PowerPact™ H-, J-, and L-Frame Circuit Breakers

Wiring Diagrams

Section 11—Wiring Diagrams

Unit-Mount Circuit Breakers


Power Micrologic Trip Unit1 Remote Operation

Upstream CB Vac (+)

06114460
Vac (+)
3P or 4P NSX cord

Z1
Z2
Z3
Z4
Z5
N LA LB LC
SDE 81
06114459

BPO BPF
+ -
HL

82 84

D2

C2

A4

A2

B4

B2
Z1

Z2
T1 MN MX
Q T2 auto
I 0 I
Z3
Z4

Z5
or manu
V

A1
L1
D1

C1
Vac (-)
manu SDE

Vac (-)

Motor Operator
3P + N
N LA LB LC NSX cord
Z1
Z2
Z3
Z4
Z5

06114461

Downstream CB
Vac (220/240 V)
+ -
HL

BSCM
Z1

Z2

B4

Q I V T1

T2
Z3
Z4
Z5

ENVT
Q
auto 0 I
manu
ENCT
A1

H2 T1
Vac
H1 T2

Schematic of the communicating motor operator .

Communicating Motor Operator


Continued on next page

140
01/2013 ™ © 2011–2013 Schneider Electric
All Rights Reserved
PowerPact™ H-, J-, and L-Frame Circuit Breakers
Wiring Diagrams

Unit-Mount Circuit Breakers (continued)


Indication Contacts

Open Closed Fault Fault Closed Open

102
104
134

124
32

22

12

82
84

92
94
34

24

14

WH
06114462

RD

YE
VT
OF3 OF2 OF1 SDE SD CAF2 CAF1 CAO1

WH
RD

GY
131
31

21

121

101
81

91
11

The diagram is shown with circuits de-energized, relays in normal position, and all devices open, connected, and charged.
Terminal connections shown as O must be connected by the customer.

Micrologic Trip Unit A or E Remote Operation


Communication MN Undervoltage Release
A/E H (WH), L(BL): data or
-(BK), +(RD): 24 Vdc power supply MX Shunt Release
ZSI (Zone Selective Interlocking) Motor Operator
Z1: ZSI OUT SOURCE A4 Opening Order
Z2: ZSI OUT A2 Closing Order
A/E Z3: ZSI IN SOURCE B4, A1 Power Supply to Motor Operator
Z4: ZSI IN ST (short time) L1 Manual Position (manu)
Z5: ZSI IN GF (ground fault) B2 Overcurrent Trip Switch Interlocking (mandatory for correct operation)
(Z3, Z4, and Z5 for L-frame circuit breaker only) BPO Opening Pushbutton
ENCT: External Neutral Current Transformer: BPF Closing Pushbutton
-Shielded cable with 1 twisted pair (T1, T2) Communicating Motor Operator
-Shielding earthed at CT end only
A/E Connection L = 12 in. (30 cm) max. B4, A1 Motor Operator Power Supply
-Maximum length of 33 ft (10 m) BSCM Breaker Status and Control Module
-Cable size of 22 AWG
-Recommended cable: Belden 9451SB or equivalent Indication Contacts

ENVT: External Neutral Voltage Tap for Connection OF2/OF1 Device ON/OFF Auxiliary Switches
E
to the Neutral using a 3P Circuit Breaker OF3 Device ON/OFF Auxiliary Switches (L-Frame)
SDE Overcurrent Trip Switch
Color Code for Auxiliary Wiring
(short-circuit, overload, ground fault, earth leakage)
RD: Red VI: Violet SD Alarm Switch
WH: White GY: Gray CAF2/CAF1 Early-Make Contact (rotary handle only)
YE: Yellow OR: Orange CAO1 Early-Break Contact (rotary handle only)
BK: Black BL: Blue
GN: Green

141
© 2011–2013 Schneider Electric ™ 01/2013
All Rights Reserved
PowerPact™ H-, J-, and L-Frame Circuit Breakers
Wiring Diagrams

Plug-In and Drawout Circuit Breakers


Power Micrologic Trip Unit1 Remote Operation

Upstream CB Vac (+)


Vac (+)

Z1
Z2
Z3
Z4
Z5
SDE 81

06114964
NSX cord BPO BPF
3P or 4P
N LA LB LC 82 84

C2
D2

B4
A4

A2

84
06114963

RD +
84 BK -

RD
A1 BL L

24/34

22/32
B4 WH

A2 WH
BL

C2 OR

A4 OR

BL
H
A2

D2

B4

B2
Z2 YE
Z1 VT MN MX
T1
Q auto
T2 0 I
I or manu
BK Z3
GN Z4
RD Z5

A1
L1
D1

C1

GN
WH

BK
41
42

44

A1
D1/C1

L1
Vac (-) manu Vac (-) SDE

Motor Operator

NSX cord
3P + N
N LA LB LC
Z1
Z2
Z3
Z4
Z5

Vac (220/240 V)
+ -

Downstream
HL

BSCM
B4
Z1

Z2

06114965

B4 GN
Z2 YE
Z1 VT

Q I V

T1
T2
ENVT auto
0 I
BK Z3
GN Z4
RD Z5

manu
OR A1

ENCT
Z3
Z4
Z5

H2 T1
A4

H1 T2
Vac

Communicating Motor Operator


Continued on next page

142
01/2013 ™ © 2011–2013 Schneider Electric
All Rights Reserved
PowerPact™ H-, J-, and L-Frame Circuit Breakers
Wiring Diagrams

Plug-In and Drawout Circuit Breakers (continued)


Indication Contacts Carriage Switches

Open Closed Fault Fault Closed Open Connected Disconnected


32

22

12

82
84

92
94
34

24

14
06114966

82 GN

92 GN
84 RD

94 RD
32 YE

22 YE

12 YE
34 VT

24 VT

14 VT

102
104
134

124

314
312

352
354
06114467
WH
RD

YE
VT

GY

GY
VT

VT
OF3 OF2 OF1 SDE SD CAF2 CAF1
WH
CAO1 CE CD

GY
RD

YE

YE
131

121

101
GY 31

GY 21

BK 81

BK 91
GY 11

311

351
31

21

81

91
11

The diagram is shown with circuits de-energized, relays in normal position, and all devices open, connected, and charged.
Terminal connections shown as  and O must be connected by the customer.

Micrologic Trip Unit A or E Remote Operation


Communication MN Undervoltage Release
A/E H (WH), L(BL): data or
-(BK), +(RD): 24 Vdc power supply MX Shunt Release
ZSI (Zone Selective Interlocking) Motor Operator
Z1: ZSI OUT SOURCE A4 Opening Order
Z2: ZSI OUT A2 Closing Order
A/E Z3: ZSI IN SOURCE B4, A1 Power Supply to Motor Operator
Z4: ZSI IN ST (short time) L1 Manual Position (manu)
Z5: ZSI IN GF (ground fault) B2 Overcurrent Trip Switch Interlocking (mandatory for correct operation)
(Z3, Z4, and Z5 for L-frame circuit breaker only) BPO Opening Pushbutton
ENCT: External Neutral Current Transformer: BP Closing Pushbutton
-Shielded cable with 1 twisted pair (T1, T2) Communicating Motor Operator
-Shielding earthed at CT end only
A/E Connection L = 12 in. (30 cm) max. B4, A1 Motor Operator Power Supply
-Maximum length of 33 ft (10 m) BSCM Breaker Status and Control Module
-Cable size of 22 AWG
-Recommended cable: Belden 9451SB or equivalent Indication Contacts

ENVT: External Neutral Voltage Tap for Connection OF2/OF1 Device ON/OFF Auxiliary Switches
E
to the Neutral using a 3P Circuit Breaker OF3 Device ON/OFF Auxiliary Switches (L-Frame)
SDE Overcurrent Trip Switch
Color Code for Auxiliary Wiring
(short-circuit, overload, ground fault, earth leakage)
RD: Red VI: Violet SD Alarm Switch
WH: White GY: Gray CAF2/CAF1 Early-Make Contact (rotary handle only)
YE: Yellow OR: Orange CAO1 Early-Break Contact (rotary handle only)
BK: Black BL: Blue
GN: Green

143
© 2011–2013 Schneider Electric ™ 01/2013
All Rights Reserved
PowerPact™ H-, J-, and L-Frame Circuit Breakers
Wiring Diagrams

Motor Operator
NOTE: The diagram is shown with circuits de-energized, relays in normal position, and all devices open,
connected, and charged.
After tripping initiated by the “Push to trip” button, the undervoltage release (MN), or the shunt release
(MX), device can be reset automatically, remotely, or manually.
Following tripping due to an electrical fault, reset must be carried out manually.

Motor Operator with Automatic Reset Motor Operator with Remote Reset

Vac (+) Vac


(+)

06114968
06114475

SDE 81 SDE 81
BPO BPF BPO BPF Reset

82 84 82 84

A4

A2
A4

A2

B4

B2
B4

B2

Q Q
auto auto
0 I 0 I
manu manu

A1
A1

L1
L1

manu SDE manu SDE

Vac (-) Vac (-)

Symbols Motor Operator with Manual Reset


Q: Circuit Breaker
Vac (+)
A4: Opening Order
06114760

A2: Closing Order


SDE 81
B4, A1: Motor Operator Power Supply
BPO BPF
L1: Manual Position (manu)
B2: Overcurrent Trip Switch Interlocking (mandatory for correct operation)
82 84
BPO: Opening Pushbutton
A4

A2

B4

B2

BPF: Closing Pushbutton


SDE: Fault-Trip Indication Contact
(short-circuit, overload, ground fault, earth leakage)

Q
auto
0 I
manu
A1
L1

manu SDE
Vac (-)

144
01/2013 ™ © 2011–2013 Schneider Electric
All Rights Reserved
PowerPact™ H-, J-, and L-Frame Circuit Breakers
Wiring Diagrams

Motor Operator (continued)


Symbols Communicating Motor Operator

Q: Circuit Breaker
B4, A1: NSX cord

06114461
Motor Operator Power Supply
BSCM: Breaker Status and Control Module

Vac (220/240 V)

+ -
HL
BSCM

B4
Q
auto 0 I
manu

A1
Vac

Schematic of the communicating motor operator .

RSU Screen for Communicating Motor Operator


06114670

B4
Auto SD SD
Manu
Enable
reset
even if
SDE SDE
220
RSU utility setup screen for the VAC Open Close
communicating motor operator command command
Enable
automatic Reset
reset command
OF OF

Open motor Close motor Reset motor


A1

Single-line diagram of communicating motor operator


Opening, closing and reset orders are transmitted through the communication
network. The “Enable automatic reset” and “Enable reset even if SDE”
parameters must be set using the RSU software using the screen by clicking the
blue text.
“Auto/Manu” is a switch on the front of the motor operator.
Terminal connections shown as O must be connected by the customer.

145
© 2011–2013 Schneider Electric ™ 01/2013
All Rights Reserved
PowerPact™ H-, J-, and L-Frame Circuit Breakers
Wiring Diagrams

SDx Module with Micrologic™ Trip Unit


NOTE: The diagram is shown with circuits de- Connection
energized, relays in normal position, and all
devices open, connected, and charged. Vac (+) 24–415 V

06114470
STD PAL Ir
or output 1 or SDG
Symbols or output 2
SD3 SD2 SD4
SD1, SD3: SDx Module Power Supply
SD2: Output 1 (80 mA max.) SDx

SD4: Output 2 (80 mA max.)


Q

SD2 SD4

Micrologic 3 SDT —
SD1
Micrologic 5 SDT or Output 1 PAL Ir or Output 2

Micrologic 6 SDT or Output 1 SDG or Output 2

Terminal connections shown as O must be connected by the


customer. Vac (-)

Operation

tr at 6 Ir
06114471

> 105 % Ir

> 90 % Ir
I

PAL Ir
SDG

SDT

Circuit breaker Circuit breaker


trip order reset

I: Charge Current
PAL Ir: Thermal Overload Pre-Alarm
SDG: Ground-Fault Signal
SDT: Thermal-Fault Signal
Q: Circuit Breaker

146
01/2013 ™ © 2011–2013 Schneider Electric
All Rights Reserved
PowerPact™ H-, J-, and L-Frame Circuit Breakers
Wiring Diagrams

SDTAM Module with Micrologic M Trip Unit


NOTE: The diagram is shown with circuits de- Connection
energized, relays in normal position, and all
devices open, connected, and charged. Vac (+) 24 to 415 V

06114472
Manual Closing
reset SDT KA1 order
Symbols KM1
SD3 SD2 SD4
SD1, SD3: SDTAM Module Power Supply
SD2: Thermal Fault Signal (80 mA max.) SDTAM

SD4: Contactor Control Output (80 mA max.) 6 8 Opening


4 10 order
Q
2 12
SD2 SD4 1 14
OFF 15 KA1
Micrologic 2 M SDT KA1 Auto reset (minutes)
SD1
Terminal connections shown as O must be connected by the
customer. KM1
KM1

Vac (-)

Operation

Class (tr) at 7.2 Ir


> 95 % T°
400 ms
< 95 % T°
06114473

SDT

KA1

KM1

%T° 400 ms before Contactor


circuit-breaker closing order
tripping order
%T° Manual or
automatic reset

I: Charge Current
SDT: Thermal Fault Signal
KA1: Auxiliary Relay (RBN or RTBT Relay)
KM1: Motor Contactor
Q: Circuit Breaker

147
© 2011–2013 Schneider Electric ™ 01/2013
All Rights Reserved
PowerPact™ H-, J-, and L-Frame Circuit Breakers
Wiring Diagrams

Modbus™ Module
Detailed connection of the circuit breakers on Connection
communication network Modbus

G3 G4
EGX / 100 / 300
24 V Power Supply
G1 G2 24 V 0 V Rx- Rx+ Tx- Tx+

White

Blue
06114474

Modbus Line
White
Blue

Termination
24 V

24 V

24 V
0V

0V

0V
D1

D1

D1
D0

D0

D0
Modbus Communication Interface Module (PowerPact H-, J-, L-Frame)
White
Blue

CCM + -

Network A B A' B'


White

Blue

Breaker A B A' B'

CT CD CE + -
White
Blue

911 914 811 812 311 314


yellow
yellow

brown
brown

black
white
black
white

blue
blue

red
red

B'/Rx+
B'/Rx+

A'/Rx-
B/Tx+
A'/Rx-
B/Tx+

A/Tx-
A/Tx-

E1 24 V
E1 24 V

CT CD CE
E2 0 V
E2 0 V

Cradle
E6
E5
E4
E3
E6
E5
E4
E3

Masterpact NT/NW

BCM BCM
(PowerPact P/R-Frame) (Masterpact NT/NW)

148
01/2013 ™ © 2011–2013 Schneider Electric
All Rights Reserved