Sei sulla pagina 1di 6

701880

research-article2017
MAC0010.1177/0020294017701880Tech Talk (12) Down to Earth: A Discussion of the General Requirements for the Earthing of Control and Instrumentation SystemsTech Talk (12) Down to Earth: A Discussion of the General Requirements for the Earthing of Control and Instrumentation Systems

Contributed Paper

Tech Talk (12) Down to Earth:


Measurement and Control
2017, Vol. 50(2) 39­–44
© The Author(s) 2017

A Discussion of the General


Reprints and permissions:
sagepub.co.uk/journalsPermissions.nav
https://doi.org/10.1177/0020294017701880
DOI: 10.1177/0020294017701880
journals.sagepub.com/home/mac

Requirements for the Earthing


of Control and Instrumentation
Systems
David W Otterson
Institute of Measurement and Control, Billingham, UK
davidotterson@ntlworld.com

This paper addresses accepted practice for the earthing of control systems in a variety of environments and is intended
to give control and instrument technicians and engineers a basic understanding of the power supply earthing systems
to which their equipment is connected. The general requirements for earthing in hazardous areas are also discussed.

I. Introduction Regulations 20022 and that there is a or when large areas of metalwork are
permanent connection from supply exposed to human contact.
Tech Talk is a series of papers designed
neutral to earth. This may not always be
as a ‘pull out’ reference library. The aim is
the case in other locations. Low voltage.  A low-voltage (LV) circuit
to disseminate knowledge of both the
This paper addresses accepted is defined as having a voltage exceeding
fundamentals of measurement and
practice for the earthing of control ELV but not exceeding 1000 V AC or
control and their practical application.
systems in a variety of environments and 1500 V DC between the conductors or
Design safety regulations exist in
is intended to give control and instrument 600 V AC or 900 V DC between the con-
most parts of the world to prevent
(C&I) technicians and engineers a basic ductors and earth.
danger to life from electric shock due to
understanding of the power supply
contact with exposed metalwork
earthing systems to which their
concurrent with a fault condition. In the High voltage.  A high-voltage (HV) circuit
equipment is connected. The general
United Kingdom, these regulations are is defined as having a voltage in excess
requirements for earthing in hazardous
comprehensively detailed in Standard of LV.
areas are also discussed. The paper is
BS 7671:2008 – Wiring Regulations
not intended as a comprehensive work
17th Edition.1 Although these
on electrical earthing and related B. Earthing
regulations are not statutory, they are
technologies.
nevertheless regarded by the Health The provision of an engineered low
and Safety Executive as requirements impedance return path to the power
likely to achieve conformity with relevant II. Definitions supply transformer, such that fault
parts of the Electricity at Work currents occurring as a result of earth
A. Nominal system voltages
Regulations 1989. leakage can be automatically detected
NFPA 70: National Electrical Code Extra low voltage.  An extra low voltage and the source of power quickly
(NEC), 2014 Edition is appropriate for (ELV) circuit is one in which the electrical disconnected.
North America. conductor potential does not exceed
In England, Scotland and Wales, the either 50 V rms, whether between con-
C. Bonding
Wiring Regulations assume that the ductors or to earth for AC, or ripple-free
electricity supply is in accordance with 120 V for DC under dry conditions. The interconnection, using low resistance
the Electricity Safety and Continuity Lower numbers apply in wet conditions, components of the conductive parts of

March 2017  Vol 50 No 2  l  Measurement and Control  39


Contributed Paper

Tech Talk (12) Down to Earth: A Discussion of the General Requirements for the Earthing of Control and Instrumentation Systems

plant and equipment, so as to provide an


Figure 1.  SELV and PELV power supply circuits Figure 2.  TN-S system circuit diagram
earth return path and ensure that
adjacent components are always at the
same potential.

III. Protection against Electric


Shock
A. General requirements
BS 7671:20081 lists and describes the period for a given supply system. This
following protection methods: depends on the circuit design
system requires that one leg of the
parameters, which topic is not covered
isolating transformer be connected to
•• The use of ELV circuitry (separated by this paper.
earth. PELV and SELV circuits are shown
(or safety) extra low voltage (SELV), The earth loop impedance of all LV
in Figure 1.
protected extra low voltage (PELV) electrical distribution sub-circuits (from the
FELV is a term which covers other ELV
and functional extra low voltage protective device via the earthed
circuits that do not meet the
(FELV)); equipment, returning through the earth
requirements for a SELV or PELV circuit
•• Automatic disconnection of supply path to the supply transformer earthed
as the ELV part of the circuit may not be
(ADS). neutral connection) must be low enough
adequately protected from accidental
to ensure that any protective device – fuse
contact with higher voltages existing in
Other forms of protection from electric or residual current detector (RCD) will
other parts of the circuit. Thus, the
shock which fall outside the scope of this operate in the event of an earth leakage
protection requirements for the higher
paper are as follows: fault. Thus, protective earthing is designed
voltage part have to be applied to the
to ensure that the circuit-protective device
entire circuit. Further discussion has thus
•• Double or reinforced insulation; will disconnect the supply and so limit the
been limited to SELV and PELV circuits.
•• Electrical separation of the supply to rise in potential, above earth potential, of
One problem with a PELV system is
one item of current-using equipment. any exposed conductive parts for the
that faults elsewhere in the installation
duration of the fault.
may induce voltages on the entire
This paper is mainly concerned with system via its protective earth conductor.
the earthing of ELV systems. However, The advantage of an SELV circuit is IV. TN-S and TT Power Supply
those engineers concerned with the that there is no earth return path which System’s Earthing
design and maintenance of such might occur via the human body. A
systems need to be aware of the disadvantage is that an over-current These are the two power supply earthing
methods of protection applied to LV protection device must be installed in systems commonly found in the United
supplied apparatus such as power each leg of each ELV circuit and sub- Kingdom.3 Their acronyms are derived
supply transformers and electrical power circuit. from the following:
distribution equipment forming an
integral part of control system cabinets T = Earth (from the French word
C. Automatic disconnection in the
and other plant-mounted instrumentation Terre);
event of a fault (ADS)
equipment.
ADS is the most widely used form of N = Neutral;
protection against electric shock. It is S = Separate.
B. ELV – SELV, PELV and FELV appropriate where basic protection
supplies consists of measures such as the
ELV circuits may be categorised as SELV insulation of live parts by barriers or A. TN-S system earthing
or PELV. The two systems are almost enclosures and fault protection exist in As shown in Figure 2, this system has
identical in that both require the same the form of earthing, equipotential the neutral of the source of energy
voltage limitation and the requirement of bonding and automatic supply connected to earth at one point only. For
adequate electrical separation from disconnection in the event of an earth a three-phase system, this is normally
higher voltages, either by insulation or leakage fault. the star point of the grid transformer’s
physical methods. They also both require ADS fault protection for circuits secondary windings. The consumer’s
the use of a safety isolating transformer operating at a voltage greater than ELV is earthing terminal is usually connected to
complying with BS EN 61558-2-6. achieved when the circuit-protective the metallic sheath or armour of the
However, they differ in that only the PELV device operates within a defined time power supply distributor’s service cable.

40  Measurement and Control  l  March 2017  Vol 50  No 2


Contributed Paper

Tech Talk (12) Down to Earth: A Discussion of the General Requirements for the Earthing of Control and Instrumentation Systems

The C&I designer is not immune from often earthed using multiple electrodes
Figure 3  TT system circuit diagram
these regulations which require all and also using the mass of reinforced
exposed metalwork on equipment concrete forming the foundations. In the
operating above ELV to be earthed. latter case, the steel structure is bonded
to the reinforcement at strategic points
via removable test links.
VI. Equipotential Bonding There is also a requirement (statutory
There is a risk from electric shock which in the United Kingdom) to construct
may arise should an earth leakage fault electrical equipment or protect it such
create a potential difference between that it can withstand the effects of
B. TT system earthing adjacent exposed conductive adverse conditions including lightning
components. To minimise this risk, all strikes. The protection for a structure will
Figure 3 shows a typical TT system of
extraneous conductive components generally also protect equipment installed
earthing.
must be bonded together and connected within it but additional protection may be
This has the neutral of the source of
to the system’s general earth. Effective required especially where electrical links
energy connected as for TN-S, but no
bonding provides an alternative earth exist between separate buildings.
facility is provided by the distributor for
leakage return path via a plant’s Surge arrestors may be installed to
the consumer’s earthing. This is a typical
structure. This complements the protect vulnerable electrical equipment in
situation where the power supply is
electrical safety earthing system. Thus, power transmission and distribution
connected via overhead line conductors.
even if the system’s main earth systems from lightning-induced voltage
With a TT system, the consumer must
connection is lost, touching adjacent spikes caused by a nearby lightning
provide their own connection to earth,
metal components should not give rise to strike or by distribution circuit switching.
that is, by installing a suitable earth
a danger from electric shock. The Consumer equipment such as computer-
electrode or connection to underground
general requirements for UK systems are based systems may additionally be
structural metalwork local to the
detailed in BS7671.1 protected by surge protectors. Both
installation.
For TN-S and TT systems, types of device work by bypassing the
equipotential bonding is not intended to voltage transient spike to earth, rather
V. Earthing Arrangements and carry any earth fault current and therefore than it passing through the connected
Protective Conductors a separate adequately sized earth equipment.
continuity conductor path must be When instrumentation and other
Guidance on the selection and
installed. electronic equipment are located
installation of earth electrodes and
Examples of items required to be outdoors, consideration should be given
conductors is given in BS 7671:2008.1
equipotential bonded are as follows: to methods of protection from lightning
Further information can be obtained
strike, where such an event may cause
from BS 7430:1998 ‘Code of Practice
severe control system damage via
for Earthing’.4 A soil resistivity test of the Control cabinets; interconnected cables. Metallic
ground is the main factor in the
Cable gland plates; enclosures forming a Faraday cage
determination of the type and extent of
which is locally earthed is one form of
earth electrode/s required. Electrodes Cable support systems; protection.
should only be driven into previously
Process pipe work and vessels; BS EN/IEC62305 Standard for
undisturbed ground.
Lightning Protection September 20065 is
Other systems which may require Air conditioning ducts; the applicable standard for the United
connecting to a common earthing point
Concrete reinforcement; Kingdom and Europe. In North America,
are as follows:
it is NFPA – 780, Standard for Lightning
Structural steelwork, steel walkways
Protection.
and handrails.
Water installation pipes;
Gas installation pipes; VIII. Control Systems ‘Clean’
VII. Lightning Protection Earthing
Other installation pipe work and
ducting; Structures (e.g. buildings and plants) With any AC power distribution network,
need to be protected from the effects of there will always be some leakage
Central heating and air-conditioning
lightning strikes by the installation of an current to earth. This is made worse on
services;
effective means of protection specifically large systems by the multiplicity of sub-
Exposed metal structural parts of a designed for the particular structure. The circuits involved, each circuit leakage
building. steel structures of process plant are being too small to operate a protective

March 2017  Vol 50 No 2  l  Measurement and Control  41


Contributed Paper

Tech Talk (12) Down to Earth: A Discussion of the General Requirements for the Earthing of Control and Instrumentation Systems

IX. Intrinsic Safety Systems


Figure 4.  IS earthing circuit diagram
Earthing
The most likely source of abnormal
voltages invading intrinsic safety (IS)
circuits is within the safe area.6,7 IS circuit
protection modules are generally
equipped with a busbar (see Figure 4),
which when connected to the neutral
star point of the grid transformer via a
low impedance earth path ensures that
any significant fault current is kept
outside of the hazardous area. The
generally accepted earth loop impedance
for an IS earth is 1 ohm; however, 0.1
ohm is preferable and often achievable.
Current flowing through the IS earth
device but contributing to the sum of electrical system currents. The use of a bonding conductor generates a potential
the earth leakage current returning to separate clean earth electrode should be difference between the IS earth point at
the supply transformer. The electrical avoided as it may result in increased the barriers and the supply transformer
safety earth may also be subject to system susceptibility to electromagnetic neutral star point. The metallic cases of
switching spikes and noise from coupling (EMC) problems. instruments in the hazardous area are
inverters. Thus, even for an earth On large systems, ELV supplies to bonded to the transformer neutral star
electrode having earth loop impedance transmitters, signalling processing point, and the instrument internal circuits
within the limits of the Standard used, equipment, receiving instruments and are connected to the barrier busbar. The
the earth impedance multiplied by the analogue to digital converters potential difference between the IS earth
total leakage current will result in an AC associated with control systems may be point at the barriers and the transformer
three-phase ripple standing voltage and derived from several separate AC to DC neutral star point is thus transferred to the
other ‘noise’ at various points around power supply units. To avoid hazardous area. Although normally safe,
the safety earth busbar and unacceptable signal errors, care must as the internal circuits are isolated from
interconnecting earth conductor be taken to ensure that the 0 V the instrument housing, this potential
network. reference node (within the allowable difference should be minimised so that in
The ‘body of earth’ is often used in uncertainty for the measurement the event of a local insulation failure, the
instrumentation and associated system) is just that, and not at a slightly IS system safety integrity is preserved.
computing systems as a 0 V reference higher voltage caused by circulating Thus, a fundamental requirement
for signals. Noise, even if only in the currents between the various instrument concerning the earthing of IS zener
order of microvolts (in the form of AC or and control system power supply barriers is that the IS earth, control signal
DC signals) on the 0 V reference, may voltage sources via their individual 0 V reference earth and the electrical
lead to unexpected results affecting reference earth connections. 0 V earth power earth must be independent of
control signals, including the failure of the connections must be individually wired each other and only meet at the ‘body of
electronics. and not ‘daisy chained’ to a reference earth’ (see section XII). This philosophy
The term ‘clean earth’ is often used in (clean) earth busbar, which is itself accords with industry best practice and
connection with control systems, but insulated from the electrical safety earth. recommendations for the earthing of
what does it mean? A definition is: ‘A The system designer should ensure electronic and computer-based systems.
low impedance earth point with that in order to avoid contamination of ELV control signal cables are often
negligible chance of conducted noise the clean earth, only the ELV 0 V DC electromagnetically screened to increase
either already present or likely to be power supplies, cable screens and cable protection against magnetic coupling
created when bonded to an electrical drain wires should be connected to it. (cross talk) from nearby power cables.
circuit’. In practice, a single clean earth Cable armouring and any electrical The screen generates a current which
cable is connected at one point only to equipment safety earth connections neutralises the source magnetic field.
the general earth, this being as close as should be connected to the power Theoretically, there is no need to earth
practical to the general earth electrode supply safety earth point. In the United this screen; however, it is common
connection. This is necessary in order Kingdom, a ‘clean’ earth should be practice to bond it to a clean earth or IS
that the current return paths do not labelled as such using the IEC 60417- earth in the case of hazardous area
share a common path with the main 5019 symbol. systems as such bonding provides

42  Measurement and Control  l  March 2017  Vol 50  No 2


Contributed Paper

Tech Talk (12) Down to Earth: A Discussion of the General Requirements for the Earthing of Control and Instrumentation Systems

avoiding this hazard is to interconnect all


Figure 5.  Interconnected cable screens
of the conductors to each other and to
earth via conducting paths with
sufficiently low resistance to permit the
dissipation of any static charge.
The accepted rate of static charge
generation in industrial processes is such
that a resistance to earth up to 106 ohm
will ensure safe dissipation of static.
Within metallic plant and equipment,
much lower resistances to earth can be
achieved and readily measured. Here, it
is usual to use a figure of 10 ohms for
the maximum resistance to earth. Where
such equipment is bolted to steel
supporting structures, the bolting will
normally ensure adequate earth bonding
without the need for separate earth
capacitive coupling screening and also XI. Electrostatic Earthing conductors.
provides a means of calculating the Thus, the requirements for protection
screen’s electrostatic potential.
A. General requirements
against static electricity may be met by a
A comprehensive treatment of earthing Many industrial processes which move common earthing system to which all
requirements for hazardous areas can be fluids and powders within pipes generate structures and items of process
found in Towle6 and Coles.7 static electricity. In hazardous areas, this equipment are electrically connected.
poses an ignition risk and a risk of shock Where conductive non-metallic and
to personnel. Although effective anti-static materials are used, the 10
X. Earthing Arrangements for
containment of explosive fluids and dust ohm target is inappropriate and the 106
Instruments’ Field Cable
is the first layer of safety protection, the ohm value may be used.
Screens
second layer is the elimination of Note that earthing of plant/equipment
Screened cables are commonly used to potential ignition sources. In the United does not necessarily eliminate static
minimise adverse effects to electronic Kingdom, this is a legal requirement charge within the fluid/product itself.
equipment from capacitive coupling under the Dangerous Substance and
(cross talk) between cables, particularly Explosive Atmosphere Regulations
for analogue signals from plant B. Bonding of metal pipes in
(DSEAR). These regulations require that
instruments through any intermediate hazardous areas
electrostatic hazards be assessed
marshalling box up to the control system alongside other potential sources of Flange joints on plant equipment and
input/output marshalling cubicle. The use ignition such as electrical and mechanical pipe work handling flammable materials
of twisted pair cables or metallic conduit process equipment. should be bonded across.
provides additional protection from While it is not always possible to Pipe work carrying non-flammable/
electromagnetic radiation. prevent the generation of static electricity, non-conducting liquids in areas where
Unless otherwise advised by an the technique of earthing can be used to flammable materials are handled should
equipment manufacturer, cable screens safely discharge it and eliminate these be subject to precautions as for
should only be earthed at one point. risks. BS 5958 – Code of Practice for the flammable liquids.
Earthing via the screen drain wire is Control of Undesirable Static Electricity Where flexible/non-metallic pipe
commonly carried out at the control (1991)8 contains detailed information on connections or in-line non-metallic
system input/output marshalling cubicle the hazards and the precautions required devices such as flow meters are involved,
with the screen at the field device being to prevent unwanted consequences the end flanges of these devices should
left un-earthed and insulated. This is to relating to static electricity. be effectively bridged by an earth
prevent any plant structure earth return The most common source of danger conductor.
current that may arise if the screen was from static electricity is the retention of
earthed at both ends. In this event, the charge on a single item of plant or
earth loop current becomes a noise XII. Supply Transformer Star
equipment (a conductor) because all of
source affecting the signal conductors. Point Earthing
the stored energy can be released in a
Figure 5 shows a typical wiring single spark to earth or to another Multiple electrode connections to earth
arrangement. conductor. The accepted method of will have varying earth loop impedance

March 2017  Vol 50 No 2  l  Measurement and Control  43


Contributed Paper

Tech Talk (12) Down to Earth: A Discussion of the General Requirements for the Earthing of Control and Instrumentation Systems

Figure 6.  Typical star point earthing circuit (TT system)

values due to factors such as the length point earthing circuit arrangement for an References
of earth bonding cable and local soil industrial installation. The connection to 1. BS 7671:2008. Wiring regulations (17th ed.).
2. Electricity Safety and Continuity Regulations
resistivity. This situation can lead to the earth electrode from each earthing 2002.
problems with electronic equipment as sub-circuit’s ‘collecting’ busbar should 3. Cronshaw G. Earthing: Your questions answered.
the various earths will have potential be kept as short as possible and the IEE Wiring Matters 2005; 16: 18–24.
differences between them. There is also cable sized so as to add negligible 4. BS 7430:2011+A1:2015. Code of practice for
protective earthing of electrical installations.
a risk due to transient surge damage. impedance to the earth loop. Note: An 5. BS EN/IEC 62305:2006. Standard for lightning
The answer is found in the commonly alternative method of connecting the IS protection.
accepted practice of connecting all Earth busbar to the Safety Earth is by 6. Towle LC. A definitive guide to earthing and
bonding in hazardous areas, May 1997.
‘earthing’ systems to a single earth connection via the 0 V earth bar.
Available online at http://www.casuarina.
electrode connection point. This com.sg/My%20Webs/pdf/Application/
electrode, whatever its physical Funding Tp1121-1.pdf
configuration, then provides a single 7. Coles M. Earthing and bonding in hazardous
The author(s) received no financial support locations. IEE Wiring Matters 2006; 18: 10–24.
earth route to the grid transformer neutral for the research, authorship and/or 8. BS 5958:1991. Code of practice for the control of
star point. Figure 6 shows a typical star publication of this article. undesirable static electricity.

44  Measurement and Control  l  March 2017  Vol 50  No 2

Potrebbero piacerti anche