Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Harmonic management
6 Standards M20
M1
M2
2.1 Definition
The presence of harmonics in electrical systems means that current and voltage
are distorted and deviate from sinusoidal waveforms.
Harmonic currents are caused by non-linear loads connected to the distribution
system. A load is said to be non-linear when the current it draws does not have
the same waveform as the supply voltage. The flow of harmonic currents through
system impedances in turn creates voltage harmonics, which distort the supply
voltage.
On Fig. M1 are presented typical current waveforms for single-phase (top) and
three-phase non-linear loads (bottom).
DB422610.eps
The Fourier theorem states that all non-sinusoidal periodic functions can be
represented as the sum of terms (i.e. a series) made up of:
b A sinusoidal term at the fundamental frequency,
b Sinusoidal terms (harmonics) whose frequencies are whole multiples of the
fundamental frequency,
b A DC component, where applicable.
M3
The harmonic of order h (commonly referred to as simply the hth harmonic) in a
signal is the sinusoidal component with a frequency that is h times the fundamental
frequency.
The equation for the harmonic expansion of a periodic function y (t) is presented
below:
h=∞
y(t )= Y0 + ∑ Yh 2sin(h ωt - ϕh )
h=1
where:
bY0: value of the DC component, generally zero and considered as such
hereinafter,
bYh: r.m.s. value of the harmonic of order h,
b ω: angular frequency of the fundamental frequency,.
b φh: displacement of the harmonic component at t = 0.
DB422611_EN.eps
peak
Total
(Ic)
I rms (IG)
Fundamental
50 Hz
I
h1
Harmonic
3 (150 Hz)
I
h3
Harmonic
5 (250 Hz) Ih5
Harmonic
7 (350 Hz)
Ih7
Harmonic
9 (450 Hz)
I
h8
Fig. M2 Example of a current containing harmonics and expansion of the overall current into
its harmonic orders 1 (fundamental), 3, 5, 7 and 9
Uh
uh (%) = 100 for harmonic voltages
M4 U1
2 2 2
h=H Y 2 Y2 + Y3 + ... + YH
THD = ∑ Y
h
= Y
h=2 1 1
THD is the ratio of the r.m.s. value of all the harmonic components of the signal
y, to the fundamental Y1.
H is generally taken equal to 50, but can be limited in most cases to 25.
Note that THD can exceed 1 and is generally expressed as a percentage.
2 2
THD = Irms
−1 equivalent to: I
rms
= I 1+ THD
1 i
i I
1
2
Irms = I1 1+ (0.4) = I1 1+ 0.16 ≈ I1 ×1.08
h=2 1
Examples include:
b Industrial equipment (welding machines, arc and induction furnaces, battery
chargers),
b Variable Speed Drives for AC or DC motors [1],
b Uninterruptible Power Supplies,
b Office equipment (PCs, printers, servers, etc.),
b Household appliances (TV sets, microwave ovens, fluorescent lighting, light
dimmers).
Harmonic voltages M5
In order to understand the origin of harmonic voltages, let's consider the simplified
diagram on Fig. M3.
DB422612_EN.eps
Zh
A B Non-linear
load
Ih
Fig. M3 Single-line diagram showing the impedance of the supply circuit for a non-linear load
DB422613_EN.eps
l
Non-linear
load
I 50 Hz
Zh Ih
Non-linear
load
Vh V = Harmonic voltage
h=Z xI
h h
Ihd Fluorescent or
discharge lamps
MV/LV
A
Ih Devices drawing rectified
Σ Ih e current (televisions,
and distorted computer hardware, etc.)
voltage
Harmonic
disturbances to
distribution network Linear loads
and other users (do not create
harmonics)
S kVA
The Power Factor must not be mixed-up with the Displacement Power
Factor (cosφ), relative to fundamental signals only.
As the apparent power is calculated from the r.m.s. values, the Power
Factor integrates voltage and current distortion.
When the voltage is sinusoidal or virtually sinusoidal (THDu ~ 0), it may be said
that the active power is only a function of the fundamental current. Then:
P ≈ P1 = U1I1cosϕ
Consequently: λ = P = U1I1cosϕ
S UI
1 rms
I cosϕ
As: 1 = 1 (see 2.1), hence: λ≈
I 2 2
rms 1+ THDi 1+ THDi
λ/cos φ
DB422615.eps
1.2
M7
1
0.8
0.6
0.4
0.2
0.8
0.6
0.4
0.2
0
-0.2
-0.4
-0.6
-0.8
600
400
200
-200
-400
-600
I = H2 2 2 2
100 rms ∑Ih = I1 + I2 + ... + IH
h=1
H
2 2 2 2
Vrms = ∑Vh = V1 + V2 + ... + VH
33
h=1
20 h
0 1 2 3 4 5 6 3.5 Usefulness of the various indicators
THDu is an indicator of the distortion of the voltage wave. Below are given
indicative values of THDu and the corresponding consequences in an installation:
Fig. M9 Harmonic spectrum for a rectangular signal U(t)
b y 5%: normal situation, no risk of malfunctions,
b 5 to 8%: significant harmonic distortion, some malfunctions are possible,
b u 8%: major harmonic distortion, malfunctions are probable. In-depth analysis
and the installation of mitigation devices are required.
THDi is an indicator of the distortion of the current wave. The current distortion
can be different in the different parts of an installation. The origin of possible
disturbances can be detected by measuring the THDi of different circuits.
Below are given indicative values of THDi and the corresponding phenomena
for a whole installation:
b y 10%: normal situation, no risk of malfunctions,
b 10 to 50%: significant harmonic distortion with a risk of temperature rise and
the resulting need to oversize cables and sources,
b u 50%: major harmonic distortion, malfunctions are probable. In-depth analysis
and the installation of mitigation devices are required.
Power factor λ is used to determine the rating for the different devices of the M9
installation.
Crest factor is used to characterise the aptitude of a generator (or UPS) to supply
high instantaneous currents. For example, computer equipment draws highly
distorted current for which the crest factor can reach 3 to 5.
Harmonic spectrum provides a different representation of electrical signals
and can be used to evaluate their distortion.
Fig. M10 Values of individual harmonic voltages at the supply terminals for orders up to 25
given in percent of the fundamental voltage U1
M11
Portable instruments
The traditional observation and measurement methods include:
Oscilloscope
An initial indication on the distortion affecting a signal can be obtained by
viewing the current or the voltage on an oscilloscope.
The waveform, when it diverges from a sinusoidal, clearly indicates the presence of
harmonics. Current and voltage peaks can be observed.
PB116800.eps
Note, however, that this method does not offer precise quantification of
the harmonic components.
b Digital analyser
Only recent digital analysers can determine the values of all the
mentioned indicators with sufficient accuracy.
They are using digital technology, specifically a high performance algorithm
called Fast Fourier Transform (FFT). Current or voltage signals are digitized and
the algorithm is applied on data relative to time windows of 10 (50 Hz systems)
or 12 periods (for 60 Hz systems) of the power frequency.
The amplitude and phase of harmonics up to the 40th or 50th order are calculated,
depending on the class of measurement.
Processing of the successive values calculated using the FFT (smoothing,
classification, statistics) can be carried out by the measurement device or by
Fig. M11 Implementation of a digital Power Quality external software.
recorder win a cabinet
Fixed instruments
Panel instrumentation provides continuous information to the Manager of the
electrical installation. Data can be accessible through dedicated power monitoring
PB116801.eps devices or through the digital trip units of circuit breakers.
PB116184-45.eps
PB116047-4.eps
systems, when single phase loads are connected between phase and neutral.
.eps
M12 Utilities are mainly focusing on low harmonic orders (5, 7, 11, and 13).
Generally speaking, harmonic conditioning of the lowest orders (up to 13) is
sufficient. More comprehensive conditioning takes into account harmonic orders
up to 25.
Harmonic amplitudes normally decrease as the frequency increases. Sufficiently
accurate measurements are obtained by measuring harmonics up to order 30.
5.1 Resonansi
Penggunaan simultan perangkat kapasitif dan induktif dalam jaringan distribusi
dapat menghasilkan resonansi paralel atau seri.Asal usul resonansi adalah nilai
DB422619_EN.eps
impedansi yang sangat tinggi atau sangat rendah pada tingkat busbar, pada
frekuensi yang berbeda. Variasi dalam impedansi memodifikasi arus dan
tegangan dalam jaringan distribusi.Di sini, hanya fenomena resonansi paralel,
yang paling umum, akan dibahas.Pertimbangkan diagram sederhana berikut ini
Ih
(lihat Gambar. M14) yang mewakili instalasi yang terdiri dari:
b transformator persediaan,b Beban linearb Beban non-linear yang menggambar
arus harmonikb Kapasitor koreksi faktor dayaUntuk analisis harmonik, diagram
ekivalen ditunjukkan pada Gambar. M15 di mana:LS = Pasokan induktansi
C
(jaringan hulu + transformator + garis)C = Kapasitansi kapasitor koreksi faktor
dayaR = Resistansi beban linierIh = Arus harmonikDengan mengabaikan R,
impedansi Z dihitung dengan rumus yang disederhanakan:
Non-linear kapasitor Linear
jLsω
beban bank beban
Z=
1-LsCω2
Gambar. M14 Diagram instalasi
dengan: ω = denyut arus harmonikResonansi terjadi ketika penyebut (1-L SCω²)
cenderung ke nol. Frekuensi yang sesuai disebut frekuensi resonansi rangkaian. Pada
DB422620.eps
frekuensi itu, impedans berada pada jumlah maksimum dan tingginya tegangan
harmonik muncul karena sirkulasi arus harmonik. Ini menghasilkan distorsi tegangan
Ls C R Ih utama. Distorsi tegangan disertai, dalam sirkuit LS + C, oleh aliran arus harmonik yang
lebih besar daripada yang ditarik oleh beban, seperti diilustrasikan pada Gambar.
M16.
Jaringan distribusi dan kapasitor koreksi faktor daya mengalami arus harmonik yang
Z
tinggi dan risiko kelebihan beban. Untuk menghindari resonansi, reaktor anti-harmonik
Gambar. M15 Diagram ekuivalen instalasi dapat dipasang secara seri dengan kapasitor. Fig. M17
ditunjukkan pada GambarM14
DB422601_EN.eps
DB422602_EN.eps
U U
h Jaringan pasokan h jaringan pasokan
M13
Ih I
h
V
h C
V
h C
I
THDi = r.m.s. 2 −1
I1
2
it may be deduced that: Ir.m.s.= I1. 1+ THDi
2.2
1.8
1.6
1.4
1.2
1
THD
Fig. M18 Increase in rms current and Joule losses as a function of the THD
M14
Losses in asynchronous machines
The harmonic voltages (order h) supplied to asynchronous machines cause the
flow of currents in the rotor with frequencies higher than 50 Hz that are the origin of
additional losses.
Orders of magnitude
b A virtually rectangular supply voltage causes a 20% increase in losses
b A supply voltage with harmonics u5 = 8% (of U1, the fundamental voltage),
u7 = 5%, u11 = 3%, u13 = 1%, i.e. total harmonic distortion THDu equal to 10%,
results in additional losses of 6%
Losses in transformers
Harmonic currents flowing in transformers cause an increase in the “copper” losses
due to the Joule effect and increased “iron” losses due to eddy currents.
The harmonic voltages are responsible for “iron” losses due to hysteresis.
It is generally considered that losses in windings increase as the square of the
THDi and that core losses increase linearly with the THDu.
In Utility distribution transformers, where distortion levels are limited, losses
increase between 10 and 15%.
Losses in capacitors
The harmonic voltages applied to capacitors cause the flow of currents proportional
to the frequency of the harmonics. These currents cause additional losses.
Example
A supply voltage has the following harmonics:
Fundamental voltage U1,
b harmonic voltages u5 = 8% (of U1),
b u7 = 5%,
u11 = 3%,
b u13 = 1%,
i.e. total harmonic distortion THDu equal to 10%. The amperage of the current
is multiplied by 1.19. Joule losses are multiplied by (1.19)², i.e. 1.4.
kVA
DB422624_EN.eps
(%)
100
90
80
70
60
50
40
30 M15
20
%
10 Electronic
0 load
0 20 40 60 80 100
1
k
40
1 0.1 h1.6 Th2
h 2
Ih
T
h I
Typical values:
b Current with a rectangular waveform (1/h spectrum): k = 0.86
b Frequency-converter current (THD ≈ 50%): k = 0.80
Asynchronous machines
Standard IEC60034-1 ("Rotating electrical machines – Rating and performance")
defines a weighted harmonic factor (Harmonic voltage factor) for which the
equation and maximum value are provided below.
13 U
HVF h i 0.02
2
h 2 h
Example
A supply voltage has a fundamental voltage U1 and harmonic voltages u3 = 2% of U1,
u5 = 3%, u7 = 1%. The THDu is 3.7% and the HVF is 0.018. The HVF value is very
close to the maximum value above which the machine must be derated.
Practically speaking, asynchronous machines must be supplied with a voltage
having a THDu not exceeding 10%.
Capacitors
According to IEC 60831-1 standard ("Shunt power capacitors of the self-healing
type for a.c. systems having a rated voltage up to and including 1 000 V – Part
General – Performance, testing and rating – Safety requirements – Guide for
installation"), the r.m.s. current flowing in the capacitors must not exceed 1.3
times the rated current.
Using the example mentioned above, the fundamental voltage U1, harmonic
voltages u5 = 8% (of U1), u7 = 5%, u11 = 3%, u13 = 1%, i.e. total harmonic
distortion THDu equal to 10%, the result is
Ir.m.s./I1 = 1.19, at the rated voltage. For a voltage equal to 1.1 times the
rated voltage, the current limit
Ir.m.s./I1 = 1.3 is reached and it is necessary to resize the capacitors.
Neutral conductors
Consider a system made up of a balanced three-phase source and three identical
single-phase loads connected between the phases and the neutral (see Fig. M20).
Fig. M21 shows an example of the currents flowing in the three phases and the
resulting current in the neutral conductor.
In this example, the current in the neutral conductor has a rms value that is higher than
the rms value of the current in a phase by a factor equal to the square root of 3.
DB422625 EN.eps
Ir
Load
M16
Is
Load
t
Load
Fig. M20 Flow of currents in the various conductors connected to a three-phase source
(A)
Konduktor netral karenanya harus berukuran sesuai.
Oleh karena itu arus dalam netral dapat melebihi arus dalam setiap fase dalam
Ir
instalasi seperti yang memiliki sejumlah besar perangkat fase tunggal (peralatan
DB422626.eps
IT, lampu neon). Ini adalah kasus di gedung perkantoran, pusat komputer, Pusat
t
Data Internet, pusat panggilan, bank, pusat perbelanjaan, zona pencahayaan ritel,
dll.
Ini bukan situasi umum, karena kenyataan bahwa daya disuplai secara bersamaan
ke beban linier dan / atau tiga fase (pemanasan, ventilasi, lampu pijar, dll.), Yang
tidak menghasilkan arus harmonik urutan ketiga. Namun, kehati-hatian khusus
Is harus diambil ketika dimensi bidang penampang konduktor netral saat
merancang instalasi baru atau ketika memodifikasi mereka jika terjadi perubahan
pada beban yang disuplai dengan daya.Pendekatan yang disederhanakan dapat
t
digunakan untuk memperkirakan pemuatan konduktor netral.Untuk beban
seimbang, arus dalam IN netral sangat dekat dengan 3 kali ke-3arus harmonik
dari arus fase (I3), yaitu .: IN ≈ 3.I3Ini dapat dinyatakan sebagai: IN ≈ 3. i3. I1Untuk
nilai faktor distorsi rendah, r.m.s. nilai arus mirip dengan r.m.s.nilai fundamental,
It oleh karena itu: IN ≈ 3. i3 ILDan: IN / IL ≈ 3. i3 (%)Persamaan ini hanya
menghubungkan kelebihan muatan netral (IN / IL) ke rasio harmonik ketiga.
t Secara khusus, ini menunjukkan bahwa ketika rasio ini mencapai 33%, arus dalam
konduktor netral sama dengan arus dalam fase. Apa pun nilai distorsi,
dimungkinkan untuk menggunakan simulasi untuk mendapatkan hukum yang lebih
tepat, yang diilustrasikan pada Gambar. M22.
In
Rasio harmonik ketiga berdampak pada arus di netral dan karenanya pada
kapasitas semua komponen dalam instalasi:b Panel distribusib Perangkat
t perlindungan dan distribusib Kabel dan system pembagasian
DB422627.eps
N/IL
t
0 20 40 (ms)
2.0
Fig. M21 Example of the currents flowing in the various
conductors connected to a three-phase load (In = Ir + Is + It)
1.8
1.6
1.4
1.2
1.0 M17
0.8
0.6
0.4
0.2 I (%)
3
00 20 40 60 80 100
15 33
Fig. M22 Loading of the neutral conductor based on the 3rd harmonic ratio
According to the estimated third harmonic ratio, there are three possible scenarios:
ratio below 15%, between 15 and 33% or above 33%.
Oversizing of equipment
b Derating of power sources (generators, transformers and UPSs) means they
must be oversized
b Conductors must be sized taking into account the flow of harmonic currents.
In addition, due the skin effect, the resistance of these conductors increases with
frequency. To avoid excessive losses due to the Joule effect, it is necessary to
oversize conductors
b Flow of harmonics in the neutral conductor means that it must be oversized as
well
Examples
Given the economic consequences for the installations mentioned below, it was
necessary to install harmonic filters.
Metallurgy factory
A set of induction furnaces caused the overload and destruction of three
transformers ranging from 1500 to 2500 kVA over a single year. The cost of the
interruptions in production were estimated at 20 k€ per hour.
LV MV HV
Odd harmonics 5 6 5 2
non-multiples 7 5 4 2
of 3 11 3.5 3 1.5
M20 13 3 2.5 1.5
17y h y 49
17 _ 17 _ 17
2.27 h 0.27 1.9 h 0.2 1.2 h
Odd harmonics 3 5 4 2
multiples of 3 9 1.5 1.2 1
15 0.4 0.3 0.3
21 0.3 0.2 0.2
21< h y 45 0.2 0.2 0.2
Even harmonics 2 2 1.8 1.4
4 1 1 0.8
6 0.5 0.5 0.4
8 0.5 0.5 0.4
10 y h y 50
10 10
0.25 10 + 0.25 0.25 + 0.22 0.19 +0.16
h h h
THDu 8 6.5 3
Z2
DB422628_EN.eps
Sensitive
loads
Z
1
Non-linear
Where impedance
loads
Z1 < Z2
Fig. M24 Non-linear loads positioned as far upstream as possible (recommended layout)
Sensitive
loads
Yes Line impedances
No
Non-linear
load 1 M21
Non-linear
load 2
Fig. M25 Grouping of non-linear loads and connection as far upstream as possible
(recommended layout)
Non-linear
DB422630_EN.eps
loads
MV
network
Linear
loads
DB422631.eps
h11, h13
h5, h7, h11, h13
Fig. M27 A Dyd transformer blocks propagation of the 5th and 7th harmonics to the upstream network
Install reactors
When variable-speed drives are supplied, it is possible to smooth the current by
installing line reactors. By increasing the impedance of the supply circuit,
the harmonic current is limited.
Installation of harmonic suppression reactors on capacitor banks increases the
impedance of the reactor/capacitor combination for high-order harmonics.
This avoids resonance and protects the capacitors.
Passive filters
Typical applications
b Industrial installations with a set of non-linear loads representing more than
500 kVA (variable-speed drives, UPSs, rectifiers, etc.)
b Installations requiring power-factor correction
b Installations where voltage distortion must be reduced to avoid disturbing
sensitive loads
b Installations where current distortion must be reduced to avoid overloads
Non-linear Filter
load Operating principle
An LC circuit, tuned to each harmonic order to be filtered, is installed in parallel
Fig. M28 Operating principle of a passive filter
with the non-linear load (see Fig. M28). This bypass circuit absorbs the
harmonics, thus avoiding their flow in the distribution network.
Generally speaking, the passive filter is tuned to a harmonic order close to the
order to be eliminated. Several parallel-connected branches of filters can be used if
a significant reduction in the distortion of a number of harmonic orders is required.
Is
I
har
I
act
AHC
M23
Non-linear Linear
load Hybrid filter load
Selection criteria
Passive filter (see Fig. M31)
It offers both power-factor correction and high current-filtering capacity. Passive
filters also reduce the harmonic voltages in installations where the supply voltage is
PB116805.eps
disturbed. If the level of reactive power supplied is high, it is advised to turn off the
passive filter at times when the percent load is low.
Preliminary studies for a filter must take into account the possible presence of
a power factor correction capacitor bank which may have to be eliminated.
Active harmonic conditioners (see Fig. M32)
They filter harmonics over a wide range of frequencies and can adapt to any type
of load. On the other hand, power ratings are limited.
Hybrid filters
They combine the performance of both active and passive filters.