Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
In this post, the focus will be on ANSI C84.1 standard nominal system voltages and voltage classes.
Refer to this article for voltage tolerances: ANSI C84.1 – Voltage Ranges.
1. Promote a better understanding of the voltages associated with power systems and utilization
equipment to achieve overall practical and economical design and operation.
2. Establish uniform nomenclature in the field of voltages
3. Promote standardization of nominal system voltages and ranges of voltage variations for operating
systems
4. Promote standardization of equipment voltage ratings and tolerances
5. Promote coordination of relationships between system and equipment voltage ratings and tolerances
6. Provide a guide for future development and design of equipment to achieve the best possible
conformance with the needs of the users
7. Provide a guide, with respect to choice of voltages, for new power system undertakings and for
changes in old ones.
Subsequently, ANSI C84.1 defines the system voltages into classes depending on the system voltage
magnitude.
ANSI C84.1 has published the following standard nominal system voltages:
Reference:
ANSI C84.1-2006
The standard establishes the nominal voltage ratings and operating tolerances for 60-Hz electric
power systems above 100 volts up to a maximum system voltage of 1200 kV (steady-state voltage
levels only). However, in this post, the focus will be on ANSI C84.1 Voltage Ranges. Refer to this
article for standard nominal system voltages and voltage classes: ANSI C84.1 - Voltage Ratings.
ANSI C84.1 specifies the steady-state voltage tolerances for an electrical power system. The
standard divides voltages into two ranges. Range A is the optimal voltage range. Range B is
acceptable, but not optimal.
ANSI C84.1 Voltage Ranges
Notes:
a. The shaded portions of the ranges do not apply to circuits supplying lighting load
b. The shaded portion of the range does not apply to 120 V - 600 V s ystems.
Please take note that transient voltages (i.e. sags and surges) go beyond these limits and are
covered by other voltage standards – ITIC and CBEMA Curves.
Range A minimum voltage is 90% of nominal voltage - refer to Note (a) for limitation
Range A maximum voltage is 104.2% of nominal voltage - refer to Note (b) for limitation
Range B minimum voltage is 86.7% of nominal voltage - refer to Note (a) for limitation
Range B maximum voltage is 105.8% of nominal voltage
In addition, the difference between minimum service and minimum utilization voltages is intended
to allow for voltage drop in the customer’s wiring. Moreover, this difference is greater for service
at more than 600 volts to allow for additional voltage drop in transformations between service
voltage and utilization equipment. The National Electrical Code (NEC) allows up to a 5% drop –
up to 3% drop in the main feeder and an additional <3% in individual branch circuits.
Therefore, for common nominal system voltages, the recommended range as per ANSI C84.1 for
120 V - 600 V systems will be as indicated below.
Furthermore, it should be recognized that because of conditions beyond the control of the supplier
and/or user, there will be infrequent and limited periods when steady-state voltages exceed
Range B limits. Utilization equipment may not operate satisfactorily under these conditions, and
protective devices may operate to protect the utilization equipment.
References:
ANSI C84.1-2006
Kusko, A. and Thompson, M. (2007). Power Quality in Electrical Systems. New York: McGraw-
Hill.
Pacific Gas and Electric Company. (1999). Voltage Tolerance Boundary