Thermal Overload Relay
CONSTRUCTION
PRINCIPLE OF OPERATION
The heating elements in the main circuit heat the bimetal tripping elements
corresponding to the motor load current. The heating elements are calibrated
such that the set trip point is achieved in accordance with the standards. By means
of trip bar, the movement / deflection of the bimetal is transmitted to plunger
which in turns operates the trip mechanism and thus the contacts are separated.
The trip point can be easily set on a scale in accordance with the nominal motor
rated current.
Bimetal elements for compensating the trip point in case of different ambient
temperature is fitted on the trip lever. Buttons are used for testing the circuit to
be protected, for resetting by hand and for conversion from manual to auto reset
mode.
DIFFERENTIAL MECHANISM
The relay operates on the differential system of protection provided by the double
slide mechanism. Under single phasing and unbalanced voltage conditions, the two
slides of the relay undergo differential deflection. One slide senses the movement
of the bimetal that has deflected the maximum, while the other senses the minimum
def lection.
The slides are linked in such a way that the difference in movements of the two
slides is amplified for actuation of the trip lever. This leads to accelerated tripping
under single phasing.
INTERNAL VIEW
Thermal Overload Relay
TECHNICAL INFORMATION
Weight
Current Range
Direct Version 0.16A – 80A
CT Version 24A – 400A Type (kgs) Type (kgs)
Auxiliary Circuit
Insulation Voltage 750V
Thermal Rating 10A
Contact Rating (AC 15 / DC 15)
220 AC 2A
380/415V AC 1.5 A
220V DC 1A
TRM 23 / 24 TRM 22 / 75
Thermal Overload Relay
RELAY SELECTION CHART
DOL STARTING
φ Motor Rating
3φ Approx. Full Overload Relay/CTR Backup
at 415V 50Hz. Load Current Range fuse rating
HP KW Amp. Amp. Amp.
0.75 0.52 1.6 1.0-1.6 4
1 0.75 2.0 1.7-2.5 6
2 1.5 3.5 3.0-4.5 10
3 2.2 5.0 4.5-7.0 16
5 3.7 7.5 6.5-10 20
7.5 5.5 11.0 10-15 25
10 7.5 14.0 13-19.5 25
15.0 11.0 21.0 15-22 50
20.0 15.0 28.0 24-34 50
25.0 18.5 35.0 26-40 63
30.0 22.0 40.0 34-51 80
40.0 30.0 55.0 40-60 100
50.0 37.0 66.0 50-75 125
60.0 45.0 80.0 70-105 125
75.0 55.0 100.0 100-150 160
85.0 63.0 112.0 100-150 160
100.0 75.0 135.0 100-150 200
TRM 23 TRM 24
TRM 22 TRM 75
Thermal Overload Relay
DIMENSIONS (IN MM)
CTR
TYPE CTR 36 CTR 40 CTR 51 CTR 60 CTR 75 CTR 105 CTR 150 CTR 200/270/400*
A 127 127 157 157 157 183 185 - -
B 42 42 43 43 43 49 50 - -
C 59 59 59 59 59 59 59 - -
D 139 139 139 139 139 139 139 - -
*Dimensions on request.
TERMINAL BLOCK (TB 34) RELAY WITH TERMINAL BLOCK (TB 34)