by the
compressive strength of standard determine the 28-day compressive inspection and testing of cores.
test cylinders, and yields in the strength indicate noncompliance There are other situations where
with the specification. Such taking cores may be desirable, or
This point of view article is pre- noncompliance may be due to the even essential. For example, it may
sented for reader interest by the fact that the concrete that was be required to subject an existing
editors. However, the opinions placed in a given part of the structure to heavier loads than
expressed are not necessarily those of structure, as well as in the test hitherto; or a change of use may be
the American Concrete Institute. cylinders, is indeed noncompliant proposed, and the load-carrying
Reader comment is invited. because its 28-day strength is lower capacity of the structure needs to

Concrete international / NOVEMBER 2001 59


be verified; or it may be necessary be acceptable to the contractor in I have encountered problems
to ascertain that the strength of preference to the wholesale with testing plans in countries
concrete has not been impaired by removal of the concrete already other than the U.S., and, because
overloading or by fatigue, fire, placed and replacement by new Concrete International has a large
explosion, chemical attack, or concrete. There is a benefit to the worldwide readership, I feel that
some other deleterious agent. owner, too: the considerable delay they should be aired. Accordingly, I
due to removal and replacement is would like to refer to European
Where to take avoided. It can be noted in passing Standard (which is also a British
the cores? that a contractual provision for Standard) BS EN 12504-1:2000.3
The decision on this depends on penalty payment for concrete with Because this standard was first
the question to which the engineer a strength lower than specified, but published in 2000, it is not yet well-
wishes to have an answer. Several accepted by the engineer, is likely known. It is likely, however, that
questions are possible. The two to have a salutary effect on the the standard will be used either as-
most common are: does the con- contractor’s efforts with respect to is or in a modified form not only in
crete comply with the specifica- the quality of concrete.1 Europe but also elsewhere, mainly
tion? and, what is the compressive in Commonwealth countries.
strength of concrete in the struc- How to decide on a An important feature of BS EN
ture in general? To answer this, testing plan? 12504-1 is that it says explicitly
cores should be taken at a number I have already referred to the what it does not cover. The Fore-
of locations spread over the whole need for a clear decision on the word states: “The standard … does
structure. But there is a caveat: location of the cores to be taken. In not consider a sampling plan.”
concrete in the uppermost part of my opinion, this has to be taken by Notes to the section headed “Scope”
any member or concrete lift is a structural engineer, and not left say: “The standard does not give
nearly always weakest and, there- to the person on the job. This guidance on the decision to drill
fore, nonrepresentative. requirement is obvious, perhaps so the cores or on the locations for
There may also be this question: obvious that it is not considered to drilling” and “This standard does
is the strength of the particularly be worthy of explicit instructions not provide procedures for inter-
highly-stressed parts of the struc- in codes of practice. The Commen- preting the core strength results.”
ture adequate? In such a case, the tary on ACI 318, Section R5.6.5 These deliberate omissions mean
locations for core-taking should be wisely says: “The building official that it is the structural engineer
carefully chosen so that the load- should apply judgment as to the involved in the core exercise who
carrying capacity of the structure significance of low test results and should decide on such matters. I
is not impaired by removing some whether they indicate need for believe this is important because I
concrete from the place where it is concern.”2 The same section says: have encountered cases where the
most needed. It follows that only “Lower strength may, of course, be testing laboratory interprets the
an engineer familiar with structural tolerated under many circum- results of core tests vis-à-vis the
action can identify the appropriate stances, but this again becomes a specification for construction and
locations. matter of judgment on the part of vis-à-vis structural safety. The
An engineer would also be aware the building official and design demarcation between testing and
of where to test to answer the engineer.” 2 structural interpretation should be
question: is the strength adequate This approach is right and carefully maintained.
for the actual loading system?, proper, but ACI 318 is not normally With respect to the choice of the
even if the strength is not adequate consulted by a testing contractor location of the cores, ACI 318 says
for the designed loading system. In who is more concerned with ASTM that cores may be drilled from the
other words, if the structure is not C 42-99, “Standard Test Method for area suspected of having a low
adequate for the original design Obtaining and Testing Drilled strength, and expects the core
situation, is it strong enough for Cores and Sawed Beams of Con- tests to represent that area.2 British
more modest loading? The owner crete.” Quite rightly, the ASTM Standard BS 6089:1981,4 while
may be willing to compromise in standard does not concern itself giving no guidance on the selec-
such a manner, perhaps by being with the testing location and plan, tion of locations of cores, proffers
recompensed by a lower price for or with the interpretation of test important advice in clause 4.2:
the work done than stated in results. It is in these respects that I “Before any programme [of testing]
contract. Such a solution may well have seen problems arise. is commenced, it is desirable that

60 NOVEMBER 2001 / Concrete international


there is complete agreement
between the interested parties on
the validity of the proposed testing
procedure, the criteria for accep-
tance…”
Following this wise advice
obviates subsequent hassle over
the interpretation of the core test
results. The “agreement” referred to
above should not be simply a
compromise between the engineer
and the contractor; it must take
into account the questions that
the engineer wishes to have
answered. European Standard BS
EN 12504-1 states explicitly in
clause 5.1: “It is essential that full
consideration is given to the aims
of the testing and the interpreta-
tion of the data, before deciding to
drill the cores.”3 The word before Fig. 1: Effect of L/D on the strength of test cylinders. 6 The 28-day strength at L/D = 2
should be noted. in MPa (psi) is: A, 14 (2000); B, 26 (3700); C, 52 (7500)

Why should length- 1.6 (see Fig. 1). The reasons for this the case, I am of the opinion that a
diameter ratio be 2? situation lie in the mode of failure cylinder (molded or a core) with
The simple answer to this of the test specimen: in a squat the value of L/D = 1 has approxi-
question is: because this is the specimen, the restraining effect of mately the same strength as a cube
value of the length-diameter ratio the platens of the testing machine whose edge is equal to the diam-
(L/D) of a standard cylinder. is much more significant than in a eter of the cylinder.
However, more should be said. In more slender specimen. In other
particular, it is worth giving the words, the use of correction factors What are the correction
reasons for the choice of L/D = 2 as necessary to normalize the test factors for L/D ?
a standard. It is also worthwhile to results to the value of strength of a The use of correction factors to
discuss the situation in cores, standard specimen is greater at “convert” the strength determined
because, unlike a test cylinder smaller values of L/D; it is clearly on a test specimen with a given
where the mold controls the value preferable to minimize the need for value L/D to the strength that
of L/D, the choice of the value of L/ correction factors. would be obtained in a test on a
D lies in the hands of those in- The use of cores with the value specimen with L/D = 2 is well
volved in testing. of L/D = 2 is appropriate only when known. But how good are those
Test programs that led to the standard molded test cylinders factors?
choice of L/D = 2 go back a long have that value. In countries using Murdock and Kesler tell us that
time. In 1925, Gonnerman wrote: cubes, the core should preferably the factors are a function of the
“The 6 by 12-in. cylinder is now have L/D = 1; this is recommended level of strength of the concrete.6
generally used for compression in European Standard BS EN 12504- Specifically, stronger concretes are
tests.”5 Supporting arguments for 1:2000, which caters both to less affected by the value of L/D
the choice of L/D = 2 were given by countries using cylinders and to than concretes of lower strength;
Murdock and Kesler in 1957.6 In those using cubes.3 In the United this is shown in Fig. 1. According to
essence, they showed that the Kingdom, which uses cubes, BS ASTM C 42-99, concretes with
variations in the calculated com- 6089:1981 requires the value of L/D strengths above 70 MPa (10,000
pressive strength of a cylinder were to be not less than 0.95 before psi) are even less affected by the
small for L/D values in the vicinity capping, and not more than 1.3.4 value of L/D. It follows that the
of 2, and were more pronounced Although it has not been correction factors tabulated in
for values between about 1.0 and unequivocally demonstrated to be ASTM C 42 and by other standards

Concrete international / NOVEMBER 2001 61


Table 1: cores with L/D = 0.5; cores with a
Correction factors for L/D according to ASTM C 42* diameter of 6 in. (150 mm) were
extracted from slabs 4-in. (100 mm)
thick or even thinner. Testing such
cores could be easily avoided
either by taking cores with a
ASTM C 42
smaller diameter or by subse-
quently subcoring the larger cores.
Admittedly, there remains the issue
of the minimum diameter of the
core to be tested in compression.
Of course, there is no problem
with cores that are too long: they
can be cut so as to achieve the
value of the ratio of the capped
length to diameter of between 1.9
and 2.1, described as preferred by
ASTM C 42. It is only when L/D is
less than 1.8 that a correction
factor needs to be applied.
Although it is not always stated
explicitly, the various correction
factors for L/D apply to normal-
weight concrete only. According to
ASTM C 42-99, they apply also to
lightweight concrete with a density
are in reality typical values or of the moisture condition of the between 100 and 120 lb/ft3 (1600
average values. Using a single set of core at the time of testing.7 All this and 1999 kg/m3). However, there is
correction factors, such as that militates against the use of cores some uncertainty about correction
given by ASTM C 42, may overcor- with varying values of L/D coupled factors for concretes of lower
rect the test results on cores with a with reliance on correction factors. density. 8
small value of L/D drilled from low- There is one other important
strength concrete; and yet, it is for observation in the paper by What size of cores?
this type of concrete that an Murdock and Kesler, derived from It is considered preferable to use
estimate of strength may be par- earlier tests: “the data on the cores with a diameter of 6 in.
ticularly important. We can see specimens whose L/D was less than (150 mm), with the alternative of
thus that the use of correction 0.5 were erratic.”6 This situation is 4 in. (100 mm) being acceptable.
factors increases the uncertainty apparent in Fig. 1. Other tests ASTM C 42-99 prescribes a mini-
about the strength of the concrete showed that the “correction factor” mum diameter of 3.75 in. (95 mm). It
being tested, as compared with a for L/D = 0.5 was 1.98 for 21 MPa allows the use of smaller diameters
situation where all the cores have (3000 psi) concrete and 1.68 for when it is impossible to obtain a
L/D = 2. In other words, if at all 31 MPa (4500 psi) concrete.5 A core with L/D of at least 1, but only
possible, tests should be per- value as high as 2.09 is quoted by for “cases other than load-bearing
formed on cores with L/D = 2. Murdock and Kesler.6 It is not situations.”
It is interesting to note that even surprising, therefore, that BS According to ASTM C 42, the
the same standard, namely ASTM C 6089:1981 states: “Little reliance minimum diameter of the cores is
42, in its various editions, gives can be placed on results obtained governed by the maximum aggre-
somewhat different sets of correc- on cores having length/diameter gate size: it “should preferably be
tion factors. These are shown in ratio of less than 0.5.”4 at least three times the nominal
Table 1, based on a paper by My conclusion from the preced- maximum size of the coarse aggre-
Bartlett and MacGregor.7 As they ing discussion is that cores with L/D gate and must be at least twice the
pointed out, the “true” value of the smaller than 1 should never be nominal maximum size…” Euro-
correction factor may be a function used, and yet I have seen the use of pean Standard BS EN 12504-1:2000

62 NOVEMBER 2001 / Concrete international


Table 2: directed by the specifying author-
Effect of maximum aggregate size (m.a.s) and core diameter on measured strength ity.” There is a section in ASTM C 42
(based on ref. 3)
that allows this authority freely to
choose any moisture condition. I
would like to emphasize the
provision for the decision by the
“specifying authority,” which
usually is the project engineer.
In the absence of a specially
chosen moisture condition, ASTM
C 42 provides for two conditions.
One of these is the “as received
condition,” which requires drying
for 12 to 24 hours at a temperature
of 60 to 80 F (16 to 17 C) and a
relative humidity below 50%. The
second condition is the “dry
simply says that, when the core proponents of the use of cores condition,” which requires drying
diameter approaches a value that with a diameter as small as 1.2 in. at the same temperature but at a
is less than 3 times the maximum (30 mm), even when the maximum relative humidity below 60% for
aggregate size, there is “a signifi- aggregate size is 3/4 in. (20 mm).11 seven days.
cant influence on the measured The confidence limits of the The significance of the careful
strength.”3 An Annex to this predicted strength of test cubes control of the moisture condition
Standard gives the relevant data, from the strength of such small of the core at the time of testing
from which Table 2 has been cores are very wide, and I, for one, lies in the fact that this condition
derived. remain skeptical about the inter- influences the apparent strength
The reason for the limitations pretation of the test results of of the core; broadly speaking, wet
on the core size is that, unlike a compressive strength of such cores record a lower strength
molded cylinder, in a core some small cores. It has also been than dry cores. The problem is
coarse aggregate particles are cut reported that the correction factor that the difference is variable and
in the drilling process and are, for the value of L/D is dependent uncertain.
therefore, not wholly bonded to on the diameter of the core.12 This article does not purport to
the cement paste matrix. The present a literature review, and I
adverse effect of incomplete bond Which moisture shall limit myself to the work by
is aggravated by the difference in condition? Bartlett and MacGregor.13 They
the modulus of elasticity between Cores are usually obtained using found that, on average, the
the aggregate and the cement water-cooled drills with diamond strength of cores dried in the air for
paste.9 When a significant propor- bits attached to a core barrel so 7 days is 14% higher than the
tion of coarse particles is in that that, when extracted from the strength of cores soaked in water
state, some of them may become parent concrete, the cores are for at least 40 hours. The value of
partially loosened during the test superficially wet. The interior of 14% appears to apply over the
and cease to carry their share of the core may be wet or dry, depend- range of strengths from 15 to 92 MPa
the applied load.8 When this ing on the situation of the concrete (2200 to 13,400 psi). The crucial
happens, a lower value of com- in service. The question to con- words are “on average” because the
pressive strength is recorded. An sider is: in which moisture condi- scatter about the 14% difference is
indirect evidence of such behavior tion should the cores be tested to considerable.
is offered by Malhotra, who found ascertain their compressive Bartlett and MacGregor point
that cores with a smaller diameter strength? Different standards and out that the actual situation is
exhibit a higher variability.10 This guides offer differing views. ASTM C more complex than “dry” and “wet”:
situation is recognized in the 42-99 states that the cores “shall be what influences the magnitude of
assessment of precision of tests on tested in a moisture condition the difference in strength of cores
cores of various sizes. representative of the in-place in the two conditions is the pres-
Nonetheless, there are some concrete” or alternatively “as ence of a moisture gradient

Concrete international / NOVEMBER 2001 63


between the exterior and the What else affects Drilling cores in a horizontal
interior of the core.13 In the ab- core strength? direction introduces another
sence of such a gradient, the It has been observed that when factor influencing the strength of
difference is not 14% but only 9%. drilling is performed in the the core. This factor is not related
They state “that the effect of 7 horizontal direction the resulting to coring but (as already men-
days of air drying is to cause a strength is lower than for cores tioned) is the consequence of the
moisture gradient that artificially drilled vertically downward. A inherent variation in strength of
increases the strength of the likely reason for this is that, concrete in the vertical direction
specimen by about 5% above the whereas drilling downward allows of a concrete member or a lift,
true in situ strength.”13 Personally, the drill to be fixed and held caused by an increase in the
I do not accept that any core test firmly in position, drilling hori- actual water-cement ratio in the
gives us the value of “the true in zontally almost inevitably permits uppermost layers of concrete.
situ strength.” In a later paper, a slight movement of the drilling Such differences should not be
Bartlett and MacGregor reported barrel, even when holding-down “corrected” but should be recog-
that the apparent reduction in bolts locate the drill. The conse- nized as a fact of life. A usual way
strength of wet cores is greater in quences of such movement to avoid this effect is not to take
cores with diameters of 2 in. (50 mm) during drilling may be seen as cores in the uppermost part of the
than in larger cores.14 shallow corrugations on the concrete member.
For these reasons, I am of the surface of the core.
opinion that mimicking the
What happens in
Another possible reason for the
moisture conditions in service is slipformed concrete?
difference between cores drilled
too elusive to be useful. In any Slipformed concrete presents a
vertically and horizontally can be
case, the strength of the core as special case. In my opinion, in
sought in the presence of bleed
determined by the compression water. Such water would have no such concrete there is no increase
test does not represent the actual effect when the load applied in the in the water-cement ratio with
strength of the concrete in the compression test is normal to the height because the apparent
structure in a meaningful way. lenses of water trapped under- upward movement of water
What the test result gives us is a neath coarse aggregate particles, occurs continuously and steadily,
value that has to be interpreted by but the lenses of bleed water owing to the slow progress of
the engineer who has to take into parallel to the axis of the core placing of concrete. For this
consideration a number of factors might result in some weakening. reason, I would not expect the
relevant to the core as well as to A reduction in strength of 8% of formation of lenses of trapped
the history of the concrete in the value for vertical cores has bleed water. A consequence of
service. I shall discuss this topic been suggested:9 this is probably this situation is that there would
more fully later. the best correction factor that we be no lowering of the apparent
Overall, then, I favor testing have, but it cannot be assumed to strength of concrete in cores
cores after immersion in water for be universally valid. In fact, drilled horizontally.
a period long enough to prevent Bartlett and MacGregor found that This direction of drilling of
the presence of moisture gradi- the direction of the core axis cores is inevitable in a silo in
ents. The advantage of this condi- relative to the direction of casting service. However, I encountered an
tion is that it is much more repro- has no effect on the strength of exception when a slipformed silo
ducible than a so-called dry cores taken from high-strength was demolished, and parts of the
condition, where the degree of concrete.14 Some support of my silo walls were laid horizontally on
dryness is uncertain, so that doubts about the general use of a the ground. Cores were then taken
accidental variations in condi- correction factor for horizontally- by drilling horizontally, that is, in
tions can arise. In this connection, drilled cores is given by the recent the direction of placing of con-
we can note that European Stan- European Standard BS EN 12504- crete. In consequence, although
dard BS EN 12504-1 says: “If it is 1:2000, which makes no reference the core is drilled horizontally, the
required to test the specimen in a whatsoever to the direction of core axis is parallel to the direc-
saturated condition, soak in water drilling.3 This is in contrast to tion of placing of concrete. It is
at 20 ± 2 C (± 4 F) for at least 40 British Guide BS 6089:1981, which therefore difficult to say whether
hours before testing.”3 enhances the strength of horizon- such a core should be classified as
tal cores by 8.7%.4 horizontal or vertical.

64 NOVEMBER 2001 / Concrete international


What is the effect of steel?
Another potential factor influ- “The demarcation between testing and structural
encing the testing of cores and
their apparent strength is the interpretation should be carefully maintained.”
presence of reinforcing steel within
the core. It is obvious that rein- requirements because I have seen its appearance.
forcement should be avoided results on tests on cores with a According to Concrete Society
wherever possible; on the other value of L/D as low as 0.5. Clearly Report No. 54,17 the 95% confidence
hand, in some structures, the such tests for the splitting tensile limits on the estimate of actual
density of reinforcement is so great strength cannot be considered to strength of the cores are as follows:
that it may be impossible to avoid conform to ASTM C 42-99. I have ±12% of the value determined on a
it. If this is the case, there is a discussed the broader question of single core, and ±6% of the average
serious risk of adversely affecting arbitrary modification of ASTM value of four cores. Overall, the
the structural integrity of the given standard tests in an earlier article.16 confidence limits are inversely
structural member by coring proportional to the square root of
through the steel. I believe that, in Why is it not easy to the number of cores tested. These
such a situation, coring should not interpret core tests? figures mean that, when the value
be resorted to, and nondestructive This assertion is included in the determined by test is X, there is a
methods of testing should be used. title of this article, but, at this 95% probability that the “true”
If, for whatever reason, cores cut stage, the reader might be sur- value lies within 12 and 6%,
through steel bars, then the cores prised: after all, I have discussed respectively, of the value deter-
can be tested for compressive the various factors influencing the mined in the test. This situation
strength, but only if there are no strength of cores and the relevant should be borne in mind when
steel bars parallel to the axis of the correction factors. It could, there- someone tries to argue that, say, a
core; this requirement is laid down fore, be thought that all that is value of 27 MPa determined on a
in European Standard BS EN 12504- needed is to apply the various single core indicates that the
1:2000.3 British Guide BS 6089:19814 correction factors and, presto, we expected value of 30 MPa has not
and also the Concrete Society arrive at the compressive strength been satisfied.
Report15 give correction factors for of concrete. The precision statement in
the presence of one or more What is the variability ASTM C 42 says that the results of
reinforcing bars in the core. The of strength? two tests (each being an average
British Guide adds that “the in-situ First of all, there is a scatter in of two adjacent cores) performed
strengths estimated from the the strength of cores even when by two laboratories should not
[given expressions] cannot be taken in close vicinity to one differ from each other by more
equated to standard cube another. Admittedly, there is also than 13% of their average. Euro-
strengths.”4 I view all this as militat- scatter in the strength of molded pean Standard BS EN 12504-1 gives
ing against the use of cores con- cylinders, but the scatter of no precision statement but ac-
taining reinforcing steel. strength of cores is larger because knowledges a greater variability of
coring itself introduces variability. cores than of molded specimens.3
How to test for splitting It may be worth repeating that, Which strength?
tensile strength? however carefully performed, the The first question is: what is
ASTM C 42-99 also provides for coring operation causes some meant by strength? It is sometimes
testing cores to determine the damage to the core: there may be a forgotten that the intrinsic or
tensile splitting strength. The weakening of the bond of large “true” strength of concrete cannot
requirements with respect to the particles of aggregate near the be measured. By “intrinsic” I mean
cores themselves are the same as surface of the core, and there may the strength of concrete that is
for compression testing, with the be a dynamic effect of drilling, independent of the characteristics
exception that capping is not to be which induces some fine cracks. It of the test specimen.
applied. It follows thus that the is, therefore, best to test more than We know that the strength of
value of L/D must not be greater one core, but this may not be molded test cylinders cured,
than 2 and must not be smaller desirable or even possible. The treated, and tested under standard
than 1. However, no correction for coring operation is expensive, and conditions (such as those of ASTM
L/D is required. I am stating these it may disturb the structure or mar C 31) represents, at best, the
Concrete international / NOVEMBER 2001 65
strength of concrete under pre- Here is my opportunity strongly to want to know how good the
cisely those conditions. I am dispute the dictum of those who concrete in the structure is. This
saying “at best” because the value say that a single test is worth more difference is crucial to the interpre-
of strength actually determined than a thousand words. In my tation of the value of strength
applies only to the type of speci- opinion, this is not correct. determined on the cores.
men used. For other types of This may be an appropriate How not to use the
specimen, say a cube, the strength place to define potential strength correction factors?
recorded would be different, and actual strength. Potential It could be expected that the
whereas the intrinsic strength of strength is the strength determined discussion of various factors
concrete is, of course, the same. on standard molded cylinders in influencing the strength of cores
In the case of cores, the situa- accordance with a standard earlier on in this article would
tion is much more complicated. procedure, such as that of ASTM C 31. make it possible to apply various
The cores are taken from concrete The cylinders will have been made correction factors so as to “con-
in situ, whose history is most as well as possible in terms of vert” the test result into a value of
unlikely to replicate the treatment consolidation and cured under either potential or actual strength.
of standard molded specimens, and constant conditions of tempera- Alas, this is not so.
the age of the cores is usually ture and humidity. In consequence, First, let me deal with the
greater, even significantly greater, the compressive strength recorded various correction factors. I have
than 28 days. is the “best” that the given mixture tried to point out that the factors
So, in interpreting the test result can achieve. Clearly, I am excluding are, at best, average values; some-
times, they are a compromise
value. It follows that a given
“I am, therefore, firmly of the opinion that a correction factor may not be
entirely appropriate in the case of
wholesale application of correction factors is the actual mixture used.
More than that: even when the
highly undersirable.” factor is appropriate, it is an
average value around which there
obtained by compression testing of the possibility of steam curing or is some scatter. Thus, it is possible
cores, we have to start with this the application of pressure in that in a particular case the correc-
question: which type of strength making the cylinder. tion factor used is excessive. It is
are we interested in? Broadly On the other hand, the actual possible that another correction
speaking, there are two types: strength is the strength of concrete factor is also excessive. As I see it,
potential strength and actual in place. Consequently, the consoli- applying several factors, one after
strength. We should know the dation has been less good than in a another, is a risky operation that
answer to this question prior to test cylinder: there are bound to be reduces the accuracy of the predic-
testing; it cannot be overempha- some excess voids. The curing has tion. I am saying this because I
sized that taking cores and testing been less good because the con- have seen a situation where the
them is of value only if we can crete in the interior of the struc- value of compressive strength on a
interpret the results in a meaning- ture could not be kept continu- core was sequentially corrected for
ful and unequivocal manner. ously wet. Likewise, the tempera- the value of L/D, then for the
Otherwise, the dispute about the ture was not kept constant. It diameter of the core, and finally
quality of concrete that led, in the follows that, at the age of 28 days, for the moisture condition; and
first place, to the decision to take the actual strength is lower than yet, we know that the effect of
cores is simply shifted to the stage the potential strength; under some moisture condition on strength is
after the cores have been taken. circumstances, the situation may greater in smaller cores than in
We should therefore heed the later on be reversed. larger ones. Therefore, the two
injunction in Concrete Society We can thus see that the poten- corrections should not be applied
Report No. 54, published in 2000, tial strength is of interest when we independently.
that states in bold letters: “No want to know that the mixture I am, therefore, firmly of the
measurements should be taken or used in construction conforms to opinion that a wholesale applica-
tests carried out if it is not known what is specified. The actual tion of correction factors is highly
what the results will be used for.”17 strength is of interest when we undesirable. If the objective of the

66 NOVEMBER 2001 / Concrete international


characteristic strength of concrete,
“It is well known that all testing involves errors due to to which the partial safety factor for
design strength is applied.4
chance...Careful performance of all tests, strict adherence ACI 318-99 applies the “85%
correction” to the compressive
strength of cores but remains silent
to standard test methods, and soundly-based judgment on the interpretation of tests on the
splitting tensile strength of cores. In
minimize the element of luck.” my opinion, the “85% correction”
should be applied to the splitting
test were to determine, say, the No. 11 simply states that the tensile strength as well because the
strength of a core with L/D = 2, a estimated potential strength is 1.3 factors responsible for this correc-
diameter of 4 in. (100 mm), and in a times larger than the estimated tion apply equally in splitting
moist condition, then this is how actual strength.15 This is unlikely to tension and in compression.
the core should have been taken be universally correct because, as Moreover, without a parity of
and tested. If this was physically ASTM C 42 says, “There is no univer- application of the correction, the
impossible, then the outcome of the sal relationship between the com- ratio of splitting tensile strength to
test should have been compared pressive strength of a core and the the compressive strength appli-
with a core from concrete with corresponding compressive strength cable to molded cylinders would
known properties and with charac- of standard-cured molded speci- become distorted in the case of
teristics similar to those of the test mens.” To my way of thinking, it cores; there is no rational reason for
core. On occasion, this may not be follows that there is no such univer- such a distortion.
possible, in which case cores are sal relationship between the esti-
not an appropriate method of Who decides?
mated strength of molded specimens The merits of this simple ap-
resolving the given problem. and the core strength. proach cannot be overemphasized,
Can we determine the I find the approach of ACI 318-992 but a party to a dispute may seek to
potential strength? and of ACI 301-9918 to be preferable. manipulate the test results to its
In seeking to “convert” the They both say that concrete shall be advantage. Before it does so, it
strength established by testing the considered adequate (which I would do well to read Malhotra’s
cores into the potential strength of understand to mean “as specified”) paper, in which he says: “The
the given mixture, attempts are when “the average of three cores is available test data on cores are full
sometimes made to allow for the equal to at least 85% of f′c and no of contradiction and confusion.”10
age and curing history of the single core is less than 75% of f′c.”2 No He also cites Bloem:18 “Core tests
concrete in the structure. I believe allowance for age or curing history is made to check adequacy of strength
that this is an uncertain operation mentioned. This approach is robust in place must be interpreted with
because this history is rarely and has the merit of simplicity. The judgment. They cannot be trans-
known reliably. Moreover, any Commentary on ACI 318-99 is persua- lated to terms of standard cylinders
possible incomplete compaction sive; it says, “Core tests having an strength with any degree of confi-
requires a correction as well, and average of 85% of the specified dence, nor should they be expected
this is not easy. I realize that excess strength are entirely realistic. To necessarily to exceed the specified
voidage can be assessed visually expect core tests to be equal to f′c is strength f′c.”18
and that the density of a concrete not realistic, since differences in the Bloem’s reference to “judgment”
specimen is affected by the pres- size of specimens, conditions of and the reference in the Commen-
ence of voids, but correcting for obtaining samples, and procedures tary in ACI 318-99 to “judgment on
these may induce a large error for curing, do not permit equal the part of the building official and
because 1% of voids reduces the values to be obtained.”2 A difficulty design engineer” lead me to empha-
compressive strength by 5%.9 that sometimes occurs is that fewer size that such judgment is not the
Because of these uncertainties, a than three cores are available. province of the testing laboratory.
rough-and-ready approach is The value of 85% in ACI 318-99 is Perhaps this approach is observed in
sometimes used; this may be no not very different from the value the U.S., but elsewhere I have seen
less reliable than fine tinkering used in BS 6089:1981, which re- technicians who, after reporting the
with corrections for individual quires the “estimated in-situ cube results of core tests, yield to the
factors. Concrete Society Report strength” to be 83% of the specified temptation to express views about

Concrete international / NOVEMBER 2001 67


structural adequacy; to do so, the cases where there are doubts 10. Malhotra, V. M., “Contract Strength
expertise of the structural engineer about the quality of concrete in a Requirements — Cores Versus In Situ
is essential. structure. Such a situation arises Evaluation,” ACI Journal, April 1977, pp.
It must be re-emphasized that from time to time, and taking and 163-172.
11. Indelicato, F., “A Statistical Method
testing and interpretation of test testing cores may be an effective
for the Assessment of Concrete Strength
results are distinct operations. My way of resolving the problem.
Through Microcores,” Materials and
view is supported by ACI 301-99, Nevertheless, as we strive to make Structures, V. 26, 1993, pp. 261-267.
which states: “Core test results will better concrete and to ensure that 12. Naik, T. R., “Evaluation of Factors
be evaluated by Architect/Engi- it complies with the specification, Affecting High-Strength Concrete Cores,”
neer and will be valid only if tests we should reduce the need for core Proceedings of the First Materials Engineering
have been conducted in accor- tests and, hopefully, reach the Congress Part I, Denver, 1990, pp. 216-222.
dance with specified procedures.”18 situation in Mark Twain’s Tom 13. Bartlett, F. M., and MacGregor, J.
As for the next step, if necessary, BS Sawyer Abroad (admittedly, con- G., “Effect of Moisture Condition on
6089:1981 says, “Action to be taken cerned not with concrete but with Concrete Core Strengths,” ACI Materials
in respect of a structural member Journal, V. 91, No. 3, May-June 1994,
apples) in which “there ain’t-a-
pp. 227-236.
in which the in situ concrete is going to be no core.”
14. Bartlett, F. M., and MacGregor, J. G.,
considered to fall below the level References “Cores from High-Performance Concrete
required has to be determined by 1. Bartlett, F. M., and MacGregor, J. G., Beams,” ACI Materials Journal, V. 91, No. 6,
the engineer.”4 “Statistical Analysis of the Compressive Nov.-Dec., 1994, pp. 567-576.
Strength of Concrete in Structures,” ACI 15. Concrete Society, “Concrete Core
Can we reduce the use Materials Journal, V. 93, No. 2, March-April Testing for Strength,” Concrete Society
of cores? 1996, pp. 158-168. Technical Report No. 11, 1976, 44 pp.;
It is well known that all testing 2. ACI Committee 318, “Building Code Addendum, 1987, pp. 45-59.
involves errors due to chance; Requirements for Structural Concrete (318- 16. Neville, A. M., “Standard Test
indeed, it is chance that is respon- 99) and Commentary (318R-99),” American Methods: Avoid the Free-For-All!,”
Concrete Institute, Farmington Hills, Mich., Concrete International, V. 23, No. 5, May
sible for the stochastic distribution
1999, 391 pp. 2001, pp. 60-64.
of strength of concrete test speci-
3. European Standard BS EN 12504- 17. Concrete Society, “Diagnosis of
mens about the mean value. This Deterioration in Concrete Structures,”
1:2000, “Testing Concrete in Structures —
distribution is reflected in the Part 1: Cored Specimens,” 8 pp. Concrete Society Technical Report No. 54,
coefficient of variation of test 4. British Standards Institution, BS 2000, 68 pp.
results. Errors are distinct from 6089:1981, “Guide to Assessment of Concrete 18. ACI Committee 301, “Specifications
mistakes caused by action, or Strength in Existing Structures,” 11 pp. for Structural Concrete (ACI 301-99),”
absence of action, by the operator. 5. Gonnerman, H. F., “Effect of Size and American Concrete Institute, Farmington
So, chance — or in common Shape of Test Specimen on Compressive Hills, Mich., 1999, 43 pp.
parlance, luck — plays a role in Strength of Concrete,” Proceedings ASTM 19. Bloem, D. L., “Concrete Strength
Part 2, 1925, pp. 237-255. Measurement — Cores Versus Cylinders,”
testing.
6. Murdock, J. W., and Kesler, C. E., Proceedings ASTM, V. 65, 1965, pp. 668-696.
Careful performance of all tests,
“Effect of Length to Diameter Ratio of
strict adherence to standard test Selected for reader interest by the
Specimen on the Apparent Compressive
methods, and soundly-based editors.
Strength of Concrete,” ASTM Bulletin, April
judgment minimize the element of
1957, pp. 68-73.
luck. As Jack Nicklaus (who has 7. Bartlett, F. M., and MacGregor, J. G.,
never played on a concrete golf “Effect of Core Length-to-Diameter Ratio on
course like the one on Das Island in Concrete Core Strengths,” ACI Materials
the Arabian Gulf) is supposed to Journal, V. 91, No. 4, July-August 1994, pp.
have said: “People tell me I am 339-348. ACI Honorary Member Adam Neville has
lucky. The funny thing is the harder 8. McIntyre, M., and Scanlon, A., recently been awarded the ACI Henry C.
“Interpretation and Application of Core Turner Medal “in recognition of his
I practice the luckier I get.” When
Test Data in Strength Evaluation of Existing contributions to the concrete industry
we make concrete we should try
Concrete Bridge Structures,” Canadian through extensive research and compre-
harder, so that the need for tests on hensive experience as a teacher, author,
Journal of Civil Engineering, V. 17, 1990,
cores is rare. and consultant.” At about the same time,
pp. 471-480.
Nevertheless, perfection is he was elected an Honorary Member of
9. Neville, A. M., Properties of Con-
unachievable, and this article has crete, 4th Edition, John Wiley and Addison the Concrete Society in the United
considered the use of cores in Wesley Longman, 1995, 844 pp. Kingdom.

68 NOVEMBER 2001 / Concrete international

Potrebbero piacerti anche