Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
2.1. Basics
2.1.1. HIGHER HEATING VALUE (HHV)
The higher heating value is the amount of heat produced by the complete combustion of a unit
quantity of fuel, when all combustion products are cooled down to the initial temperature, and the
water vapour formed during combustion is condensed.
The difference between higher and lower heating value is the latent heat of vaporization of the
water vapour formed by the combustion.
The water mass flow rate should be constant during the measurement which is ensured by
a constant feed water pressure. The varying pressure of the water network is compensated
by two overflow tanks. They provide a constant water pressure of the difference between
their water level.
The gas flow rate should be constant as well. To ensure a constant gas flow to the burner,
the gas pressure – which might be altered by the flow meter mechanics and/or the gas
network – is adjusted by a pressure valve built between the flow meter and the burner.
Elimination of the bias caused by the humidity of the gas and the ambient air. The flue gas
is always saturated with water vapour which would lead to varying amount of condensed
water with varying humidity of combustion air. This error component is compensated by
saturating both the gas and air intakes. To measure the saturated gas flow, a wet gas meter
can be used. The saturation of air inlet to the calorimeter is performed by the air humidifier
as follows. The overflowing water from the water feed at the distributor funnel is spilling
in a counterflow with the combustion air to the Raschig rings. These rings are made of a
special ceramics that provides a large surface area for evaporation.
The heat exchange between the environment and the device should be negligible. To
eliminate the bias by the ambient air, the water inlet temperature is lower from the ambient
temperature by the same extent as the outflow water is higher than that. Hence, the
ambient temperature is the arithmetic mean of the water in- and outlet temperatures.
However, the flue gas temperature slightly lower in this way than the temperature of either
the air inlet or the gas inlet. Note that the corresponding error is negligible even in the case
of low calorific value gases.
To reduce the effect of thermal radiation, the outer shell of the calorimeter is coated by
nickel and is fine polished.
1 SHELL
2 WET-TYPE LABORATORY GAS METER
3 PRESSURE REGULATOR
4 AIR HUMIDIFIER
5 BURNER
6 AIR INLET
7 COOLING WATER
8 COOLING WATER CHAMBER
9 THERMOMETER
(FOR WATER INLET TEMPERATURE)
10 THERMOMETER
(FOR WATER OUTLET
TEMPERATURE)
11 FLUE GAS OUTLET
12 CONDENSATE
OUTLET
Figure 1. – Junkers-calorimeter
3. DETERMINING THE HIGHER HEATING VALUE AND LOWER
HEATING VALUE OF NATURAL GAS
𝑚𝑤 ∙ 𝑐𝑤 ∙ (𝑡𝑤,𝑜𝑢𝑡 − 𝑡𝑤,𝑖𝑛 )
𝐻𝐻𝑉 = (2)
𝑉𝑔 ∙ 𝑓
3.3. Determination of the LHV
Lower heating value is determined according to the definition. This means that it is necessary to
collect the condensed vapour from the flue gas during the measurement period. Then the lower
heating value can be calculated as follows:
Total pressure in the gas meter (ptotal) is sum of two partial pressure: gas pressure (pg) and
saturation pressure of water vapour (ps) on tg gas temperature:
𝑝𝑡𝑜𝑡𝑎𝑙 = 𝑝𝑔 + 𝑝𝑠 (6)
where:
ps: saturation pressure of water vapour [Pa] (which can be determined using Table 1.)
t ps t ps t ps
[°C] [Pa] [C ] [Pa] [°C] [Pa]
0 611.0
1 656.7 11 1312 21 2486
2 705.6 12 1402 22 2643
3 757.6 13 1497 23 2809
4 813.2 14 1598 24 2983
5 872.1 15 1705 25 3168
6 937.9 16 1818 26 3361
7 1001.6 17 1937 27 3565
8 1072.7 18 2063 28 3780
9 1147.7 19 2196 29 4005
10 1227.5 20 2338 30 4243
Table 1. - Saturation pressure of water vapour at various temperatures
This total pressure is the sum of two other pressures, which can be measured:
𝑝𝑡𝑜𝑡𝑎𝑙 = 𝑝𝑎 + ∆𝑝, (7)
where:
pa: actual atmospheric pressure [Pa]
Δp: pressure of the U-tube manometer [Pa]
where:
ρw: density of water ( ρw = 1000 kg/m3)
mw,out – the mass of the flown out water [kg]
To determine the HHV of PB gas, we have to use similar equations presented for calculating the
HHV of natural gas. We know the total hot water mass (𝑚𝑣 ), the water outflow temperate (𝑡𝑤,𝑜𝑢𝑡 ),
the water (inflow) temperature (𝑡𝑤,𝑖𝑛 ) and the mass of the burnt PB gas (∆𝑚𝑃𝐵 ). Thus:
𝐻𝐻𝑉 ∙ ∆𝑚𝑃𝐵 = 𝑚𝑤 ∙ 𝑐𝑤 ∙ (𝑡𝑤,𝑜𝑢𝑡 − 𝑡𝑤,𝑖𝑛 ), (14)
𝑚𝑤 ∙ 𝑐𝑤 ∙ (𝑡𝑤,𝑜𝑢𝑡 − 𝑡𝑤,𝑖𝑛 )
𝐻𝐻𝑉 = , (15)
∆𝑚𝑃𝐵
To determine the LHV, we measure the mass of the condensed water and calculate according to
the equations in section 3.3., while keeping in mind that the calculations should be performed with
the mass of the burnt gas and not its volume.
𝐿𝐻𝑉 = 𝐻𝐻𝑉 − 𝑞𝑟 (16)
𝑚𝑐𝑜𝑛𝑑 ∙ 𝑟 (17)
𝑞𝑟 = ,
∆𝑚𝑃𝐵
Because in this case the calculation is done with mass rather than volume, there’s no need to
convert these results.
5. ERRORR ESTIMATION
Both the absolute and relative error should be calculated for the HHV and LHV values of natural
gas and PB gas. The error is caused by the measurement of the temperatures (water in and out)
and mass flow rates (hot water outflow, condensed water, PB gas).
6. BIBLIOGRAPHY
[1] Penninger Antal (szerk.), Maiyaleh Tarek, Kalorikus gépek, Budapest University of
Technology and Economics, Department of Energy Engineering, 2013