DO NOT SCALE FROM THIS DRAWING A A


1. GENERAL 3. LIGHTWEIGHT ROOF 10.5 TO BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER’S DETAILS AND
6.6 GANTRY AND CRADLE SYSTEM ALONG WITH SUPPORTS SHOULD BE TESTED TO INSTRUCTIONS.
1.1 THESE PERFORMANCE SPECIFICATIONS ARE APPLICABLE TO SUPPLIER DESIGNED ITEMS IN 3.1 THE SPAN OF THE ROOF SHOULD BE AS SHOWN ON THE ARCHITECTURAL GA SPECIFIED WORKING LOADS PRIOR TO USE.
ALL WP12 AND WP11 UNDERGROUND STRUCTURES TOGETHER WITH ASSOCIATED ABOVE DRAWINGS, TYPICALLY 1000mm. ROOF SHEET TO BE 1-WAY SPANNING BETWEEN 10.6 REFER TO MANUFACTURER’S LITERATURE FOR MAXIMUM UNSUPPORTED OPENING
GROUND AND ANCILLARY BUILDINGS. PURLINS. 7. HANDRAILS & BALUSTRADES SIZES.

1.2 ALL NOTES SHOULD BE READ IN CONJUNCTION WITH STRUCTURAL, ARCHITECTURAL, 3.2 IMPOSED LOAD OF 1kPa OR 1.33kN CONCENTRATED LOAD (TABLE 1607.1 OF IBC 7.1 DETAILED DESIGN AND DRAWINGS INCLUDING FIXINGS BACK TO THE MAIN 11. INTERNAL WALLS, INCLUDING DESTINATION WALLS
MECHANICAL, ELECTRICAL AND PUBLIC HEALTH DRAWINGS. 2009) FOR ROOFS >3m ABOVE GROUND LEVEL. STRUCTURE TO BE DESIGNED BY CONTRACTOR. DESIGN TO BE IN ACCORDANCE
WITH IBC 2009 1607.7 AND ARCHITECTURAL INTENT DRAWINGS M-BAR-000DS0-CA00- GLAZED WALLS AND METAL STUD WALLS
B 1.3 ALL STEELWORK AND STEELWORK CONNECTIONS SHOULD BE DESIGNED AS PER THE 3.3 WIND SUCTION CONSIDERED TO BE MAXIMUM -3.85kPa (ASCE 7-05 SECTION 6.5) EDR-995401 TO M-BAR-000DS0-CA00-EDR-995446 AND M&W SPECIFICATIONS. 11.1 REFER TO M-BAR-000DS0-CB00-EDR-990560, 990561 AND 990562 FOR STRUCTURAL B
REQUIREMENTS AND MATERIAL PROPERTIES OF GENERAL NOTES DRAWING M-BAR-00DS0- AND ROOF PRESSURE MAXIMUM 0.6kPa. TYPICAL DETAILS OF SUPPORT FRAMES FOR DESTINATION WALL.
CA00-EDR-990006, MISCELLANEOUS METAL SPECIFICATION M-BCW-000000-CBST-ESP- 7.2 HANDRAILS AND GUARDS SHALL BE DESIGNED TO RESIST THE FOLLOWING LOADS
005500 AND STEELWORK SPECIFICATION M-BCW-000000-CBST-ESP-005120. 3.4 ROOFING EXCLUDING PURLINS TO WEIGH LESS THAN 0.5kPa IN PLAN (50kg/m²). AND TRANSFER THEM THROUGH THE SUPPORTS TO THE STRUCTURE. 11.2 REFER TO M-BAR-000DS0-CA00-EDR-990501 to 990528 FOR INTERNAL WALL
7.2.1. A LOAD OF 0.73 kN/m APPLIED IN ANY DIRECTION AT HANDRAIL LEVEL. A LOAD OF INFORMATION
1.4 ALL FIXINGS TO CONCRETE STRUCTURES SHOULD USE MECHANICAL ANCHORS AS PER 3.5 THERMAL MOVEMENT TO BE RELEASED BY SLOTTED JOINTS OR SIMILAR. 1.5kN/m FOR PUBLIC AREAS OR AREAS WHERE CROWDS MAY DEVELOP.
DRAWING M-BAR-000DS0-CB00-EDR-990710. MANUFACTURER’S GUIDANCE TO BE FOLLOWED WHEN DESIGNING AND FIXING 7.2.2. A LOAD OF 0.29kN/m IN AREAS NOT ACCESSIBLE TO THE GENERAL PUBLIC AND 11.3 ANY SECONDARY FRAMING REQUIRED TO SUPPORT THE DESTINATION WALL
INTO PURLINS TO CATER FOR THERMAL MOVEMENT TO AVOID THE RISK OF THAT HAVE AN OCCUPANCY LOAD LESS THAN 50, IN ACCORDANCE WITH IBC SHOULD BE DESIGNED TO ACCOMMODATE THE FOLLOWING LOADING:
1.5 STRUCTURES AND FIXINGS MUST BE ADEQUATE TO WITHSTAND LATERAL AIR PRESSURES BUCKLING. 2009 1607.7.1. 3.1. SDL = 1.0kN/m² AND 0.538kN/m² BY GLAZING SELF-WEIGHT AT FIRST LEVEL
IN ADDITION TO LOADINGS IMPOSED BY THE ITEMS THEY SUPPORT AND WIND PRESSURES. 7.2.3. A SINGLE CONCENTRATED LOAD OF 0.89 kN, APPLIED IN ANY DIRECTION AT ANY AND ABOVE THREE LEVEL RESPECTIVELY (DENSITY OF GLAZING ASSUMED
TYPICAL LATERAL DESIGN PRESSURES ARE: 3.6 LIGHTWEIGHT ROOF DESIGN SHOULD CATER FOR DEFLECTION CRITERIA FOR POINT ALONG THE TOP IN ACCORDANCE WITH IBC 2009 1607.7.2. TO 2500kg/m³, GLAZING THICKNESS 40.28mm AT FIRST LEVEL AND 21.52mm
Electronic drawings once printed, are uncontrolled and may become out-dated. Refer to Aconex for current revision.

C 1.5.1. 0.85kPa FOR SURFACES FRONTING ONTO TRACKS OR CONNECTED TO SUCH AREAS PURLINS OF SPAN/250 UNDER DEAD AND LIVE LOAD (STATIONS AND BUILDINGS AT ABOVE THREE LEVELS). C
1.5.2. 0.6kPa FOR SURFACES IN STAIR PRESSURISATION AREAS DESIGN REQUIREMENTS VOL2.3-WPS3.01- REV, 1 SECTION 2.2.3.7). 7.3 INTERMEDIATE RAILS, BALUSTERS AND PANEL FILLERS SHALL BE DESIGNED TO
1.5.3. 0.24kPa FOR GENERAL SURFACES IN BELOW GROUND STRUCTURES WITHSTAND A HORIZONTAL NORMAL LOAD OF 0.22kN ON A 300 x 300mm AREA IN 11.4 WALLS SHOULD BE DESIGNED FOR THE FOLLOWING LOADS.
1.5.4. PRESSURES AS PER SECTION 2.9 FOR TUNNEL VENTILATION AREAS 4. SAND LOUVRE AND FRAMES ACCORDANCE WITH IBC 2009 1607. GRAB BARS RE TO BE DESIGNED TO RESIST A 4.1. IMPOSED STATIC LOAD (INTERNAL PRESSURE) = 0.24kN/m² (IBC 2009,
CONCENTRATED LOAD OF 1.11kN IN ACCORDANCE WITH IBC 2009 1607.7.1.2. SECTION 1607.13.1).
4.1 LOUVRES AND VENTS MUST BE DESIGNED TO COMPLY WITH THE FOLLOWING
1.6 ALL MATERIALS SHALL MEET THE APPLICABLE CODE REQUIREMENTS AS REQUIRED BY IBC PROJECT SPECIFICATION: SECTION 010200 [22-08 90 00] M-BCW-000000-CAED-ESP- 4.2. CROWD LOAD OF 1.5kN/m @ 1.1m HEIGHT IN PUBLIC AREAS
2009 1703.4 AND 1704.3. TEST REPORTS CONDUCTED BY AN APPROVED TESTING AGENCY 7.4 NO PART OF A HANDRAIL OR BALUSTRADE SHOULD DEFLECT MORE THAN L/250, WITH
010200. L BEING TWICE THE HEIGHT (IBC 2009, 1604.3.1, NOTE I).
OR OTHER SUCH INFORMATION AS NECESSARY SHALL BE PROVIDED. 11.5 DESTINATION WALL GLAZING IS ASSUMED TO SPAN IN A VERTICAL DIRECTION ON TO
4.2 THE SPAN OF THE LIGHTWEIGHT ROOF SHALL BE AS SHOWN ON THE ARCHITECTURAL JOISTS AS SHOWN ON DRAWINGS M-BAR-000DS0-CB00-EDR-990560 & 990561.
1.7 ARCHITECTURALLY EXPOSED STRUCTURAL STEELWORK MUST BE DESIGNED TO COMPLY 7.5 HANDRAILS AND BALUSTRADES FOR STAIRS, RAILS AND ACCESS WALKWAYS SHOULD
GA DRAWINGS AND SAND LOUVRES SHOULD TYPICALLY BE SUPPORTED BY PURLINS COMPLY WITH THE FOLLOWING PROJECT SPECIFICATIONS: SECTION 005521 [22-05 52
WITH PROJECT SPECIFICATION M-BCW-000000-CBST-ESP-005121 GRADE A U.N.O. ON AT 1m CENTRES. 11.6 THE DESIGN SHOULD WORK TO A DEFLECTION LIMIT OF SPAN/250 UNDER DEAD
D DRAWINGS. 13] M-BCW-000000-CAIF-ESP-005521 AND; SECTION 005721 [22-05 73 00] M-BCW-000000- PLUS LIVE LOAD (STATIONS AND BUILDINGS DESIGN REQUIREMENTS VOL2.3- D
CASF-ESP-005721. WPS3.01- REV, 1 SECTION 2.2.3.7).
4.3 LOUVRES SHOULD BE DESIGNED FOR THE FOLLOWING WIND LOADS IN ACCORDANCE
1.8 REFER TO ARCHITECTURAL SPEC. AND GENERAL NOTES DRAWINGS: M-BAR-000DS0- WITH ASCE 7-05:
CA00-EDR-995010, 995011, 995014 AND 995015 FOR FURTHER INFORMATION 7.6 FOR GEOMETRY AND FINISHES PLEASE REFER TO THE ARCHITECTURAL DRAWINGS 11.7 TO ALLOW FOR REPLACEMENT/MAINTENANCE OF DESTINATION PANELS, THE
4.3.1. 1.5kPa UNFACTORED POSITIVE PRESSURE (TOWARDS SUPPORTING
M-BAR-000DS0-CA00-EDR-995401 TO M-BAR-000DS0-CA00-EDR-995446. FOR FIXINGS HEAVIEST SINGLE ITEM IN THE SYSTEM SHOULD BE CAPABLE OF BEING LIFTED BY
STRUCTURE)
INTO CONCRETE REFER TO TYPICAL STRUCTURAL DETAIL DRAWINGS.
2. GRILLES FOR AIR INTAKE SHAFT OR AIR VENTING 4.3.2. 1.75kPa UNFACTORED SUCTION PRESSURE (AWAY FROM SUPPORTING THE GANTRY AND CLEANING CRADLE. FOR RATED CAPACITY OF THESE SYSTEMS
REFER TO M-BAR-000DS0-CB00-EDR-990510 & 990511.
2.1 LOUVRES AND VENTS MUST BE DESIGNED TO COMPLY WITH PROJECT SPECIFICATION M-
STRUCTURE) 8. RAISED FLOOR SYSTEMS
BCW-000000-CAED-ESP-010200 AND PERFORMANCE REQUIRED ON DRAWINGS. 4.4 STRUCTURE SHOULD BE DESIGNED TO RESIST 400 DEGREES FOR 2 HOURS IN THE 11.8 DESTINATION WALL/DISPLAY PANEL SIZE, DESIGN AND JOINT WIDTH SHOULD
8.1 SYSTEMS TO BE DESIGNED TO ACCOMMODATE UDL & POINT LOADS IN CONSIDER MOVEMENTS OF STRUCTURAL SUPPORT FRAME AND SUPPORTING SLABS
FIRE CASE. ACCORDANCE WITH THE STRUCTURAL STATION LOADING PLANS.
2.2 SPANS FOR GRILLES WILL BE AS SHOWN ON THE ARCHITECTURAL GA DRAWINGS AND IN ACCORDANCE WITH M&W SPECIFICATION REQUIREMENTS.
E E
DETAILS. MAXIMUM ANTICIPATED SPAN BETWEEN JOISTS = 1500mm, MAXIMUM ANTICIPATED 4.5 LOUVRES SHOULD NOT WEIGH MORE THAN 1.0kPa IN ELEVATION (100kg/m²), NOT
SPAN FOR SUPPORT STEELWORK = 6100mm. TO SUIT LOUVRE PRODUCT SELECTED. INCLUDING PURLINS OR SHEETING RAILS.
8.2 AS A MINIMUM RAISED FLOOR SYSTEMS SHOULD BE DESIGNED TO ACCOMMODATE A 12. PAVEMENT/SIDEWALK ACCESS/EMERGENCY
LIVE LOAD OF 2.4kPa IN ACCORDANCE WITH THE IBC 2009, TABLE 1607.1. RAISED
2.3 LIVE LOADING FOR GRILLES SUBJECT TO MAINTENANCE AND EMERGENCY ESCAPE 4.6 THERMAL MOVEMENT TO BE RELEASED BY SLOTTED JOINTS OR SIMILAR, AS SHOWN IN
FLOOR SYSTEMS SHOULD BE DESIGNED FOR LOADS FROM ENVISAGED EQUIPMENT EGRESS HATCHES
ALONG EQUIPMENT REPLACEMENT ROUTES.
ACCESS (<3m ABOVE GROUND LEVEL) SHOULD BE 5kPa UNIFORM OR 1.33kN DETAIL 2 OF M-BAR-000DS0-CB00-EDR-990530. 12.1 TYPE S-50TB ROOF ACCESS HATCH 915 x 760mm BY THE BILCO OR EQUAL AND
CONCENTRATED LOAD. LIVE LOADING FOR GRILLES SUBJECT ONLY TO MAINTENANCE (>3m APPROVED, AS SPECIFIED ON M-BAR-000DS0-CA00-EDR-995010.
8.3 FOR RAISED FLOORING GEOMETRY FINISHES SEE ARCHITECTURAL DRAWINGS.
ABOVE GROUND LEVEL) SHOULD BE 1kPa UNIFORM OR 1.33kN CONCENTRATED LOAD (IBC 4.7 LOUVRES TO BE DESIGNED TO CATER FOR DEFLECTION OF SPAN/250 OF THE
2009, TABLE 1607.1). SHEETING RAILS UNDER DEAD AND LIVE LOAD (STATIONS AND BUILDINGS DESIGN 12.2 REFER TO ARCHITECTURAL DRAWINGS M-BAR-000DS0-CA00-EDR-995272, 995273,
8.4 ANY TESTS REQUIRED BY THE RAISED FLOOR MANUFACTURER (FOR EXAMPLE
REQUIREMENTS VOL2.3-WPS3.01- REV, 1 SECTION 2.2.3.7). 995126 AND 995127 FOR FURTHER INFORMATION.
TEAR-OFF TEST TO DETERMINE THE STRENGTH OF THE SUBSTRATE) SHOULD BE
2.4 WIND SUCTION MAXIMUM PRESSURE IS -3.85kPa (APPLICABLE FOR STRUCTURES BETWEEN
CARRIED OUT AS SPECIFIED AND TO THE APPROPRIATE STANDARDS.
F GROUND LEVEL AND +3M ABOVE GROUND LEVEL ONLY). (ASCE 7-05 SECTION 6.5) 4.8 FOR FURTHER REQUIREMENTS OF THE LIGHTWEIGHT ROOF REFER TO SECTION 3. 12.3 LIVE LOADING FOR ACCESS HATCHES TO STREET LEVEL MUST BE 12kPa UNIFORM F
DISTRIBUTED LOAD AND 35kN POINT LOAD.
8.5 ACCESS FLOORING MUST BE DESIGNED TO BE COMPLIANT WITH THE FOLLOWING
2.5 TOTAL DEFLECTION UNDER DEAD AND LIVE LOADS SHALL BE LIMITED TO SPAN/250 5. ACCESS LADDERS PROJECT SPECIFICATION: SECTION 009690 [22-09 69 00] M-BCW-000000-CASF-ESP-
(STATIONS AND BUILDINGS DESIGN REQUIREMENTS VOL2.3-WPS3.01- REV, 1 SECTION 12.4 ACCESS HATCHES AND THEIR FIXINGS SHOULD BE DESIGNED FOR THE FOLLOWING
5.1 ALL ACCESS LADDERS SHOULD BE DESIGNED IN ACCORDANCE WITH ANSI A14.3-2008. 009690.
2.2.3.7) UNLESS BRITTLE, STRUCTURES ARE TO BE SUPPORTED FROM THE STRUCTURE. LOADS:
WHERE BRITTLE STRUCTURES ARE PRESENT THEY WILL BE IDENTIFIED ON THE
ARCHITECTURAL GA DRAWINGS WITH THE REQUIRED DEFLECTION LIMITS. 5.2 THE MINIMUM LIVE LOADING SHALL BE TWO LOADS OF 1.12kN EACH CONCENTRATED 9. FLOOR/CEILING ACCESS HATCHES 4.1. ACCESS HATCHES AT GROUND LEVEL SHOULD RESIST AN UPLIFT FORCE
OF -3.85kPa DUE TO WIND LOAD.
BETWEEN ANY TWO CONSECUTIVE ATTACHMENTS. EACH STEP OR RUNG IN THE 4.2. OPEN HATCH SHOULD RESIST A LATERAL PRESSURE OF 1.7kPa DUE TO
LADDER SHALL BE DESIGNED FOR A SINGLE CONCENTRATED LIVE LOAD OF 1.12kN 9.1 LIVE LOADING FOR CEILINGS SUBJECT TO MAINTENANCE WITH NO PUBLIC ACCESS
2.6 GRILLES SHOULD COMPLY WITH PROJECT SPECIFICATION: SECTION 005530 [22-05 53 00] M- WIND.
BCW-000000-CBST-ESP-005530. MINIMUM, AS SPECIFIED IN ANSI-ASC A14.3-2008: AMERICAN NATIONAL STANDARD FOR SHOULD BE 1kPa UNIFORM OR 1.33kN CONCENTRATED LOAD, REFER TO IBC 2009,
LADDERS – FIXED – SAFETY REQUIREMENTS, 4.2.1.1. TABLE 1607.1. IT IS ASSUMED THAT THERE WILL BE NO VEHICULAR ACCESS TO THE AREA ABOVE
12.5
G 2.7 MAXIMUM WEIGHT OF GRILLAGE SHOULD BE LIMITED TO 1kPa AND SUPPLIER TO ENSURE ACCESS HATCHES. G
5.3 OTHER LIVE LOADS MUST BE CONSIDERED AS SPECIFIED IN ANSI-ASC A14.3-2008: 9.2 HATCHES MUST PROVIDE A 120 MINUTE FIRE RESISTANCE OR EQUAL TO THE
WEIGHT/RESTRAINT OF GRATINGS IS SUFFICIENT TO RESIST UPLIFT IN ADDITION TO
TIMESTAMP 17/03/2017 15:21:52

PROVIDING SERVICE MECHANICAL FIXINGS AS SPECIFIED ON ARCHITECT’S DRAWING M- 4.2.1.2. SPECIFIED CEILING FIRE RESISTANCE. METAL DECKING SHOULD COMPLY WITH PROJECT SPECIFICATION: SECTION 005310
12.6
BAR-000DS0-CA00-EDR-995115. [22-05 30 00] M-BCW-000000-CBST-ESP-005310.
5.4 SAFE CAPACITY SHOULD BE CLEARLY DISPLAYED ON EACH LADDER. 9.3 LIVE LOADING FOR FLOOR AREAS SUCH AS PLATFORMS THAT WILL BE SUBJECT TO
2.8 SYSTEM TO PROVIDE INTEGRITY WITH 400°C FOR 2 HOURS UNDER WORKING PRESSURE
5.5 LADDERS SHOULD NOT BE FIXED TO BLOCKWORK WALLS UNLESS CHECKED BY
CROWD LOADING SHOULD BE 6kPa UNIFORM, REFER TO IBC 2009, TABLE 1607.1. 13. RETAIL ROLLER SHUTTER
OF FAN OPERATION, AS SPECIFIED ON ARCHITECT’S DRAWING M-BAR-000DS0-CA00-EDR-
STRUCTURAL CALCULATION. 9.4 REFER TO ARCHITECTURAL DRAWINGS FOR INDICATION OF ANY SUPERIMPOSED DEAD REFER TO M-BAR-000DS0-CA00-EDR-993007 AND 993011.
995115. 13.1
LOADING REQUIRED IN ADDITION TO FINISHES.
2.9 STRUCTURES CONNECTED TO TV PLENUM AND SHAFT SYSTEMS SHOULD BE DESIGNED 5.6 WHERE A SINGLE LENGTH OF CLIMB IS GREATER THAN 15240mm, INTERMEDIATE 13.2 WHEN IN THE CLOSED POSITION THE ROLLER SHUTTER MUST BE CAPABLE OF
PLATFORMS ARE TO BE PROVIDED EVERY 7315mm VERTICALLY. 9.5 DEFLECTION SHOULD BE LIMITED SO SPAN/250 UNDER DEAD PLUS LIVE LOAD WITHSTANDING THE LOADS REFERENCED IN 11.4
FOR THE AIR PRESSURES GIVEN IN THE TABLE BELOW, AS SPECIFIED BY AECOM. THESE
H PRESSURES ARE TO BE CONSIDERED IN THE ULS CASE ONLY. THESE LOADINGS SHOULD (STATIONS AND BUILDINGS DESIGN REQUIREMENTS VOL2.3-WPS3.01- REV, 1 SECTION H
BE CONSIDERED IN ADDITION TO OTHER WIND LOADINGS. STRUCTURES CONNECTED TO 5.7 IF A SINGLE LENGTH OF CLIMB EXCEEDS 7315mm A CAGE MUST BE PROVIDED. 2.2.3.7). 13.3 THE LOADS CONSIDERED IN THE STRUCTURE ARE:
ALL TUNNEL VENTILATION DUCTS, SHAFTS AND AIR PLENUMS SHALL BE PROPERLY SDL - ROLLING DOOR SELF-WEIGHT : 1.20kN/m
5.8 GATE THE TOP OF CAGED LADDERS TO PROVIDE SAFETY. 9.6 HATCHES SHOULD COMPLY WITH THE FOLLOWING PROJECT SPECIFICATIONS: - GLAZING SELF-WEIGHT : 0.94kN/m FOR TYPE A AND 1.40kN/m FOR TYPE B
SEALED TO MEET THE AIR TIGHTNESS (DW 143 CLASS C) UNDER WORKING PRESSURE OF
FAN OPERATION GIVEN BELOW. SECTION 005310 [22-05 30 00] M-BCW-000000-CBST-ESP-005310 AND; SECTION 008311
6. ACCESS GANTRY [22-08 31 13] M-BCW-000000-CAEDESP-008311. 14. WAYFINDING SIGNAGE
REFER TO DRAWING M-BAR-000DS0-CB00-EDR-990510 FOR STRUCTURAL
STATION TV PLENUM/SHAFT DESIGN PRESSURE RATING (kPa) 9.7
6.1 TYPICAL DETAILS FOR GANTRY INCLUDING SCHEMATIC OF RS162 ROSTEK HATCHES TO ALL TUNNEL VENTILATION DUCTS, SHAFTS AND AIR PLENUMS (IF ANY) 14.1 WALL-FIXED CANTILEVER SIGNS MUST BE FIXED TO RC WINDPOST. MIN. DIMENSION
2B4 TV FANS 1.7 MONORAIL OR SIMILAR APPROVED REQUIRED TO SUPPORT A PROPRIETARY SHALL BE PROPERLY SEALED TO MEET THE AIR TIGHTNESS (DW 143 CLASS C) UNDER 300x300mm.
CLEANING CRADLE OR ACCESS GANTRY. WORKING PRESSURE OF FAN OPERATION GIVEN IN SECTION 2.9.
1F8 TV1 & 3 1.35
14.2 SURFACE/FLUSH MOUNTED SUPPORTS MAY BE FIXED TO BLOCKWORK
J TV2 & 4 1.45 THE MONORAIL SUPPORT IS DESIGNED AND SUPPLIED BY THE 10. RISER FLOOR SYSTEMS PROVIDED FOLLOWING CONDITIONS ARE MET:
J
TP1 & 2 1.55 MANUFACTURER. A 20mm ALLOWANCE HAS BEEN MADE FOR CONNECTION OF
6.2 10.1 CONNECTION DETAIL FOR INTO CONCRETE TO BE IN ACCORDANCE WITH 14.2.1 MAX. VERTICAL LOAD PER FIXING: 0.7kN
1A2 TV1 1.25 MONORAIL SUPPORT SECTION TO UC SECTION AND CONNECTIONS ARE STRUCTURAL DRAWING FOR ANCHORS M-BAR-000DS0-CB00-EDR-990710 AND 14.2.2 MAX. TENSILE LOAD PER FIXING: 0.7kN
TV2 1.30 SPACED AT 4m CENTRES. MANUFACTURER’S DESIGN. 14.2.3 MIN. PLATE DIMENSIONS: 100x100mm
TP 1.65 14.2.4 ONLY ONE FIXING PER BLOCK PERMITTED
1B1, 1B2, 1D5, TV1 & 2 1.50 6.3 WHERE ADDITIONAL MONORAIL SUPPORT CONNECTIONS ARE REQUIRED 10.2 ALL FLOOR GRATINGS WITHIN RISERS SHOULD BE DESIGNED FOR THE
1E2,1F5 TP 1.60 ADDITIONAL STRUCTURAL SUPPORTS MAY BE REQUIRED TO STRUCTURAL FOLLOWING PERMANENT LOADS: 14.3 SELF-CONTAINED SIGNAGE UNITS MUST BE POST-FIXED TO RC SLAB USING
ENGINEER’S APPROVAL. 1.2.1. SELF-WEIGHT OF ACCESS FLOOR MECHANICAL ANCHORS. REFER TO M-BAR-000DS0-CB00-EDR-990710.
1C1, 1C2, 1C3 TV1 & 2 1.50 1.2.2. 1kPa SUPERIMPOSED DEAD LOAD
TP 1.60 6.4 ASSUMED APPLIED LOADS AT CONNECTION OF MONORAIL TO STRUCTURES IS 1.2.3. LIVE LOADING FOR GRILLES SHOULD BE 1kPa UNIFORM OR 1.33kN 14.4 CEILING MOUNTED SUPPORTS TO BE FIXED TO SOFFIT OF SLAB USING
K GIVEN IN DRAWINGS M-BAR-000DS0-CB00-EDR-990510 & 990511. THE GANTRY CONCENTRATED. REFER TO IBC 2009, TABLE 1607.1. MECHANICAL ANCHORS. REFER TO M-BAR-000DS0-CB00-EDR-990710. K
1B4, 1C4, 1D2 TV1 & 2 1.50
OR CRADLE FIXED TO THE RAILS/RAIL AND ANY ASSOCIATED MOTOR
TP 1.60
EQUIPMENT MUST BE WITHIN THE MAXIMUM SELFWEIGHT SPECIFIED. THE 10.3 IT IS ASSUMED THAT THE AREA IS FOR ACCESS ONLY AND WILL NOT BE USED FOR 14.5 SIGNAGE ABOVE LIFTS SHOULD BE CONNECTED DIRECTLY TO SECONDARY STEEL
1F4 TO BE CONFIRMED 2.0 CONTENTS OF THE GANTRY OR CRADLE MUST BE WITHIN THE RATED LIVE STORAGE OR CONTAIN ANY PLANT/EQUIPMENT. THERE IS NO CONSTRUCTION FRAME.
This drawing has been approved and
LOAD SPECIFIED. LOAD ALLOWANCE. Certified as Acceptable on behalf of the
BIM MODEL M-BAR-000DS0-CB00-BIM-000003-Structure.rvt

BACS Consortium.
14.6 SIGNAGE ABOUT TICKET MACHINES ON B03 CONCOURSE TO BE FIXED DIRECTLY
6.5 CONNECTION OF RAIL ONTO THE SUPPORT STRUCTURE MUST BE VISIBLE FOR 10.4 REFER TO ARCHITECTS’ DRAWING M-BAR-000DS0-CA00-EDR-995110. TO SECONDARY STEEL FRAME.
INSPECTION (E.G. WELDED PLATES).
REVISIONS PROJECT BACS CONSORTIUM BACS APPROVAL SCALE PAPER DRAWING TITLE
SIZE
No Date
000 17/03/2017
Description
ISSUED FOR CONSTRUCTION
Drawn
JS
Checked
ER
Approved
JB A1 DEEP UNDERGROUND STATIONS
L L
DRAWING STATUS
STANDARD DETAILS
ISSUED FOR CONSTRUCTION STRUCTURE
CONSULTANT / SUB-CONTRACTOR
CLIENT
RIYADH METRO PROJECT This drawing has been Approved and PERFORMANCE SPECIFICATION FOR
Certified as acceptable on behalf of the
www.bacsrmp.com BACS Consortium. SECONDARY ITEMS
LEAD DESIGN ENTITY (LDE) APPROVED BY LDE DRAWN BY CHECKED BY APPROVED BY DRAWING NUMBER REVISION
NAME NAME NAME NAME

M J. SHEWAN E. ROBERTS J. BATCHELOR M-BAR-000DS0-CB00-EDR-990701 000 M


© 2015 High Commission for the Development of ArRiyadh DATE DATE 17/03/2017 DATE 17/03/2017 DATE 17/03/2017
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 000 v02