Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Ventilation
Ventilation is required for safety and to
maintain acceptable temperatures and
comfort.
2
The Jetfoil Fan Range
General Information
• ø560 - ø1600 mm
• Thrust up to 3500N
• ø800 mm up to 3000 rpm, ø1250 mm up to 1800 rpm and ø1600 mm
up to 1200 rpm
• Fully adjustable die cast aluminium impellers in uni-directional and truly reversible
configurations; X-ray inspection
• Mild steel casing - hot dipped galvanised after manufacture, painted or all stainless
steel construction
• Silencers fitted where required
• Motor protection IP55
• High thrust performance
• Emergency ventilation options up to 400°C/2 hours
• Truly reversible fans provide 100% thrust reversibility. Uni-directional fans give
approximately 40% thrust for emergency use only, in the reverse mode with
increased noise level.
Applications
• Longitudinal ventilation of road tunnels • Mine ventilation
• Emergency ventilation - smoke control • Hangar/large area ventilation
3
Fan Codes
112 JMTS/40/4/9/32
Fan diameter
56 = 560 mm 100 = 1000 mm
63 = 630 mm 112 = 1120 mm
71 = 710 mm 125 = 1250 mm
80 = 800 mm 140 = 1400 mm
90 = 900 mm 160 = 1600 mm
Fan type
JMTS = Truly Symmetrical Jet Fan
JMG = Uni-Directional Jet Fan
Hub diameter
20 = 200 mm 40 = 400 mm
25 = 250 mm 50 = 500 mm
31 = 315 mm 63 = 630 mm
Motor pole
2 = 2 pole
4 = 4 pole
6 = 6 pole
8 = 8 pole
No. of blades
5 = 5 blades
6 = 6 blades
9 = 9 blades
12 = 12 blades
Fan Selector
Fan Selector is the selection software for all the Fläkt Woods Fan Group products: Axial
Flow Fans (among which Jet Fans for Tunnels), Centrifugal fans, Boxed Fans, Roof Extract
units, Plate mounted fans.
The Fan Selector allows you to choose fans which fit your required application.
All you need to do to register your details on-line is to follow the simple instructions
shown below.
2) All you need to do is to fill in the fields that have red text labels, but if you wish to complete more of the form,
this would be helpful.
3) Once you have entered your details, just click the "Register" button at the bottom of the registration page to
submit your request.
4
Fan Selector
Desktop CD
1. After logging in, the first screen displayed allows the selection of axial fans, identify and click ‘select’ to
continue.
2. The next screen displays the various types of axial fans, therefore it is necessary to filter the selection by
clicking ‘product filter’ and ‘edit’.
3. The desired thrust can be input to identify suitable fans. Other filters can be adjusted so the desired fan is
identified.
5
Jetfoil Standard Range
300/2 - Range
300/2 Unidirectional 50Hz 300/2 Reversible 50Hz
5000 3000
2500
4000
2000
3000
Thrust (N)
Thrust (N)
1500
2000
1000
1000 500
0 0
63 2 71 4 71 2 80 4 80 2 90 4 100 6 100 4 112 6 112 4 125 6 125 4 140 6 140 4 160 8 160 6 56 2 63 2 71 4 71 2 80 4 80 2 90 4 100 6100 4 112 6 112 4 125 6125 4 140 8 140 6 160 8 160 6
Thrust (N)
2000 2000
1500 1500
1000 1000
500 500
0 0
63 2 71 4 80 4 90 4 100 6 100 4 112 6 112 4 125 6 125 4 140 6 160 8 160 6 56 2 63 2 71 4 80 4 90 4 100 6 100 4 112 6 112 4 125 6 125 4 140 8 140 6 160 8 160 6
400/2 - Range
3000 3000
2500 2500
Thrust (N)
2000 2000
Thrust (N)
1500 1500
1000 1000
500 500
0 0
4000 4000
3500 3500
3000 3000
2500 2500
Thrust (N)
Thrust (N)
2000 2000
1500 1500
1000 1000
500 500
0 0
7
50Hz Unidirectional Range 300/2H
Sound
Motor Outlet Absorbed Motor Nominal Sound Pressure
Fan Blade Thrust
Pole Velocity Power Power Current power in free field,
type angle N
Speed m/s kW kW A LwA 45º, 10m
dB(A)
8
50Hz Truly Reversible Range 300/2H
Sound Pressure
in forward
Motor Outlet Absorbed Motor Nominal Sound
Fan Blade Thrust direction
Pole Velocity Power Power Current power
type angle N in free field,
Speed m/s kW kW A LwA
45º, 10m
dB(A)
9
60Hz Unidirectional Range 300/2H
Sound
Motor Outlet Absorbed Motor Nominal Sound Pressure
Fan Blade Thrust
Pole Velocity Power Power Current power in free field,
type angle N
Speed m/s kW kW A LwA 45º , 10m
dB(A)
10
60Hz Truly Reversible Range 300/2H
Sound
Pressure
Motor Outlet Absorbed Motor Nominal Sound in forward
Fan Blade Thrust
Pole Velocity Power Power Current power direction
type angle N
Speed m/s kW kW A LwA in free field,
45º, 10m
dB(A)
2 21 182 24.8 5.5 5.52 9.66 98 67
2 24 225 27.6 7.2 7.25 11.6 98 67
2 27 269 30.2 9.2 9.35 15.4 98 67
56JMTS
2 30 310 32.4 11.5 12.6 20 99 68
2 33 354 34.6 13.9 14.4 23 100 69
2 40 398 36.7 21.9 25.2 39.4 105 74
2 25 362 31.1 12.5 12.6 20 99 68
2 27 402 32.8 14.6 15 23.9 100 69
63JMTS 2 31 495 36.4 19.8 20.4 32.2 102 71
2 35 588 39.6 26.7 27.5 44.6 103 72
2 40 656 41.9 36.9 39.6 61.8 104 73
4 30 207 20.9 4.3 4.32 7.61 90 59
71JMTS 4 33 239 22.4 5.5 5.76 9.75 91 60
4 36 271 23.9 6.9 7.56 12.7 93 62
4 25 285 21.7 5.6 5.76 9.75 93 62
4 32 419 26.4 9.4 9.78 16.3 94 63
80JMTS
4 37 508 29 13.1 13.8 22.3 97 66
4 44 564 30.6 19.0 19.6 32.8 99 68
4 27 489 25.3 11.8 12.1 20.2 91 60
4 30 578 27.5 14.9 15 25.6 92 61
90JMTS 4 33 667 29.6 18.9 19.60 32.8 94 63
4 39 818 32.7 28.4 28.8 46.9 96 65
4 44 885 34.1 36.0 39.6 66.3 98 67
4 28 792 29 19.8 20.4 34.4 104 73
4 32 993 32.5 28.0 28.8 46.9 105 74
100JMTS 4 37 1242 36.3 41.1 41.4 65.6 107 76
4 40 1332 37.6 49.3 50.4 77.9 108 77
4 44 1501 39.9 55.2 58.3 96.7 110 79
6 28 1241 32.4 40.2 41.4 65.6 107 76
6 31 1438 34.9 49.4 50.4 77.9 108 77
112 JMTS 6 35 1693 37.8 63.2 63.6 97 109 78
6 37 1813 39.2 71.7 72.5 110 110 79
6 40 1980 40.9 87.8 97.8 150 112 81
6 28 936 25.2 19.4 20.4 32 97 66
6 31 1083 27.1 24.2 25.2 41.6 98 67
125JMTS 6 34 1227 28.9 29.6 30 50 100 69
6 40 1466 31.6 41.8 43.2 68.1 102 71
6 44 1544 32.4 50.0 50.4 79.3 103 72
6 26 1293 26.5 29.2 30 50 101 70
140JMTS 6 30 1627 29.7 40.2 43.2 68.1 102 71
6 35 2034 33.2 58.8 61 94.9 104 73
6 22 1736 26.8 41.5 43.2 68.1 104 73
160JMTS 6 24 1957 28.5 49.4 50.4 79.3 105 74
6 26 2209 30.3 57.8 61 94.9 105 74
11
HT Certification
The decision was made to embark on a major testing programme in conjunction with
BSRIA, a leading authority in building research. Using the expertise of Fläkt Woods and
BSRIA’s new state of the art High Temperature test rig, the Jet Fan range was successfully
tested in compliance with this demanding new legislation with minimum complications.
This investment resulted in Fläkt Woods being able to offer a British Standards Institution
Certified, CE marked Jet Fan product for use at 400°C/2 hours from 560mm to
1600mm, together with a comprehensive range of approved accessories.
Fläkt Woods have enhanced their position as the foremost provider of specialist products
for emergency high temperature smoke
control by becoming the first fan
manufacturer in the world to be able to
apply CE marking to these safety critical
products.
12
Other Accessories
Spring Vibration
Bellmouth Inlet
Isolators
Outline Drawings
It is recommended that a Fläkt Woods frame accompany the jet fan to ensure a secure
installation. Anti-vibration mounts are available for soft mounting installations.
13
Outline Drawings
Max 3.3 D
Max 5.2D
D
1.2 D
ANCI LLARY
OPTIONAL
ANCI LLARY
OPTIO NAL
1.2 D
14
Sample Project Tunnel & Metro Reference List
Road UK Limehouse Link
Country Project UK Terminal 5 - Coach Station
Algeria Algerian Road Tunnel UK T5 - Taxi Bridge
Australia Mitcham Frankston Freeway UK Blackwall Tunnel
Australia M5 East Tunnel UK New Tyne Crossing
Australia Lane Cove Yemen Sayhut-Nishtun Road Project
Austria Wske Tunnel
Belgium Gare De Namur Rail/Metro
China Hu Rong Su Tunnel Country Project
China Chong Qin Fang Dou Shan Australia Parramatta Rail Link
China Sky Pier (Tunnel 1) Austria U3 Station Erdberg
China Hu Nan Jia Hou Yan Austria U2/1 Schottenring
China Hu Nan Xue Feng Shan Tunnel Austria River City
Croatia Tunnel Trsat Austria U1 Unterwerk
Croatia Tunnel Skurinje Austria U2 Messe
Croatia Sveti Rok 2 Austria U4 Schottenring
Croatia Mala Kapela Austria Vienna Metro - Gross
Croatia Veliki Glozac Austria Vienna Metro - Leoup
Croatia Tunnel Bisko Brazil Sao Paulo Metro Line 4
Croatia Tunnel Mravince Canada TTC Shepherd
Croatia Tunnel Strazina Canada TTC Petrofit
Croatia Cardak Canada Montreal STCUM
Croatia Brezovica China Guangzhou Metro
Croatia Sveta Tri Krajla Denmark Copenhagen Metro
Croatia Mala Kapela Dubai Dubai Light Railway
Dubai Dubai International Airport Greece Attiko Metro - Elliniko Ext.
Finland Kehu Project Greece Egnatio Odos Driscos Tunnel
Finland Hakamaentie/Kivihaka Tunnel Greece Attiko Metro, Athens
Finland Vuoli Tunnel Hong Kong TKO South Hong Kong
Greece Egnatia Odos-Panagia-Grevena Hong Kong Beacon Hill Tunnel
Greece Eftaxias Hong Kong Lok Ma Chau
Hong Kong Route 8 Hong Kong Penny's Bay Line
Hong Kong Sky Plaza Hungary Budapest Metro Line 2
Hong Kong Lantau Airport & Railway Hungary Budapest Metro Line 4
India DAMEL India Delhi Metro Phase II
India C Doctor India Delhi Metro
Italy Seiano Tunnel India DMRC Phase 1 (Mc1b)
Italy Montenegrone Project Iran Mashhad Metro
Italy Martignano Italy Passante Ferroviario Di Torino
Italy Gran Sasso Italy Torino Di Bologna
Italy Mongrando Tunnel Italy Nodo Di Bologna
Italy Gra Salva Candida Italy Passante Ferroviario
Italy Cesena Tunnel Italy Turin Metro
Italy Valsassina Tunnel Italy Turin Metro Lot 6c Project
Italy Spezia Italy Rome Rail Station
Italy Lonato Tunnel Italy Avigliana
Italy Ronco Tunnel Italy Alifana Metro
Italy Val Badia Tunnel Italy Milan Metro
Italy Marinasco Tunnel New Zealand Britomart Project
Malaysia SMART New Zealand Otira Rail Tunnel
New Zealand JHT New Zealand Portugal Lisbon Metro
Norway E18 - Bjorvika Tunneln Romania Bucharest Metro
Norway Norway Road Tunnel Singapore CCL2
Norway Mesta As Singapore CCL3
Poland Rondo Tunnel Singapore CCL4
Portugal Tunnel Do Rossio Singapore CCL5
Puerto Rico Tven Urbana Singapore KPE Expressway
Qatar New Doha International Airport Singapore North East Line
Qatar NDIA Free Trade Zone Taiwan Nankang Extension Project
Saudi Arabia Jamarat Bridge Phase II Taiwan KMRT
Saudi Arabia Jamarat Bridge Basement Turkey Adana Metro
Saudi Arabia King Khalid Road Tunnel UK Bank Station
Serbia Vrmac Tunnel UK Channel Tunnel Rail Link
Singapore Singapore Metro Link UK Cooling the Tube
Sweden Arlandabanan, Stockholm UK Docklands Light Railway
Switzerland Biasca Tunnel UK Jubilee Line Extension
Taiwan Pinglin UK Liverpool Street Station
UK A3 Hindhead Tunnel UK T5 Track Transit
UK Bell Common Tunnel UK Woolwich Arsenal Extension
UK Holmesdale Tunnel Venezuela Valencia Metro
15
Precise Air Management
Fläkt Woods is a global Solutions for all your air climate and air movement needs
leader in air management. Fläkt Woods is the only company in the UK capable of providing total system
We specialise in the design solutions from the following portfolio: