Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
2- The system shown in the fig.(1) is fed by two generators G1 and G2,
G1 at the bus A and G2 at 70% distance from A in section AB. The
currents Ia and Ib supplied by them respectively are equal. The reactance
of the transformer is 10%. The line voltages and impedances are shown in
the figure. Find the setting for the impedance relays for the first, second
and third zone adjusting the first zone to reach 80%, second zone to reach
50%. C.T's and P.T's have ratios 400/5 and 166000/110 V respectively.
Show the effect of infeed on the setting relays and protection.
A B C
G1 ZAB= 20+j60 ZBC=10+j25
~
166kVline 33 kV 33 kVline
Ia
Ib 10 MVA
~ Z=10%
G2
Figure (1)
TL 12 TL 23
R 12 R 21 R 23 R 32
Figure (2)
1- An I.D.M.T. over current relay has a plug setting of 150% and has a
time setting of 0.5 . The relay is connected in the circuit through a C.T.
having ratio 500/5 A. Calculate the time of operation of the relay if the
circuit carries a fault current of 6000 A. The relay characteristic is shown
in the table (1).
2- Reference Fig. (1) given that :
Fault current = 2000 A CT Ratio : 200/1 A
Relay 1 set on 100% Relay 2 set on 125%
For discrimination the time grading margin between the relays is 0.5 sec.
Determine the time of operation of the two relays assuming the relays have
the characteristic as shown in table (1) and that the relay no.1 has a time
setting = 0.2
4- An 11-kV bus bar has duplicate incoming feeders each fitted with
1000/5 A I.D.M.T.L. relay having plug and time setting of 150% and 0.4 .
The corresponding data for an outgoing feeder is 400/5 A , 175% , and
0.3 . The substation is a firm supply for 25 MVA. For a 3-phase 250 MVA
fault, calculate the time margin between the relays for
(a) two incoming feeders in
(b) one in.
Show that the protection on a single incoming feeder (other switched out)
will not operate to a load of 25 MVA.
Plug setting
multiplier 2 3.6 5 10 15 20
Time in seconds
for a TS=1 10 6 3.9 2.8 2.2 2.1
Table(1)
R2 R1
2000A
125% 100%
Figure(1)
The shown Fig. gives the percentage differential relay applied to the
protection of an alternator winding. The relay has a 10% slope of
characteristic (I1-I2) - (I1+I2)/2. A high resistance ground fault occurred
near the grounded neutral and of the generator winding while generator is
carrying load. As a consequence, the currents in amperes flowing at each
end of the winding is as given in Fig. Assuming CT ratio of 400/5 amperes
will the relay operate the trip of the breaker?
CAIRO UNIVERSITY THIRD YEAR
FACULTY OF ENGINEERING SWITCHGEAR & PROTECTION
ELEC. POWER & MACHINES DEPT. MAGNETIC CIRCUITS
The lifting magnetic system shown in the figure has a square cross section
6*6 cm. The coil has 300 turns and a resistance of 6 ohms. Neglect
reluctance of the magnetic core and field fringing in the air gap.
(a) The air gap is initially held at 5 mm and a dc source of 120 V is
connected to the coil. Determine
i. The stored field energy.
ii. The lifting force.
(b) The air gap is again held at 5 mm and an ac source of 120 V (rms.) at
60 Hz is connected to the coil. Determine the average value of the lifting
force.
g