Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
1
NFPA 72 Chapters – Currently in 2007 Administrative Chapters
Chapters 1 – 4 Administration, Definitions & Chapter 1 Administration – 2007 Existing
Fundamentals Chapter 2 Referenced Publications – 2007 Existing
Chapter 5 – Initiating Devices Chapter 3 Definitions – 2007 Existing
Chapter 6 – Protected Premises Fire Alarm Systems Chapter 4 Reserved
Chapter 7 – Notification Appliances Chapter 5 Reserved
Chapter 8 – Supervising Stations Chapter 6 Reserved
Chapter 9 – Public Fire Alarm Reporting Systems Chapter 7 Reserved
Chapter 10 – Inspection, Testing & Maintenance Chapter 8 Reserved
Chapter 11 – Single & Multiple Station Alarms Chapter 9 Reserved
Household Systems
2
Fundamentals Fundamentals
Chapter 10 Chapter 10
The Chapter has been renamed 10.4 Personnel Qualifications.
Fundamentals. “Fire Alarm” deleted. 10.4.1 System Designer.
The Chapter includes requirements for
Emergency Communications Systems. 10.4.2 System Installer.
The word “fire” has been removed throughout 10 4 3 IInspection,
10.4.3 i T
Testing,
i and
d Maintenance
M i
in relation to fire alarm systems, as the Code Personnel. (SIG-TMS)
also covers Emergency Communications 10.4.4 Supervising Station Operators. (SIG-
Systems. SSS)
Fundamentals Fundamentals
Chapter 10 Chapter 10
10.5.6.1.2 Secondary circuits that provide power 10.5.6.3 Capacity
to the control unit and are not integral to the unit 10.5.6.3.1.(A) Battery calculations shall include a
shall be protected against physical damage. 20 percent safety margin to the calculated amp-
Added the protection of secondary power hour rating
circuits. This provides alignment with UL 864 9th
edition and the realization that over the life of
a battery, it will decay.
Fundamentals Fundamentals
Chapter 10 Chapter 10
10.6 Signal Priority. The priority of signals shall 10.15 Protection of Fire Alarm Systems.
be in accordance with 10.6 Exception (2) has been removed. This
10.6.1 ECS priority signals when evaluated by exempted the requirement for smoke or heat
stakeholders through a risk analysis in detector protecting the FACU,
FACU NAC’s
NAC s or
accordance with 12.2.2.12 shall be permitted to DACT’s if the building is fully sprinklered per
take precedence over all other signals. NFPA 13.
This includes fire alarm signals.
3
Fundamentals Fundamentals
Chapter 10 Chapter 10
10.18.2.1.2.7 Where not stored at the main fire 10.18.2.1.2.8 If the documents are located in a
alarm control unit, the location of these separate enclosure or cabinet, the separate
documents shall be identified at the main fire enclosure or cabinet shall be prominently labeled
alarm
a a cocontrol
o uunit. FIRE ALARM DOCUMENTS.
OCU S
Requires the location of the Record of Documents related to the fire alarm system
Completion to be identified at the FACU. can no longer be hidden until found by an
archeological expedition.
4
Circuits and Pathways - Circuits and Pathways -
Chapter 12 Chapter 12
12.4.2.1 Pathway Class Designations Class C. One or more pathways where
Pathways shall be designated as Class A, B, C, D, operational capability is verified via end-to-end
E, or X, depending on their performance as follows: communication, but the integrity of individual
Class A*. A pathway with a redundant path. paths is not monitored. A loss of end-to-end
O
Operational
ti l capability
bilit continues
ti pastt a single
i l communication
i ti iis annunciated.
i t d
break. Conditions that affect the intended operation Class D. A pathway that has fail-safe operation,
of the path are annunciated. where no fault is annunciated, but the intended
Class B. A pathway without a redundant path. operation is performed instead.
Operational capability stops at a break. Conditions
that affect the intended operation of the path are
annunciated.
5
Circuits and Pathways - Circuits and Pathways -
Chapter 12 Chapter 12
12.1.2.9 Pathway Survivability Level 3 c. Pathways in buildings fully protected an automatic
sprinkler system in accordance with NFPA 13, Standard
12.1.2.9.1 Pathway survivability Level 3 shall for the Installation of Sprinkler Systems and 2-hour fire
consist of the following: rated enclosure or protected area or,
a. Pathways in buildings fully protected an automatic d. Pathways in buildings fully protected an automatic
sprinkler
i kl system
t iin accordance
d with
ith NFPA 13
13, St
Standard
d d sprinkler
i kl system
t iin accordance
d with
ith NFPA 13
13, St
Standard
d d
for the Installation of Sprinkler Systems and 2-hour fire for the Installation of Sprinkler Systems and 2-hour
rated circuit integrity (CI) cable or, performance alternatives approved by the authority having
b. Pathways in buildings fully protected an automatic jurisdiction
sprinkler system in accordance with NFPA 13, Standard
for the Installation of Sprinkler Systems and 2 hour fire
rated cable system (electrical circuit protective
system(s)) or,
6
Inspection, Testing, and Maintenance Inspection, Testing, and Maintenance
Chapter 14 Chapter 14
14.2.4.2 The revisions of the fire alarm software, 14.2.7 Automated Testing.
and the revisions of the software in the systems 14.2.7.1 Automated testing arrangements that
with which the fire alarm software interfaces, provide equivalent means of testing devices to
shall be verified for compatibility in accordance those specified in Table 14.4.2.2 at a frequency
with
ith th
the requirements
i t off 23
23.2.2.1.1.
2211 at least equivalent to those specified in Table
14.4.5 shall be permitted to be used to comply
with the requirements of this chapter.
14.2.7.2 Failure of a device on an automated test
shall result in an audible and visual trouble
signal.
7
Inspection, Testing, and Maintenance Initiating Devices
Chapter 14 Chapter 17
Record of Inspection and Testing 17.4.6 Initiating devices shall be installed in all
Has been expended to 12 pages areas, compartments, or locations where
Includes mass notification system interface required by other NFPA codes and standards or
as required
equ ed by o other
e go
governing
e g laws,
a s, codes, oor
standards.
This replaces AHJ, and has been added
through the body of NFPA 72®.
8
Initiating Devices Initiating Devices
Smoke-Sensing Fire Detectors Smoke-Sensing Fire Detectors
17.7.1.11.3 Where detection is not required 17.7.3.2 Spot-Type Smoke Detectors
during construction they shall not be installed 17.7.3.2.1 Spot-type smoke detectors shall be
until after all other construction trades have
completed cleanup. located on the ceiling or, if on a sidewall,
between the ceiling and 12 in in. (300 mm) down
This is an expansion over previous text.
from the ceiling to the top of the detector.
The 4 inch restriction has been removed.
Initiating Devices
Spacing of Smoke Sensors Smoke-Sensing Fire Detectors
72, 2007 72, 2010 17.7.3.2.4.2 For level ceilings with beam depths
of less than 10 percent of the ceiling height (0.1
H), smooth ceiling spacing shall be permitted.
Spot-type
Spo ype ssmoke
o e de
detectors
ec o s sshall
a be pe
permitted
ed to
o
be located on ceilings or on the bottom of the
beams.
9
Initiating Devices Initiating Devices
Chapter 17 Chapter 17
17.10 Gas Detection. 17.10.2 Gas Characteristics and Detector
17.10.1 General. The purpose and scope of Selection.
Section 17.10 shall be to provide requirements 17.10.2.1 Gas detection equipment shall be listed
for the selection,
selection installation
installation, and operation of for detection of the specific gas or vapor to be
encountered.
gas detectors.
17.10.2.2 Any gas detection system installed on
a fire alarm system shall comply with all the
applicable requirements of Chapters 1,10,14,17
and 23 of this Code.
10
Notification Appliances Notification Appliances
Chapter 18 Chapter 18
18.4.10.1 Acoustically distinguishable spaces 3.3.2* Acoustically Distinguishable Space (ADS).
(ADS) shall be determined by the system An emergency communications system
designer during the planning and design of all notification zone, or subdivision thereof, that
emergency
e e ge cy cocommunications
u ca o s syssystems.
e s might
g be a an e
enclosed
c osed oor o
otherwise
e se p physically
ys ca y
18.4.10.2 Each ADS shall be identified as defined space, or that might be distinguished
requiring or not requiring voice intelligibility. from other spaces because of different
18.4.10.3 Where required by the authority having acoustical, environmental, or use characteristics,
jurisdiction, ADS assignments shall be submitted such as reverberation time and ambient sound
for review and approval. pressure level. (SIG-NAS)
Protected Premises
Chapter 23
Emergency Control Functions and
Interfaces – Chapter 21 All voice communications material is moving
out of chapter 6 and into chapter 24
Used to be Fire Safety Functions in Chapter 6 Fire Safety Functions are also moving to
Name changed to include non-fire alarm chapter 21
emergency functions Generalizes material in chapter 21 and allows
Includes requirements for elevator recall for both fire alarm and mass notification
correlation
11
Protected Premises Protected Premises
Chapter 23 Chapter 23
A.23.8.5.1.2 The manual means required by The manual fire alarm box required by 23.8.5.1.2
23.8.5.1.2 is intended to provide a backup means should be connected to a separate circuit that is
to manually activate the fire alarm system when not placed “on test” when the detection or
the
e au
automatic
o a c fire e de
detection
ec o sys
system
e oor waterflow
ae o sprinkler
sp e sys
system
e isspplaced
aced “on
o test.”
es The e manual
a ua
devices are out of service due to maintenance or means is only intended for use by the system
testing, or where human discovery of the fire technician or the building owner and should be
precedes automatic sprinkler system or located by the sprinkler riser or fire alarm control
automatic detection system activation. unit.
12
Supervising Station Fire Alarm Public Emergency Alarm Reporting
Systems – Chapter 26 Systems - Chapter 27
Certain legacy technologies (active multiplex, 2007 Edition
McCulloh, directly connected non-coded and Public Fire Reporting
private microwave) have been removed from 2010 Edition
the
e text
e o of the
e docu
document.
e
Public
P bli EEmergency Al
Alarm R
Reporting
ti S Systems
t
Existing systems utilizing these technologies changes in scope to clearly identify
are acceptable, because all these requirements already covered by the chapter
technologies also comply with the general and now include “emergency alarms” in addition
provisions of 26.6.3.1. to fire.
13
Single- and Multiple-Station Alarms Single- and Multiple-Station Alarms
and Household Fire Alarm Systems – and Household Fire Alarm Systems –
Chapter 29 Chapter 29
29.7.8.1.4 A dedicated cellular telephone connection shall 29.8.2.2 (5) In multiple station configurations that
be permitted to be used as a single means to transmit are comprised with multiple purpose alarms,
alarms to a constantly attended remote monitoring
smoke only, and CO only alarms, if the multiple
location.
purpose
pu pose aalarm
a de detects
ec s a
an ab
abnormal
o a a amount
ou o of
29 7 8 1 5 A MFVN shall
29.7.8.1.5 h ll b
be permitted
itt d tto b
be connected
t d tto
a DACT when the following conditions are met: CO the product will need to sound the CO alarm
(1) * The DACT shall be connected and perform as
signal on the remaining interconnected alarms.
required in 26.6.3.2.1.3. The smoke only alarm will have an option of
(2) The power supply battery backup of all MFVN remaining silent or to sound the CO alarm signal.
equipment and related transmission equipment shall
comply with the standby time requirements of Chapter 10.
14
NFPA and Mass Notification NFPA and Mass Notification
Current NFPA 72 Annex E, Mass Notification Chapter 24 Emergency Communications Systems
Systems replaced by Chapter 24 Emergency 24.1 Introduction
Communications Systems Emergency Communications Systems (ECS) shall
Content from Chapter 6
6, Protected Premises consist of two classifications of systems,
systems one-way
one way
Fire Alarm Systems and two-way.
Emergency Voice Alarm Communications
Two-Way Communication Service
15
One-Way ECS In-Building EVACs Strobes and NFPA
Relocation of section 6.9 and other requirements
Survivability requirements to reference new chapter
Permits a mass notification control unit to take
control of fire alarm notification appliances including
amplifiers, speakers, and strobes
Will require a tone or voice message any time the
priority is granted to the mass notification control unit
Strobes used for dual purposes shall not be marked
‘FIRE’, strobes to be blank or ‘ALERT’
One-Way ECS Distributed Recipient MNS Two-Way ECS Wired Emergency Services
Communication to a wide range of targeted Firefighter and warden telephones
individuals or groups Elimination of common talk
Systems include mass dialing systems,
reverse 911
911, email
email, SMS (mobile phone text
messages), and other directed
communication methods
16
Emergency Communications
Systems (ECS)
Chapter 24
24.1, 24.2, 24.3
Two-Way Wired
Bidirectional amplifiers
In-Building
Fire EVACS Emerg Svcs ECS
24.4.1 24.5.1
17