Sei sulla pagina 1di 4

Proceedings o f 2005 International Symposium on Electrical Insulating

Materials, June 5-9, 2005, Kitakyushu, Japan B5-2

THE EFFECT OF THE SECONDARY LOADS ON THE VOLTAGE SURGES


TRANSFERRED
THROUGH DISTRIBUTION TRANSFORMERS

Mohamed A. Abdallah
Alexandria University - Egypt
abdallahma@hotmail.com

Abstract: Over voltages associated with nearby or transformer: the well-known capacitive PI and the
direct lightning discharges on distribution networks Vaessen one [7]. The results show significant
have a great effect on the power quality. The surges differences in relation to both waveforms and
transferred from the primary to the secondary via amplitudes of the transferred voltages. This
transformers should be correctty evaluated having in emphasizes the importance of having an adequate
mind the protection of the installations and equipment model for the distribution transformer so as to allow
connected to the low-voltage network. Thus a the analysis of the transferred surges. It is also
transformer model adequate for these catculations necessary to consider the transformer in the under
and that can be used in the presence of loads, is load condition. In [8, 91, a simple and reliable model to
required. In this paper such a model, able to represent represent the distribution transformer, under no load
typical three-phase distribution transformers, is condition, is described. These studies came to a more
presented. Some measured and calculated advanced state, which enabted the representation of
waveforms of voltages transferred through typical the transformer in the under-load condition as well
distribution transformers, under different load [IO]. A further development was presented in [l I].
conditions, are also shown. Based on comparisons of The obtained results motivated the continuation of the
the results, the proposed model was validated. research, with the model representation for other
Simulations results are also presented for the case of distribution transformers being investigated. Based on
direct lightning hits on the primary line of a typical the characteristics of nine distribution transformers, a
distribution network, making it possible to evaluate the generic model ta represent them was obtained [12].
effect, on the over voltages, of installing surge The present work shows results of tests and
protective devices at different points of the secondary simulations considering a three-phase distribution
network. the simulations were performed through the transformer, 500 kVA, 11 kV/ 380 V, where the load
use of the EMTDC. effect can be observed. Balanced loads connected to
the secondary terminals were considered. In the
1. Introduction simulations, the model proposed in 114 was used to
Bearing in mind the ever growing use of electronic represent the transformer. Afterwards, by using the
equipment, it is fundamental that the electrical energy same model with the parameters corresponding to a
supplied to consumers present acceptable qualities 30 kVA distribution transformer and a typical
indexes. Therefore, special attention should be given distribution network, the voltages in some points of the
to the potection systems aiming at the attenuation of secondary network were determined considering the
the disturbances caused by lightning surges. So as to occurrence of a direct lightning discharge in the
correctly evaluate the surges transferred to a primary line. In this case, the simulations were
secondary network, it is necessary to know the performed through the use of the EMTDC.
characteristics of the transients that occur on the
primary line and to adequately represent the 2 Transformer model
transformer regarding its frequency behavior. The The development of the model was based on
Occurrence of lightning discharges nearby the measurements of the transformer’ s input, output and
distribution lines results in voltages induced in the transfer impedances and the transfer characteristics
medium voltage network which strikes the primary (ratio between the voltages on the secondary and on
terminals of the transformer. The induced voltages are the primary windings), as a function of frequency, with
important in the analysis of the lightning performance a simple and reliable circuit being obtained. The
of distribution lines and many investigations have methodology and the stages of the development are
been conducted on this subject [1-5]. In [q the described in [II], where a three-phase distribution
voltages transferred to the secondary of a distribution transformer, rated 30 kVA, was used as reference
transformer, under the n d o a d condition, are The general applicability of the model was verified
calculated considering two different models for the through the use of the same methodology in 500

- 800 -
kVA,11 kV 1 380 V delta-wye connected. As a result, a Figure 2: Measured and calculated transferred
model which represents reasonably well all the voltages. Transformer (500 kVA ) under the n d o a d
transformers considered was obtained and is shown condition
in Figure 1. P --Tcararfoamer

z -- MOdSl

3’
.%*
-
3 -*
-2

J
T
- 1- I]

tu)

Figure 1: Distribution transformer model [II].

Figures 2 and 3 show some measured and calculated


voltages transferred through the 500 kVA transformer
under different load conditions, for thecase of impulse
voltages with the standardized waveform 6 /50 p s)
applied to the W terminals interconnected. Initially,
the measurements were taken in the absence of loads
and then one capacitive and some resistive balanced
loads were considered. The peak values of the
impulse voltages applied were 1.14 kV and 1.15 kV,
depending on the load. The waveform of the applied
impulse was kept unaltered in all applications. As
under the test Conditions the system was linear, the
voltages shown in Figures 2 and 3 were normalized to
100 kV (this value applied to HV terminals of the
transformer instead of 1.14 kV and 1.I 5 kV). The
measured voltages were compared to those
calculated by using the modef presented in Figure 1,
whose parameters referring to the 500 kVA
transformer are shown below:- resistances (k ): 3.0
(R2), 5.0 (R3), 0.35 (R6), 1.5 (R7);- capacitances
(pF): 600 (Cl),1125.76 ((2). 146.13 (C3), 600 (C4),
400 (C5).850 (C7);- inductances (mH): 35 (L2), 15
(L3). 0.0124 (L7). The waveforms of the transferred
voltages present, in general, a damped oscillatory
behavior. For resistive loads, the lower the vafue of
“s L 4
the load impedance, the greater the damping. In the
case of the resistive toad of 10 , for instance, the Cd 1
voltage waveform can be considered practically Figure 3: Measured and calculated transferred
unidirectional. voltages. Transformer 600 kVA ) under different load
conditions. a) 510 b) 50 c) 10 d) 330 pF

A good agreement is observed between the


waveforms of the measured and calculated
transferred voltages. The average difference found on
the peak values was about 5.6 %, which is quite
reasonable. On the other hand, the voltages predicted
by the capacitive PI circuit may reach magnitudes as
high as 20 times geater than the measured ones,
even in the absence of loads.

- 801 -
3. Application in practical situations
An example of the utilization of the transformer model,
with a typical secondary network Configuration being
considered, is presented here. Besides the
transformer, the most relevant components of the
system, such as arresters, insulators, etc., are
represented in the simulations, which were performed
by using the EMTDC. The case of direct strikes to the
primary line is considered. A lightning current with
triangular waveform, peak value of 45 kA, front time of
2.25 s and time to half value of 80s was adopted. The
basic configuration considered comprises a 10 km
long primary line, with the neutral conductor grounded
every 300 m. The network components were modeled
as described in [ I O ] . The distribution transformer was
located in the middle of the MV line. For the
secondary circuit, the length of 300 m was adopted
(150 m for each side of The transformer), this circuit
being coupled with the MV line, with 1/0 A W G
aluminum conductor. The branches of the consumers
are 30 m long and connected to the secondary line
every 30 m, with the neutral being grounded at the
entrance of the consumers. The striking point is
assumed to be at the right side of the transformer; the
consumers are then identified according to their
position (left or right) and to their distance with respect
to the transformer. The closest consumer is at point 0,
the others at points 1, 2 and so on. As the distance
between them is 30 m and the length of the secondary
line from each side of the transformer is 150 m, the
consumers at the line ends are identified as E5 and
D5. The transformer was threephase. 30 kVA, and
with the following parameters relative to Figure 1:-
resistances (k ): 14 (FE), 0.8 (R3), 1.1 (R6)and 1.62 Tb*ot@b
(R7);- capacitances @F): 493 (Cl), 94.8 (CZ),21.51
(C3), 5 0 (GI) and 759.5 (C7);- inductances (mH): 16
(L2). 1.84 (L3) and 0.05 (L7). Three configurations IC) F
were analyzed concerning the position of the LV surge igure 4: Phase-to-neutral voltages at the entrances of
protection devices (SPDs) connected to the the consumers. Grounding resistance: 300 . Striking
Secondary network: no SPDs; SPDs placed only at point at a distance of 300 m from the transformer LV
the LV terminals of the transformer; SPDs at the LV line without protection. a) close to the transformer b)
terminals of the transformer and at both ends of the consumers of the right side of the transformer c ) ~

secondary (points E5 and D5). Figures 4 and 5 consumers of the left side of the transformer
present, respectively, the voltages corresponding to
the first and third situations, for a value of 300 for the The installation of SPDs causes significant reductions
grounding resistance. In both cases the lightning on the voltages at points close to the transformer. The
striking point is at the right side of the transformer, at voltage on its LV terminals varies from about 20 kV t o
a distance of 300 m from it. 1 .O kV, this value corresponding to the residual
voltage of the SPDs. As for the reduction on the peak
value of the voltage at the entrance of the consumer
closest to the transformer, although smaller it is also
significant: from about 5.0 kV to 1.0 kV. For the
consumers located on the left side of the transformer,
nsar points E l and E, the voltages decrease I 1 %
and 75 %, respectively. For the specific case
considered, no significant effect of the SPDs is
observed on the 3 The effect of the secondary loads

- 802 -
on the voltage surges voltages at the consumers [2l A. Piantini and J, M. Janiszewski, ”Analysis of
located on the right side of the transformer. This may Three Different Theories for Computation of Induced
probably be ascribed to flashovers on the MV and LV Voltages on Distribution Lines Due to Nearby
insulators, which greatly complicate the analysis of the Lightning”. Procs. of the Int. Conf. on Electricity
phenomenon. Distribution (CIRED Argentina’961, pp. Session 1 /
F+LhSSTOG3€Y3ND YOLTAOE AT WEC4US1Ja-
127-132, Buenos Aires, 1996.
[3] A. Piantini and J. M. Janiszewski. “The Influence of
the Upward Leader on Lightning Induced Voltages”.
Procs. Of the Int. Conf. on Lightning Protection (23rd
ICLP), vol. 1, pp. 352-357, Florence, 1996.
[4] C. A. Nucci, Task Force 33.01.01 of Study
Committee 33. “Lightning-Induced Voltages on
Overhead Power Lines. Part II: Coupling Models for
the €valuation of the Induced Voltages”. Electra, n.
162, p p 127-145, October 1995.
[5j C. A. Nucci et al. “Comparison of Two Coupling
Models for Lightning-Induced Over voltages
Calculations”. /€€E Trans. on Power Delivery, vol. IO,
4 n.1, pp 330339, January 1995.
I
3 [q A. Borghetti e t al, “Calculation of Vo!tages Induced
2 2 by Nearby Lightning on Overhead Lines Terminated
$ 9
on Distribution Transformels”. Procs. of the Int. Conf.
a on Power Systems Transients (IPST’95), pp. 31 2-316,
4 Lisbon, 1995.
[7l P. T. Vaessen, “Transformer Model for High
Frequencies” . IEEf Trans. on Power Delivery, vol. 3,
n.4, pp 1761-1768, Oct. 1988.
(b) [8] A. Piantini and C V. S. Malagodi, “Modeling of
Figure 5 Phaseto-neutral voltages. Grounding Three Phase Distribution Transformers for
resistance: 300 . Striking point at a distance of 300 m Calculating Lightning Induced Voltages Transferred to
from the transformer. SPDs at t h e transformer LV the Secondary ” , Proceedings of the V International
terminals and at both ends of the LV line. Symposium on Lightning Protection (V SIPDA). pp 59-
64, Sa Paulo, May 1999.
4. Conclusions [9] A. Piantini and C V. S. Malagodi. ‘Voltage
This paper presented some waveforms of voltages
Surges Transferred to the Secondary of Distribution
transferred through distribution transformers under
different load conditions. The measured results were .
Transformers ” Proceedings of the 1I t h International
Symposium on High Voltage Engineering (11th ISH).
compared with the calculated ones by making use of a
vol. 1, pp. 1.365-1.368, London, Aug. 1999.
model developed to represent the transformer. A good
[IO] A. Piantini, W. Bassi, J. M. Janiszewski and N M.
agreement was found, thus confirming the validity of
the model. Simulations using the EMTDC were then Matsuo. “A Simple Transformer Model for Analysis
perFormed for a typical distribution network and the of Transferred Lightning Surges from MV to LV Lines
voltages transferred to the secondary. with and ” . Procs. of the Idh Int. Conf. on Electricity
without SPDs, for the case of direct discharges into Distribution (1 5th CIRED), Nice, 7999.
the primary line, were calculated. In spite of the great [I11 A. G. Kanashiro, A Piantini and G. F. Burani, “A
quantity of parameters involved and the variation Methodology for Transformer Modeling Concerning
ranges d their values, the information presented in High Frequency Surges” . Procs. of the VI Int.
the paper allows one to have an overall idea of the Symposium on Lightning Protection (VI SIPDA), pp.
basic characteristics of the transferred voltages. 275-280, Sa Paulo, Nov. 2001.
[I21 A. Piantini and A. G. Kanashiro, “A High
5. References Frequency Distribution Transformer Model for
[ I ] A. Piantini and J. M Janiszewski, ”Induced Calculating Transferred Voltages ” . Procs. of the Int.
Voltages on Distribution Lines due to Lightning Conf. on Lightning Protection (26th ICLP), vol. 2, pp.
Discharges on Nearby Metallic Structures”. /E€E 429-434, Cracow, Sep. 2002
Tranactions on Magnetics, vol. 34, n 5, pp. 2799-
2802, Sep. 1998.

- 803 -

Potrebbero piacerti anche