Sei sulla pagina 1di 8

IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 28, NO.

1, FEBRUARY 2013 377

A Procedure to Study Sub-Synchronous Interactions


in Wind Integrated Power Systems
D. H. R. Suriyaarachchi, Student Member, IEEE, U. D. Annakkage, Senior Member, IEEE,
C. Karawita, Member, IEEE, and D. A. Jacobson, Senior Member, IEEE

Abstract—This paper presents a comprehensive analysis of resonance of synchronous generators with series compensated
sub-synchronous interactions in a wind integrated power system transmission lines as well as other devices such as HVDC con-
to understand and mitigate them. The proposed procedure has verter terminals. [4] reports an incident in which some gener-
two steps. In the first step, a frequency scan is performed to
determine the presence of resonant frequencies in the sub-syn- ators in a wind power plant and the series capacitors sustained
chronous range. In the second step, a detailed small signal analysis damages. Because of such incidents, it is important to under-
is performed. Participation factors are used to identify the state stand the phenomena of sub-synchronous interactions in a wind
variables that are involved in the interaction, and the control- integrated power system.
lability indices are used to determine the mitigation method. It Among many types of generators used in wind farms, the
is shown that the sub-synchronous interaction present in Type
3 wind turbine-generators connected to the grid through series doubly fed induction generator or Type 3 wind turbine-gen-
compensated lines is an electrical resonance between the generator erator [5] has been found to be most vulnerable to sub-syn-
and the series compensated line which is highly sensitive to the chronous interactions [4]. In [6], sub-synchronous resonance
rotor side converter current controller gains. between a wind farm equipped with fixed speed induction gener-
Index Terms—Doubly fed induction generator (DFIG), fre- ators and a series compensated line has been demonstrated using
quency scan, linearized model, self-excitation, small signal electromagnetic transient simulations. A small signal stability
stability, sub-synchronous interactions. analysis is performed in [7] to analyze sub-synchronous reso-
nance between a doubly fed induction generator equipped wind
I. INTRODUCTION farm and a series compensated transmission line. A more re-
cent work [8] shows that the sub-synchronous resonance present
in a variable speed systems is mainly due to the self-excita-
T HERE has been a significant growth in the integration of
wind power into power systems networks in recent years.
In year 2010, the total capacity of wind installations around
tion rather than due to the torsional interactions. However, an-
other recent publication claims, using time domain simulations,
that the sub-synchronous interaction between Type 3 wind tur-
the globe has increased by 23.6% [1]. With this increased wind
bine-generators and series compensated transmission systems
power integration, the transmission network capacities need to
is due to controller interactions [9]. In summary, there is dis-
be increased either by building new transmission lines or by en-
agreement in the industry on whether these oscillations are due
hancing the power transfer capability of the existing lines. A
to self-excitation or due to controller interactions. This paper
common approach for expanding transmission capacity is by
presents a comprehensive analysis of this problem to eliminate
using series compensation.
the doubts on the cause and nature of these oscillations.
It has been known for many years that the series capacitors
Another objective of this paper is to propose an efficient and
self-excite both synchronous and induction machines [2], but
effective procedure to identify and investigate sub-synchronous
only after the failure of an exciter shaft in one of the machines
oscillations. It is important to determine whether there are po-
at the Mohave power plant in October 1971, the severity of
tential sub-synchronous oscillation problems before carrying
the adverse effects of series capacitors on electrical machines
out a detailed study. A simplified frequency scanning method
came into the forefront of attention [3]. Since then extensive re-
is proposed as the first step of the procedure of a detailed study.
search has been performed to investigate the sub-synchronous
If the frequency scanning indicates a potential risk, a detailed
eigenvalue type study is proposed to investigate the cause and
Manuscript received October 26, 2011; revised February 10, 2012; accepted
June 05, 2012. Date of publication July 16, 2012; date of current version January nature of the problem. The eigenvalue technique is proposed in-
17, 2013. This work was supported by Manitoba Hydro and the University of stead of a time domain simulation for two reasons. Firstly, time
Manitoba. Paper no. TPWRS-01011-2011.
domain simulation of large systems is time consuming. Sec-
D. H. R. Suriyaarachchi and U. D. Annakkage are with the Department of
Electrical and Computer Engineering, University of Manitoba, Winnipeg, MB ondly, time domain simulations do not provide the information
R3T 5V6, Canada (e-mail: hiranya@ee.umanitoba.ca; annakkag@ee.umani- necessary either to understand the root cause of the problem or
toba.ca).
to design mitigation measures.
C. Karawita is with Trans Grid Solutions Inc., Winnipeg, MB R3T 2E1,
Canada (e-mail: ckarawita@transgridsolutions.com). This paper is organized as follows. Section II describes the
D. A. Jacobson is with Manitoba Hydro, Winnipeg, MB R3C 2P4, Canada proposed frequency scan model. A brief description of the
(e-mail: dajacobson@hydro.mb.ca).
linearized models used for the eigenvalue analysis is given in
Color versions of one or more of the figures in this paper are available online
at http://ieeexplore.ieee.org. Section III. In Section IV, the proposed procedure is described
Digital Object Identifier 10.1109/TPWRS.2012.2204283 with the aid of a small test system. Also, a comprehensive

0885-8950/$31.00 © 2012 IEEE


378 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 28, NO. 1, FEBRUARY 2013

Fig. 1. Induction generator frequency scan model. (a) Model I. (b) Model II.

analysis of the sub-synchronous interactions in the system is


presented in this section. The results obtained by applying
the proposed procedure to a multi-machine power system is
presented in Section V. Finally, the conclusions are given in Fig. 2. Rotor side converter controller.
Section VI.

II. FREQUENCY SCANNING


A frequency scanning method for induction generators is
not available in the literature. However, a frequency scanning
method for synchronous generators proposed in [10] and [11]
where the driving point impedance over the interested fre-
quency range is calculated as seen from the generator neutral is
widely used in the industry. In this technique, the synchronous
generator is modeled using its induction generator equivalent
shown in Fig. 1(b). In case of a fixed speed induction generator
the same equivalent circuit is applicable.
However, in case of a doubly fed induction generator the gen-
erator is operated at the desired operating point by controlling Fig. 3. Grid side converter controller.
its rotor voltage. For the purpose of frequency scanning, this
voltage source can be replaced by an equivalent impedance so
that the current flowing through the rotor circuit remains un- • The doubly fed induction generator is modeled with differ-
changed. Therefore, the doubly fed induction generator equiva- ential equations for stator flux, rotor flux, and slip.
lent circuit for frequency scanning is obtained by replacing the • The wind farm drive train is modeled using a three mass
rotor voltage source with an equivalent impedance such that model as in [15].
• The converter transformer dynamics and the dc link dy-
(1) namics are included in the wind turbine-generator unit
model [16].
where , , and are steady state values of rotor voltage, rotor • The rotor side converter is controlled in the stator flux ref-
current, and slip, respectively. The modified circuit is shown in erence frame whereas the grid side converter is controlled
Fig. 1(a). Since these quantities depend on the system frequency, in the generator terminal reference frame. Controllers for
the value of is updated for every frequency in the range of both converters have a faster inner loop for current con-
frequencies of interest. trol and a slower outer loop. The rotor side converter outer
For the remainder of this paper, the two induction generator loop controller regulates the generator speed and the stator
frequency scan models are identified as follows. reactive power whereas the grid side converter outer loop
• Model I—Modified induction generator equivalent circuit. controller regulates the dc link voltage and the reactive
• Model II—Conventional induction generator equivalent power absorbed from the network by the grid side con-
circuit. verter transformer. The rotor and grid side converter con-
trols are shown in Figs. 2 and 3.
III. LINEARIZED MODEL • The full aggregation method in [17] is used to model the
large number of turbine-generator units in the wind farm.
The traditional small signal stability assessment programs
• Dynamic phasors are used to model the ac network dy-
and transient stability programs are valid for studying low
namics as in [12].
frequency electromechanical oscillations. The machine stator
The dynamic equations are linearized around an operating
dynamics as well as the ac network dynamics are ignored in
point and the linearized dynamic equations are written in state
these programs as they produce fast transients that do not affect
space form as
the low frequency electromechanical oscillations. However, the
stator and ac network dynamics must be modeled for studies on (2)
sub-synchronous oscillations as those dynamics directly con-
tribute to sub-synchronous oscillations [12]–[14]. The dynamic The state space model of the wind farm consists of 20 state vari-
model of the wind farm is developed as follows: ables and 4 inputs. The state variables include 4 generator states
SURIYAARACHCHI et al.: A PROCEDURE TO STUDY SUB-SYNCHRONOUS INTERACTIONS IN WIND INTEGRATED POWER SYSTEMS 379

to devices that are known to cause sub-synchronous interac-


tions such as series compensated transmission lines, and HVDC
converter terminals, they are selected as candidates for the fre-
quency scan study.
All the wind farms except for Type 4 are replaced with their
Fig. 4. Simple test system. equivalent circuits (either Model I or Model II). The individual
generator-turbine units in the wind farm are aggregated using
the method described in [17]. Since the study of interactions of
(stator and rotor fluxes), 5 drive train states (rotating speeds of 3 Type 4 wind farms is not in the scope of this paper, they are
masses and 2 relative angles between the masses), 4 controller replaced with voltage sources. The synchronous generators in
states for the rotor side converter, dc capacitor voltage, 4 con- the system are replaced with their sub-transient reactance.
troller states for the grid side converter and 2 states for the con- All the static loads are represented by the corresponding load
verter transformer current. The 4 inputs comprise of the refer- models [18].
ence values for the stator reactive power injection, rotor speed, 2) Step 2—Frequency Scan Study: If the wind farms are rep-
dc voltage and reactive power injected by the grid side con- resented by Model I, the impedance is calculated using
verter. steady state system equations for each frequency under inves-
The linearized dynamic model of the network is of the form tigation. The driving point impedance when looking in to the
system from the rotor terminals is calculated for all scanning
(3) frequencies. The magnitude, resistive component and the phase
of the impedance obtained from the frequency scan are plotted
State vector consists of transmission line currents and
against the scanned frequency. A change in sign of the phase
bus voltages. The network dynamic device inputs are in .
and a dip in the impedance magnitude corresponds to a series
The current injection equation for the wind farm
network resonance seen by the wind farm under study. The fre-
(4) quency at which this is observed is the network resonant fre-
quency.
and a large fictitious resistor connected to the ground at the con- If a disturbance excites the network resonance, there will be
nection point between the generator and the PCC transformer sub-synchronous currents induced in the stator at the comple-
are used to interface the wind farm state space model with mentary frequency with being the system frequency.
the network. Since the generator currents and the current flow If a constant rotor speed is assumed, the rotor will be rotating
through the transformer can be represented as combinations faster than the rotating magnetic field produced by the induced
of states, the voltage terms in (2) and (3) can be eliminated sub-synchronous current. Therefore, the resistance to the in-
by applying Kirchhoff’s current law at the node where the duced sub-synchronous currents is negative when viewed from
fictitious resistor is connected. Once the voltage terms are elim- the rotor terminal. If the total resistance of the stator and the
inated and the generator and network equations are combined, network is less than this negative resistance, the generator will
the complete state space representation of the system can be get self-excited [19]. Therefore, a negative resistance at the net-
obtained as work resonance frequency yielding from the frequency scan re-
sults represent a self-excitation of wind farm generators.
(5) For the small test system, the frequency scan results for dif-
ferent levels of series compensation are shown in Fig. 5. The
with and . solid lines represent the results obtained when the wind farm is
When there are other dynamic devices connected to the net- represented by using Model I. The frequency scan results indi-
work, linearized dynamic models similar to the one shown in cate an existence of a resonance condition at 25.34 Hz, 35.09
(2) are combined with the network equations [14]. Hz, 42.11 Hz, and 45.63 Hz for 25%, 50%, 75%, and 90% com-
pensation levels, respectively. If a disturbance excites the net-
IV. SUB-SYNCHRONOUS INTERACTION STUDY PROCEDURE
work resonance, there will be sub-synchronous currents induced
The simple test system shown in Fig. 4 is used to demonstrate in the stator at frequencies complementary to the nominal fre-
the application of the proposed procedure to screen wind inte- quency of 60 Hz; i.e., at 34.66 Hz, 24.91 Hz, 17.89 Hz, and
grated power systems for sub-synchronous interactions. This 14.37 Hz, respectively.
system represents a wind farm with Type 3 turbine-generators Fig. 6 shows the resistance of the network seen from the
connected to a strong system via a long series compensated rotor terminal for the aforementioned compensation levels. The
transmission line. The wind farm parameters are given in equivalent resistance is positive for the tested cases indicating
Appendix A. The study procedure involves 1) screening for no self-excitation issues for the generator.
potential problems and 2) detailed eigenvalue analysis. Model I requires the calculation of the equivalent impedance
for all frequencies in the scanning range. This requires
A. Screening for Potential Problems solving steady state wind farm and network equations at all fre-
1) Step 1—System Preparation for Frequency Scan: The po- quencies in the scanning range. Although the solution of these
tential locations are first identified by inspection of the single steady state equations is possible for a small test system, as the
line diagram of the network. If wind farms are located close system gets larger it becomes computationally demanding.
380 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 28, NO. 1, FEBRUARY 2013

Fig. 5. Frequency scan results for small test system—impedance magnitude


and phase. Fig. 7. Participation factors of sub-synchronous modes with 50% compensa-
tion: States 1–4: Generator; 5–9: Drive train; 10–13: RSC controller; 14: DC
capacitor; 15–18: GSC controller; 19–20: Converter transformer; 21–28: Net-
work.

Fig. 7 shows the participation factors of the low damped sub-


synchronous oscillatory modes together with their frequency
and damping for the test system presented. These results are ob-
tained with 50% series compensation. In the figure, the system
states are grouped so that states 1 to 4 represent the generator,
5 to 9 represent the drive train, 10 to 13 represent the rotor side
converter controllers, 14 represents the dc capacitor, 15 to 18
represent the grid side converter controllers, 19 and 20 represent
the converter transformer. States from 21 onwards are network
states. Note that in Fig. 7, the network states are participating
heavily in the 24.76 Hz oscillatory mode. Therefore, it can be
identified as a network mode. Since the drive train states are par-
Fig. 6. Frequency scan results for small test system—resistance. ticipating heavily in the 3.23 Hz mode it can be identified as a
torsional mode. Similarly, the other two modes at 6.74 Hz and
2.65 Hz are identified as an electromechanical mode and a con-
The broken lines in Figs. 5 and 6 represent the results obtained troller mode, respectively. Apart from the network states, the
with the conventional induction generator frequency scan model generator states have a significant participation in the network
(Model II). As seen in the figures, the results from the conven- mode (24.76 Hz), indicating a sub-synchronous interaction be-
tional model closely follow those from Model I. This method tween the generator and the series compensated transmission
does not require simultaneous steady state equation solutions. line. Also, no participation of the network states in the torsional
Based on these observations Model II is proposed for the pur- mode reveals that there is no torsional interaction present in this
pose of frequency scan. case. This analysis was performed for a wide range of shaft stiff-
3) Step 3—Detailed Analysis: If no network resonances are ness values, inertias and compensation levels and no torsional
found during the screening study the sub-synchronous interac- interactions with the network were observed.
tion study procedure can stop after Step 2. However, if a network Table I shows a comparison of the screening study results
resonance is found during step 2, even if the net resistance seen obtained with Model I, Model II and detailed analysis. Both
by the generator is positive there can still be sub-synchronous frequency scan models can closely predict the network mode
interactions between the wind farm and the rest of the system frequency discovered from the detailed analysis. For example,
as will be shown later in this paper. It is proposed in this paper at 50% series compensation frequency scans performed using
that a detailed eigenvalue analysis is performed to obtain in- Models I and II indicate a network mode at 24.91 Hz and 25.38
formation about the oscillatory modes such as their frequency, Hz, respectively, whereas the network mode frequency obtained
damping and participation factors. The linearized model of the from the small signal analysis is 24.76 Hz. Since Model II does
wind farm and the network explained in Section III is used to not involve steady state calculations at each frequency, it is rec-
obtain these information. Note that, the detailed model includes ommended to use Model II when screening large networks. The
the dynamics of the DFIG and its controllers. Therefore, infor- difference in resonant frequency obtained with scanning per-
mation on various oscillation modes present in the system can formed at PCC and those performed using Models I or II is
be seen from such a study. that the doubly fed induction generator is not taken into account
SURIYAARACHCHI et al.: A PROCEDURE TO STUDY SUB-SYNCHRONOUS INTERACTIONS IN WIND INTEGRATED POWER SYSTEMS 381

TABLE I
COMPARISON OF FREQUENCY SCAN AND SMALL SIGNAL ANALYSIS RESULTS

in the former. Further, any self-excitation problems cannot be


identified when the frequency scan is performed at the PCC, be-
cause the doubly fed induction generator is not included. The in-
formation regarding the network mode damping is readily avail-
able from the small signal analysis.
These observation clarify any doubts as to the nature of these
sub-synchronous interactions. It is clearly demonstrated that this
sub-synchronous interaction involves the transmission network Fig. 8. (a) Sensitivity of damping to the rotor side converter controller current
and the generator. Control states do not significantly participate loop gains. (b) Participation factors of the network mode without the converter
controllers: States 1–4: Generator; 5–7: DC capacitor and the converter trans-
in this sub-synchronous oscillatory mode. former 8–12: Drive train; 13–20: Network. (c) Controllability indices.

B. Cause for the Generator-Series Compensated Line


Interaction • State variables associated with the drive train do not par-
The screening study presented above revealed that there is a ticipate in this mode.
network mode in the test system at sub-synchronous frequency • This mode is highly controllable through the rotor voltage
range and also, it ruled out that this sub-synchronous interaction control. Therefore, the damping of the sub-synchronous
is not due to net negative resistance. The detailed small signal mode is sensitive to the gains of the controllers.
analysis results revealed a presence of a low damped interaction • The sub-synchronous oscillation mode is not a torsional
between the generator and the network. oscillation mode.
Fig. 8(a) shows the sensitivity of the damping of network • This mode represents an electrical resonance between the
mode to the rotor side converter controller current loop input network and the generator which is controllable through
gains. As the input gains increase the damping of the network the rotor controllers.
mode decreases. This indicates the rotor side converter con- Note that the frequency scan is performed using a steady state
troller has an adverse effect on the network mode damping. To equivalent of the doubly fed induction generator. Although the
further strengthen this argument the system was studied with steady state voltage injected by the rotor side converter is in-
the rotor controller being disabled. Participation factors of the cluded in Model I, the frequency scan results do not take in
network mode when the converter controllers are disabled are to account the dynamic effect of the converter controllers. As
shown in Fig. 8(b). In this case the generator participation in shown in the previous analysis for some values of rotor side
the network mode is not as high as with the controllers. Further- converter current controller gains the network mode becomes
more, disabling of controllers has increased the network mode unstable. Since the sub-synchronous oscillatory mode is caused
damping to 9.74%. by an electrical resonance between the network and the gener-
Fig. 8(c) shows the controllability of the network mode using ator it can be concluded that for certain values of rotor side con-
the five available inputs. As shown in the figure, the network verter controller gains the dynamics of the controller makes the
mode is highly controllable with the two orthogonal rotor volt- net resistance seen by the generator negative and hence self-ex-
ages. In general, if a mode can be controlled by a certain input a cite the machine.
controller can influence that mode either favorably or adversely.
In this case the controllers have an adverse effect on the net- V. SUB-SYNCHRONOUS INTERACTION STUDY
work mode. Further, the analysis of observability of this mode USING A MULTI-MACHINE POWER SYSTEM
revealed that this mode has a poor observability in controller The test system shown in Fig. 9 is used as the multi-machine
state variables. Since the participation factor indicates the com- power system. It is derived from the test system to validate
bined influence of controllability and observability, the poor ob- HVDC and FACTS models [20]. The following modifications
servability leads to a poor participation. were made to the original test system.
The following conclusions can be drawn based on the above • The generator connected to bus 12 was replaced with a 200
analysis. MW Type 3 wind turbine-generator.
• The main participants of the sub-synchronous oscillation • The transmission line between buses 6 and 4 was 75% se-
mode are the state variables associated with the network ries compensated at the middle of the line. Two additional
and the generator. buses (bus 61 and 41) were introduced to connect the se-
• The participation of state variables associated with the con- ries capacitor.
trollers is relatively small. • The bus shunts at buses 4 and 5 were removed.
382 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 28, NO. 1, FEBRUARY 2013

Fig. 9. Multi-machine test system.

TABLE II Fig. 10. Participation factors of the network mode. (a) System intact condition.
FREQUENCY SCAN RESULTS FOR THE MULTI-MACHINE TEST SYSTEM (b) Outage of the line between buses 1 and 6.

• The wind farm data used in this study is same as used in


Section IV except the rotor converter controller gains
and were increased to 0.075.
A sub-synchronous screening was performed for the system
intact condition and for the system with transmission line be-
tween bus 1 and 6 is out of service. The frequency scans were
conducted at the wind farm terminal as well as at the rotor
terminal using Model II. For all the cases tested a dip in the
impedance magnitude was observed, indicating a presence of a
network resonance. The frequency of the network resonance is
given in Table II. For both cases the screening results did not
exhibit net negative resistance.
The detailed analysis performed on the system reveals a net-
work mode at 18.79 Hz with 2.89% damping and at 20.16 Hz
with damping for the system intact condition and the
Fig. 11. Electromagnetic transient simulation results for active power flow in
tested contingency, respectively. Fig. 10(a) and (b) shows the the series compensated line. (a) System intact. (b) Outage of the line between
participation factors for the network mode. The states related to buses 1 and 6.
the series capacitor and the series compensated line participate
heavily in the network mode. Also, the wind farm states, espe-
cially the generator stator flux participate in the network mode. given by the detailed analysis. For the system intact case, the
This indicates a sub-synchronous interaction between the gen- frequency of the initial transient is approximately 19.6 Hz.
erator and the network further confirming the conclusions made We have successfully applied this procedure to screen and
in Section IV-B. study sub-synchronous interactions in a large heavily meshed
Fig. 11 shows the active power flow through the series com- power system consisting of 59 buses, six wind farms with Type
pensated line obtained from an electromagnetic transient sim- 3 generators, and 5 series compensated transmission lines. The
ulation using PSCAD/EMTDC. A three phase solid short cir- wind farms were located in the near electrical proximity of the
cuit was applied on the transmission line between buses 1 and series capacitors. When frequency scans were performed using
6 at 2 s and it was cleared after 100 ms. For the system intact Model II, a resonance has been observed only at one wind farm
case, the fault was cleared without tripping the line. As shown in when the system is under an N-2 contingency. For this contin-
the figure, a sub-synchronous oscillation can be observed in the gency, although the wind farm is not radially connected to the
power flow through the series compensated line as predicted by series compensated line, a large portion of its power transfers
the detailed analysis. Also, as predicted the system is unstable through those lines. Also, no self-excitation (net negative re-
under the contingency. The frequency of the oscillation during sistance) of the wind farm generators was observed from the
the contingency is 20.4 Hz which is very close to the frequency screening study. A detailed analysis performed on the system for
SURIYAARACHCHI et al.: A PROCEDURE TO STUDY SUB-SYNCHRONOUS INTERACTIONS IN WIND INTEGRATED POWER SYSTEMS 383

TABLE III TABLE V


WIND TURBINE AND DRIVE TRAIN PARAMETERS CONVERTER CONTROLLER GAINS

TABLE VI
PCC TRANSFORMER AND TRANSMISSION LINE PARAMETERS

TABLE IV
GENERATOR, DC CAPACITOR, AND CONVERTER TRANSFORMER PARAMETERS

networks are due to an electrical resonance between the network


and the generator. The rotor voltage controllers can significantly
influence the damping of this mode. It has also been shown that
the observed sub-synchronous oscillations are not due to tor-
sional interactions.

APPENDIX
WIND FARM AND TEST SYSTEM PARAMETERS
the system intact and the aforementioned contingency exhibited The wind farm is operated at unity power factor at the point
a sub-synchronous interaction between the wind farm generator of common coupling (PCC) and the wind speed is assumed to
and the series compensated line only for the N-2 contingency. be 12 m/s. Table III shows the wind turbine and drive train pa-
The oscillatory mode frequency was 39.4 Hz and its damping rameters for the wind farm. The wind farm generator, dc capac-
was 1.9%. These observations were confirmed by comparison itor and converter transformer parameters are given in Table IV.
with electromagnetic transient simulations. The rotor side converter and grid side converter controller gains
In summary, the detailed analysis performed on multi-ma- are given in Table V. Note that the integral gain is the ratio
chine power systems confirms that the sub-synchronous oscilla- between the proportional gain and the integral time constant.
tions associated with wind farms with Type 3 turbine-generators For example, the integral gain for the rotor speed controller is
and series compensated networks are due to an electrical reso- given by . Point of common coupling trans-
nance between the network and the generator. former and the transmission line parameters used for the small
test system are given in Table VI.
VI. CONCLUSION
REFERENCES
A comprehensive procedure to study sub-synchronous oscil- [1] World Wind Energy Report 2010, World Wind Energy Agency, 2011.
lations in power systems with Type 3 wind turbine-generators [2] J. W. Butler and C. Concordia, “Analysis of series capacitor application
and series compensated transmission lines has been proposed in problems,” AIEE Trans., vol. 56, pp. 975–988, Aug. 1937.
[3] R. G. Farmer, A. L. Schwalb, and E. Katz, “Navajo project report on
this paper. In the initial step a frequency scanning is performed subsynchronous resonance analysis and solutions,” IEEE Trans. Power
to identify the presence of network resonances. The use of a con- App. Syst., vol. PAS-96, no. 4, pp. 1226–1232, Jul./Aug. 1977.
ventional induction generator equivalent circuit was compared [4] J. Daniel, C. Han, S. Hutchinson, R. Koessler, D. Martin, G. Shen, and
W. Wong, ERCOT CREZ Reactive Power Compensation Study, Grid
against a more accurate equivalent circuit and it was shown Systems Consulting Group, Power Systems Division, ABB Inc., 2010.
that the conventional equivalent circuit is adequate. It has been [5] Accommodating High Level of Variable Generation, North American
shown that, if a network resonance is revealed in the first step, it Electric Reliability Corporation, 2009.
[6] R. K. Varma, S. Auddy, and Y. Semsedini, “Mitigation of subsyn-
is essential to perform a detailed eigenvalue analysis regardless chronous resonance in a series-compensated wind farm using facts con-
of whether the net resistance seen by the generator rotor is neg- trollers,” IEEE Trans. Power Del., vol. 23, no. 3, pp. 1645–1654, Jul.
ative or positive. The proposed detailed analysis clearly iden- 2008.
[7] A. Ostadi, A. Yazdani, and R. K. Varma, “Modeling and stability
tifies the participating state variables, and the controllability of analysis of a DFIG-based wind-power generator interfaced with a
the sub-synchronous oscillation mode. Case studies performed series-compensated line,” IEEE Trans. Power Del., vol. 24, no. 3, pp.
for a simple power system and two multi-machine power sys- 1504–1514, Jul. 2009.
[8] L. Fan, R. Kavasseri, Z. L. Miao, and C. Zhu, “Modeling of DFIG-
tems revealed that the sub-synchronous oscillations associated based wind farms for SSR analysis,” IEEE Trans. Power Del., vol. 25,
with Type 3 wind turbine-generators and series compensated no. 4, pp. 2073–2082, Oct. 2010.
384 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 28, NO. 1, FEBRUARY 2013

[9] G. D. Irwin, A. K. Jindal, and A. L. Isaacs, “Sub-synchronous control U. D. Annakkage (M’95–SM’04) received the B.Sc.
interactions between type 3 wind turbines and series compensated ac (Eng.) degree from the University of Moratuwa,
transmission systems,” in Proc. IEEE PES General Meeting, Detroit, Moratuwa, Sri Lanka, in 1982 and the M.Sc. and
MI, Jul. 24–28, 2011. Ph.D. degrees from the University of Manchester
[10] L. A. Kilgore, D. G. Ramey, and M. C. Hall, “Simplified transmission Institute of Science and Technology (UMIST),
and generation system analysis procedures for subsynchronous reso- Manchester, U.K., in 1984 and 1987, respectively.
nance problems,” IEEE Trans. Power App. Syst., vol. PAS-96, no. 6, He is presently a Professor at the University of
pp. 1840–1846, Nov. 1977. Manitoba, Winnipeg, MB, Canada. His research
[11] B. L. Agrawal and R. G. Farmer, “Use of frequency scanning tech- interests include power system stability and control,
niques for subsynchronous resonance analysis,” IEEE Trans. Power security assessment and control, operation of restruc-
App. Syst., vol. PAS-98, no. 2, pp. 341–349, Mar./Apr. 1979. tured power systems, and power system simulation.
[12] C. Karawita, “HVDC interaction studies using small signal stability Dr. Annakkage is an editor of the IEEE TRANSACTIONS ON POWER SYSTEMS.
assessment,” Ph.D. dissertation, Univ. Manitoba, Winnipeg, MB,
Canada, 2009.
[13] C. Karawita and U. D. Annakkage, “Multi-infeed hvdc interaction
studies using small-signal stability assessment,” IEEE Trans. Power C. Karawita (S’04–M’09) received the B.Sc. (Eng)
Del., vol. 24, no. 2, pp. 910–910, Apr. 2009. degree from the University of Moratuwa, Moratuwa,
[14] C. Karawita and U. D. Annakkage, “A hybrid network model for small Sri Lanka, in 2002 and the M.Sc. and Ph.D. degrees
signal stability analysis of power systems,” IEEE Trans. Power Syst., from the University of Manitoba, Winnipeg, MB,
vol. 25, no. 1, pp. 443–451, Feb. 2010. Canada, in 2006 and 2009, respectively.
[15] O. Anaya-Lara, N. Jenkins, J. Ekanayake, P. Cartwright, and M. He is currently working at TransGrid Solutions
Hughes, Wind Energy Generation Modelling and Control. Chich- Inc., Winnipeg. His research interests include power
ester, U.K.: Wiley, 2009. system stability and control and power system
[16] R. Pena, J. C. Clare, and G. M. Asher, “Doubly fed induction gener- simulation.
ator using back-to-back PWM converters and its application to variable
speed wind-energy generation,” Proc. Inst. Elect. Eng., Elect. Power
Appl., vol. 143, no. 3, pp. 231–241, May 1996.
[17] M. Pöller and S. Achilles, “Aggregated wind park models for analyzing
power system dynamics,” in Proc. 4th Int. Workshop Large-Scale Inte-
gration of Wind Power and Transmission Networks for Offshore Wind D. A. Jacobson (M’85–SM’05) received the B.Sc.
Farms, Billund, Denmark, Oct. 20–21, 2003. and M.Sc. degrees in electrical engineering and the
[18] IEEE Task Force on Load Representation for Dynamic Performance, Ph.D. degree from the University of Manitoba, Win-
“Standard load models for power flow and dynamic performance sim- nipeg, MB, Canada.
ulation,” IEEE Trans. Power Syst., vol. 10, no. 3, pp. 1302–1313, Aug. He has been employed with Manitoba Hydro
1995. in the System Planning Department for 20 years.
[19] IEEE Subsynchronous Working Group, “Readers guide to subsyn- Since 2002, he has been involved with a variety of
chronous resonance,” IEEE Trans. Power Syst., vol. 7, no. 1, pp. groups in the wind industry. In addition to leading
150–157, Feb. 1992. interconnection or exploratory studies of wind
[20] S. Jiang, U. D. Annakkage, and A. M. Gole, “A platform for valida- generators in Manitoba, he is also a stakeholder in
tion of FACTS models,” IEEE Trans. Power Del., vol. 21, no. 1, pp. many U.S. studies that have investigated multi-GW
484–491, Jan. 2006. connections and major 765 kV overlays.
[21] H. Li and Z. Chen, “Transient stability analysis of wind turbines with Dr. Jacobson is a contributing member of the NERC Interconnection of Vari-
induction generators considering blades and shaft flexibility,” in Proc. able Generation Task Force. He is a steering committee member of the CanWEA
33rd Annu. Conf. IEEE Industrial Electronics Society (IECON), Taipei, Pan-Canadian wind integration study. He is a Distinguished Member of Cigre
Taiwan, Nov. 5–8, 2007. and has contributed to many working group reports over the years including:
[22] P. Kundur, Power System Stability and Control, N. Balu, Ed., 1st ed. Joint Study Committee C1/C2/C6.18 Coping with Limits for Very High Pene-
New York: McGraw-Hill, 1994. tration of Renewable Energy, C6.08 Integration of Large Share of Fluctuating
Generation, and C4.601 Power System Security Assessment. He is a member
D. H. R. Suriyaarachchi (S’11) received the B.Sc. of the IEEE Wind Power Coordinating Committee and is the current Technical
(Eng) degree from the University of Moratuwa, Committee Program Chair.
Moratuwa, Sri Lanka, in 2003 and the M.Sc. degree
from the University of Manitoba, Winnipeg, MB,
Canada, in 2008. He is currently pursuing the Ph.D.
degree at the Department of Electrical and Computer
Engineering, University of Manitoba.
His research interests include power system sta-
bility and control, power system simulation, and re-
newable energy.

Potrebbero piacerti anche