Sei sulla pagina 1di 25

इंटरनेट मानक

Disclosure to Promote the Right To Information


Whereas the Parliament of India has set out to provide a practical regime of right to
information for citizens to secure access to information under the control of public authorities,
in order to promote transparency and accountability in the working of every public authority,
and whereas the attached publication of the Bureau of Indian Standards is of particular interest
to the public, particularly disadvantaged communities and those engaged in the pursuit of
education and knowledge, the attached public safety standard is made available to promote the
timely dissemination of this information in an accurate manner to the public.

“जान1 का अ+धकार, जी1 का अ+धकार” “प0रा1 को छोड न' 5 तरफ”


Mazdoor Kisan Shakti Sangathan Jawaharlal Nehru
“The Right to Information, The Right to Live” “Step Out From the Old to the New”

IS 15528 (2004): Gaseous Fire Extinguishing Systems -


Carbon Dioxide Total Flooding and Local Application (
Sub-Floor and In-Cabinet), High and Low Pressure
(Refrigerated) Systems [CED 22: Fire Fighting]

“!ान $ एक न' भारत का +नम-ण”


Satyanarayan Gangaram Pitroda
“Invent a New India Using Knowledge”

“!ान एक ऐसा खजाना > जो कभी च0राया नहB जा सकता ह”


है”

Bhartṛhari—Nītiśatakam
“Knowledge is such a treasure which cannot be stolen”
IS 15528:2004

Indian Standard
GASEOUS FIRE EXTINGUISHING SYSTEMS —
CARBON DIOXIDE TOTAL FLOODING AND
LOCAL APPLICATION ( SUB-FLOOR AND
IN-CABINET ), HIGH AND LOW PRESSURE
( REFRIGERATED) SYSTEMS

ICS 13.220.10

(3 BIS 2004

BUREAU OF INDIAN STANDARDS


MANAK BHAVAN, 9 BAHADUR SHAH ZAFAR MARG
NEW DELHI 110002

Price Group 8
Fire Fighting Sectional Committee, CED 22

FOREWORD

This lndian Standard was adopted by the Bureau of Indian Standards, after the draft finalized by the Fire
Fighting Sectional Committee had been approved by the Civil Engineering Division Council.

This standard is intended for use by those concerned with purchasing, designing, installing, testing, inspecting,
approving, and operating carbon dioxide ( C07 ) total flooding and local application extinguishing systems, in
order that such equipment/system will function as intended throughout its life.

It is important that the fire protection of a building or plant be considered as a whole. Carbon dioxide systems
I_orm only a part, though an important part, of the available fire protection facilities. However, it should not be
assumed that their adoption necessarily removes the need to consider supplementary measures, such as the
provision of portable fire extinguishers or mobile appliances for first aid or emergency use, or measures to deal
\vitll special hazards.

Carbon dioxide is recognized as effective for extinguishing Class B fires and where electrical risks are present.
I Iowever, it should not be forgotten in the planning of comprehensive schemes that there may be hazards for
which this technique is not suitable, or that, in certain circumstances or situations, there may be dangers in its
wse, requiring special precautions.

The discharge of carbon dioxide creates a dangerous oxygen deficiency, which may result in unconsciousness
~ind subsequent suffocation, Carbon dioxide should be used normally in unoccupied area.

Advice on the above can be obtained from organizations involved with the installation of carbon dioxide total
flooding systems.

The objective of this standard is to provide the users of carbon dioxide systems specific requirements for
the control of fires of Class B type. It does not cover the design of explosion suppression systems.

It is essential that fire extinguishing equipment be carefully maintained to ensure instant readiness when required.
The importance of maintenance cannot be too highly emphasized.

This standard has been prepared to meet the need for the dissemination of information on established
system design, Its requirements represent the best technical data known at the time of preparation but, since a
wide field is covered, it has been impracticable to consider every possible factor or circumstance that might
affect implementation.

It is a basic assumption that this standard be used only by persons competent in the field of application with
which it deals. This is of particular importance in fire protection work, Accordingly, it is emphasized that the
design requirements in this Standard are to be interpreted only by trained and experienced designers.

This standard does not include specific requirements for carbon dioxide systems for marine applications. However,
the method of calculation in this standard may be of some assistance in the design of such systems.
IS 15528:2004

Indian Standard
GASEOUS FIRE EXTINGUISHING SYSTEMS —
CARBON DIOXIDE TOTAL FLOODING AND
LOCAL APPLICATION ( SUB-FLOOR AND
IN-CABINET ), HIGH AND LOW PRESSURE
( REFRIGERATED) SYSTEMS
1 SCOPE due to obscuration of vision and reduction of oxygen
concentrations below that which wi II not support Iife,
1.1 This standard lays down the requirements for not only in the immediate area of discharge, but also in
carbon dioxide systems, utilizing high pressure or adjacent areas to which the gas may migrate. Therefore,
refrigerated low pressure carbon dioxide as the fire the safety requirmlents given in 5.1 shall be strictly
observed.
extinguishant system.
4.2 Uses of Carbon Dioxide
1.2 The carbon dioxide shall comply with the
requirements of IS 15222. Carbon dioxide is suitable for extinguishing the
following types of fire:
1.3 General principles may well apply for other uses
such as in-cabinet subfloor for which additional a) Under certain conditions, fires involving
considerations may have to be taken into account. carbonaceous solid materials, usually of an
organic nature, in which combustion normally
2 REFERENCES
takes place with the formation of glowing
The standards listed in Annex A contain provisions embers ( Class A fires ).
which through reference in this text, constitute
b) Fires involving flammable and combustible
provisions of this standard. At the time of publication, liquids ( .Class B fires).
the editions listed were valid. All standards are subject
to revision and the parties to agreements based on c) Fires involving combustible gases, except
this standard are encouraged to apply the most recent when, after extinguishment, an explosive
editions of the standards indicated in Annex A. atmosphere may develop due to a
continuation of escaping gases ( Class C
3 DEFINITIONS fires ).

For the purpose of this standard, the definitions given d) Fires involving live electrical apparatus.
in IS 15493 shall apply.
4.3 Limitations of Carbon Dioxide Systems
4 USES AND LIMITATIONS OF CARBON
Carbon dioxide systems are not suitable for use on
DIOXIDE
fires involving the following:
4.1 General
a) Chemicals containing their own supply of
The extinguishing medium corbon dioxide is a oxygen, such as cellulose nitrate.
colorless, odourless and electrically non-conductive b) Reactive lmetals and their hydrides ( for
gas. Carbon dioxide is approximately one and a half example, sodium, potassium, magnesium,
times heavier than air. titanium and zirconium ).
Carbon dioxide extinguishes fires principally by 5 SAFETY REQUIREMENTS
reducing the oxygen content in the atmosphere to a
point where it will not support combustion. 5.1 Safety of Personnel

The relationship between the temperature and 5.1.1 Protection ofOccupants


pressure of liquid carbon dicxide is shown in Fig. 1,
The discharge of carbon dioxide in fire extinguishing
At31 “C, the liquid and vapour have the same density,
concentration creates serious hazards for personnel,
and of course the liquid phase disappears. This is
such as reduced visibility and suffocation, during and
called critical temperature of carbon dioxide.
after discharge period. Suitable safeguards shall also
NOTE — Carbon dioxide concentrations, as required be provided to ensure prompt evacuation, to prevent
for use in extinguishing systems, pose hazards to personnel entry into such areas and provide a means for prompt
1
1S 15528:2004

—-.—.- ..— —..—-—. —..——


CRI 1IGAL TEMPERATURE I
I
10.0
9.0
\
8.0
i
7.0
\
6.0
5.0 (

4.0 7

3.0

2.0

SOLID REGION VAPOUR

1.0
/
0.9
/
0.8
/
0.7 N
/
0.6
0.5
–TRIPLE-POINT

‘“’itmmmtt
0.3
I

0.2

0.1
I

183
v
193
I
203
I

213
I
223
1
233
?

243
I f
L,

253
I
ATMOSPHERIC
I
263
I
[
273
1
,
PRESSURE

283
I
293 303
L
313
TEMPERATURE, “K

-90 -80 -70 -60 -50 -40 -30 -20 -10 0 10 20 30 40


TEMPERATURE, ‘C

FIG. 1 VARIATIONOF PRFSSURE OF CARBON DIOXIDE wnm CHANCE IN TEMPERATIJRE( CONSTANTVOLIJME )

rescue of any trapped personnel. the system shall be isolated and the lock-off control
activated.
5.1.2 Precautions for Enlet-ing Confined Spaces and
Low Lyit7g A i-eas Entry into confined spnces for any purpose shall be
controlled by a permit-to-work system. Provisions
Entry into confined spaces poses additional shall be made for ensuring that the atmosphere within
hazards because of restrictions on freedom of the space is safe for entry and shall remain so for the
movement, ventilation, escape or rescue. Before entry duration of entry. In cases where effective ventilation
into floor and ceiling voids, ducts, process vessels cannot be ensured, the permit shall specify the
or similarly confined spaces, the automatic release of respiratory protective equipment to be used and any
2
IS 15528:2004

other special precautions to be observed to ensure 5.2.3 Electrostatic Discharge


safe working conditions.
The discharge of liquid carbon dioxide is known to
Where it is possible for carbon dioxide gas to collect produce electrostatic charges which, under certain
in low-lying areas, pits, wells and shaft bottoms, conditions, could create a spark. Carbon dioxide fire
consideration shall be given to adding an odoriferous extinguishing systems protecting areas where
substance to the carbon dioxide. In such areas, the explosive atmospheres couId exist shall utilize metal
installation of additional ventilation systems shall be nozzles and be properly bonded and earthed. In
considered. addition, objects exposed to discharge from carbon
dioxide nozzles shall be earthed to dissipate possible
5.1.3 Entry to Protected Areas
electrostatic charges. Where pipe work is to be bonded
Entry into a protected area shall normally only be made and earthed, it shall colmply with IS 7689.
when the total flooding system has been placed under
6 SYSTEM DESIGN
manual control by means of a Iock-offvalve.
6.1 General
5.2 Safety Precautions
The requirements for total flooding systems and
5.2.1 General
those for local application systems are given in 6.2
The minimum safety precautions associated with to 6.18.
the use of carbon dioxide at fire extinguishing
6.2 Total Flooding Systems Basis for Design
concentrations are as follows:
The construction of the enclosure to be protected
a) Inhibit switch and time delay ( with alarm
by carbon dioxide total flooding systems shall be
hooter ),
such as to prevent ready escape of the gas. Openings
b) Safety interlock, and and ventilation systems shall be closed or shut
c) Lock-off valve. down automatically before, or at least
simultaneously with, initiation of discharge of the
5.2.2 Electrical Clearance carbon dioxide, and remain shut. Where openings
cannot be shut or where there is an absence of
All system components shall be so located as to
walls or ceilings, additional carbon dioxide quantities
maintain minimum clearance from live parts as per
shall be provided as specified in 6.7. Openings to
Table 1.

Table 1 Clearance from Carbon Dioxide Equipment to Live Uninsulated Electrical Components
( Clause 5.2.2)

S1 No. Nominal System Maximum System Design Basic Minimum Clearance


Voltage, kV Voltage, kV Insulation Level, kV mm
(1) (2) (3) (4) (5)
i) up to 15.8 14.5 110 178
ii) 23 24.3 150 254
iii) 34.5 36,5 200 330
iv) 46 48,3 250 432
v) 69 72,5 350 635
vi) 115 121 550 1067
vii) 138 145 650 1270
viii) 161 169 750 1 473
ix) 230 242 900 1930
1 050 2134
x) 345 362 1 050 2134
I 300 2642
xi) 500 550 1 500 3 150
1 800 3658
xii) 765 800 2050 4 242
NOTE — The clearance is the air distance between equipment, including piping and nozzles, and unenclosed or un-
insulated live electrical components at other than ground potential.

3
1S 15528:2004

the outside atmosphere, where wind conditions may 6.3.2 Leakage and Ventilation
affect the carbon dioxide losses, might necessitate
Since the efficiency of carbon dioxide systems depends
special consideration.
upon the maintenance of an extinguishing concentration
Examples of hazards and their enclosures that can of carbon dioxide, leakage of gas from the area shall
be successfully protected by total flooding systems be kept to a minimum and compensated for by applying
include rooms, vaults, enclosed machines, ducts, ovens, extra gas.
containers, and their contents.
Where possible, openings such as doorways and
6.3 Design Quantity of Carbon Dioxide windows shall be arranged to close automatically before
or simultaneously with the start of the carbon dioxide
6.3.1 Factors to be Considered discharge, or the requirements of 6.7 and 6.11 shall
To determine the quantity of the carbon dioxide be followed. For personnel safety, see 5.1.
required, the volume of the room or of the enclosure Where air handling ventilation systems are involved,
to be protected shall be taken as a basis. From this they shall be shut down or isolated by dampers, or
volume only, solid structural members, such as both, before or simultaneously with the start of the
foundations, columns and beams, are to be deducted. carbon dioxide discharge. Where this is not practical,
The following shall be taken into account: additional compensating gas shall be provided.
a) Room size, 6.3.3 Types of Fires
b) Material to be protected,
Fires which can be extinguished by total flooding
c) Particular risks, methods can be divided into two categories,
d) Openings that cannot be closed, namely:
e) Ventilation systems which cannot be shut a) Surface fires involving flammable liquids,
down, and gases and solids; and
f) Temperature of protected area. b) Deep-seated fires involving solids subject
For flash or surface type fires, such as will be present to shouldering.
with flammable liquids, any non-closing openings shall Surface fires are the most common hazard suitable
be compensated for by additional carbon dioxide as for extinguishment by total flooding systems. They
specified in 6.4.5. If the quantity of carbon dioxide are extinguished promptly when carbon dioxide is
required for compensation exceeds the basic quantities introduced into the enclosure in sufficient quantity
required for flooding without leakage, the system both to overcome leakage and to provide an
shall be designed for local application in accordance extinguishing concentration suitable for the
with 7. particular materials involved.
For deep-seated fires such as those involving solids, For deep-seated fires, the extinguishing concentration
non-closing openings shall be restricted to those shall be maintained for a sufficient period to allow
bordering on, or actually in the ceiling, if the size of the shouldering to be extinguished and the material
the openings exceed the pressure relief venting to cool to a point at which reignition will not occur
requirements set out in 6.5. after dissipation of the inert atmosphere.
To prevent fire from spreading through openings 6.3.4 Pressure Adjustment
to adjacent hazards or work areas, which may be
possible reignition sources, such openings shall be The quantity of carbon dioxide shall be adjusted
provided with automatic closures or local application to compensate for ambient pressures that vary
nozzles. The gas required for such protection shall more than 11 percent ( equivalent to approximately
be in addition to the normal requirement for total 915 m of elevation change ) from standard sea level
flooding ( see 6.15). When neither method is practical, pressure ( 760 mm Hg ). The ambient pressure is
protection shall be extended to include these adjacent affected by changes in altitude, pressurization or
hazards or work areas. depressurization of the protected enclosure,
and weather-related barometric pressure changes.
In the case of process and storage tanks, where safe The adjusted storage quantity is determined by
venting of flammable vapours and gases cannot be multiplying the number of carbon dioxide containers
realized, external local application systems are used (IV), determined in accordance with 6.2, by the ratio
for protection across the openings, and the area per of average ambient enclosure pressure to standard
nozzle given by specific approval or listing may be sea level pressure. The atmospheric correction factors
increased by 20 percent. are given in Table 2.
4
IS 15528:2004

Table 2 Atmospheric Correction Factors 6.4.3 Volume Factor


( Clause 6.3.4) The volume factor used to determine the basic quantity
of carbon dioxide to protect an enclosure containing
S1 No. Equivalent Enclosure Atmospheric
a material requiring a design concentration of
Altitude Pressure Correction
M mndHg Factor 34 percent shall be in accordance with Table 4.
(1) (2) (3) (4) The quantity of COj required shall be further calculated
i) –0.920 840 1.11 to compensate for any special conditions, such as
-0.610 812 1.07 unclosable openings, forced ventilation, the free volume
-0.300 787 1.04
of air receivers that may discharge into the risk, altitude
ii) 0,000 760 1.00 ( substantially above or below sea level ) or any other
iii) 0.300 733 0.96 causes for the extinguishant loss.
0,610 705 0.93
0.920 678 0.89 As the average small space has proportionally
iv) 1.220 650 0.86 more boundary area per enclosed volume than a
1.520 622 0.82 larger space, proportionally greater leakages are
1.830 596 0.78 anticipated and accounted for by the graded volume
v) 2.130 570 0.75 factors in Table 4.
2.440 550 0.72
2.740 528 0,69 The least gas quantities for the smallest volumes are
vi) 3.050 505 0.66 tabulated to clarify the intent of COI 2 and 3 of
Table 4 and thus avoid possible overlapping at
6.4 Carbon Dioxide Requirements for Surface Fires borderline volumes.

In two or more interconnected volumes in which the


6.4.1 General
‘free flow’ of carbon dioxide is likely to take place,
the carbon dioxide quantity shall be the sum of the
The quantity of carbon dioxide for surface fires is based
quantities calculated for each volume, using its
on average conditions assuming reasonably prompt
respective volume factor from Table 4. If one volume
extinguishment. An allowance for normal leakage is
requires greater than normal concentration, the higher
included in the basic volume factors, but corrections
concentration shall be used in all interconnected
shall be made for the type of material involved and
volumes.
for any other special conditions.
6.4.4 Material Conversion Factor
6.4.2 Flammable Materials
For materials requiring a design concentration of
Consideration shall be given to the determination more than 34 percent, the basic quantity of carbon
of the design concentration of carbon dioxide dioxide calculated from the volume factor given
required for the type of flammable material in Table 4 shall be increased by multiplying this
involved in the hazard. The design concentration quantity by the appropriate conversion factor given
is determined by adding a suitable factor in Fig. 2.
(30 percent ) of the theoretical minimum concentration.
In no case shall a concentration of less than 34 percent 6.4.5 Special L’onditions — Total Flooding Systems
be used. 6.4.5.1 General

Table 3 gives the theoretical minimum carbon dioxide Additional quantities of carbon dioxide shall be
concentration to prevent ignition of some common provided to compensate for any special conditions
liquids and gases. that may adversely affect the extinguishing efficiency
of the system.
For materials not given in Table 3, the minimum
theoretical carbon dioxide concentration shall be 6.4.5.2 Unclosable openings
obtained from a recognized source or determined
Any openings that cannot be closed at the time of
by test. If accepted residual oxygen values are
extinguishment shall be compensated for by the
available, the theoretical carbon dioxide
addition ofa quantity of carbon dioxide equal to the
concentration shall be calculated by the following
anticipated loss at the design concentration during
equation:
a 1 min period. This amount of carbon dioxide shall
be applied through a regular distribution system
21–02
Percent, C02 = x 100 ( see 6.5 and 6.6 ). For ventilating systems that
21 cannot be shut down, additional carbon dioxide
5
IS 15528:2004

Table 3 Minimum Carbon Dioxide Concentrations for Extinguishment


( Clause 6.4.2)

sl No. \laterii]l l%eoretical Minimum C(), Minimum Design CO,


Concentration, Pcrccnt Concentration, Percent
(1) (2) (3) (4)
i) Acetylene 55 66
Acetone 27 ( S6’@ Note 2 ) 34
Aviation gas grades 115/145 3() 36
ii) Benzol benzene 31 37
Butadicne 34 41
Butane 28 34
iii) Butane-1 31 37
Carbon disulfidc 60 72
Carbon monoxide 53 64
ii, ) Coal gas or natural gas 31(see Note2) 37
Cyclopropaoe 31 37
[>iethyl ether 33 40
v) Dirnethyl ether 33 40
Dowtherm 38 ( see Note 2 ) 46
Ethane 33 40
vi) Ethyl alcohol 36 43
Ethyl ether 38 ( see Note 2 ) 46
Ethylene 41 49
vii) Ethylene dichloride 21 34
Ethylene oxide 44 53
Gasoline 28 34
viii) J-lexanc 29 35
I [igher paraffin 28 34
I{ydrocarbons 62 75
C~ IIZ,,,+ 2M – 5
F!ydrogen
ix) Hydrogen sulfide 30 36
Isobutane 20 ( see Note 2 ) 36
Isobutylcne 26 34
x) lsobutyl formate 26 34
.IP4 30 36
Kerosene 28 34
xi) Methane 25 34
h4cthyl acetate 29 35
Methyl alcohol 33 40
xii) Methyl butene-1 3() 36
Methyl ethyl ketone 33 40
Methyl formate 32 39
xiii) Pentanc 29 35
Propane 30 36
l’ropyiene 30 36
xiv) Quench, lubrication oils 28 34
NOTES
1 The theoretical minimum extinguishing concentrations in air for the above materials II ere obtained from a compilation
of USA Bureau of Mines’ Limits of flammability of gases and vapours ( Bu]]etins 503 and 627 ).
2 Concentrations calculated from accepted oxygen values,

shall be added to the space through the regular when the design concentration is greater than 34
distribution system, in an amount computed by dividing percent.
the volume moved during the liquid discharge period
6.4.5.3 High tenzpevut~me
by the flooding factor. This shall be rntiltiplied by
the material conversion factor ( determined in Fig. 2 ) For applications where the normal temperature of the
6
IS 15528:2004

Table 4 Flooding Factors 6.4.5.4 Low tetnperalure


( Clauses 6.4.3 and6.4.4 )
For applications where the normal temperature of
A B c: the enclosure is below– 8°C at one percent increase
Volume of Volume Factor Calculated in the calculated total quantity of carbon dioxide shall
Space \ Quantity be provided for each 2.3°C below-1 8°C.
1113 m~lkg CO, kg CO@3 + kg
(1) (2) - (3) (4) 6.5 Carbon Dioxide Requirements for Deep-Seated
Fires
4 0.86 1.15
4 to 15 0.93 1.07 4.5 6.5.1 General
15 to 46 0.99 1.01 15.1

47 to 130 1,11 0,90 45.4 The quantity of carbon dioxide for deep-seated
type fires is based on tight enclosures. After the design
131(0 1400 1.25 0.80 I 13.5
concentration is reached, the concentration shall
> 1 400 1.38 0.77 I 135,0
be maintained for a substantial period but not less
than 20 min. Any possible leakage shall be given
enclosure is above 93°C, hazards may be more special consideration since no allowance is included
susceptible toreignition. Therefore, additional carbon in the basic flooding factors.
dioxide is advisable to hold the extinguishing
concentrations for a longer period of time, allowing 6.5.2 Combustible Materials
the extinguished material to cool down and thereby
For combustible materials capable of producing
reduce the chance of reignition when the carbon
deep-seated fires, the carbon dioxide concentrations
dioxide dissipates.
cannot be determined with the same accuracy as
surface burning materials. The extinguishing
One percent increase in the calculated total quantity
concentration will vary with the mass of material
of C02 shall be provided for each additional 5°F above
present because of the thermal insulating effects.
200°F ( 93°C ).
Flooding factors have therefore been determined on

~
u
$3
z
o
z
lx
>
82
c1

1
30 34 40 50 60 70 80 90

MINIMUM DESIGN C02 CONCENTRATION, PERCENT

FIG. 2 MArERIAL CONVERSIONFAC-IORS

7
IS 15528:2004

the basis of practical test conditions. 6.6 Rate of Application

The design concentrations in Table 5 shall be achieved The minimum design rate of application shall be based
for the hazards listed. Generally, the flooding on the quantity of carbon dioxide and the maximum
factors in Table 5 provide the design concentration time to achieve design concentration as follows:
for the rooms and enclosures listed.
a) For surface fires, the design concentration
Flooding factors for other deep-seated fires shall be shall be achieved within 1 min.
justified to the satisfaction of the appropriate authority
b) For high pressore systems, if a part of the
before use. Consideration shall be given to the mass
hazard is to be protected by local
of material to be protected because the rate of cooling
application, the discharge rate for the total
is reduced by the thermal insulating effects.
flooding portion shall be calculated as
6.5.3 Volume Consideration specified in 6.12.
c) For deep-seated fires, the design
When calculating the net cubic capacity to be
concentration shall be achieved within
protected, allowance should be made for the
1 min and maintained for 7 rnin, but the rate
reduction of volume by permanent non-removable
shall be not less than that required to
impermeable structures materially reducing the
develop a concentration of 30 percent
voi Lime.
in 2 min.
The basic quantity of carbon dioxide required to
protect an enclosure shall be obtained by treating the 6.7 Extended Rate of Application
volume of the enclosure by the appropriate flooding
Where leakage is appreciable and the design
factor given in 6.4.2.
concentration must be obtained quickly and maintained
6.5.4 Special Conditions for an extended period of time, carbon dioxide provided
for leakage compensation may be applied at a reduced
6.5.4.1 General rate.
Additional quantities of carbon dioxide shall be
Figure 3 maybe used as a guide in estimating discharge
provided to compensate for any special conditions
systems.
that may adversely affect the extinguishing efficiency
( see 6.3.2,6.3.3 and 6.3.4). 6.7.1 This type of system is particularly applicable
to enclosed rotating electrical apparatus, such as
6.5.4.2 Unclosable openings
generators, motors and converters, but it may also
Any openings that cannot be closed at the time of be used on ordinary total flooding applications where
extinguishment shall be compensated for by the suitable.
addition of carbon dioxide equal in volume to the
6.7.2 The minimum design concentration shall be
expected leakage volume dyring the extinguishing
obtained within the time limits specified in 6.6(c).
period. If leakage is appreciable, consideration
shall be given to an extended discharge system 6.7.3 The extended rate of
discharge shall be sufficient
( see 6.7). to maintain the minimum concentration.

Table 5 Flooding Factors for Specific Hazards


(Clause 6.5.2)

SI No. Design Concentration Flooding Factor Specific Ilazarxt


,- \
m~lkg C02 kg CO@3
(1) (2) (3) (4) (5)
i) 50 0.62 1.60 Dry electrical hazards in general
areas <0 -56.6 m3
ii) 50 0.75 1.33 Dry electrical hazards in general
areas >56.6 m3
iii) 65 0.50 ( 9 I kg ) Min Bulk paper storage, ducts, and
2.00 covered trenches
iv) 75 0.38 2.66 For storage vaults, dost
collectors

8
IS 15528: 2004

489.00
440.10
391.20
342.30
293.40
244.60

195.60

146.70

: 97.80
.-
E

2
~“ 48.90

5 ‘w;
& 34,23
~ 29.34
j 24.45

19.58

1 1 I I 1 I xl

l=”
I
~4.67
I

9.78

Iv4 v
4---- 1 I I I I I I ! I I I 1 I 1 I I I 1
0.3 0.6 0.9 1.2 1.51.821,2 .42!73.1 6.1 9.2 12.21 ~,318~124j731

HEIGHT OF ATMOSPHERE ABOVE CENTRE OF OPENING, METRES

FIG. 3 CALCULATEDC02 Loss RATE BASED ON AN ASS[JM~D21 “C TEMPERATURE


WITHIN THE ENCLOSUREAND 21 “C AMBiIiNI- OUTSIDE

6.7.4 For enclosed rotating electrical equipment, a The method for the venting of flammable vapours
minimum concentration of 30 percent shall be and pressure build-up from the discharge of
maintained for the deceleration period, but not less quantities of carbon dioxide into closed areas shall
than 20 min. be considered. The pressure venting consideration
involves such variables as enclosure strength and
6.8 Piping Systems injection rate.
Piping shall be designed in accordance with 8 and 6.10 Hazard Specification
IS 15493 to deliver the required rate of application
at each nozzle. The hazard shall be isolated from other hazards or
combustibles in such a way that fire will not spread
High pressure storage temperatures can range from outside the protected mea. The entire hazard shall
–18° to 54°C without requiring special methods of be protected. The hazard shall include all areas that
compensation for changing flow rates. are likely to be coated with combustible liquids or
shallow solids coatings, such as areas subject to
6.9 Local Application/In-cabinet Subfloor Systems
spillage, leakage, dripping, splashing, or condensation,
Local application systems shall be designed, installed and all associated materials or equipment, such as
and tested in accordance with the applicable freshly coated stock, drain boards, hoods and ducts,
requirements covered in 6.5 and with the additional that might extend fire outside or lead fire into the
requirements of this clause. protected area.

9
IS 15528:2004

A series of connected hazards can be subdivided into portion;


smaller groups or sections with the approval of the lV~ = total quantity of carbon dioxide for the
regulatory authority. Systems for such hazards shall total flooding portion, in kg; and
be designed to give immediate independent protection
T~ = liquid discharge time for the local
to adjacent groups or sections as needed.
application portion, in minutes.
6.11 Carbon Dioxide Requirements
6.13 Duration of Discharge
The quantity of carbon dioxide required for local
The minimum effective discharge time for use in
application systems shall be based on the total rate
calculating the quantity shall be 60 s. The minimum
of discharge needed to blanket the area or volume
time shall be increased to compensate for any hazard
protected and the time that the discharge must be
condition that would require a longer cooling period
maintained to ensure complete extinguishment.
to assure complete extinguishment.
For systems with high pressure storage, the calculated
Because the tests conducted in the approvals of
quantity of carbon dioxide shall be increased by
carbon dioxide nozzles will require that fires be
40 percent to establish the nominal cylinder
extinguished within 20 s, a minimum duration of 30 s
storage capacity since only the liquid portion of the
has been set for this standard. This allows a safety
discharge is effective. This increase in cylinder
factor for conditions which are unpredictable. It is
storage capacity is not required for the total flooding
important to recognize that this discharge time is
portion of the combined local application of total
minimum and that such conditions as high temperatures
flooding systems.
and the cooling of unusually hot surfaces within the
Where long pipelines are involved, or where the hazard area require an increase in the discharge time
piping may be exposed to higher than normal to ensure complete and effective extinguishment.
temperatures, the quantity shall be increased by an
Where the fuel has an auto-ignition point below its
amount sufficient to compensate for liquid vaporized
boiling point, such as paraffin wax and cooking oils,
in cooling the piping.
the effective discharge time shall be increased to permit
6.12 Rate of Discharge cooling of the fuel to prevent reignition. The minimum
discharge time shall be 3 min.
Nozzle discharge rates shall be determined by either
the surface method or the volume method as covered The maximum temperature of a burning liquid fuel
in 6.150 r6.16. is limited by its boiling point where evaporative
cooling matches the heat input. In most liquids,
The total rate of discharge for the system shall be the
the auto-ignition temperature is far above the
sum of the individual rates of all the nozzles used on
boiling temperature so that reignition after
the system.
extinguishment can be caused only by an external
For low pressure systems, if a part of the hazard is to ignition source. However, there are a few liquids that
be protected by total flooding, the discharge rate for have auto-ignition temperatures much lower than
the total flooding part shall be sufficient to develop their boiling temperatures. Common cooking oils
the required concentration in not more than the and melted paraffin wax have this property. To
discharge time used for the local application part of prevent reignition of these materials, it is necessary
the system. to maintain an extinguishing atmosphere until the
fuel has cooled below its auto-ignition
For high pressure systems, if a part of the hazard is temperature. A discharge time of 3 min is adequate
to be protected by total flooding, the discharge rate for small units, but a longer time is needed for larger
for the total flooding part shall be calculated by dividing capacity units.
the quantity required for total flooding by the factor
1.4 and by the time of the local application discharge 6.14 Rate by Area Method of System Design
in minutes.
6.14.1 General
The rate of discharge may be calculated using the
The area method of system design is used where the
following equation:
fire hazard consists primarily of flat surfaces or low-level
objects associated with plane surfaces.
~F= ‘F
1.4 TL System design shall be based on listing or approval
data for individual nozzles. Extrapolation of such data
where
above or below the upper or lower limits shall not be
QF = rate of flow for the total flooding permitted.

10
IS 15528:2004

6.14.2 Nozzle Discharge Rates stated in specific approvals.

The design discharge rate through individual nozzles Nozzles should be installed perpendicular to the
shall be determined on the basis of location or hazard and centred over the area protected by the
projection distance, in accordance with specific nozzle. They may also be installed at angles between
approvals or listings. 45° and 90° ( see 3.2 ) from the plane of the hazard
surface as prescribed in 9.8. The distance used in
The discharge rate for overhead type nozzles shall determining the necessary flow rate and area coverage
be determined solely on the basis of distance from shall be the distance from the aiming point on the
the surface each nozzle protects. protected surface to the face of the nozzle measured
along the axis of the nozzle.
6.14.3 Area Protected by Nozzle
When installed at an angle, nozzles shall be aimed at
The maximum area protected by each nozzle shall be
a point measured from the nearside of the area protected
determined on the basis of location or projection
by the nozzle, the location of which is calculated by
distance and the design discharge rate, in accordance
multiplying the fractional aiming factor in Table 6 by
with specific approvals or listings.
the width of the area protected by the nozzle.
The same factors used to determine the design
Table 6 Aiming Factors for Angular Placement of
discharge rate shall be used to determine the maximum
Nozzles Based on 150 mm Freeboard
area to be protected by each nozzle.

The portion of the hazard protected by individual S1 No. Discharge Anglel) Aiming Factorz)
overhead-type nozzles shall be considered as a square (1) (2) (3)
area. i) 45° to 60° ‘/4

ii) 60° to 75° !4 to 3/8


The portion of the hazard protected by individual tank
iii) 75° to 90° 3/8 to !4
side or linear nozzles shall be either a rectangular or
a square area, in accordance with spacing and discharge iv) 90° ( perpendicular ) Y2 centre
limitations stated in specific approvals or listings.
l)ln degrees from the plane of hazard surface.
When coated rollers or similar irregular shapes are to ‘)The fraction of the width of the area protected.
be protected, the projected wetted area shall be used
to determine nozzle coverage.
Nozzles shall be located so as to be free of possible
When coated surfaces are to be protected, the area obstruction that could interfere with the proper
protected per nozzle may be increased by 40 percent projection of the discharged carbon dioxide.
over the areas given in specific approvals or listings
Nozzles shall be located so as to develop an
for a liquid surface. Coated surfaces are defined as
extinguishing atmosphere over coated stock
those designed for drainage which are constructed
extending above a protected surface. Additional
and maintained so that no pools of liquid will accumulate
nozzles may be required for this purpose, particularly
over a total area exceeding 10 percent of the protected
if stock extends more than 0.6 m above a protected
surface. This does not apply where there is a heavy
surface.
build-up of residue.
The possible effects of air currents, winds and
Where local application nozzles are used for protection
forced drafts shall be compensated for by properly
across openings, the area per nozzle given by specific locating nozzles or by providing additional nozzles
approval or listing may be increased by 20 percent. to protect the outside areas of the hazard
When deep layer flammable liquid fires are to be adequately.
protected, a minimum freeboard of 150 mm shall be 6.15 Rate by Volume Method System Design
provided unless otherwise noted in approvals of
nozzles. 6.15.1 General

6.14.4 Location and Number of Nozzles The volume method of system design is used where
the tire hazard consists ofthree-dimensional irregular
A sufficient number of nozzles shall be installed over objects that cannot be easily reduced to equivalent
the entire area on the basis of the unit areas protected surface areas.
by each nozzle.
6.15.2 Assumed Enclosure
Tank side or linear-type nozzles shall be located in
accordance with spacing and discharge rate limitations The total discharge rate of the system shall be based

11
IS 15528:2004

on the volume of an assumed enclosure entirely 6.15.4 Location and Number of Nozzles
surrounding the hazard.
A sufficient number of nozzles shall be used to
The assumed enclosure shall be based on an actual adequately cover the entire hazard volume on the basis
closed floor unless special provisions are made to take of the system discharge rate as determined by the
care of bottom conditions. assumed volume. The design discharge rate through
individual nozzles shall be determined on the basis
The assumed walls and ceiling of this enclosure shall
of location or projection distance.
be at least 0.6 m from the main hazard unless walls
are involved, and shall enclose all areas of possible 6.16 Distribution System
leakage, splashing or spillage.
6.16.1 General
No deductions shall be made for solid objects within
this volume. The system shall be designed to provide prompt and
effective discharge of carbon dioxide before excessive
A minimum dimension of 1.2 m shall be used in amounts of heat can be absorbed by materials within
calculating the volume of the assumed enclosure. the hazard.

If the hazard is likely to be subjected to winds or forced The carbon dioxide supply shall be located as near
drafts, the assumed volume shall be increased to to the hazard as practicable and yet not exposed to
compensate for losses on the windward sides. the fire. The pipeline shall be as direct as practicable
with a minimum number of turns in order to get carbon
6.15.3 Total Discharge Rate
dioxide to the fire promptly.
The total discharge rate for the basic system shall be
The system shall be designed for automatic operation
equal to 16 kg/min/m3 of assumed volume.
except where the appropriate regulatory authority
If the assumed enclosure has a closed floor and is permits manual operation.
partly defined by permanent continuous walls
6.16.2 Piping Systems
extending at least O.6 m above the hazard ( where
the walls are not normally part of the’ hazard ), the Piping shall be designed in accordance with 9 to deliver
discharge rate may be reduced proportionally to not the required rate of appl ication at each nozzle.
less than 4 kg/min/m3 for actual walls completely
surrounding the enclosure ( see Fig. 4 ). High pressure storage temperatures can range from

‘OO h

75

50

?5

25

0
4 6 8 10 12 14 16
kg/rein/m 3

FIG. 4 DISCHARGERATE

12
IS 15528:2004

0° to 49°C without requiring special methods of tolerance of ‘~~ ~ percent the mass being
compensating for changing flow rates. determined by w~ighing.
NOrE — The tilling ratio is the ratio of mass of liquefiable
7 PROTECTED ENCLOSURE REQUIREMENTS
gas in the containers to lhe mass of water the container
7.1 Where venting of an enclosure may be necessary will hold at 15”C’.
to relieve pressure build-up due to the discharge of Where the container design does not incorporate a
large quantities of carbon dioxide, the area necessary
safety pressure relief device, it shall be incorporated
for free venting shall be not less than that determined
in the container valve.
from the following equation:
8.2.2 Storage Container Arrangement
2.236 x102x QxV
x —
Kxfix v“ The arrangement of storage containers and accessories
shall be as follows:
where
~. a) The necessary carbon dioxide quantity
vent opening area, in mm2;
shall be contained in one bank. The supply
Q= extinguishant mass flow rate, in kg/rein; to separate distinct hazards could be from
p= enclosure max. structural safe working a single bank where there is no likelihood
pressure, in kPa; of the fire spreading from one hazard to
v= specific volume of extinguishant at another and provided that the cylinder bank
room temperature and pressure, in is not placed within any of the hazards. The
mJ/kg; total quantity of the bank shall correspond
J/l= specific to the largest quantity of carbon dioxide
volume of vented
required to protect any one area or object.
extinguishantlair mixture in m3/kg; and
The release systems of the bank and the
K. orifice flow coefficient ( dimensionless, pipes shall be arranged in such a way that
and usually 0.5 to 0.6 for small openings each protected zone will be flooded
in walls ). individually. A typical high pressure storage
facility using a number of cylinders is shown
If values of V and V] corresponding to 35 percent
in Fig. 5.
concentration and standard room temperature and
pressure are substituted, and if X is in mm2 and Q in b) Storage temperatures should not exceed, nor
kg/rein, the equation becomes fall below, the following range unless the
system is designed to operate effectively at
247.3x Q storage temperatures outside this range:
/,y.
K@ 1) Total flooding systems temperature
8 CARBON DIOXIDE SUPPLY range Max 55”C; A4in – 18”C.
2) Local application systems temperature
8.1 Quality
range Max 49°C; Min O°C.
The extinguishant used shall be carbon dioxide External heating or cooling should be used
complying with the requirements of IS 15222. to keep the temperature located within the
A non-combustible, non-toxic trace gas that is desired range. Where special container
compatible with the extinguishant and the materials charges are used, the container should be
of construction maybe added to the charge to facilitate appropriately marked.
leak testing. c) Where gas pressure, from pilot cylinders
fed through the system discharge manifcld
8.2 High-Pressure Systems
( that is using back pressure rather than a
8.2.1 Storage Containers separate pilot line ), is used to release the
remaining slave cylinders, and the supply
The carbon dioxide supply shall be stored in
consists of three cylinders, one cylinder shall
containers designed to hold carbon dioxide. The
be used for such operation. If the supply
containers shall comply with the following:
consists of three cylinders or more, there shall
a) Requirements as per IS 8198 ( Part 1 ) and be one pilot cylinder more than the minimum
IS8198(Part3) required to actuate the system. During the
full discharge acceptance test, the extra pilot
b) The container shall be internally dry and
cylinder shall be arranged to operate as a slave
be filled with dry carbon dioxide to the
cylinder.
maximum filling ratio of 0.667 within a
13
IS 15528:2004

I
A A

‘w>
NOZZLES

I A- DIRECTIONAL VALVES

y\J
VENT —
T CHECK RELIEF VALVE

m
VALVES DISCHARGE PIPED
“7
INTO OUTSIDE
ATMOSPHERE

LRELIEF
VALVE

L INITIAL
CYLINDERS
Jl- RESERVE
CYLINDERS
J

FJci. 5 A TYPICALHIGH-PRESSURESTORAGEFACILITY

An example of cylinder arrangement for three or more 8.3 Low-Pressure Systems


cylinders is to locate a slave cylinder at the farthest
8.3.1 Low-Pressure Refrigerated Storage Containers
point ( No. 1 position) from the manifold outlet, and
two or more pilot cylinders in the next two or more The carbon dioxide supply shal) be stored in
positions ( Nos. 2, 3, and soon), numbering toward containers designed to hold carbon dioxide. The
the manifold outlet. Actuation of any remaining pilot containers shall comply with the following:
cylinder(s) should provide sufficient pressure in the
manifold to actuate the slave cylinders and all other a) Requirements as per IS 8198 ( Part 1 ) and
pressure-actuated devices and interlocks. ( Part 3 ).
b) The design shall ensure the temperature of
Alternate I — When Nz gas pressure from pilot
the carbon dioxide in the container shall be
cylinder fed through the system discharge is used to
maintained between –16°C and –18°C at a
release the remaining slave cylinders, there shall be
pressure of approximately 2.0 MPa. Means
one pilot cylinder of same capacity of slave cylinder
shall be provided to indicate continuously
minimum required with >10 MPa pressure with
the quantity of carbon dioxide.
pressure regulator suitable to reduce the pressure for
the operation of slave cylinder valve for the multiple c) An automatic refrigerating system shall
use. Maximum 20 cylinders can permit for discharge. ensure that the temperature and pressure of
Pressure switch also can provide outlet of pressure carbon dioxide are kept within the required
regulator for the alarm indication for pilot cylinder limits.
pressure is not available for the activation of the d) An over-pressure alarm shall be provided
system. Since cylinder with >10 MPa pressure pilot that will sound a local warning at
cylinder can operate number of times, and after every approximately 10 percent below the
operation pilot cylinder need not to send for Nzfilling. pressure at which the pressure relief device
One standby pilot also can propose if the system operates.
having large quantity of slave cylinders. e) A low-pressure alarm shall also be provided
that will sound a local warning at not less
.41ternate 2 — Carbon dioxide master cylinder can
than 1.7 MPa.
also use for the discharge of slave cylinders in the
system without using any N~ pilot cylinders. Part f) A contents loss alarm shall also be provided
of master cyiinder COZ gas will operate the slave to indicate a loss exceeding 10 percent of
cylinder and balance quantity of CO~ gas fed to the mass. All alarms shall be extended to a
manifold. C02 master cylinder shall operate directly normally manned remote monitoring
and manually .- location.

14
IS 15528:2004

d The audible warning connected with loss, in net content of more than 10 percent, it shall be
pressure monitoring shall be independent refilled/replaced. Online continuous gas weight monitoring
arrangement is recolmmcaded.
of the electrical circuit supplying the
refrigeration unit. 9 DISTRIBUTION SYSTEM
h) The cylinder shall have sufficient insulation
9.1 General
to limit the loss of carbon dioxide to not more
than 1.5 percent or 5 kg, whichever is the In addition to the requirements of IS 15493, the
greater, up to 6 t charge, not more than piping shall withstand the maximum developed
0.8 percent for 6 to 10 tcharge and not more storage pressure, as per Table 7.
than 0.5 percent for over 10 tcharge in 24 h
in the event of a failure of the refrigerating Table 7 Typical System Pressures
system at the highest expected ambient
temperature. sl Examples Nominal Maximum
No. of System Storage Developed
j) Insulation materials shall be protected to Pressure Pressure Storage Pressure
avoid mechanical damage. WiPa at 55”C, MPa
k) Containers shall be fitted with pressure (1) (2) (3) (4)
gauge(s), safety valve(s) and pressure relief i) Low-pressure 2.1 3.1 manifold relief
valves as per IS 14150. Care shall be taken syste131s valve setting
to ensure that during the filling of the ii) High-pressure 5.2 15.5
containers the temperature of the carbon systems
dioxide corresponds to the value necessary
to the proper functioning of the system. For determining the size of distribution systems,
m) The pressure relief valves shall be mounted see 6.
in pairs on a two-way changeover valve
9.2 Steel Pipe
arranged to ensure that one relief valve always
provides protection against excessive Discharge pipes and pipe fittings shall be in
pressure within the container and the accordance with IS 15493.
discharge from the valve shall be piped to
a safe location external to the building. It Stainless steel pipe and fittings may be used in all
shall not be possible for the two-way applications, but shall be subject to appropriate design
changeover valve to isolate both relief valves strength calculations.
at the same time.
9.3 Piping Joints
n) Shall have means provided to prevent
containers from being overfilled. 9.3.1 Joint of’Ferrous Pipes
P) Where the entire contents of a low-
Jointing of ferrous pipes shall be mechanical, welded,
pressure container are not to be discharged
screwed or flanged and comply with IS 10234.
at the same time, all control or directional
valves shall be arranged to close after the 9.4 Dirt Traps
required quantity has been discharged.
A dirt trap consisting of a tee with a capped nipple,
8.4 Container Condition at least 51 mm long, shall be installed at the end of
each pipe run.
Container shall be thoroughly dried before filling,
especially if the container has been hydrostatically 9.5 Safety Devices
tested.
9.5.1 Pressure Relief Device
NOTES
1 A likely source of contamination would be the presence Where there is a possibility of carbon dioxide
of free water in the system container before filling with entrapment in pipework ( for example, between
carbon dioxide.
container valves and directional valves ), a suitable
2 The requirements of the appropriate authorities pressure-relief device shall be fitted as follows:
covering containers could take precedence over the
requirements of this Standard, for example, in marine a) For 2.1 MPa systems, the device shall be
or aviation areas. Accordingly, the appropriate authority
designed to operate at 3.1 MPa + 5 percent.
should be contacted for advice.
3 All high pressure cylinders shall be weighed atleast
b) For 5.2 MPa systems, the device shall be
once in six months. If at any time a container shows a designed to operate at 15.0 MPa + 5 percent.

15
1S 15528:2004

Means should be provided for safely depressurizing where


such piping in theevent that the operating pressure
Q,, = flow rate, in kg/rein;
of thedevice has not been attained. Where a valve is
fitted for this purpose it shall be monitored. D = inside pipe diameter ( actual ), in mm;
L = equivalent length of pipeline, in m; and
9.5.2 Discharge Indicator
Y and Z = factors depending on storage and line
The discharge indicator shall be as follows: pressure.

a) Manually reset, and NOTES


1 For systems with low-pressure storage, flow shall be
b) Provide visible indication that carbon dioxide
calculated on the basis of an average storage pressure
has been discharged. of 2.1 MPa absolute during discharge. The discharge rate
for equivalent orifices shall be based on the values given
9.6 Pipe and Orifice Size Determination in Table 9. Design nozzle pressures shall not be less
than 1.1 MPa,
Pipe sizes and orifice areas shall be selected on the
basis of calculations to deliver the required rate of 2 For systems with high-pressure storage, flow shall be
calculated on the basis of an average storage pressure
flow at each nozzle.
of 5.2 Ml>a during discharge for normal 21 “C storage.
The following equation or curves developed from it The discharge rate through equivalent orifices shall be
based on the values given in Table 10. Design nozzle
shall be used to determine the pressure drop in the
pressure at21 ‘C storage shall be not less than 2.1 MPa.
pipeline:
Figure 6A and Fig. 6B give flow information
10-5X 0.8725 D525 Y for – 18°C storage temperature on the basis of
Q2M .

LO.043 19D125Z above equation.

I I 1 I I 1 I I I I I I I
I

OsQm
\ 1 X1 I . 1 \ 1 xl 1
I

a 1.4

1.3

1.2

1.1
1.0
0.9
0.8
0 0.5 1 2 3 4 5678

L/Dl .25, ~/mm 1.25

FIG. 6A PRESSUREDROPIN PIPELINEFOR2.07 MPA STORAGESYSTEMS

16
IS 15528:2004

5.17 I I I I I I I I I I I

5.0 ~Qh2- - I I I I I

4.5

g4.o

Ill

;3.5
u)
LLl
%3.0

2.5
, ,, ,
2.0
1.5 I I II II I \l \l!l!ll\llll Y
o 0,5 1 2 345678

L/D 1.25 ,m/mm 1.25

FIG. 6B PRESSUREDROPIN PIPELINEFOR5.17 MPA STORAGESYSTEMS

9.7 Nozzle the system or for individual hazards where the


system is to protect multiple hazards simultaneously,
9.7.1 The nozzles shall be designed and located in shall be within 65 to 85 percent of the cylinder
such a manner that an even distribution of gas will outlet area or of the area of supply pipe, whichever is
be achieved throughout the protected space and, at smaller. The system protecting materials subject to
the same time, the discharge from the nozzles shall glow or shouldering ( see hazards in Table 3 ) the
not cause undue splashing of flammable liquids or total area of all discharge outlets shall be within
creation of dust clouds that might aid spread of fire, the range of 3 to 10 percent of cylinder outlet area,
cause explosion or otherwise adversely affect the except that the total area of all discharge outlets
contents of the protected space. When installed in shall not exceed 85 percent of the supply pipe area.
duct work spacing and sizing of nozzles is dependent
upon the following factors: 9.7.3 Nozzles vary in design and discharge
characteristics and shall be selected to suit the intended
a) Velocity in duct; purpose.
b) Location and effectiveness of dampers; 9.7.4 For installations intended for surface fire
c) Possible loading of duct walls with protection, the aggregate cross-sectional area of
combustible deposits; and nozzle outlet shall not exceed 85 percent or be less
than 35 percent of the aggregate release outlet area
d) Duct length and cross-section dimensions.
of the system, or minimum cross-sectional area of
NOTE — No allowance is needed for inlet and outlet
the pipe, as determined from Table 8, whichever is
duct openings, C02 tire extinguishing system protecting
areas where explosive atmospheres could exist shall utilize smaller.
metal nozzles and shall be properly grounded. ( Since
9.7.5 For installations intended for deep seated
discharge of liquid C02 is known to produce electrostatic
charges which under certain conditions could create a fire protection, the aggregate cross-sectional area of
spark. ) nozzle shall not exceed 85 percent of the cross-sectional
area of the pipe as determined from Table 9, nor be
9.7.2 For systems protecting quick burning less than three percent of the aggregate release
materials, the total area of all discharge outlets for outlet area of the system.
17
IS 15528:2004

9.7.6 Nozzles shall be capable of withstanding Table 8 Orifice Code Numbers and Equivalent
pressures up to 14 Mpa and shall be of Leaded tin Orifice Sizes
bronze (see IS 318). ( Clauses 9.7.4 and9.2.8 )
9.7.7 Nozzles used in the local application installations
S1 Orifice Equivalent Equivalent Single
shall be so connected and supported that these may
No. Single Orifice ‘Orifice Area-
not be readily put out of adjustment. Diameter
——
9.7.8 Irrespective of the number of orifice or the shape mm inch mm2 inch2
of the nozzle, it shall be marked, permanently and (1) (2) (3) (4) (5) (6)
indelibly, to show its equivalent single orifice diameter. i) I 0.79 1/32 0.49 0.0008
All nozzles having an equivalent single orifice diameter 1.5 1.19 3164 1.11 0.001 7
of 2.38 mm and more shall also be marked with a code 2 1.59 1/16 1.98 0.003 1
number as given in Table 8. ii) 2.5 1.98 5/64 3.09 0.0047
3 2.38 3132 4.45 0.0069
9.7.9 The limitations for nozzle spacing and 3.5 2.78 7/64 6.06 0.0094
coverage as well as minimum and maximum distance iii) 4 3.18 1/8 7.94 0.0123
above flammable liquid surfaces ( in depth) shall be 4.5 3.57 9/64 10.00 0.0155
determined for each type and size of nozzle and 5 3,97 5/32 12.39 0.0192
checked and verified by a testing laboratory. Where iv) 5.5 4.37 11/64 14.97 0.0232
this information is not provided, the limitations 6 4.76 3/16 17.81 0.0276
for spacing and location of nozzles shall be governed 6.5 5.16 13/64 20.90 0.0324
by the following: v) 7 5.56 7/32 24.26 0.0376
7.5 5.95 15/64 27.82 0.043 1
a) Nozzles shall not be spaced more than 1 m 8 6.35 1/4 31.68 0.049 1
apart. A single row of nozzles may be vi) 8.5 6.75 17164 35.74 0.0554
satisfactory for area, up to 1.25 m width; and 9 7.14 9/32 40.06 0.062 1
9.5 7.54 19/64 44.65 0.0692
b) One additional row of nozzles shall be
provided for each additional 1.25 m width of vii) 10 7.94 5/16 49.48 0.0767
11 8.73 11/32 59.87 0.0928
hazard area, or fraction thereof.
12 9.53 3/8 71.29 0.1105
9.7.10 Where nozzles are likely to get clogged by viii) 13 10.32 13/32 83.61 0.1296
foreign materials these shall be provided with 14 11.11 7/16 96.97 0.1503
frangible discs which shall automatically rupture 15 11.91 15/32 111.29 0.1725
by the pressure of the discharging gas. ix) 16 12.70 1/2 126.71 0.1964
18 14.29 9/16 160.32 0.2485
10 IDENTIFICATION 20 15.88 5/8 197.94 0.3086
x) 22 17.46 11/16 239.48 0.371 2
Each container shall be identified by being coloured
24 19.05 314 285.03 0.441 8
red approximating Signal Red of IS 5 over the whole
32 25.40 1 506.45 0.7850
of the cylinder.
xi) 48 38.40 1 1/2 1 138.7 1.7650
11 COMMISSIONING AND ACCEPTANCE 64 50.80 2 2025.8 3.1400
TESTLNG NOTE — Formerly, a plus sign following the orifice
code number indicated equivalent diameters 0.4 mm
11.1 Criteria for Acceptance greater than that indicated by the numbering
system, for example, No. 4 indicated an equivalent
The completed carbon dioxide system shall be diameter of 3.18 mm ( 4/32 inch) and No. 4+, 3,47 mm
commissioned in accordance with IS 15.493 and the ( 9/64 inch ).
system’s performance proved by at least one of the
following methods: hydrostatic pressure test of 1.25 times
the calculated pipework’s maximum
a) Subject the system to a full discharge developed storage pressure at 55”C, then
test, performed in accordance with purge the system to remove the moisture
IS 15493 and the results shall comply and prove free passage.
with 6.
2) Subect the protected area to an enclosure
b) Where a full discharge test using carbon integrity test.
dioxide is not required by the appropriate
authority, the following proc&dure shall 11.2 Commissioning Certification
apply:
When the system is commissioned, the installation
1) Subject the distribution system to a contractor shall issue a test certificate.
18
IS 15528:2004

Table 9 Discharge Rate per 64.5 mmz or Table 10 Discharge Rate per 64.5 mm2 or
Equivalent Orifice Area for Low-Pressure Equivalent Orifice Area for High-Pressure
Storage 2.07 MPa Storage 5.17 MPa
( Clauses 9.6 and9.7.5 ) ( Clause 9.6)

S1 No. Orifice Pressure Discharge Rate S1 No. Orifice Pressure Discharge Rate
MPa kg/min/mm2 MPa kg/min/mm2
(1) (2) (3) (1) (2) (3)
i) 2.07 2.970 0 5.17 3.258
2.00 2.041 ii) 5.00 2.706
1,93 1.671
iii) 4.83 2.403
ii) 1,86 1.443
1.79 1.284 iv) 4.65 2,174
1.72 1.165 v) 4.48 1.995
iii) 1.65 1.073 vi) 4.31 1.840
1.59 0.992
vii) 4,14 1.706
1.52 0.918
viii) 3,96 1.590
iv) 1.45 0.851
1.38 0.792 ix) 3.79 1.488
1.31 0.737 x) 3.62 1,397
v) 1.24 0.688 xi) 3,45 1.309
1.17 0.642
xii) 3.28 1.224
1.10 0.600
xiii) 3.10 1.140
vi) 1.03 0.559
xiv) 2.93 1.063
xv) 2.76 0.985
11.3 Failure
xvi) 2.59 0.908
xvii) 2.41 0,830
Where the system fails to comply with either
IS 15493 or this clause, the fault shall be rectified xviii) 2.24 0.760
and, if necessary, the system retested. xix) 2,07 0.690

ANNEX A
( Clause 2 )

LIST OF REFERRED INDIAN STANDARDS

IS No Title IS No Title

5:1995 Colours for ready mixed paints 10234:1982 Recommendation for general pipe
and enamels (jourth revision ) line welding

318:1981 Specification for leaded tin bronze 14150:1994 Hydraulic fluid power — Pressure
ingots and castings relief valves — Mounting
surfaces
7689:1989 Guide for the control of
undesirable static electricity 15222:2002 Specification for carbon dioxide
(first revision ) as fire extinguishing media for
fire protection
8198 Code of practice for steel cylinders
for compressed gases: 15493:2004 Gaseous fire extinguishing
systems — General requirements
(Part l): 1984 Atmospheric gases ( first
revision )

(Part 3):1984 High pressure liquefiable gases


(first revision )

19
Bureau of Indian Standards

BIS is a statutory institution established under the Bureau of Indian ,Sta/?dards Act, 1986 to promote
harmonious development of the activities of standardization, marking and quality certification of goods and
attending to connected matters in the country.

Copyright

BIS has the copyright of all its publications. No part of these publications may be reproduced in any form
without the prior permission in writing of BIS. This does not preclude the free use, in the course of implementing
the standard, of necessary details, such as symbols and sizes, type or grade designations. Enquiries relating
to copyright be addressed to the Director (Publications), BIS.

Review of Indian Standards h

Amendments are issued to standards as the need arises on the basis of comments. Standards are also reviewed
periodically; a standard along with amendments is reaffirmed when such review indicates that no changes are
needed; if the review indicates that changes are needed, it is taken up for revision. Users of Indian Standards m
should ascertain that they are in possession of the latest amendments or edition by referring to the latest issue
of ‘BIS Catalogue’ and ‘Standards : Monthly Additions’.

This Indian Standard has been developed from Doc : No. CED 22 ( 7144 ).

Amendments Issued Since Publication

Amend No. Date of Issue Text Affected

BUREAU OF INDIAN STANDARDS


Headquarters:

Manak Bhavan, 9 Bahadur Shah Zafar Marg, New Delhi 110002


Telephones: 23230131,23233375,2323 9402 Website: www.bis.org.in

Regional Offices : Telephones

Central : Manak Bhavan, 9 Bahadur Shah Zafar Marg 23237617


NEW DELHI 110002 { 23233841

Eastern : l/14C. I.T. Scheme VI IM, V. I. P. Road, Kankurgachi 23378499,23378561


KOLKATA 700054 { 23378626,23379120
Northern : SCO 335-336, Sector 34-A, CHANDIGARH 160022 2603843
{ 2609285
Southern: C. I. T. Campus, IV Cross Road, CHENNA1600 113 22541216,22541442
{ 22542519,22542315
Western : Manakalaya, E9 MlDC, Marol, Andheri (East)
. [ 28329295,28327858
MUMBAI-400 093 ~ 28327891,28327892

Branches: AHMEDABAD. BANGALORE. BHOPAL. BHUBANESHWAR. COIMBATORE.


FARIDABAD. GHAZIABAD. GUWAHATI. HYDERABAD. JAIPUR. KANPUR.
LUCKNOW. NAGPUR. NALAGARH. PATNA. PUNE. RAJKOT. THIRUVANANTHAPURAM.
VISAKHAPATNAM.
Printed at New India Printing Press, Khurja, India

Potrebbero piacerti anche