Sei sulla pagina 1di 30

MOPX Separation System

Parameter List

List No. 31830-6181-8

Printed Dec 1996


Book No. 1810139-02 V3

Alfa Laval Marine & Power


Alfa Laval reserve the right to make changes at any time without
prior notice.
Any comments regarding possible errors and omissions or
suggestions for improvement of this publication would be
gratefully appreciated.
Copies of this publication can be ordered from your local
Alfa Laval company.
Published by: Alfa Laval Separation AB
Marine & Power Oil Treatment Division
S - 147 80 Tumba
Sweden
© Copyright Alfa Laval Separation AB 1996.
Study instruction manuals and observe the
warnings before installation, operation,
service and maintenance.

Not following the instructions can result in


serious accidents with fatal injuries.

P000272A
In order to make the information clear only foreseeable conditions have
been considered. No warnings are given, therefore, for situations
arising from unintended usage of the machine and its tools.

A summary of the safety information is found in the Safety chapter


under divider 1.
Contents

1 Scope 1

2 Process Parameters 3

3 Installation Parameters 5

4 Timer Sequence
Parameters 7

5 Service Mode Parameters


90, 94, and 95 9

5.1 Countdown of Timers


P50 – P89 9

5.2 Alarm Log 10


5.2.1 Examples of
Logged Alarms 11

5.3 Timer function 13

6 Additional Parameter
Information 15

6.1 Process Parameters 15

6.2 Installation Parameters 20

6.3 Timer Sequence Parameters 21


6.3.1 Starting Sequence 21
6.3.2 Separation Sequence 22
6.3.3 Sludge Discharge
Sequence 22
6.3.4 Stopping sequence 22

7 Sequence Diagram 23

7.1 Purifier mode 23

7.2 Clarifier mode 24

1810139-02
1810139-02
1 Scope

This parameter list is valid for the following


separation systems:
MOPX 205
MOPX 207

MOPX 309
MOPX 310
MOPX 213

Including the EPC-41 control unit with


PROM: 31830-6213-1.

1810139-02 1
1 Scope MOPX Parameter List

2 1810139-02
2 Process Parameters

The EPC-41 control unit controls the separa-


tion process. It can be programmed for differ-
ent separation systems and different condi-
tions within the system, by setting parameters.
The process parameters can be easily adjusted,
as often as required, to meet changes in the
operating conditions, e.g. oil temperature,
alarm points, time between sludge discharges.
Each separator has its own EPC-41 control
unit. Up to three separation systems can be
interconnected via cables between their con-
trol units. The separators can work in parallel
or series operation. Only two separators can
work in series; the third must work in parallel
or act as a stand-by. The first separator in
series should always be defined as a purifier
and the second as a clarifier.

NOTE

P2 is factory set to P (purifier). If you


change it to C (clarifier) you get all
the factory settings for a clarifier,
which is shown in column “Factory
set value, Clarifier” in the tables.

WARNING

Disintegration
hazard

If the time between sludge discharges


is set too long, sludge accumulation
and bowl imbalance may occur.

1810139-02 3
2 Process Parameters MOPX Parameter List

Factory set value Plant


Parameter Description or unit Range set
Purifier Clarifier value

P11 Max. time between Minutes 0 – 999 30 30 .....


sludge discharges P1 = P61
Changing of P1 automatically
changes P61.
P21 Purifier/Clarifier mode P = Purifier P or C P .....
C = Clarifier
P31 Series configuration 0 = No separator in series 0, 12, 13, 23 0 0 .....
12 = The 1st and the 2nd sepa-
rator work in series
13 = The 1st and the 3rd separa-
tor work in series
23 = The 2nd and the 3rd sepa-
rator work in series
P41 Sludge discharge sig- 1 = Every purifier discharge 1–4 --- --- .....
nal from purifier to 2 = Every 2nd purifier
clarifier discharge
3 = Every 3rd purifier discharge
4 = Every 4th purifier discharge
If P3 = 0 then P4 = “- - -”.
P51 High temperature °C or °F 0 – 115 °C or 0 0 .....
alarm 0 – 255 °F
P61 Low temperature °C or °F 0 – 115 °C or --- --- .....
alarm 0 – 255 °F
P71 Temperature set point °C or °F 0 – 110 °C or --- --- .....
0 – 240 °F
P81 P-band % 10 – 500 --- --- .....
P91 I -time Minutes 0.1 – 10.0 --- --- .....
P10 to
Not used --- ---
P14
P151 HFO / DO selection of HFO = Heavy Fuel Oil HFO or do HFO HFO .....
type of oil do = diesel oil
For lubricating oil select HFO
P16 to
Not used --- ---
P19
1. For more information, see‘‘Additional Parameter Information’’ on page 15.

4 1810139-02
3 Installation Parameters

NOTE

EPC-41 parameter P21 is factory set


to 50 Hz. If connected to a 60 Hz
supply an alarm will occur. Set P21 to
60 Hz and press the reset button. The
alarm will disappear.

The installation parameters must be set before


the initial start-up and before process para-
meters are set.
The parameters rarely need to be adjusted
again.

NOTE

Alfa Laval can not be held


responsible for injuries and damage
caused by usage of parameters not
recommended by Alfa Laval

Factory set value Plant


Parameter Description or unit Range set
Purifier Clarifier value

P20 Separator type 2.1 = MOPX 1.2 – 2.1 2.1 2.1 2.1
P21 Power frequency Hz 50 or 60 50 50 .....
Check that the frequency is cor-
rect, see label on the separator.
P22 Not used --- ---
1
P23 EPC-41 address 1 = Single unit or the 1st linked 1– 8 1 1 .....
control unit
2 = The 2nd linked control unit
3 = The 3rd linked control unit
4-8 = Not used
Up to 3 control units can be linked
together.

1810139-02 5
3 Installation Parameters MOPX Parameter List

Factory set value Plant


Parameter Description or unit Range set
Purifier Clarifier value

P24 For remote communication with 48 48 .....


P25 Profibus protocol 2 2 .....
P26 to --- ---
Not used
P32
P33 Emergency stop 0 = Emergency stop only 0 or 1 0 0 .....
function 1 = Mechanical vibration switch
P341 Alarm delay time Seconds 1 – 30 15 15 .....
P351 Low temperature Seconds 1 – 999 15 15 .....
alarm delay after MV1
change over
P361 Remote control 0 =
No remote control 0 – 3, 10 – 13 0 0 .....
1 =
Remote switches
2 =
Remote computer
3 =
Not applicable
10 =
No remote control, alarm
A4-1 cancelled
11 = Remote switch, alarm A4-1
cancelled
12 = Remote computer, alarm
A4-1 cancelled
13 = Not applicable
P371 Heater type 0 = No or common heater with 0–2 0 0 .....
separate controller
1 = Heatpac EHS-62 controlled
by EPC-41
2 = Heater with control valve,
controlled by EPC-41
P38 Size of Heatpac kW 0, 7, 8, 14, 16, --- --- .....
heater If P37 = 1 then P38 is set to 16, 22, 24, 36, 40,
otherwise P38 = “- - -”. 50, 56, 65, 72
P39 Run time of steam Seconds 0 – 999 --- --- .....
control valve If P37 = 2 then P39 is set to 120,
otherwise P39 = “- - -”.
P401 Temperature reading C = °C C or F C C .....
F = °F
P411 Max. start time for Minutes 0 – 999 15 15 .....
heater
P42 Not used --- ---
P431 Extra alarm function 0 = Alarm indication on display. 0 or 1 0 0 .....
No action.
1 = Alarm indication on display.
Oil feed off during
separation sequence.
P44 to --- ---
Not used
P49
1. For more information, see‘‘Additional Parameter Information’’ on page 15.

6 1810139-02
4 Timer Sequence Parameters

The timer sequence parameters control the


operation of the system; i.e. start, separation,
sludge discharge and stop functions.

Factory set value Plant


Parameter Description or unit Range set
Purifier Clarifier value

Starting sequence

P501 Sludge discharge Seconds 0 – 99.9 3 3 .....


Draining of bowl Seconds 0 – 999 15 15 .....
P51
operating system
P521 Bowl closing water Seconds 0 – 999 15 15 .....
1
P53 Bowl sealing water Seconds 0 – 999 45 --- .....
1
P54 Oil feed on during Seconds 0 – 999 30 30 .....
stabilizing period
P55 to Not used --- ---
P59
Separation sequence

P601 Not used --- ---


P611 Time between sludge Minutes 0 – 999 30 30 .....
discharges P61 = P1
Changing of P61 automatically
changes P1.
P62 to Not used --- ---
P69
Sludge discharge sequence
P701 Displacement water. Seconds 0 – 999 20 20 .....
Oil feed off
P71 Not used --- ---
1
P72 Sludge discharge Seconds 0 – 99.9 3.0 3.0 .....
P73 to Not used --- ---
P77
P781 Draining of bowl Seconds 0 – 999 15 15 .....
operating system
P79 Not used --- ---

1810139-02 7
4 Timer Sequence Parameters MOPX Parameter List

Factory set value Plant


Parameter Description or unit Range set
Purifier Clarifier value

Stopping sequence
P80 Bowl closing water on Seconds 0 – 999 15 15 .....
P81 Bowl displ. water Seconds 0 – 999 90 --- .....
P82 Oil feed on Seconds 0 – 999 --- 30 .....
P83 to Not used --- ---
P85
P86 Separator motor off Seconds 0 – 999 180 180 .....
P87 to Not used --- ---
P89
1. For more information, see‘‘Additional Parameter Information’’ on page 15.

8 1810139-02
5 Service Mode Parameters 90, 94, and 95

With aid of the service mode parameters


information can be requested and displayed,
for instance the countdown of timer sequences
can be displayed while they are running.
Factory set value Plant
Parameter Description or unit Range set
Purifier Clarifier value

P90 Service mode 0 = No service mode 0, 1, 2, 50 0 0 .....


1 = Countdown of timers
P50 – P89
12 = Power frequency
50 = Alarm log, including self re-
setting alarms
P91 For remote 0 0
P92 communication with 19,2 19,2
P93 Profibus protocol 60 60
P94 Count down timer 0.0 - 10.0 0.0 0.0
P95 Indication of P94 timer Hours 0.0 - 10.0 --- --- .....
actual value
P96 to Not used
P99

5.1 Countdown of Timers


P50 – P89
By setting P90 to 1, the mode selector in
PS
position L and then by pushing the alarm reset 42

button, a countdown of each activated timer


(P50 – P89) can be displayed during
G006482A

operation.

Timer P61 shows that it is 32 seconds left to next


sludge discharge.

1810139-02 9
5 Service Mode Parameters 90, 94, and 95 MOPX Parameter List

5.2 Alarm Log


By setting P90 to 50, the mode selector in
position L and then by pushing the alarm reset
button, the 32 latest alarms can be displayed,
including self resetting alarms.
Each logged alarm consists of three
consecutive groups of information:
1. The accumulated alarm log time, which
shows how long the EPC has been in
operation since the previous alarm.
If the interval between two alarms is
greater than 999.5 hours (≈ 41 days) the
whole alarm log will be reset to 0.
2. The alarm is indicated in the same way as
when it occurred, except for the alarms
starting with an E:
• alarm code starting with an A.
• LED and an alarm code, for instance
“High or low oil temperature”.
• LED indications only.
• “alarm” code starting with an E (events
with no alarm released)
There is only one event for EPC-41,
which is a self resetting function;
E2 = low pressure
3. The actual value of parameter P1
(maximum time between sludge
discharges).

10 1810139-02
MOPX Parameter List 5 Service Mode Parameters 90, 94, and 95

5.2.1 Examples of Logged Alarms


• The capital “H” indicates that this is the

I000881A
latest alarm which has been logged. The
EPC had been in operation 48 hours and
20 – 29 minutes since the previous alarm.
Every tenth minute is displayed, but
several alarms can be logged within this
period.
The alarm was a “Power failure”.

I001103A
P1 (maximum time between sludge

I000891A
discharges) was set to 30 minutes.

Between these two alarms 10 hours and 0 – 9


minutes had elapsed (58.2 – 48.2).

• This event occurred 58 hours and 20 – 29

I000901A
minutes ago.

The event was a “Low pressure”.

I000912A
P1 indicated 30 minutes.
I000891A

• 106 operating hours and 30 – 39 minutes


I000921A

ago the first logged alarm occurred.

The alarm was a “Low temperature”.


S000121A

(Which is indicated by the LED and the


figures on the display).
I001151A

P1 setting was 30 minutes.


I000891A

1810139-02 11
5 Service Mode Parameters 90, 94, and 95 MOPX Parameter List

• If the accumulated time becomes more


than 999.5 hours it will the first time be

I001341A
indicated by capital “H” and 1000 is
subtracted from the displayed value.

S000121A
The second time it happens, another 1000
is subtracted from the displayed value etc.

I001311A
I000891A
Between these two alarms 10 hours have
elapsed (H 5.0 = 1005.0 hours)

I001321A
S000121A
I001331A
I000891A

• This indicates the end of the log.


I001001A

12 1810139-02
MOPX Parameter List 5 Service Mode Parameters 90, 94, and 95

5.3 Timer function


By setting P94 to >0.0 a count down timer is
activated. It is intended as a reminder of
service to be made after the elapsed running
hours. If e.g. P94 is set to 2.70 it means 2700
hours. Each 0.1 indicates 100 hours. When
2700 hours of operation have elapsed, an
alarm will be released and 3h - - - is indicated
in the front window. The alarm is repeated at
each start of the EPC. To avoid this the P94
timer has to be started or set to 0.
When P94 is >0 the actual count down value
is displayed when P95 is activated. P95 is just
an indication of the elapsed time in P94. It can
not be set.

To restart the timer, go to P94. Push third


button once (display flashes). Push button one
once. The timer is now restarted with the same
value. When the display is flashing, a new
value can be entered.

1810139-02 13
5 Service Mode Parameters 90, 94, and 95 MOPX Parameter List

14 1810139-02
6 Additional Parameter Information

6.1 Process Parameters The only way to get a clean sludge


space is to make appropriate
P1 Max time between sludge discharge adjustment of the interval based on
Long intervals between sludge regular inspection.
discharges can cause the sludge to
N.B. Alfa Laval assumes no responsibility
accumulate and solidify. The sludge
for the actual choice of discharge
may then break up at sludge discharge
interval times, as these depend entirely
and create imbalance in the bowl.
on local feed characteristics.

WARNING Fuel oil cleaning


Conditions may change completely
Disintegration when bunkers are changed. Therefore,
hazard great care must be given to the
discharge interval setting for each new
If the interval between sludge bunker. In case the current discharge
discharges is too long, there is risk of interval exceeds the recommended
heavy side breakdown. initial value, the interval setting has to
be reduced according to table on next
page, when a new, unknown bunker is
As many factors influence the sludge to be separated.
discharge interval, the choice of
interval must be based on experience. Use of unstable fuel or mixing of
When the bowl is opened for routine incompatible fuel oils may cause
cleaning, the sludge space should be precipitation of sludge and overloading
inspected and, if necessary, the interval of the separator.
between discharges changed
accordingly. WARNING

Clean sludge space: the interval may Disintegration


be prolonged. “Clean sludge space” hazard
means that no noticeable amount of
solidified sludge remains in the sludge Each new bunker requires review of
space. the discharge time setting.
Dirty sludge space: the interval must
be shortened. “Dirty sludge space”
means that some solidified sludge has
accumulated in the sludge space.

1810139-02 15
6 Additional Parameter Information MOPX Parameter List

Type of oil Initial discharge Time to first bowl inspection

Distillate (1.5 - 6 cSt /40 °C) 4 hours 1 week

Marine Diesel Oil (max. 13 cSt / 40 °C) 2 hours 1 week

Intermediate / Heavy Fuel Oil 0.5 hour 2 days

Lubricating oil cleaning


The interval between discharges must
be shortened if the separator has been
out of service for 24 hours or longer
while the diesel engine has been
running.
In order to have a reasonable starting
point the table below shows
recommended initial discharge
intervals and operating time to first
inspection.
Main lubricating oil system

Initial discharge Time to first bowl inspection

Recommended interval 1 hour 1 week


for cross head engines

Stuffing box oil 5 minutes After one batch

Recommended interval 0.5 hour 2 days


for trunk piston engines

P2 Purifier/clarifier mode
The MOPX separator can be defined as
a clarifier or as a purifier. It can operate
as a single separator or in parallel or
series. This is defined by the
parameters P2, P3 and P23. See P3 for
the relationship between these
parameters.
If a separator operates in series when
the mode is changed the parameter P3
has to be changed accordingly.

16 1810139-02
MOPX Parameter List 6 Additional Parameter Information

P3 Series configuration
Up to three EPC-41 control units can
be linked together. Only two of the
three connected separators can work in
series. The first separator in series
should always be defined as a purifier
and the second separator as a clarifier.
The relationship between the
parameters P2, P3 and P23 is shown in
the following table.
N.B. The 1st linked control unit must always
have the power on (the separator does
not need to be operating) when the 2nd
and the 3rd separators are operating in
series.
Type of operation First linked control unit Second linked control unit Third linked control unit
Single operation: P2 = P (Purifier) - -
P3 = 0 (No separator in
series)
P23= 1 (Single unit)
Parallel operation: P2 = P P2 = P P2 = P
P3 = 0 P3 = 0 P3 = 0
P23= 1 (1st linked P23= 2 (2nd linked control P23= 3 (3rd linked control
control unit) unit) unit)
Series operation P2 = P P2 = C (Clarifier) P2 = P
1st and 2nd separator: P3 = 12 (1 and 2 in P3 = 12 P3 = 0
series) P23= 2 P23= 3
P23= 1 This separator works as a
stand-by unit; i.e. in parallel
operation or not used.
Series operation P2 = P P2 = P P2 = C
1st and 3rd separator: P3 = 13 (1 and 3 in P3 = 0 P3 = 13
series) P23= 2 P23= 3
P23= 1 This separator works as a
stand-by unit.
Series operation P2 = P P2 = P P2 = C
2nd and 3rd separator: P3 = 0 P3 = 23 (2 and 3 in series) P3 = 23
P23= 1 P23= 2 P23= 3
This separator works as
a stand-by unit.

1810139-02 17
6 Additional Parameter Information MOPX Parameter List

P4 Sludge discharge signals from P7 Temperature set point


purifier to clarifier To be set according to plant
The number of sludge discharges application. See also P5 and P6.
initiated by the first separator (purifier) P8 P-band (Proportional band)
before a discharge signal is sent to the If P37 = 0 then P8 = “- - -”.
second separator to start its sludge If P37 = 1 or 2 then P8 is automatically
discharge sequence. P4 should be set in preset to 40%.
the purifier controller.
P9 I-time (Integral time)
P5 High temperature alarm If P37 = 0 then P9 = “- - -”.
P5 should be set sufficiently above the If P37=1 or 2 then P9 is automatically
temperature set point P7. preset to 1.2 minutes.
5 – 10 °C (10 – 20 °F) higher than P7
is recommended.
If P5 = 0 (monitoring temperature
sensor (Pt 100) not connected)
then P6 = P7 = “- - -”.

P5, P6 and P7 can be set both for heavy


fuel oil (HFO) and for diesel oil (DO),
see P15. If both oils are to be used, the
following must be done:
1. Set P5, P6 and P7 for “HFO” (P15
is factory set to “HFO”).
2. Change P15 to “do”.
3. Go back to P5 and set P5, P6 and
P7 for DO.

If only diesel oil is to be used for the


installation, the following must be
done:
1. Set P5 greater than 0.
2. Change P15 to “do”.
3. Go back to P5 and set P5, P6 and
P7 for DO.

P6 Low temperature alarm


Should be set sufficiently below the
temperature set point P7.
5 – 10 °C (10 – 20 °F) lower than P7 is
recommended.

18 1810139-02
MOPX Parameter List 6 Additional Parameter Information

How to set P8 and P9:


If the temperature varies with regularly
repeated oscillation, setting of the
proportional band and integral time is
necessary.
• Increasing the value of parameter
P8 (proportional band width) will
result in a slower and more stable
control action.
• Increasing the value of parameter
P9 (integral time) also results in
slower response from the EPC-41.

We recommend that you follow these


guidelines:
1. Set P9 = 10 minutes.
2. Decrease P-band (P8) band in steps
until the process reaches the point
where it starts to oscillate with a
constant amplitude. Test the
stability after each step by
introducing a step-change of load

P000041A
or set point.
3. When you have discovered the Constant amplitude
point where the process oscillates
with a constant amplitude note the
following figures:
A = The value of P-band (P8).
B = The time for one full period in
P000051A

seconds.
4. Calculation of optimal parameter
settings.
P-band I-time
P8 = 2.2 × A P9 = 0.8 × B
The settings above give a rather good
result but may be adjusted according
to individual characteristics in different
loops.

1810139-02 19
6 Additional Parameter Information MOPX Parameter List

P15 HFO / DO selection of oil type P35 Low temperature alarm delay after
To prevent false alarm (A7-10) when MV1 change over
cleaning diesel oil the type of oil must When the oil feed change over valve
be specified. changes position the flow rate and thus
Once P5, P6 and P7 are set for HFO the oil temperature may be influenced.
or DO they automatically follow the By delaying the temperature alarm, a
selection of P15. false alarm is avoided as the oil
If P15 = “HFO” and P5 is set > 0 then temperature has time to stabilize.
P5 for DO is automatically reset to P35 should be set according to plant
50 °C (120 °F). application. If a delay time above 120
If P15 = “do” then P53 =P70 = 0. seconds is necessary, check the heating
See P5 for the relationship between P5, system and the installation layout.
P6, P7 and P15. P36 Remote control
Remote control can be applied in form
of:
6.2 Installation Parameters
• external switches
P20 Separator type • external computers
When P20=2.1 the specific functions
for theMOPX are automatically set. P37 Heater type
The EPC-41 control unit is designed
P23 EPC-41 address for control of:
If the separator works as a single unit
the EPC-41 address is always 1. • Heatpac EHS-62 (P37 =1)
When using more than one separator in • Heater with heating media control
the same system (parallel or series) valve (P37=2)
each interconnected EPC-41 control
N.B. If a different type of heater is installed
unit must be identified.
(P37 = 0), only a start/stop signal is
The EPC-41 address shows the order in
available from the EPC-41 control unit.
which the control units are linked.
If a steam heating system is connected
See also P3 for the relationship
to the EPC-41 and if the system is
between the parameters.
equipped with an optional shut-off
P34 Alarm delay time valve, and provided P37= 0 or 2, the
Activation of most alarm functions can valve is opened when the heater is
be delayed up to 30 seconds, except for started.
• emergency / vibration alarm
The valve is shut:
• high temperature alarm,
which have a fixed delay time of 2 • when the heater is stopped
seconds. • at high temperature alarm
If operating two separators in series,
• at power failure
P34 for the clarifier separator must be
3 seconds longer. • at EPC stand-by mode

20 1810139-02
MOPX Parameter List 6 Additional Parameter Information

P40 Temperature reading P53 Sealing water


Degrees Celsius (°C) or Fahrenheit Sealing water is used in the bowl to
(°F) temperature readings available. prevent oil from discharging through
P5, P6 and P7 have to be set according the water outlet in a purifier. The
to °C or °F. amount of sealing water in the bowl is
P41 Max. start time for heater balanced by the gravity disc.
Sets the maximum allowed start time During the starting sequence sufficient
for the heater. Minimum temperature water must be admitted to the empty
limit (P6) must be reached within this bowl to establish an adequate water
time. seal. Insufficient water will lead to a
broken water seal.
P43 Extra alarm function If a broken water seal occurs during the
Extra alarm functions can be starting sequence the time setting can
connected. By setting P43 to 1 the oil be increased. P53 should be set accord-
feed to the separator will be stopped ing to experience.
when the extra alarm occur. Recommended values:
MOPX 213: 45 sec.
MOPX 205, 207, 309 & 310: 30 sec.
N.B. If more than 100 secs is required for
6.3 Timer Sequence MOPX 205, or 140 seconds for the
Parameters MOPX 207, 309, 310 & 213 this
indicates a malfunction.
6.3.1 Starting Sequence N.B. Before increasing the sealing water,
make sure that the appropriate gravity
P50 Sludge discharge
disc is fitted to the separator bowl.
To ensure that the bowl is always
emptied at start (e.g. after power N.B. This function is blocked in the clarifier
failure). mode (P2 = C, and P51 = “- - -”).
P52 Bowl closing water P54 Oil feed on during stabilizing period
For proper closing of the separator Oil admitted to separator bowl during a
bowl during start-up sequence. If more stabilizing period.
than 60 seconds is required, it may If more than 30 seconds is needed for
indicate a malfunction. the purifier and 60 seconds for the
clarifier it may indicate a malfunction.

1810139-02 21
6 Additional Parameter Information MOPX Parameter List

6.3.2 Separation Sequence 6.3.4 Stopping sequence


P61 Time between sludge discharges P80 Bowl closing water on
The same as P1 (setting one parameter To be set for proper closing of the bowl
will set both to the same value). (on until P86)
Bowl closing water is supplied for 2 P81 Bowl displacement water on
seconds every 15 minutes. Purifier mode only; the bowl is filled
N.B. In series operation the time sequence up in order to prevent vibration.
for the clarifier must be longer than for MOPX 213 is 90 secs, and for smaller
the purifier, in order to synchronize sizes 45 secs is recommended
sludge discharges initiated from the P82 Oil feed on
purifier. Clarifier mode only; the bowl is filled
up in order to prevent vibration.
P86 Separator motor off
The separator motor is automatically
6.3.3 Sludge Discharge Sequence
switched off.
P70 Displacement water Restarting is blocked for 3 minutes.
Filling of displacement water to the
bowl eliminates the risk of oil loss at
the next sludge discharge.
If more than 40 seconds are required,
this indicates a malfunction.
N.B. If P2 = C (clarifier mode), then P70
starts but the valve is not activated
(i.e. no displacement water added).
P72 Sludge discharge
Sludge discharge initiated by MV15
admitting water to the separator bowl.
If more than 4 seconds are required,
this indicates a malfunction.
P78 Draining of bowl operating system.
Stabilizing period to allow water to
drain from the opening chamber.
Should be set according to experience.

22 1810139-02
7 Sequence Diagram

7.1 Purifier mode


The duration of the monitoring functions and output signals when the separator is operated as a
purifier is illustrated in the diagram.
Valve Stand- Starting sequence Separation Sludge discharge Stopping
Relay, Terminal Activated function by sequence sequence sequence
Sensor OFF P50 P51 P52 P53 P54 P61 P70 P72 P78 P80 P81 P86 OFF
3s 15 s 15 s 45 s 30 s 30 min 20 s 3s 15 s 15 s 90 s 180 s
Mon. functions

PS42 X7:4 Low oil pressure

PS41 X7:3
High oil pressure

- X7:1
Extra alarm

XS1 X8:4 Vibrations1

XS2 X8:4 Emergency stop1

- X9:3 Heater fault

TT1 X11:1-3 High oil temperature2

TT1 X11:1-3 Low oil temperature2

PS42 7:4 Switch function

Output signals

X1: 1,2 Motor starter

Blocking vibration
XS1 X2: 3,4
switch

MV1 X4: 4 Oil to separator

MV10A X5: 1 Closed drain valve

MV10 X5: 2 Displ./Sealing. water

MV15 X5: 3 Bowl opening water

MV16 X5: 4 Bowl closing water3

1. Emergency Stop (XS2) is normally connected to terminal X8:4. If the optional vibration switch (XS1) is installed
it is connected to terminal X8:4 and the Emergency Stop (XS2) is connected to the system power supply.
2. With optional sensor TT1 installed P50 will not start if the temperature is too low or too high.
3. During P61 intermittently 2 seconds every 15 minutes.

1810139-02 23
7 Sequence Diagram MOPX Parameter List

7.2 Clarifier mode


The duration of the monitoring functions and output signals when the separator is operated as a
clarifier is illustrated in the diagram.
Valve Standby Starting Separation Sludge discharge Stopping
Relay, Terminal Activated function sequence sequence sequence sequence
Sensor P50 P51 P52 P54 P61 P70 P72 P78 P80 P82 P86
OFF 3s 15 s 15 s 30 s 30 min 20 s 3s 15 s 15 s 30 s 180 s OFF
Mon. functions

PS42 X7:4 Low oil pressure

PS41 X7:3
High oil pressure

- X7:1
Extra alarm

XS1 X8:4 Vibrations1

XS2 X8:4 Emergency stop1

- X9:3 Heater fault

TT1 X11:1-3 High oil temperature2

TT1 X11:1-3 Low oil temperature2

PS42 7:4 Switch function

Output signals

X1: 1,2 Motor starter

Blocking vibration
XS1 X2: 3,4
switch

MV1 X4: 4 Oil to separator

MV10A X5: 1 Closed drain valve

MV10 X5: 2 Displ./Sealing. water

MV15 X5: 3 Bowl opening water

MV16 X5: 4 Bowl closing water3

1. Emergency Stop (XS2) is normally connected to terminal X8:4. If optional vibration switch (XS1) is installed it
is connected to terminal X8:4 and the Emergency Stop (XS2) is connected to the system power supply.
If the emergency stop button is pushed while the EPC is in stand-by mode the separator motor is stopped.
2. With optional sensor TT1 installed P50 will not start if the temperature is too low or too high.
3. During P61 intermittently 2 seconds every 15 minutes.

24 1810139-02

Potrebbero piacerti anche