CWDM Troubleshooting Procedures
For each troubleshooting please follow each steps from CAS E I to CASE V one by one
1. Query the current alarm management and identify which link (L1R or L2R) reads LOS and No
input power alarm.
Open the NEright click on ETMp cardquery current alarm management
3
CASEIII:GIS (Access Side Problem)
If the NE’s time management query is successful try the next steps.
1. Check the received power levels on both C1R and C2R ports of ETMp card on CWU side
Open the NEright click on ETMp cardoptical power querycheck the
IN(OAC_CTP_So)Query
If one of the received levels is ok then the connection between GIS and ETMp is fine.
2. Check the packet exchange between GIS and ETMp
Open the NEright click on ETMp cardoptical power queryselect GE Tran&Reve from
Policy drop down arrowQuery
3. Take a look on Transmit and Received Packet values by querying repeatedly.
If the received packet value is not changed (stuck on a value) or became zero every time we
queried, it is definitely the GIS problem
MSAGs in Bole, Arada, Addis Ketama, Laghar (Filowoha), Old Airport, Kirkos, Yaka, Sidis Kilo & Nefas Silk
their CWE OAC sides are directly connected to IP Switch. The other MSAGs found in other sites not
mentioned in the above list are connected to IP switch through M900 (DWDM) so you have to check it
first M900 network.
1. Check the received power levels on both C1R and C2R ports of ETMp card on CWE side
4
If the received packet value is not changed (stuck on a value) or became zero every time we
queried, it is definitely the IP problem
1. Check the received power levels on both C1R and C2R ports of ETMp card on CWE side
2. Check the received power level and performance of OCH and OAC Side of the near –end GEM8 card
Open M900 NEright click on appropriate GEM8 cardoptical power querycheck the IN
(OAC_CTP_So) and IN (OCH_CTP_So)Query
And the Queried in put power in both OCH and OAC side and performance value of OCH side is
good, go to the next CASE .if not the problem is definitely in the M900 Network
4. If the Queried value is different from the desired value, repeat the above steps in Far-end GEM8
card. If everything is OK, check the packet exchange between Far-end GEM8 and IP switch.
Open NEright click on Far-end GEM8 cardoptical power queryselect GE Tran&Reve from
Policy drop down arrowQuery
5. If receiving packet value is not changed (stuck on a value) or became zero every time we queried, it
is definitely IP problem
N.B. The Near-end GME8 is found in DWDM ring network named with CWE name. And the Far-end
GME8 is located on sites mentioned in the beginning of CASE IV.
e.g. Lebu MSAGs Near-end GME8 is found in Lebu DWDM. Its far-end GME8 is located in Nefas silk.
5
Case V: Transmission Problem
If the NE’s time management query is successful try the next steps.
1. Check the received power levels on both L1R and L2R ports of ETMp card on CWU and CWE side
Open the NEright click on ETMp cardoptical power querycheck the
IN(OCH_CTP_So)Query
If one of the received levels is ok in both CWE and CWU side then the connection between CWE
and CWU is fine.
2. Check the packet exchange between GIS and ETMp
Open the NEright click on ETMp cardoptical power queryselect GE Tran&Reve from
Policy drop down arrowQuery
3. Take a look on Transmit and Received Packet values by querying repeatedly.
If the transmit packet value is not changed (stuck on a value) or became zero every time we
queried, it is definitely the Transmission problem
6
Signal Flow and Fiber Connection
7
fig 2 CWU side fiber connection
8
7 FAN Alarm Major FAN ALM FAN Fault. Replace FCB board.
8 Module Inner Major Module Inner Module fault. Reset the board or
Temperature Temperature Replace the board.
Over Threshold over threshold
Alarm
9 Module Inner Major Module Inner Poor ventilation Check the FAN in or
Temperature Temperature inside. clean the dust
Over Threshold over threshold screen in the
Alarm device.
10 Module Inner Major Module Inner The environment Check the room
Temperature Temperature temperature is too temperature and
Over Threshold over threshold high. air-condition.
Alarm
11 Card Not Minor Board not There is a board Configure it.
Configure configure ALM found by EMS,but not
Alarm configured.
12 Card Mismatch Minor Board mismatch The reported Board Reconfigure the
Alarm ALM type mismatch with board.
the configured one.
13 Card Dismount Minor Board Dismount The communication Reset the board or
Alarm ALM between board and Reset NCP.
NCP break.
14 Output Power Major Output power The input power too Check the input or
Too High Alarm too high ALM high. Adjust the output
Power.
15 Output Power Major Output power Fault in this board. Replace the board.
Too Low Alarm too low ALM
16 Output Power Major Output power The input power too Clean the optical
Too Low Alarm too low ALM low. connector of input
and output.
17 No Output Critical No Output The LD has been shut Open the LD in
Power Alarm power ALM down in EMS. EMS.
18 No Output Critical No Output No input power. Clean the optical
Power Alarm power ALM connector of input
and output.
19 Fan Failure Critical Fan Failure The fan failure. Replace the FAN
Alarm Alarm card or replace the
FAN.
20 Fan Failure Critical Fan Failure The connection of Connect the fan
Alarm Alarm the fan failure. again.
9
Input Power Best Working State
Best
Detection Detection Performance Low High working
card point item Threshold Threshold state
input power
ETMp L1R &L2R (dBm) -31 -9 (-22 upto -10)
input power
ETMp C1R & C2R (dBm) -11 0 (-9 upto -2)
input power
GEM8 IN OCH (dBm) -17 0 (-17 upto -6)
input power
GEM8 IN OAC (dBm) -11 0 (-8 up to 0)
THE END