Sei sulla pagina 1di 32

CE+T TSI 1.5-3.

0kVA Media Inverter System


Installation Manual
TSI 1.5-3.0kVA Media Inverter System Installation Manual
TSI-MSY-SYS-IO-R3.0

Table of Contents
Safety Recommendations...................................................................................... 5
1.0 Introduction .................................................................................................... 6
1.1 TSI MEDIA Inverter System................................................................... 6
1.2 Theory of Operation............................................................................... 6
1.3 The basic MEDIA System layout............................................................ 7
1.4 System dimensions ............................................................................... 8
2.0 System Technical Description........................................................................ 9
2.1 Safety standards .................................................................................. 9
2.2 Environmental Parameters..................................................................... 9
2.3 Typical Load Supported......................................................................... 9
2.4 EMC Standards...................................................................................... 9
3.0 Installation ................................................................................................... 10
3.1 Overview.............................................................................................. 10
3.2 Installing the Inverter Shelf................................................................... 10
3.3 Wiring ................................................................................................... 12
3.3.1 Connecting AC Input Power...................................................... 12
3.3.2 Connecting DC Input Power...................................................... 13
3.3.3 Grounding the System............................................................... 14
3.3.4 Remote Monitoring and Control................................................ 15
3.3.4.1 Basic Monitoring........................................................ 15
3.3.4.2 Remote ON/OFF....................................................... 17
3.3.5 AC Output Wiring - Receptacle................................................. 18
3.3.6 AC Output Wiring - Hardwired................................................... 19
3.4 Installing the Inverter Modules............................................................. 20
3.5 T2S Controller ......................................................... 20
4.0 System Commissioning............................................................................... 21
5.0 Troubleshooting........................................................................................... 23
6.0 Specifications and Supplemental Data........................................................ 24
7.0 Appendix .................................................................................................. 26
7.1 Dimensioned Views.............................................................................. 26
7.2 Mounting Configurations...................................................................... 27
7.3 Sockets and Connectors...................................................................... 28
7.4 PDU Configurations............................................................................. 29
7.5 Inverter Module Indicators .................................................................. 30

CE+T America, inc.


1075 Satellite Blvd NW, Suite 300 Suwanee, GA 30024
Tel: 678-405-4636 Fax: 770-495-0992
www.cetamerica.com
3
TSI-MSY-SYS-IO-R3.1 Page 3
List of Figures

Fig. 1-1 System Block Diagram............................................................................................6


Fig. 1-2 Single shelf configuration, 1.5kVA to 3.0kVA...........................................................8
Fig. 3-1 Single phase AC input...........................................................................................12
Fig. 3-2 Dual phase AC input..............................................................................................12
Fig. 3-3 DC Input connector and Anderson connectors......................................................13
Fig. 3-4 Grounding the shelf...............................................................................................14
Fig. 3-5 T2S front panel......................................................................................................15
Fig. 3-6 Alarm Connector...................................................................................................16
Fig. 3-7 Alarm Connector...................................................................................................16
Fig. 3-8 Remote ON/OFF connection at X5.......................................................................17
Fig. 3-9 4 NEMA 15R receptacles, Single Phase AC output connection . .........................18
Fig. 3-10 2 NEMA 15R, one twist lock receptacles in PDU Single phase AC out . ..............18
Fig. 3-11 2 Twist-Lock receptacles, dual AC output connections.........................................18
Fig. 3-12 Single phase AC output connection......................................................................19
Fig. 3-13 Dual phase AC output connection.........................................................................19
Fig. 7-1 Front View.............................................................................................................26
Fig. 7-2 Side View...............................................................................................................26
Fig. 7-3 Isometric View with PDU extension.......................................................................27
Fig. 7-4 Flush-mount configuration.....................................................................................27
Fig. 7-5 Mid-mount Configuration.......................................................................................27
Fig. 7-6 Socket type and location on PDU Extension.........................................................28
Fig. 7-7 Input, output connectors on rear of Inverter shelf..................................................28
Fig. 7-8 Four NEMA socket configuration...........................................................................29
Fig. 7-9 Two Twist-lock socket configuration......................................................................29
Fig. 7-10 Two NEMA, one Twist-lock socket configuration...................................................29
Fig. 7-11 Inverter Module Status, Power LEDs....................................................................30
Fig. 7-12 Output Power Indicator LEDs ...............................................................................30

NOTE:
This document is subject to modification without prior notice from the manufacturer.
NOTE:
The present equipment is protected by several international patents and trademarks.

Page 4 TSI-MSY-SYS-IO-R3.0
Safety Notes
Review the drawings and illustrations contained in this manual before proceeding. If there are any questions
regarding the safe installation or operation of this product, contact CE+T America or the nearest CE+T America
representative. Save this document for future reference.

To reduce the risk of injury or death, and to ensure the continued safe operation of this product, the following
symbols have been placed throughout this manual. Where these symbols appear, use extra care and attention.

NOTE:

A NOTE provides additional information to help complete a specific task or procedure.

ATTENTION:
The use of ATTENTION indicates specific regulatory/code requirements that may affect the placement of
equipment and /or installation procedures.

CAUTION!

The use of CAUTION indicates safety information intended to PREVENT DAMAGE to material or
equipment.

WARNING!

WARNING presents safety information to PREVENT INJURY OR DEATH to the


technician or user.
Safety Precautions
Only qualified personnel may install, operate and service the system.
All operators are to be trained to perform the emergency shutdown procedure

Verify the voltage requirements of the equipment to be protected (load), the AC input voltage to the power supply (line), and
the output voltage of the system prior to installation.

Equip the utility service panel with a properly rated circuit breaker for use with this system.

When connecting the load, DO NOT exceed the output rating of the system.

The system contains more than one live circuit! Even though AC voltage is not present at the input, voltage may still be present
at the output.

This product is intended to be installed only in restricted access areas as defined by UL60950 and in accordance with the
National Electric Code, ANSI/NFPA 70, or equivalent local agencies

TSI-MSY-SYS-IO-R3.1 Page 5
1.0 Introduction
This document applies to the TSI MEDIA Inverter System products. This shelf mounted power system operates
off of both AC and DC input sources to provide conditioned and uninterrupted power to connected loads. Its
unique packaging allows for easy installation and system management.
These products utilize CE+T’s patented TSI technology within the MEDIA Inverters. The TSI with its Enhanced
Power Conversion (EPC) mode is the industry’s most energy efficient option to power conversion solutions.

1.1 TSI MEDIA Inverter System


The TSI MEDIA Inverter System utilizes Twin Sine Inverters (TSI) to provide reliable power for critical
AC loads (e.g. CATV, headends, Telco central offices, local exchanges, industrial applications and data
centers).
The system also provides the highest available efficiency among 48Vdc inverter systems, low Mean
Time to Repair (MTTR) due the ability of the inverter modules to be “hot swapped” in the event of an N+1
redundancy, a small footprint and an integrated power system.
The system is designed to be installed in a climate-controlled environment.

1.2 Theory of Operation


Parallelable, rack-mounted inverter systems provide a pure AC sine wave output at 120V or 240Vac,
60 or 50Hz, with any kind of load. Utilizing both a 48Vdc and a 120/240V AC input, these high density
systems range from 1500VA to 3000VA and are mountable in a standard 19 inch cabinet or either a 19
inch or 23 inch open relay rack.

Surge Arrestor
(optional)
Output
Interface 120V 1P AC
or
Circuit Breakers
120V 1P AC
Inverter Module NEMA 15R 240V 2P AC
or
240V 2P AC TSI MEDIA
-48Vdc Inverter Module
(Option)
Twist/Lock

T2S (Option)
Controller

Fig. 1-1 System Block Diagram

Page 6 TSI-MSY-SYS-IO-R3.0
1.0 Introduction, continued

1.3 The Basic MEDIA System layout

8
9

7
2 1
4
3
5

MEDIA system components


1 Knockouts for DC wiring; provides access to DC terminal 6 Optional AC Output Circuit Breakers (1 per receptacle)
blocks
7 Optional Surge Protector
2 Mounting bracket
8 Knockouts for AC wiring; provides access to
3 DC Input circuit breaker; 1 per each 1.5kVA Inverter AC terminal blocks
Module
9 Optional Power Distribution Unit (PDU) panel;
4 T2S Status Monitor NEMA receptacles accessible here.

5 1.5kVA Inverter Module

TSI-MSY-SYS-IO-R3.1 Page 7
1.0 Introduction, continued

1.4 System dimensions


A single MEDIA type shelf (H x W x D in/mm): 19/480 x 12/305mm x 3.5/89 [2U]

3.46" [88mm]

17.46" [443.5mm] m]
"[287m
11.30

Fig. 1-2 Single shelf configuration, 1.5kVA to 3.0kVA

Page 8 TSI-MSY-SYS-IO-R3.0
2.0 System Technical Description

Parameter Value
System Capacity 1.5kVA to 3.0kVA
AC Input Voltage 120Vac or 240/120Vac
DC Input Voltage -48Vdc
AC Output Voltage 120Vac or 240/120Vac
Audible noise < 35dB (A)
Cooling Forced convection*

2.1 Safety standards


The Inverter System is designed to meet the following standards:

UL 1778
UL60950-1

2.2 Environmental Parameters

Parameter Value
Operating Temperature -20°C to +40°C
Storage Temperature -40°C to +70°C
Relative Humidity 95%, non-condensing
Vibration IEC 721-3-3
Shock IEC 721-3-2

*Verify sufficient space is allowed for air circulation and the configuration of the system does not interfere with cooling air circulation.

2.3 Typical loads supported


The TSI MEDIA Inverter System utilizes Twin Sine Inverters (TSI) to provide Telecom-grade
reliable power for critical AC loads (e.g. CATV, Central Offices, local exchanges, industrial
applications and Data Centers).

The system also provides the highest available efficiency among 48Vdc inverter systems.
Serviceability and low Mean Time to Repair (MTTR) are minimized by the ability of the inverter
modules to be “hot swapped”. The architecture of the system can be configured for redundancy
and a high power density in a smaller footprint resulting in a more efficient use of equipment
space.

2.4 EMC Standards


EN 5502
FCC 47 CFR Part 15

TSI-MSY-SYS-IO-R3.1 Page 9
3.0 Installation

CAUTION!
Installation and commissioning must be done and conducted by trained personnel only. Before conducting any
isolation testing, contact the manufacturer for the approved procedure.

3.1 Overview
The MEDIA Inverter System is designed to be mounted as part of either an open relay rack or cabinet.
Mounting brackets are provided to allow installation in industry standard 19” or 23” equipment racks.
Verify the mounting hardware provided is as required for your application prior to instalation.

Verify sufficient space is allowed for proper air circulation.


Verify the following hardware is on hand;
Brackets, 2 or 4 each
Screws, 2 or 4 each

3.2 Installing the inverter shelf


Installation Procedure:

Page 10 TSI-MSY-SYS-IO-R3.0
3.0 Installation, continued

3.2 Installing the Inverter shelf, continued


1. Mount brackets to side of shelf with two supplied screws (Mid Mount shown)

2. Mount uprights

TSI-MSY-SYS-IO-R3.1 Page 11
3.0 Installation, continued

3.3 Wiring

The Earth Ground connection shall be made at the location referenced with the symbol .

Input ground must be connected to the appropriate terminal.

Once the frame is secured in its mounting, ensure that the proper earth grounds are made before connecting
AC or DC circuits to the system.

NOTE:

Note: at this point, the Inverter Modules are not installed in the shelf.

NOTE:
If blank PDU extension is mounted, it must be removed to expose AC intput connectors

Wiring the system is comprised of 5 operations that must be followed in sequence.

3.3.1 Connecting AC input Power


Verify Upstream and downstream AC circuit breakers are open, and make AC input connections
as shown below. Verify jumper is removed before connecting Dual phase AC input wires.

L1 Jumper N L1 L2 N

Fig. 3-1, Single phase AC input Fig 3-2, Dual phase AC input

AC Input Current 120 Vac Upstream AC Breaker Recommended Gauge* Termination Torque
12A per MEDIA Module 30A 1-pole UL489 120V - #10AWG, 90C Copper Wire Screw lock 4.5 - 5.5
@ nominal power (VA) 20A 2-pole UL489 240V - #12 AWG, 90C Copper Wire connector in-lbs
*Actual size to be determined by, and in compliance with, local utility codes.

TSI shelf is supplied with screw terminal: Neutral, Line and Ground.

Page 12 TSI-MSY-SYS-IO-R3.0
3.0 Installation, continued

3.3 Wiring, continued

3.3.2 Connecting DC Input Power


Verify Upstream and downstream DC circuit breakers are open and connect the Anderson
connector from the battery string(s) to the DC input connector indicated below.

CAUTION!

When multiple shelves are installed in the cabinet, verify the cable sizes (cross section, mm2 ) and circuit breaker
capacity are sufficient to allow safe connection and operation of the system and are in compliance with local utility
codes.
Installation Notes:
Integrator must provide branch circuit protection with breaking capacity related to short circuit capacity of upstream DC source.

It must be installed close enough to permit easy Break Before Make.

Appropriate type can be chosen within the table here below.

TSI is supplied with safety labels, which must be applied to the breaker in a visible way.

The insulation cover of connecting cables must meet the local and international standards and the cross section related to the upstream
protections.

Anderson PowerPole connectors for the incoming DC power are included. Proper crimping tools should be provided at job site.

from Battery Strings


DC+

DC-

Fig. 3-3, DC Input connector and Anderson connectors

DC input current at 40Vdc DC breaker Allowable Gauge* Connector Type


34A (By MEDIA module) 40A by Inverter #6AWG to #16AWG Anderson PP75 Powerpole®

*Actual size to be determined by, and in compliance with, local utility codes.

Verify the circuit breaker capacity matches the installation with regard to cable length, battery capacity).

DC Input Connector Specifications


Current Rating (A)* 75
Voltage Rating (AC/DC)* 600
Contact Barrel Wire Size**
AWG / mm3 #6 to #16
Max wire insulation diameter**
in / mm 0.437 / 11.10

* UL Rated for 65°C largest wire or cable size

** To be determined by, and in compliance with, local utility codes

TSI-MSY-SYS-IO-R3.1 Page 13
3.3 Wiring, continued
3.3.3 Grounding the System

Grounding Connection Notes

In order to provide a ready, reliable source of backup power it is necessary to connect the
system to an effective grounding and earthing system that not only provides for the safety
of the service personnel responsible for its operation and maintenance, but also facilitates
the proper operation and protection of the equipment within the network. Such a grounding
system provides protection with respect to operator safety, system communication, and
equipment protection.

Safety Ground

The safety ground is a two-part system, comprised of the utility service and the Media
Inverter System system.

1. First, utility service;

As a minimum requirement for the protection of equipment, the local utility service must
provide a low-impedance path for fault current return to Earth. This must meet or exceed
the requirements of the US National Electrical Code. The connection between the system
and the utility must also meet or exceed the requirements of the US National Electrical
Code.

2. Second; the grounding system

The grounding system consists of a low-impedance connection between the enclosure


and an Earth Ground (located at least 6’ away from the Utility Earth connection). This
impedance between the system and Earth must be 25 Ohms or less at 60 Hertz.

Strike (Lightning) Ground

Lightning strikes, grid switching, or other aberrations on the power line and/or
communications cable have the potential to cause high-energy transients which can
damage the powering or communitations systems. Without a low-impedance path to
ground, the current, when traveling through wires of varying impedance, can produce damaging
high voltage. The most viable method available to protect the system from damage is to
divert these unwanted high-energy transients along a low-impedance path to ground. A low-
impedance path to ground prevents these currents from reaching high voltage levels and
posing a threat to equipment. The single-point grounding system provides a low-impedance
path to ground, and the key to its success is the proper bonding of the ground rods, so the
components of the grounding system appear as a single point of uniform impedance. CE+T
America recommends the use of a surge arresting device electrically bonded to the ground
System.

WARNING: Low impedance grounding is mandatory for personnel safety, critical for the
proper operation of the system and must be in place and connected to the system before
the supply cables are connected.

To Frame Ground

Fig. 3-4, Grounding the shelf

Page 14 TSI-MSY-SYS-IO-R3.0
3.3 Wiring, continued
3.3.4 Remote Monitoring and Control
3.3.4.1 Basic monitoring
TSI Monitoring of Media inverters is accomplished through the T2S controller.
Connection Notes:
There are 3 free potential changeover contacts provided. Maximum wire size is 0.5mm
When TSI system consists in several shelves, the alarm must be connected on the shelf where the T2S is located.

WARNING!

Relays are energized while idle (i.e. relays de-energized when event occurs).

TSI Monitoring
T2S
3
Alarm contacts
Major + Minor + prog.
3
Alarm lights
Major + Minor + prog.
USB
Communication
config. + trouble shooting
extented via USB
Add. configuration
(2) Redundancy (Yes present or No)
YES
Log file
200 messages
Possible
Extended monitor
display + TCP/IP via CANDIS Shelf

TSI Monitoring Functions

TSI systems are equipped with relays outputs for remote alarms and
LEDs (1 through 3) on the front panel of the T2S indicate the following
alarm conditions:
1. Major Alarm LED (contact 5-6 closed when No alarm)
2. Minor Alarm LED (contact 8-9 closed when No alarm)
3. User-selectable Alarm (with T2S)
4. USB Port
5. Access to locking latch to remove T2S from Inverter shelf

Fig. 3-5, T2S front panel

NOTE:
All alarms are qualified in Minor alarm except those configurable by T2S. These configurable alarms are identified
by the ID601 to 900. Refer to list of factory settings.

TSI-MSY-SYS-IO-R3.1 Page 15
3.3 Wiring, continued

3.3.4.1 Basic monitoring, continued

T2S digital input connection with T2S (alarm connector pins 1-3, Fig. 3-6)

Two external input contacts can be monitored through the T2S. They can be used for rack
alarms such as Door Opening, Over-temperature, Fan status, Manual BYPASS engaged,
etc.

The voltage present on terminal 1 and 3 is +5V (galvanically insulated). Care should be taken
to avoid connecting any external voltage on terminal 1 to 3.

External signals should be applied to these terminals via Voltage-free contacts.

The function is activated when the 2 terminals concerned are short-circuited (i.e. when the
external Voltage-free contact is closed)

T2S digital output connection (alarm connector pins 4-12 Fig. 3-6)

MAJOR, MINOR and selectable relays provide an open or closed free potential contact.

Relay characteristics

Maximum switching capacity: 2A @ 30VDC, (1A @ 60VDC )


Maximum switching power: 60W
Maximum voltage: 60VDC
Maximum switching current: 2A
Connecting input/output alarm wires (Fig. 3-7)

To connect the input and output alarm wires, follow the procedure below.

1. Strip approximately .25" (6mm) of insulation from the alarm wire*.


2. Use a small-tipped flat blade screwdriver or similar tool and press inward on the
Orange capturing tab.
3 Insert wire into opening, and release.
4. Reverse procedure to remove wire.

* For this connector, the allowable wire gauge range is #20AWG to #28AWG. The actual size to
be determined by, and in compliance with, local utility codes

Typ., #20AWG, 0.5mm2

Fig. 3-6, Alarm Connector pin-out Fig. 3-7, Wire insertion

Page 16 TSI-MSY-SYS-IO-R3.0
3.3 Wiring, continued

3.3.4.2 Remote ON/OFF


TSI system can be remotely activated or stopped (stand-by mode).
NOTE:
Changeover contacts must be used. For transition, the TSI verifies one input is released while the other is short-
circuited. If both transitions are not detected, the inverter does not change its operating status

The voltage present on terminals 1 and 3 are +5V (galvanically insulated). Care should be taken
to avoid connecting any external voltage on terminals 1 and 3. Maximum wire size is 1 mm
(#22AWG)

States Pins 1-3 Pins 2-3 Status


1 Open Open System working normally

2 Close Open TSI output switched off


DC AC LED off
DC DC LED solid green
AC DC LED solid green
3 Open Close System working normally
4 Close Close System working normally

Functional table for remote ON/OFF function

These 3 wires must be used for the redundancy on the remote ON/OFF. Use NO/NC relay contact.

NOTE:
State #3 should be implemented by default. Changing status of these inputs (State #3 State #2 State #3)
forces the TSI modules to start running without T2S.

NOTE:
Mating connectors supplied as part of shelf assembly. Maximum wire gauge is #22AWG.
Common
OFF

ON

Optional Surge Arrestor 1 2 3


Alarm terminals

Fig 3-8 Remote ON/OFF connection at X5

TSI-MSY-SYS-IO-R3.1 Page 17
3.3 Wiring, continued

3.3.5 AC Output Wiring - Receptacle


The TSI Media Inverter System can be configured with NEMA and Twist-lock style output
connectors or with a hardwired AC output connection.

Verify Upstream and downstream AC circuit breakers are open and make AC output connections
as shown below.

To customer’s equipment

Fig. 3-9, Four NEMA 15R Receptacles in PDU Extension, Single phase AC out connections

To customer’s equipment

Fig. 3-10, Two NEMA 15R, one twist lock Receptacles in PDU Extension, Single and Dual phase AC out connections

To customer’s equipment

Fig. 3-11, Two twist lock Receptacles in PDU Extension, Dual phase AC out connections

Page 18 TSI-MSY-SYS-IO-R3.0
3.3 Wiring, continued

3.3.6 AC Output Wiring - Hardwired


Verify Upstream and downstream AC circuit breakers are open and make AC output connections
appropriate to your system configuration as shown below.

L1 L2 N
L1 Jumper N

Fig. 3-12, Single phase AC output connection Fig. 3-13, Dual phase AC output connection
(No PDU or Blank PDU extension) (No PDU or Blank PDU extension)

NOTE:
If blank PDU extension is mounted, it must be removed to expose AC output connectors

AC output Current 120 Vac Downstream AC Breaker Recommended Gauge* Termination Torque
12.5A per MEDIA Module 30A 1-pole UL489 120V - #10AWG, 90C Copper Wire Screw lock 4.5 - 5.5
@ nominal power (VA) 20A 2-pole UL489 240V - #12 AWG, 90C Copper Wire connector in-lbs
*Actual size to be determined by, and in compliance with, local utility codes.

TSI shelf is supplied with screw terminal: Neutral, Line and Ground.

CAUTION!

The bulk output shelf does not include any disconnect or protecting devises for AC output, they must be provided
in the field according to local practices. Prior to any intervention on AC output make sure DC input & AC Input
have been actually disconnected.
The shelf with receptacles solution includes protecting devices for AC output.
The shelf is not hot plug device

Prior any handling of the shelf, wait a few minutes (min 5 minutes) for complete discharge of
internal capacitors that have been energized.
The safety standard IEC/EN62040-1-1 requires that, in case of output short circuit, the inverter must disconnect
within 5 seconds. This parameter can be adjusted in T2S, however, if the parameter is set at a value > 5 seconds,
an external protection must be provided in order that the short circuit protection operates within 5 seconds.

The default value is set at 60 seconds.

TSI-MSY-SYS-IO-R3.1 Page 19
3.0 Installation, continued
3.4 Installing Inverter Modules
Once the shelf has been fully wired, the Inverter Modules can be installed. Before installation of any of the
modules, verify all upstream and downstream circuit breakers are in the OFF (open) position
Follow the procedure below:

1. Slide Module into position 2. Push firmly until the connection is


properly engaged

3. Close cover; latch module into 4. Verify cover completely closed


place.If cover does not close, and securely latched.
remove module and repeat step 2.

CAUTION!

For safety reasons, any slot without module must be filled with a blank housing.

3.5 How to remove a T2S Controller


The T2S module is locked in the shelf by a lock pin. To remove the T2S from the shelf, insert a small flat
screwdriver in the square hole under the USB port and lift up the lock pin. The T2S can then be removed from the
shelf.

Page 20 TSI-MSY-SYS-IO-R3.0
4.0 System Commissioning
Perform the following tests and checks as part of the commissioning and turn up procedure:

SYSTEM IDENTIFICATION RECORD SERIAL OR MODEL NUMBER


Shelf serial number 
T2S serial number
Inverter serial numbers

INSTALLATION CONTROL (Write OK or N/A (Not Available) in the column) OK or NA


Shelf is properly placed and stable
Shelf is installed in a dry area or protected against water
Cable support
Positive battery connection « 
(check individual or common connection)
Negative battery connection «  
(check individual or common connection)
Check cross section and breaker protection for DC input, AC input and output cables
AC input connection properly done (L + N) or (L1 + L2 + N) on terminal
AC output connection properly done (L + N) or (L1 + L2 + N) on terminal
PE connection properly done even if mains are not connected
Inverter module
Neutral N is connected to EARTH (If required!)
Check with Multimeter for short circuits (AC in, AC out, DC)

For assistance with this procedure, please contact:


CE+T America, inc.: Tel: 678-405-4636 Fax: 770-495-0992

TSI-MSY-SYS-IO-R3.1 Page 21
4.0 System Commissioning, continued

COMMISSIONING CHECKLIST VERIFIED


Check the commercial AC before closing breaker .Switch ON the commercial AC
Check if inverters are working (Green LED for ACout position)
Check the DC power supply and switch ON the DC breakers
Check output voltage (at terminals or at breaker)
Check if inverters are working properly
Check if system is alarm free (Disable the alarm if any)
Read configuration file with T2S and review all parameters. Some parameters must be adapted
according to the site. Refer to T2S operating manual
Switch OFF AC and verify system is working on DC
Switch ON AC and check if system correctly transfers load
Switch OFF system and start on AC only
Switch OFF system and start on DC only
Test with load (if available)

ALARM TEST [DEFAULT] result


Switch ON AC input and DC input and check that there are no alarms present
Pull out one inverter and check alarm according to redundancy
Pull out two inverters and check alarm according to redundancy
Switch OFF AC input (commercial power failure) and check the alarm according to the configuration
Switch OFF DC input (DC power failure) and check that the alarm according to the configuration
Check the different digital inputs

For assistance with this procedure, please contact:


CE+T America, inc.: Tel: 678-405-4636 Fax: 770-495-0992

Page 22 TSI-MSY-SYS-IO-R3.0
5.0 Troubleshooting
Use the following table in the event of component or system failure.

SYMPTOM POSSIBLE SOLUTION


Check power supplies
Check breaker or switch both inside and outside the shelf
Inverter doesn’t power up:
Check if inverter is correctly inserted into the shelf
Check LED Status

Check if T2S is present and properly inserted


Make sure Remote ON/OFF is not engaged
Check the configuration and settings
Inverter doesn’t start: Check threshold levels (AC and DC)
Check LED status
Use T2S operating manual for additional troubleshooting

Check if the inverters are running

Check if the output breakers (if applicable) are engaged


Check if any short circuits are present on the output
No power output:
Check status of inverters
Make sure output breakers inside the shelf are engaged (if applicable)
Use T2S operating manual for additional troubleshooting

For technical assistance, please contact:


CE+T America, inc.: Tel: 678-405-4636 Fax: 770-495-0992

TSI-MSY-SYS-IO-R3.1 Page 23
6.0 Specifications

GENERAL
EMC (immunity) IEC 1000-4

EMC (emission) FCC PART 15

Safety UL 1778

Cooling Forced

MTBF >200,000 hrs

Efficiency (MAX) On Line (REG) 90%

Enhanced Power Conversion (EPC) 93%

Dielectric strength DC/AC (@ 0.6mA) 4,242 Vdc

True Redundant Systems Compliant

RoHS Compliant

Terminal blocks

Or NEMA receptacles

Connection I/O Or Twist Locks

Or combination NEMA and Twist Locks

Protected against reversal of polarity

Self adaptive to wide operating conditions and comprehensive table of troubleshooting codes

AC OUTPUT POWER
Nominal Output power (**) n x 1500 VA (where n is the number of inverter modules)

Output power (resistive load) (**) n x 1200W

Short time overload capacity 150% for 15 seconds

Load power factor Full power rating from 0 inductive to 0 capacitive

Internal temperature management and cut off

DC INPUT SPECIFICATIONS
Nominal voltage (DC) 48 V

Voltage range (DC) 40 - 60 V

Nominal current (at 40Vdc) (**) n x 34 A (where n is the number of inverter modules)

Maximum input current (for 5 sec.) (**) n x 42 A

Voltage ripple < 2mV

Input voltage boundaries user selectable

AC INPUT SPECIFICATIONS
Nominal voltage (AC) 120V Single Phase or 240/120V Dual Phase

Voltage range (AC) (each phase) 83 -140 V

Conformity range Adjustable

Power Factor >99%

Frequency range (selectable) 50 - 60 Hz

Synchronization range 47 - 53 Hz / 57 - 63 Hz

Page 24 TSI-MSY-SYS-IO-R3.0
6.0 Specifications, continued

AC OUTPUT SPECIFICATIONS
Nominal voltage (AC) 120V Single Phase or 240/120 V Dual Phase

(Single or dual phase selectable at order)

Voltage range (AC) (adjustable) 90 to 130 V each phase

Voltage accuracy 2%

Frequency 50/60 Hz

Frequency accuracy 0.03 %

Total harmonic distortion (resistive load) <3 %

Load impact recovery time 0.4 ms

Turn on delay 30 s

Nominal current (**) at 120V n x 12.5 A (where n is the number of inverter modules)

Protected against reverse current

Crest factor at nominal power 2.2

Short circuit management and protection

Short circuit clear up capacity 10 x In for 20msec

Available while Mains is available at AC input port

Magnitude control and management

TRANSFER PERFORMANCE
Total transient voltage duration (max) 0s

ENVIRONMENT
Altitude above sea < 1500m

Ambient temperature (**) -20 to 40 C

Pmax at 100% LOAD

Storage temperature -40 to 70 C

Relative humidity 95% , non condensing

SIGNALING & SUPERVISION


Display Synoptic LED
Alarms output Dry contacts on shelf

Supervision Use optional devices

WEIGHT & DIMENSIONS


Width (in / mm) 17.65 / 448

Depth (in / mm) 11.77 / 300

Height (in / mm) 3.5 / 89 (2U)

Weight (lb / kg) ~ 25.0 / ~11.3

Material (casing) Coated steel

(*) Operation within lower voltage networks leads to derating of power performances

TSI-MSY-SYS-IO-R3.1 Page 25
7.0 Appendix
7.1 Dimensioned Views

482.60mm [19.00in]

462mm [18.19in]

443.50mm [17.46in]

Fig. 7-1 , Front View

88mm [3.46in]

287mm [11.30in]

305.47mm [12.03in]

Fig. 7-2 , Side View

Page 26 TSI-MSY-SYS-IO-R3.0
7.0 Appendix, continued

7.1 Dimensioned Views, continued

443.
50m
m [1
7.46
in]

88mm [3.46in]

in]
[1 2.13
1 7mm
308.

Fig. 7-3 , Isometric View with PDU extension

7.2 Mounting Configurations

Fig. 7-4 , Flush-mount Configuration

127mm [5.00in]

Fig. 7-5 , Mid-mount Configuration

TSI-MSY-SYS-IO-R3.1 Page 27
7.0 Appendix, continued

7.3 Receptacles and Connectors

Fig. 7-6 , Receptacle type and location on PDU Extension

Fig. 7-7 , Input, output connectors on rear of Inverter shelf

Page 28 TSI-MSY-SYS-IO-R3.0
7.0 Appendix, continued

7.4 PDU Configurations

Fig. 7-8 , Four NEMA socket configuration

Fig. 7-9 , Two Twist-lock socket configuration

Fig. 7-10 , Two NEMA, one Twist-lock socket configuration

TSI-MSY-SYS-IO-R3.1 Page 29
7.0 Appendix, continued

7.5 Inverter Module Indicators

Output Power (redundancy not counted)

The output power LEDs indicate the amount of power (percentage of rated power) provided by the module.
The number of bars that are illuminated combined with whether or not they are on steady or flashing
indicate the ouput power level or overload condition as indicated by the figure below.

Page 30 TSI-MSY-SYS-IO-R3.0
This page intentionally blank

TSI-MSY-SYS-IO-R3.1 Page 31
CE+T America, Inc 1075 Satellite Blvd Suite 300 Suwanee, GA USA 30024
Tel: 678 405 4636 Fax: 770 495 0992
www.cetamerica.com

TSI 1.5-3.0kVA MEDIA Inverter System Installation Manual TSI-MSY-SYS-IO-R3.0

Potrebbero piacerti anche