CM MECHANICAL DOCKLEVELER PIT DETAILS
TRUK STOP® CONDUIT RUN DETAILS (Back Cover)

CUSTOMER

ADDRESS

JOB

DOCKLEVELER: MECHANICAL Model Number QUANTITY

DOCKLEVELER RATING PER ANSI MH14.1-1987:


30K 35K 40K 45K

LIP LENGTH: 16" 18" 20"

TRUK STOPS: STAR 1 STAR 4 TRUK ALERT


STAR 2

NOTE: All TRUK STOPS, except STAR 1, require 115V, 1Ø.

CERTIFIED FOR CONSTRUCTION

BY DATE

COMPANY

CITY & STATE


5559 R4 MAY 2006

Death or serious injury could result from failure to follow Kelley


specifications for pit dimensions and/or configurations, or conduit
location; improper installation of dock leveler, anchoring devices
or optional/accessory equipment; installation into improperly for-
mulated, prepared or placed concrete or concrete which is other-
wise inadequate or unsound.
1
CM DOCKLEVELER PIT DETAILS

90°
“E” 90°

“C”
“G”
CL PIT
“H”

“F”
90°
“D”
“A”
4”

“B”

3”

DOCK “E”
3/4" DIA. ANCHOR BOLT, HEIGHT
FIELD INSTALLED — 34”
3/8" SIDE OF 8-3/4”
SUPPLIED BY OTHERS
PIT TO SIDE OF
BUMPER
MOUNTING
PLATE SEE NOTE 1
BUMPER
1/4" MOUNTING
ANGLE

2 LAMINATED BUMPERS
FURNISHED BY
KELLEY COMPANY, INC. NOTE 1: IF A STAR TRUK STOP IS TO BE INSTALLED AND THE
DRIVEWAY IS SUSCEPTIBLE TO FROST, PLACE A
STYROFOAM BLOCK IN THE CONCRETE IN THIS AREA. THIS
WILL PREVENT DAMAGE TO THE STAR TRUK STOP WHEN
DRIVEWAY RISES.

5559 R4 MAY 2006 2


LOCATION FOR SINGLE CONTROL BOX
FOR STAR TRUK STOP

CONTROL
BOX

48"

ANCHOR LAYOUT FOR CURB ANGLE

3" 12" 12" 12" 3" 3"

3"

1/4"

CONCRETE ANCHORS, 1/2" DIA., 6" LONG, LOCATED AS SHOWN

CM DOCKLEVELER PIT DIMENSIONS

NOM. DOCKLEVELER SIZE 6' x 6' 6' x 8' 6' x 10' 6.5' x 6' 6.5' x 8' 6.5' x 10' 7' x 6' 7' x 8 7' x 10'
PIT LENGTH DIM. "A" 63" 87" 111" 63" 87" 111" 63" 87" 111"
PIT WIDTH DIM. "B" 73" 73" 73" 79" 79" 79" 85" 85" 85"
PIT DEPTH
DIM. "C" 19-1/2" 19-1/2" 23-1/2" 19-1/2" 19-1/2" 23-1/2" 19-1/2" 19-1/2" 23-1/2"
Rear
PIT DEPTH
DIM. "D" 20" 20" 24" 20" 20" 24" 20" 20" 24"
Front
CURB ANGLE
DIM. "E" 79" 79" 79" 85" 85" 85" 91" 91" 91"
Front & Rear
CURB ANGLE
DIM. "F" 60" 84" 108" 60" 84" 108" 60" 84" 108"
Side
CURB ANGLE
DIM. "G" 21" 21" 21" 21" 21" 21" 21" 21" 21"
Bumper
CURB ANGLE
DIM. "H" 17" 17" 21" 17" 17" 21" 17" 17" 21"
Bumper

3 5559 R4 MAY 2006


TRUK STOP CONDUIT RUN LOCATION DETAILS
THROUGH WALL TO BOX
FOR SIGNAL LIGHT
1/2" CONDUIT
NOTE: ALL MOTOR POWER WIRES OR OTHER
HIGH VOLTAGE WIRES SHOULD BE RUN IN A
SEPARATE CONDUIT FROM ALL LOW VOLTAGE
CONTROL CIRCUIT WIRING. 4"
TO POWER
SUPPLY
1/2" CONDUIT 19-3/4”

9-3/4”
CONTROL
BOX NOTE: SIGNAL LIGHT MUST BE
ON TRUCK DRIVER’S SIDE
OF DOOR OPENING.

3/4” CONDUIT (NOT REQUIRED FOR


STAR 1 OR TRUK ALERT) EXIT
CONDUIT INSIDE BUILDING NEAR
15" WALL UNDER CONTROL BOX.

43"

C
L Dockleveler Pit

ADDITIONAL CONDUIT REQUIREMENTS FOR STAR 4


EXIT CONDUIT INSIDE BUILDING NEAR
16" WALL UNDER CONTROL BOX.

14" FOR HYDRAULIC HOSES USE


2" CONDUIT (DRAIN WASTE
OR VENT PVC PIPE WITH 45°
LONG SWEEP ELBOW)
1/2" CONDUIT
STAR 4, (ONLY IF 15"
USED WITH LIP LIMIT
SWITCH)
41" 3" EXIT CONDUIT AT ANGLE TO DOCK
42"
FACE 3" ABOVE DRIVE

C
L Dockleveler Pit

1612 Hutton Drive, Suite 140 • Carrollton, Texas 75006


Phone: (800) 558-6960 • Fax: (972) 389-4752

5559 R4 MAY 2006 4