Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
CHAPTER 3
OVER CURRENT AND EARTH FAULT RELAY COORDINATION
Relay coordination has to be carried out based on many other power system
studies and Equipment Sizing calculation, are listed below
a. Load Flow Studies
b. Short Circuit Studies
c. Motor Starting Studies
d. Transient Stability Studies
e. Harmonic Analysis
f. CT Sizing
1. Symmetrical faults.
The symmetrical fault is also called as balanced fault. The Faults occurs only
when all the three phase are short critical simultaneously. There are two types of
symmetrical faults.
1. (L.L.L.G) all the three phases are short circuited to ground.
2. All the three phases are short-circuited.
The symmetrical faults will occur only 2 to 5% of the total system faults. The analysis
of symmetrical faults is mandatory for the resulting the capacity of the circuit
breakers, for choosing relays of corresponding type and other protective switchgear.
There are different types of relays which are used to isolate the devices under
critical conditions
1. Magnitude Relays.
2. Impedance Relays.
3. Directional Relays.
4. Pilot Relays
5. Differential Relays
6. Latching Relays.
7. Reed Relays.
8. Bucholz Relays.
9. Over Load Protection Relays.
10. Solid State Relays.
11. Inverse definition Minimum Time Relays (IDMT Relays).
A few relays related to the thesis are explained as below.
20
Differential Relays
Differential relay get in operation when two (or) more equipment electrical
exceed certain predetermined value. Whenever there is a difference between the
magnitude and phase difference of the currents.
The above figures shows the two CT Transformer connected on both sides of
the transformer the one CT will be linked on the primary side and another CT will be
connected to the secondary side of the transformer. The relay present in the system
will compare the currents on both sides of the transformer, whenever there is a
difference in current occurs then the relays get in operation. The difference relays can
be either of voltage balance differential relays, (or) bi-used differential relays.
Buchholz Relays
Their relays are gas operated. These relays will come to into operation
whenever there is imminent fault occurs. The early failure is nothing but small
mistake in which due course will develop into significant faults. It will be
accommodated in between the transformer tank and conservator. These are used only
for oil immerged relays.
Solid state relays are mainly composed of BTT, SCR, IGBTC, MOSFETS’s,
AND TRIAC for the switching operation. The power required to operate the relay is
lesser when compared to other relays. The control energy needed for the functioning
of a relay is deficient. There is no mechanical contact, Hence the relay is operated
with high speeds.
In these above picture photos, a sensitive semiconductor device is used for the
switching operation. The control signal will be given to the LED, which is turn gives
supplies to the photo sensitive device get into conduction, using LED. Due to this
installation of SSR, the relays operate in a faster mode and its life span is higher when
composed to the other relays. The advantages of this relays are make very less noise.
Latching Relays
Latching Relays is a relay which maintains its state each after the actuation of
the relay. The name of the relay is impulse relay. The latching relay is mainly chosen
for the low power consumption. It consists of internal magnets in which the current
supplied to the coil, maintain the contact position and there is no separate power to
support the holding.
a). Current Flows (No position). b). Current stop and relay stays in position c).
Current flows in opposite Direction.
Latching relays are consists of this coils, and the latching relays does not have
any default position since these coils are responsible for the position of the armature.
In the loop type relay, the armature position is usually determined using direction of
current flow in the coil. But in the case of two coil type, depending on the current
flow, the armature position is determined.
24
Reed relay
Polarized Relay
These relays are very sensitive to the direction of the current flow, since the
names itself identify the process. If it is a type of electromagnetic relay then it uses
magnetic forces to attract the armature and the same for the other side.
The armature used in this type of relays uses magnetic force which attracts (or)
repeats the armature whenever the current flows through the electromagnet, it
produces a magnetic flux. The magnetic force extended by the magnet exceeds certain
limit, then the armature change is occurred, the force is reduced than permanent
magnet force and due to this effect, the armature return to its original position.
26
stay in their own position. Depends on the parameters combination and the
interactions, a force will effect on the magnitude of the current power and the value of
the working gap. The two famous types of relays of this type including differential
and bridge type relays. In medium and normal size of the relay model, only this type
of relay is widely used.
These are different types of earth fault relays. This occurred during star point
treatments of generators.
a. Isolated star point.
b. Compensated star point.
c. Earthed via Reactor (Or) transformer.
d. Earthed through Registrar RE.
e. Directly Earthed star point.
f. Star point treatment through neutral earthing Registrar RE.
g. Protection is needed in case of earth fault external.
h. Protection is required in case of internal faults.
Depending upon the cable capacity of the earth fault currents is isolated at star
points. This is the only method which is possible when the cable sizes are within the
network system and do not vary. In most of the power stations, however these types of
network are not available on most of the cable network system. If the fault occurs in
one conductor then the voltage of system will increase by factor.√3 times of the good
conductor.
IE = 3.I0 ≈ √3. Ui . ῶ . CE.
with IE earth fault current at earth fault location.
CE earthing capacitance = zero capacitance of the network.
ῶ. 2πf = angular frequency.
28
This method is possible only when the cable capacities are within the network
systems. In major power stations, the condition that is the cable dimensions is not
within the network. In the case of earth fault, a fault occurs at any one conductor, then
the voltage will increase by √3 factor of the remaining two good conductors and
thereby the line to line voltage is achieved.
IE = 3.I0 ≈ √3. Ui . ῶ . CE.
With
IE - Earth fault current at earth fault location
CE – Earthing capacitance = zero capacitance.
ῶ = 2π f (angular frequency).
In the case of earth fault, the residual current which present are very low and
the cable capacities of the entire network system are mainly paid using independence.
The reactor is used almost of the generator to determine the earth fault current
value. Due to this method the earth fault will depend on network system.
IE ≈ √3.Ui ῶ CE - 1
3 ῶ LD
IE ≈ √3.Ui ῶ CE - 1
3 ῶ LD
With
29
The system voltage will increase to 1.4 factors due to earth factor FE when compared
to the other two good conditional conductors.
IE ≈ √3.Ui 1
______ + I ῶ. CE
3RE
IE ≈ √3.Ui
√1/ 3RE2 + ῶ. CE 2
In the case of earth fault at the conductor, the voltage will increase approximately of a
max. Factor 1.4 due to earth fault factor F against the two good conditional
E
conductors.
In the case of directly earthed star point the high one phase short circuit
currents, which is the multiple of the nominal generator current.
T2
T2
G2
G1
T1
T1
QE QE
RE
TE
With
RE - ear thing resistance with temperature suspension
31
RE ≈ 318 Ω IRE = 20 A rated for a period of 10 s and IRE (count) = 15 A; URE = 11KV /
√3.
QE - single phase vacuum contactor of the series 12,400A, with short switching lines.
IE - cable type current transformer for backup earth fault detection at neutral earthing
resister RE. 50/1A with 2.5 VA for max 120 min at 10% IN.
T1, T2 - cable type current transformers for earth fault detection within the generators.
In the above case the generator is connected to the bus bar through the earthing
resistor. The star point of the generator which is connected to MV switch gear is
switched to neutral earthing. If the circuit breaker of the generator, whose start point is
neutral resister RE, then the corresponding circuit breaker will be in closed position.
The start point of generator only one should be earthed through neutral resistor RE.
Otherwise, third harmonic will flow across the star points.
To protect the system against fault, the inductance and capacitance will be introduced
in the system. The introduction of inductance and capacitance will make the system in
stable condition.
If the fault occurs beyond the generator range, then the earth current IE will be
determined by the neutral earthing resistance and the source will be secondary. If the
fault is of selection theory, then the relays IDMT are used for solving the earth faults
problem. The IDMT relays are used on transmission lines to ensure that the line
current will not exceed the safe value. During fault if it exceeds then IDMT takes
minimum time to trip the circuit breaker.
In the internal earth fault, the stator earth relay will has to disconnect the generator
which is not in running condition.
The cable type transformer T1 and T2 are installed to find out the earth faults within
the generator protection range.
The current will be same for the fault that is occurring outside of the protection field
of the transformer, and the rating will be same.
If the earth fault occurs within the protection range, then the current rating will be
added. If the earth fault current exceeds more that 5A, them the generator, circuit
breaker will be automatically disconnected from the network and the generator circuit
breaker tripping will be done not more than 10 sec maximum.
If the generator not grounded then the stator earth fault will to the grounded generator
which is usually in operating condition.
The earth fault current of the generator will be identified when, the primary
connection (L1, L2, L3) are solved by means of earth fault relay. This earth fault relay
will detect.
TE is used to find out the residual currents that are available in the path of
resistor. The neutral earthing resistor overload condition will be prevented by means
earth fault relay, and the relays are root picked in correct faulted state.
The pickup rate of the earth fault relay is determined using adjusting the pick
up time10 s after the latest.
The over temperature detecting facility is provided so that the overheating of the
resistor will be reduced, this over temperature detecting equipment is another source
for isolating if the earth fault do not pick up at the right period.
The pre request will be given for both overload protection and over temperature
relays, to isolate the generator from location of the faults. Following the above case
the earth fault relay is used to operate for a specified time.
33
After the expiry of the time, the earth fault relay will get in operation and the
fault current will be grounded properly through the neutral grounding resistor.
The planning, design, and operation of power systems require load flow
calculations to analyze the steady-state (quiescent) performance of the power system
under various operating conditions and to study the effects of changes in equipment
configuration. The basic load flow question gives the load power consumption at all
buses of a known electric power system configuration and the power production at
each generator to find the power flow in each line and transformer of the
interconnecting network and the voltage magnitude and phase angle at each bus are
founded. Based on the Analyzing the solution of this problem for various conditions
helps ensure that the power system is designed to satisfy its performance criteria while
incurring the most favourable investment and operation costs.
The load flow studies that were carried out determines the following
a. Component or circuit loadings
b. Steady-state bus voltages
34
Modern systems are complex and have many paths or branches in which power
can flow over the systems. Such systems form networks of series and parallel paths.
Load flow Analysis provides the maximum load current and minimum load current in
both the directions it constitutes the basis for selection of CT Ratios and Plug settings
of Relays.
Plug setting multiplier of relay is the ratio of fault current to its pick up current.
The selection of required current setting will be given by plug setting multiplier plug
and the plug is withdrawn inorder to adjust the current setting at the time of on load
condition, due to this the maximum current taping is connected default and the
opening of the secondary side of the CT is avoided.
Computer programs are used to solve load flows are divided into two types
static (offline) and dynamic (real time). Most of the load flow studies for system
analysis are based on static network models. Real-time load flows (online) that
incorporate data input from the real networks are typically used by utilities in
automatic Supervisory Control and Data Acquisition (SCADA) systems. Such
systems are used primarily as operating tools for optimization of generation, var
control, dispatch, losses, and tie line control. This discussion is concerned only with
only static network models and their analysis.
Tie line control in power system which will regulate the active and reactive
power flow between the micro grid and the bulk grid at the point of interconnection.
By means of this tie line control the micro grid is allowed to behave as a aggregated
power entity that can be made dispatch able by the utility. This tie line method is used
35
to associate the renewable energy sources, wind energy which push the management
burden inside the micro grid
To balance the load flow problem pertaining that are to be balanced, steady-
state operation of power systems, a single-phase, positive sequence model of the
power system are used. Three-phase load flow analysis software is available, but they
are not needed for routine industrial power system studies.
A load flow calculation determines the state of the power system for a given
load and generation distribution. It represents a steady-state condition as if that state
has been held fixed for some time. In actuality, line flows and bus voltages fluctuate
constantly by any small variation in loads status lights, motors, and other loads
whenever turned on and off. However, these small fluctuations can be ignored in
calculating the steady-state effects on system equipment.
As the load distribution, and possibly the network, will vary considerably
during different time periods, it may be necessary to obtain load flow solutions
representing different system conditions such as peak load, average load, or light load.
These solutions will be used to determine either optimum operating modes for
standard conditions, such as the proper setting of voltage control devices, or how the
system will respond to abnormal conditions, such as outages of lines or transformers.
Load flows form the basis for determining both when new equipment additions are
needed and the effectiveness of new alternatives to solve present deficiencies and meet
future system requirements.
The load flow model is also the basis for several other types of studies such as
short-circuit, stability, motor starting, and harmonic studies. The load flow model
supplies the network data and an initial steady-state condition for these studies.
36
The short circuits cannot always be prevented, but we can only attempt to
mitigate some degree contain their potentially damaging effects. One should, at first,
aim to design the system so that the likelihood of the occurrence of the short circuit
fault becomes very small. If a short circuit occurs, however, mitigating its effects
consists of
interrupting equipment at all voltage levels that is capable of withstanding the fault
currents and isolating the faulted area. It follows, therefore, that the primary reasons
for performing short-circuit studies are the following
Short circuit studies are as necessary for any power system, like other
fundamental system studies such as power flow studies, transient stability studies,
harmonic analysis studies, etc.
Short-circuit studies can be performed at the planning stage to help finalize the
system layout, determine voltage levels, and size cables, transformers, and conductors.
For existing systems, fault studies are necessary in the cases of added generation,
installation of extra rotating loads, system layout modifications, rearrangement of
protection equipment, verification of the adequacy of existing breakers, relocation of
already acquired switchgear to avoid unnecessary capital expenditures, etc. “Post-
mortem” analysis may also involve short-circuit studies in order to duplicate the
reasons and system conditions that led to the system’s failure.
These types of short circuits are also referred to as “shunt faults,” since all four
exhibit the common attribute of being associated with fault currents and MVA flows
diverted to different paths from the prefault “series” ones.
In conventional Three-phase short circuits often turn out to be the most severe
of all. Hence It is thus customary to perform only three phase-fault simulations when
39
For systems, where any one or more of the above conditions exist, it is
advisable to perform a single line-to-ground fault simulation. The fact that medium-
and high-voltage circuit breakers have 15% higher interrupting capabilities for single
line-to-ground faults should be taken into account if elevated single line-to-ground
fault currents are found. Line-to-line or double line-to-ground fault studies may also
be required for protective device coordination requirements. It should be noted that,
since only one phase of the line-to-ground fault can experience higher interrupting
requirements, the three-phase fault will still contain more energy because all three
phases will experience the same interrupting requirements.
Other types of fault conditions that may be of interest which included are so-called
“series faults”
(Anderson [B1]) and pertain to one of the following types of system unbalances:
i. One line open. Any one of the three phases may be open.
ii. Two lines open. Any two of the three phases may be open.
iii. Unequal impedances. Unbalanced line impedance discontinuity.
The term “series faults” is used because the above unbalances are associated
with a redistribution of the pre-fault load current. Series faults occur when assessing
40
the effects of snapped overhead phase wires, failures of cable joints, blown fuses,
failure of breakers to open all poles, inadvertent breaker energization across one or
two poles and other situations that result in the flow of unbalanced currents.
The symmetrical components theory dictates that for a three-phase system, three
sequence systems need, in general, to be set up for the analysis of an unbalanced fault
condition. The first is the positive sequence system, which is defined by a balanced set
41
of voltages and currents, equal in magnitude, following the standard phase sequence
of a, b, and c. The second is the negative sequence system, which is similar to the
positive sequence system but it is defined by a balanced set of voltages and currents
with a reverse phase sequence of a, c, and b. Finally, the zero sequence system is a
system defined by a set of voltages and currents that are in phase with each other and
not displaced by 120 degrees, as is the case with the other two systems. The topology
of the zero sequence system can be quite different from that of the Positive and
negative sequence systems because it depends heavily on the power transformer
connections and system neutral grounding, factors which are not of importance when
determining the topology of the other two sequence networks.
Static system equipment like transformers, lines, cables, bus ways, and static
loads present, under balanced conditions, the same impedances will flow to the
positive and negative sequence currents. In case of the same components present, then
different impedances will flow through the zero sequence currents. Rotating
equipment like synchronous generators, motors, the positive sequence impedances are
the ones typically used for balanced power flow studies. All sequence impedances
must be calculated, measured, provided by the equipment manufacturers, or estimated.
The zero sequence impedance may not exist for some rotating equipment, depending
on the machine grounding.
is present, and no other sources are involved, a study should be considered whenever
the motor horsepower exceeds 10–15% of the generator kVA rating, depending on
actual generator characteristics. The study should also recognize contingent
condition(s), i.e., the loss of a source (if applicable).
It may be necessary to make a study for smaller horsepower sizes depending on
the daily fluctuation of nominal voltage, voltage level, size and length of the motor
feeder cable, amount of load, regulation of the supply voltage, the impedance and tap
ratio of the supply transformer(s), load torque versus motor torque, and the allowable
starting time. Finally, some applications may involve for starting large groups of
smaller motors of sufficient collective size to impact system voltage regulation, during
the interval of starting.
Motor starting study provides the essential information of time vs current
during motor starting. This is very necessary for the setting of the relay curves should
be above these motor starting curves to prevent the maloperation of relays during
motor starting.
For years, system stability was a problem almost exclusively to electric utility
engineers. Small independent power producers (IPPs) and co-generation (co-gen)
companies were treated as part of the load and modelled casually. Today, the structure
of the utility industry is going through a revolutionary change under the process of
deregulation. A full-scale competition in the generation market is on the horizon.
Increasing numbers of industrial and commercial facilities have installed local
generation, large synchronous motors, or both. The role of IPP/co-gen companies and
other plants with on-site generation in maintaining system stability is a new area of
interest in power system studies When a co-generation plant is connected to the
transmission grid, it changes the system configuration as well as the power flow
pattern. This may result in stability problems both in the plant and the supplying
utility.
43
Traditionally, the primary source of harmonics in power systems has been the
static power converter used as rectifiers for various industrial processes; however, the
static power converter is now used in a variety of additional applications such as
adjustable speed drives, switched-mode supplies, frequency changers for induction
heating, etc. Semiconductor devices are being increasingly used as static switches that
modulate the voltage applied to loads. Examples of these are soft starters for motors,
static var compensators, light dimmers, electronic ballasts for arc-discharge lamps,
etc. Other examples are devices with nonlinear voltage-current characteristics such as
arc furnaces or saturable electromagnetic devices. Since nonlinear loads represent an
ever-increasing percentage of the total load of an industrial or commercial power
system, harmonic studies have become an important part of overall system design and
operation. Fortunately, the available software for harmonic analysis has also grown.
Guidelines for the acceptance of harmonic distortion are well-defined in IEEE Std
519-1992
By modelling power system impedances as a function of frequency, a study can
be made to determine the effect of the harmonic contributions from nonlinear loads on
the voltages and currents in the power system. The harmonic study provides the
information on the maximum distortion for which relay should not maloperate.
3.7 CT Sizing
Proper selection and sizing of Current Transformers are first important step in
over current relay coordination. CT ratio should be selected based on the Full load
current of component with the overload margin. Protection CT shall be sized in such a
way that it is not saturated for maximum fault current. However new numerical relays
allows CT saturation without any maloperation.
44
3.8. 1 Introduction
Conventionally overcurrent (OC) relay settings are provided based on full load
current of power system components. Time Dial Setting (TDS) and Type of curve are
chosen to ensure that the coordination with the downstream relays. This conventional
procedure for setting the relays went well for a long time. However introduction of
Embedded Renewable Generation, Cogeneration in plants in process industries and
islanding from the grids, Change in the Grid Topology etc. results in the drastic
change in the fault current. This leads to problems like nuisance tripping of relays,
improper coordination or longer time taken to operate the relays for a fault. The
Situation got worse in the continuous addition of renewable generation, most
sophisticated grid islanding schemes, Energy efficient motors which draw high
starting current, technological advancements in controlled switching for transformer
and reactor to reduce the inrush current etc. made the conventional method of relay
setting obsolete. These technical improvements along with new feature in the new
numerical relays provide a better platform to coordinate the relays to reduce the
operating time of relay, prevent the nuisance tripping and ensure the coordination
between the relays in all the grid topologies.
Over current Relays are categorized as Instantaneous, definite time and inverse
time relays. Modern numerical relays from famous manufacturers like ABB, Areva,
GE, Siemens etc. has three stages of Protection. Stage 1 & 2 shall be either Inverse
curve or definite time whereas Stage 3 is Instantaneous without any time delay. Also
these relays have the additional feature of multiple group setting depending on the
digital input to the relay which may corresponds to particular topology of grid
45
conditions. In addition to these relays have inrush or starting multipliers which may be
effectively used to prevent the mal-operation of relays during motor starting or
transformer charging. In addition to standard curves such as Normal Inverse (NI),
Very Inverse (VI), Extremely Inverse (EI), Long Time Inverse (LTI), Standard
Inverse (SI) etc. relays also have the feature of developing user defined curves based
on the user requirements. All these features available in the new relay are utilized with
sophisticated software program to reduce the fault clearing time and prevent the
nuisance tripping of the relays.
Stage: 1&2 (Inverse Definite Minimum Time Delay – IDMT Relay – 51)
Plug setting for inverse relays shall be selected based on the maximum possible
load current and over load margin. In HV substation this depends on the worst case
power-flow current with some future margin.
c. Curve Selection
Selection of curve for the relay is also involved task. Conventionally normal
Inverse or Stand Inverse is selected for plain feeders and Extremely Inverse is used for
Transformer Feeders and Motor Feeders.
Plug setting for Definite Time relays depends upon whether time
discrimination is adopted or not. If time bias is not used i.e. Definite Time is set as
minimum time then the pickup setting shall be higher than the starting or inrush or
through fault current. However present modern of numerical relays provides many
options related to starting and inrush, hence pickup setting can be lowered in normal
operating condition which reduces the damage. i.e. Even when there is fault with
minimum short circuit current, this options make to fall in the Definite Time region of
the relay characteristics, otherwise which falls in Inverse characteristics of the relay in
conventional setting. This result in significant reduction of fault clearing time and
leads to damage.
a. Pickup up setting
Pickup setting shall be higher than the starting or inrush or through fault
current. However present modern numerical relays provides many options related to
starting and inrush and hence pickup setting which can be lowered in normal
operating condition that reduces the damage. I.e. whenever fault occur with minimum
short circuit current this options enable to fall in the instantaneous region of the relay
characteristics which falls in Inverse characteristics of the relay in conventional
setting. This result in significant reduction of fault clearing time will leads to damage.
Earth fault settings also Similar to the over current relay setting except the below facts
47
Grading Margin
The current and time settings selection shall start at the load end and worked
back towards the power source. Grading margins between protection relays shall be
typically as follows:
Grading Margin :
(Er1 + Er2 + Ect) x T/100 + Tcb + T0 +Ts
=(5 + 5 + 5) x 0.25/100 + 0.1 + 0.02 + 0.03
= 0.2175 ˂ 0.25s
Where,
48
Ect = CT Error
Ts = Safety Margin
3.9. Summary
In this chapter the basics of Relay coordination and steps involved in the relay
coordination were discussed.