Sei sulla pagina 1di 192

Power Transformer Design Aspect

Didik Susilo Widianto


Technical Director
PT UNINDO – AREVA
Contents 1. Introduction
2. Transformer core
3. Inrush Current
4. Transformer Winding
5. Insulation and Cooling Medium
6. Transformer Losses
7. Insulation Structure & Dielectric Withstand
8. Transformer Thermal Aspect
9. Short Circuit Analysis
10. Engineering
11. Manufacturing Process
12. Accessories, Protection & control
13. Final Acceptance Test
14. Technology Application

3 > Title of presentation - Date - References 3


1. Introduction

4 > Title of presentation - Date - References 4


Basic Theory

Faraday’s law
The electromotive force (e.m.f) is proportional to
the rate of linked flux changes

E = - N x dΦ/dt
 E = Electro motive force
 N = Number of turn
 dΦ/dt = Change the flux against time

Lenz’s law
The e.m.f is such any current produced acts to
opposite the linked flux.
Current Flux Current Counter Flux

5 > Title of presentation - Date - References 5


NO LOAD Condition

E = - N dΦ
Φ/dt = - N d(Φ
Φm Sin(ω
ωt))/ dt = - Nω
ω. ΦmSin(ω
ωt – π/2)
At f = 50 Hz, Φ = Β.Α  E = 222.14 . Ν.Β.Α
At f = 60 Hz, E = 222.14 .N.B.A.(f/50) E1
E = e.m.f (electromotive force) in Volt
Φ = Flux in Weber I0
Ip
B = Peak Induction in Tesla
Φ
A = Core cross section in m2 Im
I0 = No load current in Amp. I0
Im = Magnetizing current in Amp.
Ip = Losses current in Amp. E1 E2

E2
N1 N2
6 > Title of presentation - Date - References 6
ON LOAD Condition

V1 I1.X1
I2 R2 X2
I0 + I1 R1 X1 I1.R1
E1 I1 + I0
E2 V2
V1 E1
I1
Ip
I0
N1 N2
I2 Im Φ
Θ
E1 : N1 = E2 : N2
V2
I1 x N1 = I2 x N2
I2R2

Θ = the load power factor I2.X2


E2
7 > Title of presentation - Date - References 7
Power Transformer Main Parts
Oil Preservation

Bushing

Core

Transformer Tank

Winding

Control Cubicle

Cooler Transformer Liquid

8 > Title of presentation - Date - References 8


Transformer Power Rating

 Transformer power rating is expressed by MVA as a product of


rating voltage and rating current.
 The power rating [S] is a product of reactive power [Q] and
active power [P];

S [MVA] = S(Q2 [MVAR] + P2 [MW] )


 Referring to IEC 60076 – 1;
S [MVA] = S3 x E2[kV] x I2[Amp] 10-3
 Referring to ANSI/IEEE C57.12.00;
S [MVA] = S3 x V2[kV] x I2[Amp] 10-3
= S3 x (E2 + ∆V)[kV] x I2[Amp] 10-3
Hence, in ANSI/IEEE standard the power rating has considered
voltage drop at stated power factor

9 > Title of presentation - Date - References 9


Voltage Drop/Rise

∆V = V2 – V1
I2 R2 X2
I1 R1 X1

E2 V2
V1 E1

N1 N2

∆V = K (VR.CosΘ Θ) + K2/200 x (VR.Sin Θ – VX.CosΘ


Θ + VX.SinΘ Θ)

VX VZ ∆V = Voltage drop/rise [%]


K = Loading factor
VR = Transformer resistance [%]
VX = Transformer reactance [%]
VZ = Transformer impedance [%]
Θ Θ = Load power factor
VR
10 > Title of presentation - Date - References 10
Tap Regulation

 Tap Regulation ; the required voltage ratio to control the


fluctuated voltage of network to deliver the expected
constant voltage.
 Two type of tap regulator = Tap Changer ;
1.OLTC (On Load Tap Changer) = Tap regulation when the
transformer energized/under loading.
2.OCTC (Off Circuit Tap Changer) = Tap regulation when the
transformer de-energized (no transformer terminal is
connected to any network/generator)
 Tap regulation is expressed by the number of step & the
percentage of nominal voltage for each step regulation.
 Example = 150 kV + 7 x 1.5% / -10 x 1.5%

11 > Title of presentation - Date - References 11


Flux Behavior Due To Tap Regulation

 Two type of tap regulation ;


 CFVV = Constant Flux Variable Voltage
 The transformer volt/turn as well as the core flux will
constant along the tap regulated positions.
 This is the most common tap regulation system.
 VFVV = Variable Flux Variable Voltage
 The transformer volt/turn as well as the core flux will
vary referring to the tap regulated positions.
 This is used due to high current tap regulation at
furnace application or booster type regulation.

12 > Title of presentation - Date - References 12


Position Of Tap Changer

 Normally, the most optimum solution for tap changer


location is the neutral end of winding for STAR
connected winding.
 For DELTA connected winding with insulation class of
72.5 kV and lower, the line end location of tap changer is
normally the most optimum solution.
 For DELTA connected winding with insulation class
higher than 72.5 kV class, the middle electrical location
of tap changer will be the optimum.
 The electrically as well as geometrically location of tap
changer will also determine the impedance & losses
behavior.

13 > Title of presentation - Date - References 13


Tap Regulation vs Power Rating

 There are two kinds of power rating;


 CONSTANT Power Rating;
The power is constant for all tap regulation position.
 REDUCED Power Rating;
The power is reduced with constant current rating from a
certain tap regulation position.

Reduced Power
Constant Power from tap n
S
V V S
I
I

Tap 1 n p Tap 1 n p

14 > Title of presentation - Date - References 14


Autotransformer Concept

Seri Winding I2 = Is
Ns = N2 – N1

Tap Changer
I1
V2

V1 Ic = I1 – I2
N1 = Nc
Common Winding

I1, I2 = Current primary (1) & secondary (2)


V1, V2 = Voltage primary (1) & secondary (2)
Common Winding = N1 x (I1 – I2)
Seri Winding = (N2 – N1) x I2

15 > Title of presentation - Date - References 15


On Load Tap Changer

ON TANK OLTC IN TANK OLTC

16 > Title of presentation - Date - References 16


ACTIVE PART - Areva definitions
Frame Tank Location
Upper Yoke Top Frame
Insulation Cup

Coil Clamping
Block
Cross Brace

Top Platform

Tie Rod

Bottom
Platform

Flux Packet

Coil Support
Blocks
Oil Diaphragm

Tank Base
17 > Title of presentation - Date - References 17
2. Transformer Core

18 > Title of presentation - Date - References 18


CORE

 Purpose : the path for the flux lines with low


magnetic reluctance

Core material in power transformer ;


 Cold Rolled Grain Oriented Silicon Steel.
 Available thickness = 0.23 mm, 0.27 mm, 0.30 mm
 Lamination insulation = CARLITE 0.012 mm
 Grade ;
 Conventional Grain Oriented = High losses.
 Hi-B Grain Oriented = Medium losses.
 Laser/plasma refinement GO = Low losses.

19 > Title of presentation - Date - References 19


Induction vs Core Loss

20 > Title of presentation - Date - References 20


Core Stacking - Mitred Joints

But Lap Joint

Step Lap Joint

21 > Title of presentation - Date - References 21


Core Cutting

Three Legs Core


½W

Five Legs Core (3 wounds + 2 return)


22 > Title of presentation - Date - References 22
Bandaged Core

23 > Title of presentation - Date - References 23


Core Determination Factors
 No Load Loss (and No Load Current) ;
 No load loss is independent with the loading of the transformer, but it is
dependent with the applied voltage per turn of the winding.
 It has more significant economical component cost in capitalization than other
losses due to it’s appearance independency with the cyclic loading.
 IEC standard tolerance for no load loss = +15%, no load current = +30%.
 Over excitation capability ;
 For generator application, the transformer shall be designed for over excitation
up to 140% in 5 second during load rejection.
 For distribution application (and general purpose), the transformer has to be
designed by considering
 Over voltage up to 110% continuous at no load condition.
 Over voltage up to 105% continuous at full load condition.
 Core temperature limit at required maximum ambient temperature
(Design limit < 140oC at center, < 105oC at surface to avoid gassing).
 Sound power / sound pressure level.
 The local regulation for sound pressure/sound power limit.
 Installation location ; populated area, remote area.
24 > Title of presentation - Date - References 24
Core Saturation Capability For Load Rejection

145

140
135
Percent Excitation

130

125
120

115
110

105
0.1 1 10 100
Time - Minutes

25 > Title of presentation - Date - References 25


3. Inrush Current

26 > Title of presentation - Date - References 26


Definition

Inrush Current is the excitation current that will occur due


to the existence of magnetic flux remnant when the
transformer is first switched into the service.

The inrush current can have the peak value up to 5 times


the nominal current. The most unfavorable inrush
current arises when switching in take place at a zero
voltage transition.

Due to the magnitude of the inrush current, the over


current relay may interpret this current as the failure
current to open the circuit breaker on the system.

27 > Title of presentation - Date - References 27


Inrush Current Calculation

 Maximum Inrush Current can be estimated with the some


empirical factors referring to the core stacking method, gap
between core and the first excited winding, primary winding
connection, network & transformer impedance and transformer
core behavior. This is an important information to determine the
over current and differential relays setting point.
 The actual inrush current is difficult to be estimated as this will
be dependent to the existence of remanence flux due to
previous system cut out at certain voltage angle.
 Maximum inrush current estimation method;
 Empirical formula.
 Electromagnetic transient computer software;
 EMTP (Electro Magnetic Transient Program), CANADA.
 SLIM – electromagnetic function, AREVA

28 > Title of presentation - Date - References 28


Estimating Inrush Current

Empirical formula to calculate the peak of inrush


current is as followings;

S2.U
ωt – y) – e-(t-t0)/ττ.SinQ). K
Ipeak = Z . Sin(ω
t

Where;
K = Constanta value referring to the transformer connection
(Grounded STAR, DELTA) and other circumstantial.
U = Applied voltage (rms)
Zt = Transformer + network impedance.
y = Energization angle.
τ = Transformer time constant.
t = Core saturation time referring to maximum, remnant &
saturation induction behaviour.
Q = Angle function of core induction.
29 > Title of presentation - Date - References 29
Some Aspect Effecting Inrush Current
 Transformer number of phases and primary winding
connections;
 Single phase transformer and/or shell type has higher inrush
current than three phase transformer and/or core type.
 DELTA connection of primary winding three phase transformer
has lower inrush current than grounded STAR.
 Transformer capacity;
 Higher transformer MVA rating has lower ratio between inrush
current and primary nominal current, but longer decay time.
 Transformer core steel, core design and nominal induction;
 HiB core steel has lower inrush current than CRGO material.
 But lap joint has lower inrush current than Step lap joint.
 Lower impedance transformer normally has lower air core
reactance and then higher inrush current.

30 > Title of presentation - Date - References 30


B
Flux nominal + remnant

Φrem

time H
Flux nominal

Inrush current
Excitation
current
time

31 > Title of presentation - Date - References 31


4. Transformer Windings

32 > Title of presentation - Date - References 32


Winding

Type of winding;
Layer winding;
 Single layer.
 Multilayer.

Helical winding.
Disc winding.
 Plain/continuous disc
 Intershielded disc.
 Interleaved disc.

Multistart winding.
33 > Title of presentation - Date - References 33
Winding Conductor

Type of material conductor;


Electrolytic copper.
Aluminum.
Form of conductor;
Round wire.( for small distribution
transformer)
Rectangular wire.
Twin/Tripple/Quadrople conductor.
CTC (Continuous Transposed Cable).
Netting-CTC/Paper less CTC

34 > Title of presentation - Date - References 34


Winding – Areva terminology

Axial/Radial
Packing for
transposition

Directed Oil
Flow washers

External DOF
washer

Internal DOF
washer

Transposition
set

Segment
Spacer

35 > Title of presentation - Date - References 35


Disc Winding

PROTECTION FOR
SCISSOR EFFECT

Extra paper = 2 layers


overlapped of Clupack

36 > Title of presentation - Date - References 36


CTCs winding
Epoxy bonded

Try to use CTC with max. 55 strands per cable.


Epoxy bonded in low chip type is recommended for force capability.
Strand thickness 1.2 mm to 2.6 mm.
Strand width 5.0 mm to 12.5 mm.
Insulation increase of each strand = 0.10 PVA + 0.05 low chip epoxy.
Insulation increase of bundle, minimum 0.50 mm.
Minimum key spacer thickness for ZIG-ZAG cooling = 4.0 mm.

37 > Title of presentation - Date - References 37


Soft Cross Over for CTC – DISC winding

Missing turn block = 1


cable thick
Inside cross over
protection

Cross over block =


thick pressboard

38 > Title of presentation - Date - References 38


Heavy current helical winding

39 > Title of presentation - Date - References 39


Intershielded Disc Winding

Provide the best controllable high


frequency dielectric voltage distribution

40 > Title of presentation - Date - References 40


Intershield Disc Winding Technology Research

 In 2007 : To Tests Models ISDW With Few Turns/Disc With Results To Be


Used As Input For The Design Of A Full Size 800 kV UHVDC ISDW Prototype

 To Design With EDT&PD Team; To Build And To Test A Full Size 800 kV
UHVDC ISDW Prototype

41 > Title of presentation - Date - References 41


Intershielded Disc Winding

42 > Title of presentation - Date - References 42


5. Insulation and Cooling Medium

43 > Title of presentation - Date - References 43


Cooling Medium

INTERNAL COOLING MEDIUM


Besides the thermal absorption, the internal cooling
medium also functions as the insulation medium.
 Class A;
 Mineral oil (Inhibited or Un-inhibited oil).

 Class K;
 Silicon oil
 Synthetic ester
 Hi-Temp natural liquid (seeds).

44 > Title of presentation - Date - References 44


Oil Molecules

45 > Title of presentation - Date - References 45


Oil Specification

46 > Title of presentation - Date - References 46


Oil Finger Print

47 > Title of presentation - Date - References 47


Oil’s Aromatic Check (Sulphur Content and other)

48 > Title of presentation - Date - References 48


Future – Environmental Friendly Liquid
 Environmental liquid = Enviro-Temp FR3 by COOPER
 Inhibited oil = Nitro 10XT by NYNAS

Property – typical values Inhibited oil FR3

Antioxidant, phenols 0.08% per Wt n.a.

Oxidation stability by 120oC 500 hours continuous

Biodegradable in 21 days 25% 100%

Saturated moisture at 25oC 80 ppm 1200 ppm

Temp. rise for unity life time *) 60/65/78 K 80/110/130 K

Flash point 145oC 330oC

Pour point -57oC -18oC

49 > Title of presentation - Date - References 49


Natural ester dielectric behavior
Dielectric Strength versus Water Content
80

70
D 1816 Dielectric Breakdown (kV)

60

50

40

30

Envirotemp FR3 fluid


20
conventional transformer oil

10

0
0 100 200 300 400 500 600

Water Content (ppm)

50 > Title of presentation - Date - References 50


Eco-Design/vegetable oil transformer
History;
 2005: order for joint development with customers of vegetable oil transformers
 2006: oil characteristics review and prototype transformers design, manufacture and
test
 2007 Q1: commissioning and monitoring of 90MVA 132kV transformer in UK
 2007 : devel of PTR design rules book, oil specification , manufacturing and filling
process , maintenance rules and nominal parameters
 2007 : commercial agreement with oil supplier Cooper for local vegetable oil
distribution.

Achievement
 Environmentally friendly transformers and reactors
filled with vegetable oil
 Vegetable oil totally biodegradable , with higher fire point
than mineral oil (envirotempFR3 oil from COOPER)
 transformers and reactors up to 245kV, and rated power up
to 100 MVA (existing new references)
 Application for Higher ratings to be evaluated if potential
for joint development with customers

51 > Title of presentation - Date - References 51


6. Transformer Losses

52 > Title of presentation - Date - References 52


Power Transformer Losses

Losses is the active energy component


to be absorbed by the transformer and
associated component such as fan,
pump, control circuit. Mainly this losses
will become the heat energy.
Losses contain;
Core loss = No load loss.
Load loss
Auxiliary loss

53 > Title of presentation - Date - References 53


Core Loss

Core Loss = No Load Loss ; is the loss of the


energy when the transformer under no load
condition (the primary terminal is connected to
the power source, the secondary/tertiary etc are
open). This loss is expressed by Watt or kWatt.
Core loss contains;
 Hysteresis loss; The magnetic power that inherently
absorbed due to the magnetic behavior of the
transformer core material. This energy is required to re-
align the magnetic domain for the flux at certain time.
 Eddy-current loss; The loss of active power caused by
the circulating current as the result from the
perpendicular flux into the core plate with it’s resistive
component characteristic. Thinner plate will give lower
eddy-current loss of core material.

54 > Title of presentation - Date - References 54


Hysteresis Core Loss
Bmax [T]
Ph = kh.f.Bmaxn
kh= Hysteresis constant depend on the
core material (3x10-3 to 20x10-3)

n = Exponent varies from 0.5 to 2.3 δB


dependent on the core material

Hpeak [A/m]

55 > Title of presentation - Date - References 55


Eddy-Current core loss

Pe = ke.f2.t2.Bmax2
ke = Constant depends on the core grade, typical values = 200 to 1000
t = core plate thickness [m]
B

56 > Title of presentation - Date - References 56


Load Loss

The current flowing through the windings


of a loaded transformer will create loss
energy in the form of heat.
The load loss is normally expressed at
75oC or 85oC.
85oC shall use thermally upgraded paper

This load loss is containing


 DC losses = the dominant component loss is caused by
the product of current to the DC resistance of winding
conductor
 Stray losses = the loss is caused by the leakage
magnetic impinging on the winding conductor and other
internal conductive material inside the transformer.

57 > Title of presentation - Date - References 57


DC loss
1 2 3

DC losses = I12Rdc1 + I22 (Rdc2 + Rdc3)


Rdc = ρ . L/A

 I1, I2 = current flowing in winding 1,2,3 [A]


 Rdc = DC resistance of each winding. [Ω]
 ρ = winding conductor resistivity. [Ω
Ωm]]
 L = Length of winding conductor. [m]
 A = Winding conductor cross section. [m2]
58 > Title of presentation - Date - References 58
Winding Conductor Property

Propeties Unit Copper Aluminum

Conductivity % IACS 100 60.97

Resistivity@20oC ρ (Ω
Ω.m) 1.7241 x 10-8 2.8280 x 10-8

Temperature
K 235 225
reference

Specific mass Kg/m3 8890 2703

59 > Title of presentation - Date - References 59


Conductivity vs temperature

For Copper at temperature T1 and T2


ρ2 = ρ1 x (235 + T2) / (235 + T1)
Resistivity at 75oC = 2.1 x 10-8 Ωm.
DC loss at 75oC in Watt = 2.36 x 10-12.τ2.M
 τ = current density [A/m2]
 M = conductor mass [kg]
For Aluminum at temperature T1 and T2
ρ2 = ρ1 x (225 + T2) / (225 + T1)
Resistivity at 75oC = 3.46 x 10-8 Ωm.
DC loss at 75oC in Watt = 12.8 x 10-12.τ2.M
 τ = current density [A/m2]
 M = conductor mass [kg]

60 > Title of presentation - Date - References 60


Eddy Current Loss in AC system
 When the winding is AC (Alternating Current) loaded, the
leakage flux impinges on the winding conductors and as a
consequence eddy currents are generated in these
conductors. This eddy current will push the distributed
current on the skin area of conductor. This phenomena is
known as SKIN EFFECT.

Conductor

Flux line

AC current line
61 > Title of presentation - Date - References 61
Eddy loss distribution

The eddy loss distribution is not uniform


along the winding. Normally the eddy
losses at winding end is higher than at
winding middle.
It is important to control the eddy loss at
top end winding to avoid very high hot
spot gradient temperature.
Brad
B rad Brad

1 2

1 2
62 > Title of presentation - Date - References 62
Stray losses of inside metallic parts & tank

 Inside tank of a power transformer is containing a lot


number of leakage flux.
 The higher transformer impedance will result the bigger
number of leakage flux.
 Leakage flux impinging onto metallic structural parts and
tank wall + cover will contribute the additional load loss.
This loss is normally controlled between 5% to 15% of the
total load losses.
 This additional loss due to leakage flux is controlled by
the following methods;
 Magnetic shunt panel to collect the leakage flux.
 Copper or aluminum flux rejecter.
 A-magnetic metallic part.
 Splitting the wide plate width.

63 > Title of presentation - Date - References 63


Infra Red Thermal Investigation

Infra Red Thermal Check


To avoid local hot spot > 125oC

64 > Title of presentation - Date - References 64


7. Insulation Structure & Dielectric Withstand

65 > Title of presentation - Date - References 65


Dielectric Voltage Withstand Test
 International standard reference;
 SPLN
 IEC 60076 part 3.
 ANSI/IEEE C57.12.00 & C57.12.10
 Continuous over voltage up to 110% no load, 105% full load
condition.
 Applied voltage withstand = the over voltage withstand between
each winding to other part in the transformer for one minute.
 Induced voltage withstand = the over voltage withstand between
each turn and/or disc of each winding and the winding to earth for
few seconds dependent on the testing frequency 120 x fnetwork/ftesting
[seconds]. This over voltage may have magnitude up to twice of
nominal voltage.
 Transient over voltage withstand = the over voltage withstand due
to switching and /or lightning. The wave shape has duration up to
few microseconds with it’s instantaneous peak over voltage
withstand may have magnitude up to 3.5 times the nominal peak
voltage for

66 > Title of presentation - Date - References 66


IEC Standard Insulation Level

Highest voltage Power frequency Full wave impulse Minimum air clearance
(kV peak) (mm)
(kV r.m.s) (kV r.m.s)
7.2 20 60 90

12 28 75 110

17.5 38 95 170

24 50 125 210

36 70 170 280

72.5 140 325 630

115 185 450 830

123 230 550 900

170 275 650 1250

325 750 1450

245 395 950 1900 2250

300 460 1050 2300 2650

362 510 1175 2700 3100

67 > Title of presentation - Date - References 67


Voltage Withstand Criterium

No Flash over (puncture and creepage)


Partial Discharge under requirements;
Less than 100 pC at 110% voltage.
Less than 300 pC at 130% voltage.
Less than 500 pC at 150% voltage.

FREE PARTIAL DISCHARGE ;


 Less than 50 pC at 150% voltage.

68 > Title of presentation - Date - References 68


INSULATION Coordination

»The Radial and Axial stresses between windings


and to Earth have to be managed by an insulation
structure which considers the combined individual
stresses.
»This structure has to consider both electrical
requirements and thermal requirements for oil flow
»Ithas to consider the effects of voltage transients
and the problems of manufacture and processing
»Ithas to be economic using minimum clearances
and minimum of expensive components.

69 > Title of presentation - Date - References 69


Oil Strength Behavior

70 > Title of presentation - Date - References 70


Water Content in Paper
»0.5% dryness  PD inception voltage is 83% induced voltage.
»1.0% dryness  PD inception voltage is 41% induced volatge.

71 > Title of presentation - Date - References 71


Water Content Equilibrium

72 > Title of presentation - Date - References 72


Dryness of insulation vs voltage withstand
Water Content in paper shall be less than 0.5% (from 17% originally).
Oil breakdown shall be greater than 60 kVrms/2.5 mm (IEC) from 30 kV/2.5 mm.

73 > Title of presentation - Date - References 73


Transformer Active Part Insulation:

a. MINOR INSULATION : Insulation between individual


sections and pairs of discs in a winding or inter turn of
layer winding.
b. MAJOR INSULATION : Insulation between windings

c. END INSULATION : Insulation between windings and


the core.

d. LEAD INSULATION : Insulation on exit leads.

e. CLEAT BAR : Insulation on interconnecting leads

74 > Title of presentation - Date - References 74


Top End Insulation

Optimised number of angle rings

Standard Block
Stress Ring Profile thickness

Standard Oil Ducts

75 > Title of presentation - Date - References 75


Cleat bar clearances

A = Cylinder to Plane OR treat as


Tie Rod profile for analysis.
B = Cylinder to Plane.
C = Cylinder to plane.
D & E will affect calculation limits.
F = Point to Plane ?

76 > Title of presentation - Date - References 76


FEM Models

High Voltage Stress Detection

77 > Title of presentation - Date - References 77


Insulation Structures
Validation Criteria

 Peak Stress in paper coverings


 Peak Stress in Oil adjacent to covered electrodes
 Peak and Average Stress in Oil ducts
 Cumulative Stress in Oil
 Bulk Oil Volume Stresses
 Peak and Cumulative Creep Stress
 Failure Probability of small oil volumes at peak
stress

78 > Title of presentation - Date - References 78


608 series (4% grading):
Bulk oil stress critical path from HV winding to LV winding
100
|E|[kV/mm]

²
10

stress (absolute value)


cumulative stress
Strength gas saturated oil
Strength degassed oil

1
0 5 10 15 20 25 30 35 40 45 50
path [mm]

Stress in duct next to HV Stress Ring


79 > Title of presentation - Date - References 79
ACTIVE PART - clearances
Creep is an electrical failure
using a solid object as a path

Electrical
Creep = Y

80 > Title of presentation - Date - References 80


ACTIVE PART (coil erection cleat bar)
Tap changer
(or Tap switch)

HV Line Lead
T&D

Tap lead
connections

Tap lead Cable


connections Run/Channel

81
PTR Quality > Title of presentation - Date - References 81
Bus Bar Connection For High Current Lead Exit
82 > Title of presentation - Date - References 82
Tap Changer Connection
83 > Title of presentation - Date - References 83
Inside CT Connection Lead Exit = Ground Level

84 > Title of presentation - Date - References 84


Flash Over To Sharp Edge Of Metal Steel
Flash is the distance between two objects, using Oil or
Gas as a path (sharp edges, corners e.t.c. are high
risk) Consider the closest point is not always the
RISK!

Electrical
Clearance
checks

- FLASH

X
x = FLASH
DISTANCE
85 > Title of presentation - Date - References 85
PARTIAL DISCHARGES > 1000 nano Coulomb
A track path can display a “tree” shaped pattern

86 > Title of presentation - Date - References 86


CREEPAGE - FAILURES

Creep from
HV to tank
wall along
the support
Creep from
board
HV wdg to
LV leads
during
Impulse
tests

87 > Title of presentation - Date - References 87


FLASH OVER / BREAKDOWN - FAILURE

88 > Title of presentation - Date - References 88


8. Transformer Thermal Aspect

89 > Title of presentation - Date - References 89


Thermal Aspect To Control Ageing & Lifetime

90 > Title of presentation - Date - References 90


Transformer Life Time

Transformer life time is mostly determined by the life time of


winding conductor insulation paper.

Cellulose insulation paper is built of several chain of glucose


molecules. The number of glucose molecule in the cellulose
paper is known as DEGREE POLIMERIZATION.
 New insulation paper  Degree polymerization > 850.
 End life of insulation paper  Degree polymerization < 200.
 At DP < 200  paper will be brittle as it has the tensile strength
of HALF of new paper tensile strength.

THERMAL ASPECT has significantly contributed in the reducing


of glucose chains on paper.

91 > Title of presentation - Date - References 91


Glucose Molecule Of Cellulose Insulation

92 > Title of presentation - Date - References 92


HEAT Source

Total Active Losses in kiloWATT


»(A) I2R + Eddy losses (Max Loss > Minimum Tap)
»(B) Stray Losses (Steel Structure + Tank)
»(C) Core Losses
»(D) Sun Radiation

TOTAL Losses to be evacuated = A + B + C + D

93 > Title of presentation - Date - References 93


COOLING MEDIUM

 INTERNAL COOLING MEDIUM


The internal cooling medium has function also as internal
insulation medium.
 Mineral oil (Inhibited or Un-inhibited oil)
 Silicon oil
 Synthetic ester
 Hi-Temp natural liquid (seeds).

 EXTERNAL COOLING MEDIUM


 Air
 Water

94 > Title of presentation - Date - References 94


Directed Cooling

»Convection

»Conduction

»Fan

95 > Title of presentation - Date - References 95


Temperature Identification

1.3 x gradient
core

cooler
gradient
winding

Bottom oil

Mean oil

Top oil

Average winding

Hot spot
96 > Title of presentation - Date - References 96
Temperature Rise and Driven Factors
 Temperature Rise for Class A (IEC / ANSI C57);
 Top oil rise ; = 60K / 55 K or 65 K.
 Average oil rise ; = 65 K / 55 K or 65 K (By resistance method)
 Hot spot rise ; = 78 K / 65K or 80K.
 Site elevation height;
 The standard elevation height is 1000 m above sea level.
 Climatic temperature behaviors;
 Yearly average ambient temperature (IEC std = 20oC) 
transformer life time.
 Hot monthly average ambient temperature (IEC std = 30oC)
 Maximum ambient temperature (IEC std = 40oC)  transformer
loading capability

Insulation class A E B F H

Operating temperature 105oC 120oC 125oC 145oC 220oC

97 > Title of presentation - Date - References 97


Class A Temperature Design Limits

*) suitable for Maximum temperature design limit [oC]


thermally up graded
paper insulation Oil Winding Metal part Consequences

Annual average 80 98 / 110 * 110 Life time

Cyclic load 105 120 / 130 * 130 Gas generation

Emergency 115 140 140 Gas generation

Short emergency 115 160 160 Gas generation

Thermal short circuit


Conductor
1.Copper 115 250 160
softening
2.Aluminum 115 200 160

98 > Title of presentation - Date - References 98


Cooling Method – Oil Immersed

Oil circulation External cooling IEC 60076 ANSI C57 BS 171

Natural flow Air Natural flow ONAN OA ON

Natural flow Air Forced flow ONAF FA OB

Forced/Blasted Air Natural flow OFAN *) *)

Forced/Blasted Air Forced flow OFAF FOA OFB

Forced & Directed Air Forced flow ODAF FOA OFB

Forced & Directed Water Forced flow OF(D)WF FOW OFW

*) not specifically indicated

99 > Title of presentation - Date - References 99


Rules Reference List
Material Properties
Thermal Conductivities of Solid Dielectric Materials
Material Thermal Conductivity (W/ m/ K)
Paper 0.17
Pressboard 0.21
Nomex 0.125
PVA Enamel 0.16

Thermal Conductivities of the Core


Direction Thermal Conductivity (W/ m/ K)
In the plane of the laminations 21
Perpendicular to the plane of the laminations 3.3

Thermodynamic Properties of Cooling Liquids


Property (units) Oil Ester Synthetic Silicone
Oil
Cubic Expansivity (/ K) 0.000795 0.000750 0.000700 0.001040
3
Density (kg/ m ) 849 931 810 912
Dynamic Viscosity (kg/ m/ s) 0.00399 0.009589 0.01500 0.02052
Specific Heat Capacity (J/ kg/ K) 2080 2216 2400 1525
Thermal Conductivity (W/ m/ K) 0.1272 0.1535 0.1000 0.1500

100 > Title of presentation - Date - References 100


Directed Oil Flow

 Examples of washer applications (External):

Duct maintained with sticks

Duct maintained with segments

101 > Title of presentation - Date - References 101


PRE-ASSEMBLY - directed oil flow
Directed Oil Flow arrangements may not be present in TX designs, dependant upon
local Design influences

Bottom Oil
Annulus
(Ring)

Directed Oil
Flow entry point

Check that the Oil path is


clear & free from leaks

102 > Title of presentation - Date - References 102


Future Material Insulation

103 > Title of presentation - Date - References 103


Alternative Insulation - Hybrid Design

CALENDERED
KRAFT BOARD Angle Rings
and Caps
CALENDERED
KRAFT BOARD Support Washers

NOMEX® T-993 Static Rings


Creped NOMEX®
CALENDERED Cylinders
KRAFT BOARD
Conductor
NOMEX® T-410 Insulation

Axial & Radial


NOMEX® T-994 Spacers

PRECOMPRESSED Clamping Rings, Blocks


KRAFT BOARD

104 > Title of presentation - Date - References 104


Transformer life Time

105 > Title of presentation - Date - References 105


106 > Title of presentation - Date - References 106
107 > Title of presentation - Date - References 107
108 > Title of presentation - Date - References 108
9. Short Circuit Analysis

109 > Title of presentation - Date - References 109


Definition
Short circuit current is the current flowing thru the transformer
part at the condition that the secondary side of power flowing
from primary to secondary has been short circuited.
Since the power transformer is the reactive apparatus, the short
circuit current will be limited by this transformer impedance
inherently.
There are two kind of short circuit analysis;
Symmetrical short circuit analysis such as three phases short
circuit.
Asymmetrical short circuit such as single phase to ground or
two phases short circuit and/or to ground.
Symmetrical short circuit current will be the biggest short circuit
current for all loaded winding with all the winding terminals are
brought out.
For unloaded winding such as stabilizing winding, the single phase
short circuit as well as the two phases short circuit shall be
analyzed.

110 > Title of presentation - Date - References 110


Short Circuit Withstand

A). Thermal capability.


The transformer conductor shall be designed to limit the
produced heat due to short circuit below the temperature
where the conductor material will start to loose it’s
designed tensile strength for certain period of time. This
clearance time will be used as the protection coordination
reference.
1. Thermal limit for Copper conductor  250 oC.
2. Thermal limit for Aluminum conductor  200 oC.
B). Dynamic capability.
Each part inside the power transformer has to be
supported and clamped sufficiently to anticipate the
forces happen due to the result of the peak of short
circuit current and the leakage induction.

111 > Title of presentation - Date - References 111


IEC 60076 – 5 ; Minimum Short Circuit Impedances

112 > Title of presentation - Date - References 112


Oscillogram Showing The SC Current and Forces

113 > Title of presentation - Date - References 113


Short Circuit Current
Ipeak = S2 x Iccrms
  x Πr
−  arctan   + 
  r  2 x x
DC Offset K = 1 + e × sin arctan
r
x r

U Icc

Clearance time = 3 seconds

114 > Title of presentation - Date - References 114


Short Circuit -Thermal Withstand

For Copper Conductor, Θ1 shall be less than 250oC


2 x ( Θ0 + 235)
Θ1 = Θ0 +
106000
-1
J2 x t

For Aluminum Conductor, Θ1 shall be less than 200oC


2 x ( Θ0 + 225)
Θ1 = Θ0 +
45700
-1
J2 xt

Θo = Initial temperature in oC
Θ1 = Average winding temperature at certain time in oC
J = RMS short circuit current density in A/m2
t = Clearance time in second, max. 10 seconds
115 > Title of presentation - Date - References 115
Short Circuit - Dynamic Withstand

A moving charge q, at the speed V, in a magnetic field B,


is subject to a force F according to LAPLACE' s law

q V
r r r
F = qV ∧ B B
F

116 > Title of presentation - Date - References 116


Axial & Radial Stresses

 Axial Stresses come from radial component of the


leakage field. This axial stresses can be minimized by an
adequate balancing of the magneto motive forces on the
whole height of the winding.
 The clamping device through flitch plate, tie rod,
clamping beam are pre-loaded with the bigger force than
axial short circuit force to anticipate any movement and
deformation due dynamic short circuit force.
 Radial Stresses come from axial component of the
leakage field. This type of force can not be minimized as
this is directly dependent on the magneto motive force
of inner and outer side windings.
 The concentrically winding shape is the best geometry
to resist the radial stresses.
 The inherently conductor tensile/compressive strength
shall be higher than the available short circuit forces.
Sometime the reinforced material (e.g. CPR) is required.

117 > Title of presentation - Date - References 117


B
RADIAL FORCES I I
Frad Frad
mmf
F = I dl x B
core

AXIAL FORCES I I

Fax Fax

118 > Title of presentation - Date - References 118


Mean Hoop Stress

dl
α
p σS σS
Leakage/ flux Rav α X
e
e
2B I

B F
Y
Rav

119 > Title of presentation - Date - References 119


Hoop Stresses Of Multilayers

 leakage field in the middle of the layer

 J −1 ni Ii 12 nJ I J 
B = µ0 µr  ∑ + 
 i Hi HJ 
B W1 W2 Wn

 Hi = electrical height of the layer k F F


F
F H
F
 Electromagnetic pressure F

R1 R2

B2

r r r R2
p=I ∧B

120 > Title of presentation - Date - References 120


Self Supporting / Counter Pressure

 Layer type winding: self supporting reaction equivalent


counterpressure
with the thin cylinder hypothesis (RJ>>eJ)

PJ .RJ
σ=
eJ
Hooke’s law ⇒ σ = E.I = E.

pJ PJ
E= Young modulus of material

∆(2.Π.RJ ) ∆RJ
as
i= =
2.Π.RJ RJ
Internal counterpressure ∆R J
RJ PJ = eJ .E.
RJ2
∆RJ

121 > Title of presentation - Date - References 121


Bending Stress Between Supports

 Layer type winding : Bending stress ; reaction of support

dbs
Ft (
FtJ = pJ RJ − FnJ )
2RJ
d bs
+ or
RJ
dMf
0 - x FtJ = −
dx

-Ft
and Hook law : EIy’’=-Mf
E : Young modulus
I : inertia
Mf : bending torque

122 > Title of presentation - Date - References 122


Buckling Stress

123 > Title of presentation - Date - References 123


Axial Forces

124 > Title of presentation - Date - References 124


Tilting Stress

125 > Title of presentation - Date - References 125


Compressive Stress On Radial Spacer

e1 e2 en

Swidth
126 > Title of presentation - Date - References 126
Shearing Stress on CTC

 Epoxy cable : shearing stress on epoxy

F
τ

with epoxy
without epoxy

Epoxy avoid any relative movement from one strand to another

127 > Title of presentation - Date - References 127


Clamping Forces

 Clamping forces : reduction of number of elements

F4,0 F3,1 = F4,0


F2,n = F2,n-1
+ F3,n-1
F3,0 F2,1 = F3,0

F2,0
F1,1 = F1,0 F1,n = F1,n-1
+ F2,0
F1,0

initial step 1 step n


nb of elements : 4 nb of elements : 3 nb of elements : 2

128 > Title of presentation - Date - References 128


Clamping Structure

 Clamping structure reactions


if F2,n > F1,n if F1,n > F2,n
Rt= -F2,n Rt= 0 Rt= -(F1,n + F2,n ) Rt = 0 Rt= -(F1,n -F2,n )

F2,n F2,n F2,n

F2,n F2,n

F1,n F1,n
F1,n F1,n F1,n

Rb = -F1,n Rb = -(F1,n + F2,n ) Rb = 0 Rb= -(F2,n -F1,n ) Rb = 0

Clamping forces ≥ Σ of reactions on each layer

129 > Title of presentation - Date - References 129


Axial Clamping System

Clamping the winding assembly with pre-compressed load >


the axial force per phase & active part weight/3

130 > Title of presentation - Date - References 130


Maximum Allowed Forces And Stresses

131 > Title of presentation - Date - References 131


10. Engineering

132 > Title of presentation - Date - References 132


Mechanical Design

kV

1200

H-Range
220

N-Range
110

E-Range

25 75 2500 MVA

Mechanical Design  standardize the best practice

133 > Title of presentation - Date - References 133


Transformer Tank

TOP BEAM

TOP END
WEDGE
 E RANGE

TIE-ROD
 Maximum Voltage ≤
170 kV
CRADLE

 Weight of core steel


sheet, max 20 Ton
 Center-center distance
max 1350 mm

UPPER
CLAMPRINGS

LOWER
CLAMPRINGS

134 > Title of presentation - Date - References 134


Transformer Tank

TOP BEAM

 N RANGE
FLITCH PLATE
 Maximum Voltage ≤ 275
kV
UPPER
CLAMPRINGS
 Weight of core steel
sheet, max 40 Ton
LOWER
CLAMPRINGS  Weight of Part active max
80 Ton
 Center-center distance
max 1600 mm

YOKE
SUPPORT

135 > Title of presentation - Date - References 135


Engineering Tools

 Full integrated engineering program :


 TARGET (Transformer Architecture Generating Tools)
 As Main Program to design main variable of transformer part
active, optimation tools for choosing design vs Price level
 Link (export/import) to verification tools

136 > Title of presentation - Date - References 136


Vérification Tools

 Verification tools :
 Overload  capability of overloaded
 Invodat  capacitance network and voltage distribution
 Corecalc  Core losses and temp
 Annuli  Force oil entry evaluation
 ASC  Detailed core Design Program
 Choc  Transient impulse voltage Analysis
 Clearstress  Voltage Stress Evaluation
 DOF  Direct Oil Flow Evaluation
 Fluxshunt  Dimensional analysis for flux within tank shunt
 Gradcalc  Winding Gradient Evaluation
 Radinsulation  Lead clearances, thermal performances
 RothFEM  Forces, stresses, impedances and flux ploting

137 > Title of presentation - Date - References 137


Vérification Analyses

TRANSFORMER LEAKAGE
FLUX (GRID-FLUX LINES)

U Example of impulse wave 1.2µs /


50µs
50 µs

Breaking time

100%
Full wave

50%

Wave chopped on the tail


0%
times in µs
1.2 µs Falling time
Undershoot
Voltage

30%

138 > Title of presentation - Date - References 138


11. Manufacturing Process

139 > Title of presentation - Date - References 139


Manufacturing Process

Core cutting Core stacking Winding Insulation

Active part
assembly

Drying

Repack

Assembly

Testing

140 > Title of presentation - Date - References 140


Core Stacking

141 > Title of presentation - Date - References 141


Winding Manufacturing

142 > Title of presentation - Date - References 142


Check Cross Over Of Winding

143 > Title of presentation - Date - References 143


Connection & Insulation

144 > Title of presentation - Date - References 144


Active Part Tanking After Repack

145 > Title of presentation - Date - References 145


146 > Title of presentation - Date - References 146
Single Phase Reactor: New Design

147 > Title of presentation - Date - References 147


Single Phase Autotransformer
240 / 3 MVA 250 / 150 kV
148 > Title of presentation - Date - References 148
Yoke Shield for reactor

149 > Title of presentation - Date - References 149


12. Accessories, Protection & Control

150 > Title of presentation - Date - References 150


Protection and Additional Accessories

A. PROTECTION DEVICE
- Protective Relay (Bucholz)
Function : to trip out the trafo if there is a
release of gas arising from the
decomposition of the solid and liquid
insulating material due to the action of
heat or electric arcing.
Principal Of Operation
- During normal operation, the relay is
completely filled with oil.
- When gas forms inside the trans-
former, it tends to flow towards the
conservator
- it accumulated progressively inside the
relay there by LOWERING the oil level.
- If gas continues to form, the oil level will A. Upper Float
affect the lower float B and relative B. Lower Flat
switch which is connected to the circuit
and causes disconnection of the
transformer power supply.

151 > Title of presentation - Date - References 151


Protection and Additional Accessories

- Protective Relay (Bucholz)

152 > Title of presentation - Date - References 152


Protection and Additional Accessories

- RS 2001 relay for OLTC


Function :
to protect tap changer and transformer from
1. Flap Valve
any damage if a defect arises in the tap
2. Permanent Magnet
changer . This relay operates to put the trafo
off circuit 3. Reed Switch
Principal Operation:
It responds only if oil flows occur from tap
changer head to the oil conservator

153 > Title of presentation - Date - References 153


Protection and Additional Accessories

- Winding Temperature Indicator

Function :
to measure the winding
temperature
Principal Of Operation:
measure the winding
temperature by means of a
special bulb surrounded by
heating resistance through
which passes a current
proportional to the current
passing through the
9. Microsw. Setting
transformer winding subject to 1. Case Pointer
a given load and immersed in 2. Locking Glass 10. Junction Box
Ring
insulating oil at temperature 11.Glass or
3. Fixing Rear polycarbo-nate
Flange window
4. Air Hole 12. Potentiometer for
5. Capillary Output heating resistance
adjustment
6. Dial
7.Microsw. Setting
Dial
8. Max. indicating
pointer

154 > Title of presentation - Date - References 154


Protection and Additional Accessories

- Oil Temperature Indicator

1. Case 8. Max. indicating pointer


2. Locking Glass Ring 9. Microsw. Setting
Function : Pointer
3. Fixing Rear Flange
to measure the oil temperature inside power 10. Junction Box
4. Air Hole
transformer tank 5. Capillary Output
11.Glass or polycarbo-
nate window
6. Dial
7.Microsw. Setting Dial

155 > Title of presentation - Date - References 155


Protection and Additional Accessories
- Oil Level Indicator
Function :
to measure the level reached by the oil in a transformer
conservator
Principal Of Operation
- The changing oil level in the conservator is detected by
a float attached to a suitably – long rod which is
connected to the magnetic transmission axle
- A permanent magnet, whose flux passes through
attachment flange 2.0, is coupled to the pin turned by the
float-carrying arm. The aforementioned parts fitted to
flange 2.0 are placed inside the conservator through a
hole made in a suitable position which is perfectly
sealed by the flange it self.
- A second permanent magnet inside instrument gauge
1.0, dragged round by the first magnet, moves a second
shaft on which the optical level- indicator pointer and a
cam are fitted. The cam trips the microswitch (Es) which
electrically indicate that the oil has reached a certain
level.

156 > Title of presentation - Date - References 156


Protection and Additional Accessories

- Pressure Relief Device

Function :
an equipment to relieve large volumes of gas or
insulating fluid rapidly when the pressure inside a
transformer reaches a pre-determined limit.

157 > Title of presentation - Date - References 157


Protection and Additional Accessories

B. ACCESSORIES
- Oil Sampling Valve - Butterfly Valve

F=close position
O=open position

158 > Title of presentation - Date - References 158


Automatic Voltage Regulator - KVGC

159 > Title of presentation - Date - References 159


Fibre Optic Temperature monitor
 1 - 8 Channels
 Cooling/Alarms/Protection
 -30°C to +200°C
 Programmable relays
 Analog output
 0–1ma or 4–20ma
 Ring Lug Terminals
 Memory Retention
 90 days at 1/minute – factory set
 Power Input
 Universal AC/DC
 Self Diagnostics
 Applications
 Small to Large Power Transformers
 RS 232 Port
 Options for RS 485 and Protocol Converter

160 > Title of presentation - Date - References 160


Protection and Additional Accessories

- Screw and Globe Type Valve

161 > Title of presentation - Date - References 161


13. Final Acceptance Test

162 > Title of presentation - Date - References 162


Definition

 Final Acceptance Test is the crucial moment for a


transformer , verifying the manufactured transformer has
met the guaranteed performances and is ready to
function under specified circumstance.
 Purpose of testing is to ensure that the transformer has
fulfilled the quality performance and to validate the
specific contractual requirements.
 Validate the design
 Validate the manufacturing process.
 Compare the measurements with the technical data
specification.
 Establish a finger print of the transformer, useful for
comparison with the future/on site measurement such as
SFRA, capacitance, insulation resistance etc.

163 > Title of presentation - Date - References 163


Testing Procedures

The testing procedures are divided in three parts as


followings;
1. Routine Tests; These tests are subjected to be
performed on each individual transformer prior to
delivery.
2. Type Tests (IEC) / Design Tests (ANSI/IEEE);
These kind of tests are performed on one
transformer representing the other transformers
with the similar design.
3. Special Tests (IEC) / Other Tests (ANSI/IEEE);
These tests are non-mandatory tests and have to
be agreed between the manufacturer and the
purchaser.
164 > Title of presentation - Date - References 164
Routine Tests

Routine Test is containing the following tests;


1. Insulation resistance measurement.
2. The electric strength of the transformer liquid.
3. Winding resistance measurement.
4. Voltage ratio & polarity/vector group checks.
5. Load loss & impedance measurement.
6. No load loss & no load current measurement.
7. Dielectric – routine tests (induced & applied tests)
8. Tap changer test (OLTC and/or DETC).
9. Functional tests on control devices, CT ratio checks.

165 > Title of presentation - Date - References 165


Type/Design & Special/Other Tests

Type tests (IEC) /Design tests (ANSI/IEEE);


1. Temperature rise test.
2. Dielectric – type test (lightning impulse test)

Special tests (IEC) /Other tests (ANSI/IEEE);


1. Dielectric – special test (PD measurement)
2. Zero sequence impedance measurement.
3. Sound level measurement.
4. Capacitance and power factor.
5. Harmonic measurement of no load condition.
6. Fans and/or oil pump power consumption measurement.
7. SFRA (Swept Frequency Response Analysis).
8. DGA (Dissolved Gas Analysis) measurement.
9. Tank destructive test.
10. Transformer short circuit.

166 > Title of presentation - Date - References 166


Insulation Resistance Measurement

 This insulation is normally known as MEGGER insulation


test. This measures the DC insulation value containing the
oil or other transformer liquid, cellulose pressboard,
insulation paper and other insulation material between
windings and winding to core.
 The power supply is DC voltage source 1000 VDC up to
5000 VDC. Due to capacitance of different insulation
medium, the insulation value of combined materials will
take some times prior to get the stabilized result.
 The acceptance criterium ;
 Interwinding insulation = minimum 500 Ohm.
 Winding to core = minimum 200 Ohm.
 The wet insulation material may result very low insulation
resistance.

167 > Title of presentation - Date - References 167


Winding DC Resistance Measurement

 Winding DC resistance is measured thru two bushings for


each winding. The measurement is performed with bridge
connection of VOLT – Ampere meters or high accuracy
digital multimeter.
 Care shall be taken for the effect of self-inductance. Hence
the oil temperature shall be recorded.
 Anomalous result can detect bad connection joint within
the winding, inter winding or winding to bottom terminal of
bushing.
Rstd

V2

Rx
DC power

V1
supply

Rx = Rstd x V1/V2
168 > Title of presentation - Date - References 168
Load loss & impedance measurement
This test will measure the load loss and impedance referring
to the rated current at some of tap changer positions.
The AC 3 phases supply is normally injected on the HV side
of the transformer. The power supply voltage is increased
until the nominal current is reached. The voltage giving
the rated current is the impedance voltage. This is
normally expressed as percentage of the rated voltage at
particular tap changer position.
If the rated current can not be reached due to testing
limitation or other reasons, the following correction factor
will be used. The minimum test current is 50% rated
current
Pextrapolation = Ptest x (Irated : Itest)2
During test, the transformer oil has to measured to correct
the copper temperature as ambient temperature reference.
The measured resistance has to be extrapolated to 75oC
(85oC for ANSI/IEEE with 65oC rise).

169 > Title of presentation - Date - References 169


Correction factor for load loss due to temperature

The load loss [Pcu/Pal] is containing I2Rdc + stray loss and


guaranteed at 75oC for IEC standard transformer and
ANSI/IEEE standard transformer with 55oC temperature rise.
For ANSI/IEEE standard transformer with 65oC temperature
rise, the temperature reference for load loss is 85oC.
The DC resistance & load loss are measured at testing
laboratory ambient temperature (Θ Θambient). For in case the oil
temperature during load loss measurement has exceeded
3oC different with the actual ambient temperature, this oil
temperature shall be used for measurement ambient
temperature.

[235 + 75 (or 85)] [225 + 75 (or 85)]


KCU = KAL =
[235 + Θambient] [225 + Θambient]

Pcu(al) 75oC (or 85oC) = I2Rdc x K + Stray loss / K


170 > Title of presentation - Date - References 170
No Load loss and Current

 The 3 phase, AC, power supply at 90%, 100%, 110% of


rated voltage is connected to the LV winding to induced
the nominal voltage on HV as well as the other winding.
The total (3 phases) losses & injected current to reach
the rated voltage are known as no load loss, no loda
current respectively.

 Correction factor for no load losses;

U’ - U
P0 = Pm x ( 1 + )
U’
P0 = Corrected no load loss
Pm = Measured no load loss
U’ = Mean Voltage
U = RMS voltage

171 > Title of presentation - Date - References 171


Applied Over Voltage Test

Purpose ; to check the voltage withstand between the tested


winding to other separated windings (not in series/parallel
connection), core, steel structure and tank.
The test is made of single phase AC voltage at rated frequency
for 60 seconds duration applied to one winding while other
windings & core are grounded.
The test is successful if no collapse of the test voltage occurs.

VHVN

172 > Title of presentation - Date - References 172


Induced Over Voltage Withstand Test
 Purpose; To ensure that the insulation between turns, between
discs, inter windings, winding to core/steel structure, cleat bars
withstand the over voltage switching referring to guaranteed
power frequency insulation class.
 Two type of induced test;
 Short duration Over Voltage Test (ACSD);
 AC single phases power supply for STAR connection non-uniform
insulation. For ANSI/IEEE standard and some customer requirements
are requiring the three phases power supply for STAR connection
non-uniform insulation.
 AC three phase power supply for WYE or DELTA connection of
uniform insulation.

rated frequency
Time (seconds) = x 120 , but no less than 15 seconds
test frequency

 Long duration Over Voltage Test (ACLD); Over voltage up to 130%


or 150% Um for 30 minutes with partial discharge measurement.
173 > Title of presentation - Date - References 173
Time Duration For ACSD & ACLD Induced Test

U1
tinduced
U2

1.1Um 5 min 5 min


5 min 5 min

ACSD U1 = induced voltage


U2 = 1.3 Um for < 300 pC
= 1.5 Um for < 500 pC
1.1Um < 100 pC
U1 For phase to earth Um : S3
tinduced
U2

1.1Um 5 min 30 min


5 min 5 min

ACLD
174 > Title of presentation - Date - References 174
Partial Discharge Measurement
Partial Discharge Measurement is measuring the small discharge
activity inside as well as outside around the transformer prior to
flash over occurrence. This measurement is a good tool to ensure
the transformer quality.
• Corona discharges occurs due to the sharp edge electrode.
• Surface discharges (creepage) occurs due to overstress component
parallel to the dielectric medium surface.
• Internal discharges occurs due to the non-homogenous dielectric
medium.
• Electric trees due to the particle or cavity in the solid insulation.
• Floating discharging occurs due to badly grounded component.
• Contact noise occur in case bad contact terminal.

175 > Title of presentation - Date - References 175


Single Phase Induced Voltage Vectorial

HV = WYE
non-uniform

U1

2/3 UInduced
LV = DELTA
UInduced

v2 = 1/2u2 N
Usupply u2
1/3 UInduced
1 phase w2 = 1/2u2

V1 & W1

176 > Title of presentation - Date - References 176


Three Phases Induced Voltage Vectorial
HV = WYE
uniform

U1

LV = DELTA
u2
UInduced :S3 ed
u c
nd
UI

w2 v2 N

Usupply
3 phase

W1 V1

177 > Title of presentation - Date - References 177


Temperature Rise Test

 Purpose : to check the temperature rises (top oil, average


winding & hot spot) do not exceed the guaranteed temperature
rises.
 The test can be performed by BACK TO BACK test or SHORT
CIRCUIT methods. The short circuit method is mostly used for
this temperature rise test.
 In the short circuit method, all three phases low voltage
windings are short circuited to generated the total losses as
well as the current, Principally the test is performed by
supplying the current to provide the total losses (no load + load
losses) for oil temperature check and then to provide the rated
current for winding temperature check.
 Since the oil time constant is very long (it can take several
hours) while the conductor time constant is practically only few
minutes, the injected current for total losses is performed first
to get stabilized oil temperature then followed by reduced
current to rated current to get winding temperature at rated
capacity one hour prior to shut down.

178 > Title of presentation - Date - References 178


DC Resistance For Temperature Analysis
 Oil temperature can be detected by direct measurement
referring to oil temperature indicator.
 Winding temperature at rated capacity is calculated by
comparing the DC resistance value at cold condition
with known ambient temperature and the DC resistance
value at rated current just prior to shut down.
 The transformer has to be cleared for any capacitive
charge before taking the hot DC resistance measurement
by using charging stick. The charging time has to be
kept as short as possible to keep measurement
accuracy, but this period may need several minutes.
 The hot DC resistance is extrapolated from several
measured DC resistance values after shut down and
cleared charging.
 If there is tap changer with several tap positions, the tap
position with highest load loss is taken as reference for
temperature analysis.

179 > Title of presentation - Date - References 179


Some Of Equations For Temperature Rise Analysis
1. Power Supply is provided on HV tap pos. with highest load loss.

(Pload loss + Pno load)


Iinjected = Irated x Pload loss

Iinjected
Vinjected = Vrated x Z(%) x
Irated

2. Top Oil Rise and Average Oil Rise at Rated Capacity


x
(Pload loss + Pno load)
DToil = (max. {Tcover, ,Ttop rad’} – Tamb) x
Pload loss

x
(Pload loss + Pno load)
DAOT = ½ x (Ttop rad + Tbot rad) – Tamb) x
Pload loss

180 > Title of presentation - Date - References 180


Some Of Equations For Temperature Rise Analysis

3. Winding Temperature Gradient at Rated Current.

y
R2 Irated
GRCU = x (234.5 + T1) – (234.5 + T2) – DAOT x
R1 Iinject

y
R2 Irated
GRAL = x (228.1 + T1) – (228.1 + T2) – DAOT x
R1 Iinject

4. Average Winding Temperature Rise and Hot Spot Rise.

DTCU = DAOT + GRCU DTAL = DAOT+ GRAL

HSCU = DToil + HSF x GRCU HSAL = DToil+ HSF x GRAL

181 > Title of presentation - Date - References 181


Some Of Equations For Temperature Rise Analysis
Definitions;
1. Iinjected = Injected current [A]
2. Irated = Rated current at stated tap [A]
3. Vinjected = Testing Voltage [kV]
4. Pload loss = Maximum load loss [kW]
5. Pno load loss =Measured no load loss [kW]
6. T1, T2 = Ambient temperature at condition 1,2 respect.[oC]
7. Tcover = Oil temperature on top cover [oC]
8. Ttop rad = Oil temperature on top radiator [oC]
9. Tbot rad = Oil temperature on bottom radiator [oC]
10. DToil = Top oil temperature rise [K]
11. DAOT = Mean oil temperature rise [K]
12. DT = Average winding temperature rise [K]
13. GR = Winding gradient temperature [K]
14. x = Exponent for oil temperature due to losses.
 0.8 for ON cooling of < 2500 kVA.
 0.9 for ON cooling
 1.0 for OF or OD cooling
15. Y = Exponent for winding gradient due to current.
 1.6 for ON or OF cooling
 2.0 for OD cooling

182 > Title of presentation - Date - References 182


Lightning Impulse Tests

 Purpose ; To check the transformer capability against


the fronted over voltage caused by atmospheric
discharge with time peak between 0.1 ms to 20 ms and
tail duration of less than 300 ms.
 Considering the transformer as a complex network of
RLC component, the distribution of such very high
frequency over voltage such as lightning impulse will be
highly influenced by the capacitive component of
transformer.
 The lightning impulse test is performed by comparing
the result of 100% impulse test against the 50% and/or
75% impulse test result. If there is failure, the voltage
wave form as well as the current wave form will have
different shape as the wave of reduced level.

183 > Title of presentation - Date - References 183


Full Wave Impulse
100%

50%

front time tail time

Front time = 1.2 ms + 30%


Tail time = 20 ms + 20%
Peak value + 3%
184 > Title of presentation - Date - References 184
Voltage Wave Current Wave

50% impulse

100% impulse

185 > Title of presentation - Date - References 185


14. Technology Application

186 > Title of presentation - Date - References 186


Single Phase Solution

187 > Title of presentation - Date - References 187


Single Phase Reactor: Original Design

188 > Title of presentation - Date - References 188


Less Maintenance

189 > Title of presentation - Date - References 189


ATT expérience in Industrial Transformers
 Electrolysis Industry => Rectifier Transformers
(Aluminium, Zinc, Copper, Chlorine)

 Chemical, Oil&Gas Industry => Converter Transformers

 Steel Industry => Electrical Arc Furnace


(EAF)Transformers

190 > Title of presentation - Date - References 190


Furnace transformer on UTR

SLN LE-NICKEL
3 x 1 PHASE 33.3 MVA
50 Hz, 63 Kv / 300 ~ 1800 Volt
OLTC ± 16 x 750 Volt
ODWF

191 > Title of presentation - Date - References 191


192 > Title of presentation - Date - References 192

Potrebbero piacerti anche