Software Installation
ESC 03 01
OPERATING INSTRUCTIONS
© Ericsson AB 2016, 2017. All rights reserved. No part of this document may be
reproduced in any form without the written permission of the copyright owner.
Disclaimer
The contents of this document are subject to revision without notice due to
continued progress in methodology, design and manufacturing. Ericsson shall
have no liability for any error or damage of any kind resulting from the use
of this document.
Trademark List
All trademarks mentioned herein are the property of their respective owners.
These are shown in the document Trademark Information.
Contents
1 Introduction 1
2 Work flow 1
2.1 ESC Scratch Installation Flow 1
2.2 ESC Replacement Flow 3
Glossary 18
1 Introduction
Cabinets such as Enclosure 6130, 6140, and 6150 come with a preconfigured
control unit, ESC 03 01. In case of a HW replace or factory reset of the unit,
the software, license, and configuration need to be re-installed following this
document.
2 Work flow
Collect sie
information
Collect ESC SW
Load LKF
L0001
ESC replacement
This section describes how to prepare the site-specific USB memory stick for
the ESC software installation.
3.1 Prerequisites
This section contains information about the documentation, equipment, and
conditions required for the procedure.
3.1.1 Equipment
Ensure that the following tools are available:
• ESC Name
• Default gateway
The first time an ESC is installed, an initial grace period is started, which permits
unrestricted use for 21 days. All ESC features are activated during the grace
period. This enables node usage while waiting for the license key file to arrive.
When the ESC 03 01 hardware is ordered, the attached licenses will also be
ordered automatically. A License Authentication Code (LAC) will be delivered
to the customer. The LAC together with the ESC 03 01 serials number shall be
used to generate the LKF per site from the ELIS system.
license
2. Check that the file type of the license key is the XML file format (.xml).
To display the file type, right-click on the file and select ‘‘Properties’’.
2. Copy for this enclosure applicable configuration file templates that are
available in Section 4 on page 8.
3. Paste the configuration file templates into the empty Notepad text
document.
4. In the text document, replace the text that corresponds to the bold text in
Table 1 according to the site configuration data.
autoconf
2. Check that the file type is the CLI file format (.cli).
To display the file type, right-click on the file and select Properties .
If license file is not available when preparing the USB stick, skip the
license file saving in step 3 and load the license file later via ESC GUI.
1. Insert the USB memory stick into a USB port on the PC.
To display the file system format, open Windows Explorer, right-click on the
USB device, and select Properties.
• autoconf
• license
4. Transfer the three file copies to the memory stick. The files must be placed
in the root of the stick, not in a folder.
This section provides a template for the configuration file for Enclosure 6130,
6140, 6150, 6330, and 6340, and supporting the Megmeet controller or
Emerson controller. Replace the
bold text with relevant site configuration data, as described in Table 1.
Configuration template rows that start with ";" only have the purpose to explain
the command rows immediately below the comment row.
File template
commit t
endTransaction t
; To change the password of the ESC, replace the last two default with new password. 1st default is the current
changepwd default default default
; Add MC1800
createMO t2 SDN=0,PowerManager=HGM,PowerSystem=MC1800
setMOattribute t2 SDN=0,PowerManager=HGM,PowerSystem=MC1800
powerSystemType="MC1800"
createMO t2 SDN=0,PowerManager=HGM,PowerSystem=MC1800,Ref=0
setMOattribute t2 SDN=0,PowerManager=HGM,PowerSystem=MC1800,Ref=0 dep="SDN=0,SerialPort=MC1800,Equipment=1"
; Door
createMO t2 SDN=0,PowerManager=HGM,PowerSystem=MC1800,AlarmPort=Door
; Climate-system
createMO t2 SDN=0,PowerManager=HGM,PowerSystem=MC1800,AlarmPort=ClimateSystem
; Digital 3
createMO t2 SDN=0,PowerManager=HGM,PowerSystem=MC1800,AlarmPort=Digital3
; Digital 4
createMO t2 SDN=0,PowerManager=HGM,PowerSystem=MC1800,AlarmPort=Digital4
startTransaction t2
createMO t2 SDN=0,PowerManager=HGM
; Configuration handling of batteries
createMO t2 SDN=0,PowerManager=HGM,Battery=1
; Add M530B
createMO t2 SDN=0,PowerManager=HGM,PowerSystem=M530B
setMOattribute t2 SDN=0,PowerManager=HGM,PowerSystem=M530B powerSystemType="M530B"
createMO t2 SDN=0,PowerManager=HGM,PowerSystem=M530B,Ref=0
setMOattribute t2 SDN=0,PowerManager=HGM,PowerSystem=M530B,Ref=0 dep="SDN=0,SerialPort=M530B,Equipment=1"
; Door Alarm
createMO t2 SDN=0,PowerManager=HGM,PowerSystem=M530B,AlarmPort=Door
; Alarm 1
Configuration File Template for Enclosure Cabinets
; AC cabinet
startTransaction t
createMO t SDN=0,AlarmPort=1
setMOAttribute t SDN=0,AlarmPort=1 portId 1
createMO t SDN=0,AlarmPort=2
setMOAttribute t SDN=0,AlarmPort=2 portId 2
createMO t SDN=0,AlarmPort=3
setMOAttribute t SDN=0,AlarmPort=3 portId 3
createMO t SDN=0,AlarmPort=4
setMOAttribute t SDN=0,AlarmPort=4 portId 4
commit t
endTransaction t
; DC cabinet
; Create the 4 External alarms. Naming should be the same for all DC-cabinet variants
startTransaction t
;Climate system
createMO t SDN=0,AlarmPort=ClimateSystem
setMOAttribute t SDN=0,AlarmPort=ClimateSystem portId 1
; Default is Normally Closed
setMOAttribute t SDN=0,AlarmPort=ClimateSystem inputActive activeWhenOpen
commit t
endTransaction t
4.2.5 SAU
SAU is a unit that can be connected to ESC0301 if more external alarm ports
are required. This part is applicable for any cabinet using a SAU.
startTransaction t
createMO t SDN=0,SerialPort=EC-SAU
setMOAttribute t SDN=0,SerialPort=EC-SAU portNumber 2
setMOAttribute t SDN=0,SerialPort=EC-SAU mode RS485
setMOAttribute t SDN=0,SerialPort=EC-SAU protocol HDLC
setMOAttribute t SDN=0,SerialPort=EC-SAU bitRate 115200
setMOAttribute t SDN=0,Serialport=EC-SAU dataBits 8
createMO t SDN=0,ECbus=1
setMOAttribute t SDN=0,ECbus=1 depSerialPort "SDN=0,SerialPort=EC-SAU"
commit t
endTransaction t
startTransaction t
createMO t SDN=0,AlarmPort=SAU1-1
setMOAttribute t SDN=0,AlarmPort=SAU1-1 depEquipment="SDN=0,ECBus=1,Equipment=SAU1"
setMOAttribute t SDN=0,AlarmPort=SAU1-1 portId 1
createMO t SDN=0,AlarmPort=SAU1-2
setMOAttribute t SDN=0,AlarmPort=SAU1-2 depEquipment="SDN=0,ECBus=1,Equipment=SAU1"
setMOAttribute t SDN=0,AlarmPort=SAU1-2 portId 2
createMO t SDN=0,AlarmPort=SAU1-3
setMOAttribute t SDN=0,AlarmPort=SAU1-3 depEquipment="SDN=0,ECBus=1,Equipment=SAU1"
setMOAttribute t SDN=0,AlarmPort=SAU1-3 portId 3
createMO t SDN=0,AlarmPort=SAU1-4
setMOAttribute t SDN=0,AlarmPort=SAU1-4 depEquipment="SDN=0,ECBus=1,Equipment=SAU1"
setMOAttribute t SDN=0,AlarmPort=SAU1-4 portId 4
createMO t SDN=0,AlarmPort=SAU1-5
setMOAttribute t SDN=0,AlarmPort=SAU1-5 depEquipment="SDN=0,ECBus=1,Equipment=SAU1"
setMOAttribute t SDN=0,AlarmPort=SAU1-5 portId 5
createMO t SDN=0,AlarmPort=SAU1-6
setMOAttribute t SDN=0,AlarmPort=SAU1-6 depEquipment="SDN=0,ECBus=1,Equipment=SAU1"
setMOAttribute t SDN=0,AlarmPort=SAU1-6 portId 6
createMO t SDN=0,AlarmPort=SAU1-7
setMOAttribute t SDN=0,AlarmPort=SAU1-7 depEquipment="SDN=0,ECBus=1,Equipment=SAU1"
setMOAttribute t SDN=0,AlarmPort=SAU1-7 portId 7
createMO t SDN=0,AlarmPort=SAU1-8
setMOAttribute t SDN=0,AlarmPort=SAU1-8 depEquipment="SDN=0,ECBus=1,Equipment=SAU1"
setMOAttribute t SDN=0,AlarmPort=SAU1-8 portId 8
createMO t SDN=0,AlarmPort=SAU1-9
setMOAttribute t SDN=0,AlarmPort=SAU1-9 depEquipment="SDN=0,ECBus=1,Equipment=SAU1"
setMOAttribute t SDN=0,AlarmPort=SAU1-9 portId 9
createMO t SDN=0,AlarmPort=SAU1-10
setMOAttribute t SDN=0,AlarmPort=SAU1-10 depEquipment="SDN=0,ECBus=1,Equipment=SAU1"
setMOAttribute t SDN=0,AlarmPort=SAU1-10 portId 10
createMO t SDN=0,AlarmPort=SAU1-11
setMOAttribute t SDN=0,AlarmPort=SAU1-11 depEquipment="SDN=0,ECBus=1,Equipment=SAU1"
setMOAttribute t SDN=0,AlarmPort=SAU1-11 portId 11
createMO t SDN=0,AlarmPort=SAU1-12
setMOAttribute t SDN=0,AlarmPort=SAU1-12 depEquipment="SDN=0,ECBus=1,Equipment=SAU1"
setMOAttribute t SDN=0,AlarmPort=SAU1-12 portId 12
createMO t SDN=0,AlarmPort=SAU1-13
setMOAttribute t SDN=0,AlarmPort=SAU1-13 depEquipment="SDN=0,ECBus=1,Equipment=SAU1"
setMOAttribute t SDN=0,AlarmPort=SAU1-13 portId 13
createMO t SDN=0,AlarmPort=SAU1-14
setMOAttribute t SDN=0,AlarmPort=SAU1-14 depEquipment="SDN=0,ECBus=1,Equipment=SAU1"
setMOAttribute t SDN=0,AlarmPort=SAU1-14 portId 14
createMO t SDN=0,AlarmPort=SAU1-15
setMOAttribute t SDN=0,AlarmPort=SAU1-15 depEquipment="SDN=0,ECBus=1,Equipment=SAU1"
setMOAttribute t SDN=0,AlarmPort=SAU1-15 portId 15
createMO t SDN=0,AlarmPort=SAU1-16
setMOAttribute t SDN=0,AlarmPort=SAU1-16 depEquipment="SDN=0,ECBus=1,Equipment=SAU1"
setMOAttribute t SDN=0,AlarmPort=SAU1-16 portId 16
createMO t SDN=0,AlarmPort=SAU1-17
setMOAttribute t SDN=0,AlarmPort=SAU1-17 depEquipment="SDN=0,ECBus=1,Equipment=SAU1"
setMOAttribute t SDN=0,AlarmPort=SAU1-17 portId 17
createMO t SDN=0,AlarmPort=SAU1-18
setMOAttribute t SDN=0,AlarmPort=SAU1-18 depEquipment="SDN=0,ECBus=1,Equipment=SAU1"
setMOAttribute t SDN=0,AlarmPort=SAU1-18 portId 18
createMO t SDN=0,AlarmPort=SAU1-19
setMOAttribute t SDN=0,AlarmPort=SAU1-19 depEquipment="SDN=0,ECBus=1,Equipment=SAU1"
setMOAttribute t SDN=0,AlarmPort=SAU1-19 portId 19
createMO t SDN=0,AlarmPort=SAU1-20
setMOAttribute t SDN=0,AlarmPort=SAU1-20 depEquipment="SDN=0,ECBus=1,Equipment=SAU1"
setMOAttribute t SDN=0,AlarmPort=SAU1-20 portId 20
31/1543-LZA
createMO t 701 6009 Uen E | 2017-05-09
SDN=0,AlarmPort=SAU1-21 15
setMOAttribute t SDN=0,AlarmPort=SAU1-21 depEquipment="SDN=0,ECBus=1,Equipment=SAU1"
setMOAttribute t SDN=0,AlarmPort=SAU1-21 portId 21
createMO t SDN=0,AlarmPort=SAU1-22
setMOAttribute t SDN=0,AlarmPort=SAU1-22 depEquipment="SDN=0,ECBus=1,Equipment=SAU1"
Preparing USB Memory Stick for ESC Software Installation
Glossary
ESC
Ericsson Site Controller
FAT32
File Allocation Table partition format where
the cluster values are represented by 32-bit
numbers
IP
Internet Protocol
LAC
License Authentication Code
LKF
License Key File
NTP
Network Time Protocol
OSS
Operations and Support System
SID
Site Installation Documentation
SW
Software
USB
Universal Serial Bus