Ball cocks in water closet tanks shall be installed so that the critical level of the water
inlet is above the full opening of the overflow pipe at least _____.
(A) 1/2 inch
(B) 1 inch
(C) 3 inches
(D) 6 inches
(B) 1 inch
For questions #4 through #6, choose the answer you think is correct for the minimum
height of the atmospheric vacuum breaker critical level above the point specified.
Above the highest part of a urinal equipped with a flushometer valve: _____
(A) 1 inch
(B) 3 inches
(C) 6 inches
(D) 12 inches
(C) 6 inches
For questions #4 through #6, choose the answer you think is correct for the minimum
height of the atmospheric vacuum breaker critical level above the point specified.
PEX tubing shall not be installed within the first _____ of piping connected to a water
heater.
(A) 12 inches
(B) 18 inches
(C) 24 inches
(D) 36 inches
(B) 18 inches
Each outlet on a nonpotable water system that is used for special purposes shall be
posted _____.
(A) DANGER - PROCESSED WATER
(B) DANGER - CONTAMINATED WATER
(C) DANGER - POLLUTED WATER
(D) CAUTION - NONPOTABLE WATER DO NOT DRINK
(D) CAUTION - NONPOTABLE WATER DO NOT DRINK
The piping material(s) not approved in the cold water piping located inside a building is
_____.
(A) PVC
(B) PE
(C) asbestos cement
(D) all of the above
(D) all of the above
Water valves 2-1/2 inches and larger may have bodies that are _____.
(A) galvanized
(B) die-cast
(C) aluminum core
(D) cast iron
(D) cast iron
Changes in direction of copper tubing may be made with _____.
(A) non deforming bending equipment
(B) heat annealing
(C) metallic fittings
(D) plastic fittings
(A) non deforming bending equipment
Copper water tube Type "M" may be installed within a building _____.
(A) below slab only
(B) above ground only
(C) for cold water only
(D) if it is wrapped
(B) above ground only
Immediately ahead of each water-supplied appliance and each slip joint or appliance
supply is required a _____.
(A) control valve
(B) check valve
(C) backwater valve
(D) solenoid valve
(A) control valve
After al owing for friction and other pressure losses, the residual water pressure shall be
at least _____.
(A) .433 psi
(B) 7.5 psi
(C) 15 psi
(D) 29 psi
(C) 15 psi
A water piping system with a pressure of 110 psi will require a(an) _____.
(A) reduced pressure backflow device
(B) extra-heavy pipe and fittings
(C) pressure regulator and strainer
(D) pressure-relief valve
(C) pressure regulator and strainer
Any water heater connected to a separate storage tank and having valves between the
heater and tank shall be provided with a _____.
(A) fulIway valve
(B) fulIway gate valve
(C) water pressure regulator
(D) water pressure-relief valve
(D) water pressure-relief valve
Cast-iron fittings, up to and including two inches in size, when used in connection with
potable water piping, shall be _____.
(A) extra heavy
(B) flanged
(C) disallowed
(D) galvanized
(D) galvanized
Water piping may be installed in the same trench with less than 12 inches of separation
from a building sewer constructed of _____.
(A) cast iron
(B) clay
(C) asbestos cement
(D) bituminized fiber
(A) cast iron
The available pressure at the water meter is 80 psi. At the highest supply outlet, 36 feet
above the water meter, the pressure would be _____ psi when sizing a water system
according to Chapter 6.
(A) 62
(B) 44
(C) 116
(D) 80
(A) 62
Building supplies shall be no smaller than that required for the installation and, in no
case, smaller than _____ inch(es).
(A) 1/2
(B) 3/4
(C) 1
(D) 2
(B) 3/4
Copper tubing used for water piping under a concrete slab within a building shall be
_____.
(A) installed with brazed joints with cast brass fittings
(B) protected with a factory-applied coating
(C) installed without joints where possible
(D) installed with Type K copper tube with brazed joints
(C) installed without joints where possible
CPVC water pipe may be used for hot and cold water distribution systems _____.
(A) in residences only
(B) within a building
(C) belowground only
(D) aboveground only
(B) within a building
Copper or stainless steel flexible connectors for water heater connectors shall be limited
to _____.
(A) 12 inches
(B) 18 inches
(C) 24 inches
(D) 36 inches
(C) 24 inches
Whenever fixtures and/or fixture fittings are installed that require a residual water
pressure higher than 15
pounds per square inch _____.
(A) that minimum pressure shall be provided
(B) provisions shall be made to use fixtures that do not require higher residual pressure
(C) the piping system shall be not less than copper tubing Type L
(D) A and C apply
(A) that minimum pressure shall be provided
The duration for a water system pressure test shall be for a period of not less than
_____ minutes.
(A) 5
(B) 10
(C) 15
(D) 30
(B) 10
Except for plastic piping, water piping systems shall be permitted to be tested with
_____.
(A) 10 psi air pressure
(B) 50 psi air pressure
(C) 10 psi CO2
(D) 60 psi CO2
(C) 10 psi CO2
In occupancies where plumbing fixtures are installed for _____, hot water shall be
required for bathing, washing, laundry, cooking and similar purposes.
(A) public use
(C) private use
(B) commercial use
(D) daycare facilities
(C) private use
Except as required in Sections 1602.1 and 1603.1, nonpotable water systems shall
have a _____ with black uppercase lettering, with the words "CAUTION: NONPOTABLE
WATER, DO NOT DRINK."
(A) white background
(B) blue background
(C) green background
(D) yellow background
(D) yellow background
Plastic materials for _____ piping outside underground shall have a blue insulated
copper tracer wire or other approved conductor installed adjacent to the piping.
(A) building supply
(B) well
(C) irrigation
(D) hose bibb
(A) building supply
Any water system that prevents dissipation of building pressure back into the water
main shall be provided with an approved, listed, and adequately sized _____ or other
approved device.
(A) double-check valve
(B) expansion tank
(C) temperature & pressure relief valve
(D) PRV
(B) expansion tank
Pipe joint material shall be insoluble in water, nontoxic, and applied _____.
(A) on male threads only
(B) on pipe threads and inside fittings
(C) on inside fitting threads only
(D) in warm weather only
(A) on male threads only
The minimum wall thickness for threaded plastic pipe (not molded fittings) shall be
_____.
(A) Schedule 40
(B) Schedule 80
(C) 1/8 inch
(D) 1/16 inch
(B) Schedule 80
When brazing, the alloys shall have a liquid temperature above _____ degrees F.
(A) 800
(B) 840
(C) 1,000
(D) 1,200
(C) 1,000
_____ systems shall be clearly identified, have a purple background with uppercase yel
ow lettering.
(A) Gray water
(B) Reclaimed (recycled) water
(C) Rainwater catchment
(D) None of those listed
(D) None of those listed
The area of coverage of a single fire sprinkler shall not exceed _____.
(A) 100 square feet
(B) 200 square feet
(C) 300 square feet
(D) 400 square feet
(D) 400 square feet
What size drain for the fire sprinkler system shall be provided on the system side of the
water distribution shut of valve? _____
(A) ½ inch
(B) ¾ inch
(C) 1 inch
(D) 1-½ inch
(A) ½ inch
Non-metallic pipe and tubing for fire sprinklers shall be protected from exposure to the
occupied space by a material having a minimum fire rating of _____ minutes?
(A) 15
(B) 30
(C) 45
(D) 60
(A) 15
The minimum separation from a wood burning stove to a fire sprinkler shall be
measured in a straight line from the nearest edge of the sprinkler to _____.
(A) the centerline of the wood burning stove
(B) the nearest edge of the wood burning stove
(C) the far edge of the wood burning stove
(D) the nearest igniter
(B) the nearest edge of the wood burning stove
The sprinkler pipe size from the water supply source to a sprinkler shall not be less than
_____ inch.
(A) 3/8
(B) 1/2
(C) 3/4
(D) 1
(C) 3/4
What is the minimum temperature rating of intermediate temperature fire sprinklers
when installed in attics and concealed spaces directly beneath a roof? _____
(A) 135° F
(B) 170° F
(C) 175° F
(D) 225° F
(C) 175° F
The water distribution size of the fire sprinkler system in a single family home has been
determined to be 1 inch. The available pressure at the service is 55psi. The water meter
listing specifies a flow rate of 14
gpm. With a water service developed length of 38 feet, the available psi for fire
sprinklers is _____.
(A) 49.8
(B) 50.8
(C) 51.8
(D) 55.0
(A) 49.8
The minimum water test time for a fire sprinkler system is _____ minutes.
(A) 15
(B) 30
(C) 60
(D) 120
(A) 15
Nonmetallic fire sprinkler pipe shall be certified for residential sprinkler installations and
shall have a pressure rating of not less than _____ psi at 120° F.
(A) 100
(B) 120
(C) 130
(D) 150
(C) 130
The water supply for a one story dwelling unit of 1785 square feet shall have the
capacity to provide the required flow rate to the sprinklers for a period _____ minutes.
(A) 5
(B) 7
(C) 10
(D) 15
(B) 7