Water Cooled Centrifugal Chiller

Job Information Technical Data Sheet


Job Name Tabuk mall
Date 1/18/2016
Submitted By Fateh Khan
Software Version 10.80
Unit Tag CH-01 TO 04-01
Starter FPA# AUTO_FPA_EXPORT
Country of Origin USA

Unit Overview
Model Number Capacity NPLV Voltage Starter Type ASHRAE 90.1 LEED EA Credit 4
kW COP
WSC126M 4220.0 6.108 480 V / 60 Hz Fixed Speed '04, '07 & '10 Qualifies

Unit
Model Number: WSC126MBNN2S/E4812-JE-2**/C4812-CLYY-2*****/R134-CBABM-U
Approval: AHRI and ETL / cETL
Vessel Code: ASME
Compressor Quantity Capacity Control Refrigerant Type Refrigerant Weight
1 Inlet Guide Vanes R134a 1299 kg
Evaporator
Entering Fluid Temperature Leaving Fluid Temperature Fluid Type Actual Fluid Flow Minimum Fluid Flow
14.39 °C 5.50 °C Water 113.42 l/s 55.0 l/s
Length Diameter Number of Tube Fouling Factor
Passes Material Wall Thickness
3.7 m 121.9 cm 2 Copper 0.635 mm 0.01761 °C.m²/kW
Condenser
Entering Fluid Temperature Leaving Fluid Temperature Fluid Type Fluid Flow
34.00 °C 38.78 °C Water 252.68 l/s
Length Diameter Number of Tube Fouling Factor
Passes Material Wall Thickness
3.7 m 121.9 cm 2 Copper 0.635 mm 0.04403 °C.m²/kW

Unit Performance
Design Points Rated with AHRI Condenser Relief
Capacity Input Efficiency RLA NPLV Part Load Efficiency Evaporator Fluid Condenser Fluid
kW kW COP A COP 75% 50% 25% Pressure Entering Pressure Leaving
COP COP COP Drop Temperature Drop Temperature
kPa °C kPa °C
4220.0 854.6 4.938 1146 6.108 6.229 6.663 3.726 15.7 14.39 34.8 38.78
Performance Points Rated with Constant Condenser EWT
Point # % of Capacity Input Efficiency RLA Evaporator Fluid Condenser Fluid
Design kW kW COP A Flow Temperature Pressure Flow Temperature Pressure
Load l/s Entering Leaving Drop l/s Entering Leaving Drop
°C °C kPa °C °C kPa
1 100.0 4,220.0 854.6 4.938 1,146 113.42 14.39 5.50 15.7 252.68 34.00 38.78 34.8
2 75.0 3,165.0 628.8 5.033 877 113.42 12.17 5.50 15.7 252.68 34.00 37.57 34.9
3 50.0 2,110.0 453.6 4.652 696 113.42 9.95 5.50 15.7 252.68 34.00 36.41 35.0
4 30.6 1,292.0 322.8 4.003 578 113.42 8.22 5.50 15.8 252.68 34.00 35.50 35.1
Chiller unable to run at requested load point (1055 kW). The minimum capacity at the entered design conditions is (1292 kW)
5 25.0
Standard Stall

Page 1 of 3
Water Cooled Centrifugal Chiller
Service Data
Service Points Rated with Constant Condenser EWT
Point # Superheat Subcooling Evaporator Fluid Condenser Fluid
Δ °C Δ °C Temperature Pressure Velocity Temperature Pressure Velocity
°C kPa(g) m/s °C kPa(g) m/s
1 0.6 4.4 5.1 249.9 1.2 39.3 895.3 1.6
2 0.6 3.5 5.2 250.9 1.2 37.9 860.2 1.6
3 0.6 2.5 5.3 252.0 1.2 36.7 827.2 1.6
4 0.6 1.6 5.4 252.9 1.2 35.7 802.1 1.6
Chiller unable to run at requested load point (1055 kW). The minimum capacity at the entered design conditions is (1292 kW)
5
Standard Stall

Physical
Evaporator
Inlet Location Header Type Header Material Tube Sheet Material Design Pressure (Waterside)
Right Dished, Grooved Carbon Steel Carbon Steel 1 MPa
Condenser
Inlet Location Header Tube Sheet Material Design Pressure
Type Orientation Material (Waterside)
Marine Water Box,
Right Rear Carbon Steel Carbon Steel 1 MPa
Flanged

Electrical
Voltage RLA LRA Power Power Factor MCA MOCP
Connection
480 V / 60 Hz / 3 Phase 1146 A 6520 A Single Point 0.90 1439 A 2011 A

Starter
Type Model Location Enclosure Type Motor Protection
Solid State RVSS2K Free Standing NEMA 1 Standard
Phase Voltage Monitor: Approval
Under / Over Voltage, Phase Loss / Unbalance Protection CSA ETL

Sound (without insulation)


Sound Pressure
63 Hz 125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz Overall 75% Load 50% Load 25% Load
69.0 69.0 72.0 76.0 80.0 83.0 83.0 78.0 88.5 86.5 86.5 87.5
Sound Pressure (dB) measured in accordance with ANSI/AHRI Standard 575-2008 (‘A’ weighted)

Options
Basic Unit
Packaging: Bagging only
Insulation
Thermal: 0.75" on Evaporator Shell, Suction Piping, Compressor Inlet, Motor Barrel & High Humidity
Head: Evaporator Return & Connection Heads
Control
Communication Protocol: Modbus
Starter
Disconnect / Breaker Type: Circuit Breaker

Page 2 of 3
Water Cooled Centrifugal Chiller
Lifecycle Cost
Operation Electricity Cost Annual Energy Cost Life of Equipment Total Lifecycle Equipment
and Energy Cost
2340 hours / year 0.12 $/kWh $111,937.00 25 years $3,064,020.00

Warranty
Unit Startup: By Others (International)
Standard Warranty: First Year Entire Unit Parts only (no Labor)
Delayed Warranty Start: None (Startup 12-18 months after ship date)

AHRI Certification
Certified in accordance with the AHRI Water-Cooled Water-Chilling and Heat Pump Water-Heating Packages
Using Vapor Compression Cycle Certification Program, which is based on AHRI Standard 550/590 (I-P) and AHRI
Standard 551/591 (SI). Certified units may be found in the AHRI Directory at www.ahridirectory.org.

Notes
1. Above RLA, MCA and MOCP values are per Compressor.
2. Performance kW & COP values are total values unless noted otherwise.
3. Minimum flow is based upon standard condenser water relief and not increased lift due to constant condenser water
temperature.
4. This model utilizes a water cooled oil cooler as standard equipment.
5. Use only copper supply wires with ampacity based on 75°C conductor rating. (Exception: for equipment rated over 2,000
volts, 90°C or 105°C rated conductors shall be used). Connections to terminals must be made with copper lugs and
copper wire.
6. For orientation purposes, left and right hand vessel connection locations are determined by facing the OITS panel
(Operator Interface Touch Screen). The unit front is the long dimension side with the OITS panel and rear is the opposite
side long dimension.

Accessories
Optional
Part Number Description
017503301 Flow Switch, Paddle, 3-8" Dia, 150PSI, Qty 1 (Not WDC)
017503301 Flow Switch, Paddle, 3-8" Dia, 150PSI, Qty 1 (Not WDC)

Page 3 of 3