Sei sulla pagina 1di 2

====================================================================================

NEUTRAL GROUNDING TRANSFORMER CALCULATION


====================================================================================

Department System Engineering


Tool Electrical Protection System
Version 1.0.0
Date 29-10-2018

Project Data
Project Name NAM YEN
Customer Name Dai Phat
Project Capacity 2*5MW
Prepared By Harjit
Reviewed By SKM
Revision 0
System Data
kW 5000
MW 5.000
kVA 6250.000
MVA 6.250
kV 10.5
Hz 50
PF 0.8
Primary Current-Ip 297.619
Secondary Current-Is 0.496
HD% 5
HD-pu 0.050
Base MVA 10
CT Ratio
CT-1-Primary Current 600
CT-1-Secondary Current 1
CT-2-Primary Current 600
CT-2-Secondary Current 1
CT Ratio-1 600.000
CT Ratio-2 600.000
CTR*PTR 57273.000
Transformation Ratio-1 6.286
Transformation Ratio-2 6.286
PT/NGT Ratio
PT Primary kV 10.5
PT Secondary kV 0.11
NGT Primary kV 10.5
NGT Secondary kV 0.11
PT Primary V 10500.000
PT Secondary V 110.000
PT Ratio 95.455
NGT Primary V 10500.000
NGT Secondary V 110.000
NGT Ratio 95.455

Page- 1
Neutral Grounding Transformer
Generator Capacitance/Phase uf 0.1863
Surge Capacitor Capacitance/Phase uf 0.25
Transformer Capacitance/Phase uf 0.007
Cable Length Meter 50
Cable Parallel Runs Numbers 2
Cable Capacitance/Phase/kM uf 0.3
Voltage Rise Factor due to transient in single phase fault % 1.6
Voltage Rise Factor due to AVR operation % 1.05
Total Cable Capacitance uf 0.0300
Total Capacitance uf 0.4733
Total Capacitive Impedance-Xco Ohm 6728.7416
Total Capacitive Current/Phase-Ico Ampere 0.9010
Capacitive Zero Sequance Current-Icg Ampere 2.7030
Neutral Grounding Transformer Calculated Primary Voltage Volt 10184.758
Neutral Grounding Transformer Roundup Primary Voltage Volt 10500
Neutral Grounding Transformer Secondary Voltage Volt 110.000
Capacitve Reactance to Ground Ohm 2242.9139
Neutral Grounding Resistor Ohm 0.246
Neutral Grounding Resistor Calculated Current Ampere 258.171
Neutral Grounding Resistor Roundup Current Ampere 259
Resistive Component of Ground Fault Current Ampere 2.705
Secondary Resistor Power kVA 16.396
Charging Power kVA 16.387
Transformer Calculated Capacity kVA 28.3988
Transformer Short Time Calculated Capacity for 30 Second kVA 35.00
Transformer Calculated Rating kVA 5.6798
Transformer Roundup Rating kVA 7

====================================================================================

Page- 2