Sei sulla pagina 1di 8

Hydraulic Calculations

for
Project Name: HOME 2 SUITES RICHMOND
Location: 5350 Point West Circle, RICHMOND, TX, 77469
Drawing Name: HOME 2 SUITES FP AUTOSPRINK Calculation Date: 3/23/2018

Design
Remote Area Number: 1
Remote Area Location: 1ST FLOOR
Occupancy Classification: Light Hazard

Density: 0.10gpm/ft²
Area of Application: 900ft² (Actual 870ft²)
Coverage per Sprinkler: 225ft²
Type of sprinklers calculated: Pendent
No. of sprinklers calculated: 5

In-rack Demand: N/A gpm at Node: N/A


Hose Streams: 0.0 gpm at Node: 5 Type: Allowance at Source

Total Water Required (including Hose Streams where applicable):


from Pump at Node: 5: 104.37 @ 117.516
Type of System:
Volume of Dry or PreAction System: N/A

Name of Contractor: KAUFFMAN COMPANY


Address: 13225 FM 529 #A, HOUSTON, TEXAS 77041
Phone Number: 713-937-4144
Name of designer: MICHAEL NEWELL
Authority Having Jurisdiction: CITY OF RICHMOND

Notes:

Automatic peaking results Left: N/A Right: N/A

© M.E.P.CAD, Inc. AutoSPRINK 2018 v14.1.4.0 1 3/23/2018 2:08:05PM Page 1


Hydraulic Graph
Job Name: HOME 2 SUITES RICHMOND 1.85
N
Remote Area Number: 1 Date: 3/23/2018

Pump
Summary Sheet
Node: 5

Pump Rating:250.00 @ 100.000 Supply:Static:46.000


Residual:40.000
Flowing:1115.00

© M.E.P.CAD, Inc. AutoSPRINK 2018 v14.1.4.0 3/23/2018 2:08:07PM Page 2


Summary Of Outflowing Devices Job Number: C-486
Report Description: Light Hazard (1)
Actual Flow Minimum Flow K-Factor Pressure
Device (gpm) (gpm) (K) (psi)
Sprinkler 101 14.82 14.82 5.6 7.000
Sprinkler 102 18.05 14.82 5.6 10.390
Sprinkler 103 23.09 14.82 5.6 16.996
Sprinkler 104 23.44 14.82 5.6 17.520
Sprinkler 105 24.97 14.82 5.6 19.887

Most Demanding Sprinkler Data

© M.E.P.CAD, Inc. AutoSPRINK 2018 v14.1.4.0 3/23/2018 2:08:08PM Page 3


Job Name: HOME 2 SUITES RICHMOND
Remote Area Number: 1 Date: 3/23/2018

Supply Analysis
Static Residual Flow Available Total Demand Required Pressure
Node Name @ @
(psi) (psi) (gpm) (psi) (gpm) (psi)

Pump Analysis
Churn Residual @ Flow Available @ Total Demand Required Pressure
Node
(psi) (psi) (gpm) (psi) (gpm) (psi)

5 115.000 100.000 250.00 155.222 104.37 117.516

Node Analysis
Node Number Elevation (Foot) Node Type Pressure at Discharge at Notes
Node Node
(psi) (gpm)

1 -4'-0 Supply 8.034 104.37

101 9'-1 Sprinkler 7.000 14.82

102 9'-1 Sprinkler 10.390 18.05

103 9'-1 Sprinkler 16.996 23.09

104 9'-1 Sprinkler 17.520 23.44

105 9'-1 Sprinkler 19.887 24.97

2 -4'-0 7.969

3 1'-6½ 5.556

4 1'-6½ P1 5.469

(-112.020)
5 1'-6 P2 117.516

6 1'-6 117.516

7 1'-5 117.337

8 9'-6 113.583

9 7'-3 113.982

10 9'-6 27.250

11 10'-2 23.019

© M.E.P.CAD, Inc. AutoSPRINK 2018 v14.1.4.0 3/23/2018 2:08:09PM Page 4


Job Name: HOME 2 SUITES RICHMOND
Remote Area Number: 1 Date: 3/23/2018

Node Number Elevation (Foot) Node Type Pressure at Discharge at Notes


Node Node
(psi) (gpm)

12 9'-6 25.080

13 10'-2 19.639

14 10'-2 10.622

© M.E.P.CAD, Inc. AutoSPRINK 2018 v14.1.4.0 3/23/2018 2:08:09PM Page 5


Job Name: HOME 2 SUITES RICHMOND
Remote Area Number: 1 Date: 3/23/2018

Pipe Information
Flow added Length C Factor Notes
Elev 1 Fittings & Total(Pt)
Node 1 K-Factor this step Nominal ID (Foot) Fitting/Device (Equivalent
(Foot) Devices
(q) Length)
Fitting
Pf Friction Elev(Pe) Fixed Pressure Losses,
Equiv. (Foot)
Elev 2 Total Flow Loss Per Unit when applicable, are added
Node 2 Actual ID Length Total (psi)
(Foot) (Q) Friction(Pf) directly to (Pf) and shown as
(Foot) (Foot)
a negative value.

17'-1½ 150 7.000 • • • • • Route 1 • • • • •


101 9'-1 5.6 14.82 ¾ (See
Sprinkler,
Notes) 17'-0 -0.479
0.120247 2E(7'-0), T(3'-0)
14 10'-2 14.82 0.8740
34'-1 4.101

(See 14'-2 150 10.622


14 10'-2 18.05 ¾
Flow (q) from Route 2
Notes) 3'-0
0.525061 T(3'-0)
13 10'-2 32.87 0.8740
17'-2 9.017

(See 0'-8 150 19.639


13 10'-2 23.09 ¾
Flow (q) from Route 3
Notes) 3'-0 0.289
1.405027 T(3'-0)
12 9'-6 55.95 0.8740
3'-8 5.152

15'-0 150 25.080


12 9'-6 1¼

0.144639
10 9'-6 55.95 1.3940
15'-0 2.170

(See 137'-1½ 150 27.250


10 9'-6 48.41 1¼
Flow (q) from Route 4
Notes) 50'-0 0.975
0.458295 4E(8'-0), BV(12'-0), PO(6'-0)
9 7'-3 104.37 1.3940
187'-1½ 85.757

(See 83'-7½ 120 113.982


9 7'-3 4
Notes) 107'-11½ -0.975
0.003004 2T(26'-4), BV(15'-9½), 3E(13'-
8 9'-6 104.37 4.2600
191'-7 0.576
2)

(See 22'-6 120 113.583


8 9'-6 4
Notes) 60'-7½ 3.504
0.003004 2E(13'-2), f, CV(18'-6), BV(15'-
7 1'-5 104.37 4.2600
83'-2 0.250
9½)

(See 8'-3 120 117.337


7 1'-5 4
Notes) 60'-7 -0.027
0.003004 2BV(15'-9½), CV(28'-11½)
6 1'-6 104.37 4.2600
68'-9½ 0.207

0'-0 120 117.516


6 1'-6 3
0.000
0.014859
5 1'-6 104.37 3.0680
0'-0 0.000

Pump 117.516
5 104.37
Rating: 100.000 @ 250.00

4 Churn Pressure: 115.000

(See 0'-0 120 5.469


4 1'-6½ 4
Notes) 28'-11½ 0.000
0.003004 GV(2'-7½), T(26'-4)
3 1'-6½ 104.37 4.2600
28'-11½ 0.087

© M.E.P.CAD, Inc. AutoSPRINK 2018 v14.1.4.0 1 3/23/2018 2:08:11PM Page 6


Job Name: HOME 2 SUITES RICHMOND
Remote Area Number: 1 Date: 3/23/2018

Pipe Information
Flow added Length C Factor Notes
Elev 1 Fittings & Total(Pt)
Node 1 K-Factor this step Nominal ID (Foot) Fitting/Device (Equivalent
(Foot) Devices
(q) Length)
Fitting
Pf Friction Elev(Pe) Fixed Pressure Losses,
Equiv. (Foot)
Elev 2 Total Flow Loss Per Unit when applicable, are added
Node 2 Actual ID Length Total (psi)
(Foot) (Q) Friction(Pf) directly to (Pf) and shown as
(Foot) (Foot)
a negative value.

(See 5'-6½ 120 5.556


3 1'-6½ 6
Notes) 17'-7 2.402
0.000428 E(17'-7)
2 -4'-0 104.37 6.3570
23'-1½ 0.010

(See 157'-8 140 7.969


2 -4'-0 6
Notes) 33'-1
0.000341 E(22'-1), EE(11'-½), S
1 -4'-0 104.37 6.2800
190'-9 0.065

8.034 Hose Allowance At Source


100.00

1 204.37
Total(Pt) Route 1

1'-1 150 10.390 • • • • • Route 2 • • • • •


102 9'-1 5.6 18.05 ¾ (See
Sprinkler,
Notes) 3'-0 -0.479
0.173268 T(3'-0)
14 10'-2 18.05 0.8740
4'-1 0.711

10.622 Total(Pt) Route 2

1'-5 150 16.996 • • • • • Route 3 • • • • •


103 9'-1 5.6 23.09 ¾ (See
Sprinkler,
Notes) 10'-0 -0.479
0.273160 E(7'-0), T(3'-0)
13 10'-2 23.09 0.8740
11'-5 3.122

19.639 Total(Pt) Route 3

15'-3½ 150 17.520 • • • • • Route 4 • • • • •


104 9'-1 5.6 23.44 ¾ (See
Sprinkler,
Notes) 6'-0 -0.479
0.280948 2T(3'-0)
11 10'-2 23.44 0.8740
21'-3½ 5.978

(See 0'-8 150 23.019


11 10'-2 24.97 ¾
Flow (q) from Route 5
Notes) 3'-0 0.289
1.074950 T(3'-0)
10 9'-6 48.41 0.8740
3'-8 3.941

27.250 Total(Pt) Route 4

1'-5 150 19.887 • • • • • Route 5 • • • • •


105 9'-1 5.6 24.97 ¾ (See
Sprinkler,
Notes) 10'-0 -0.479
0.315888 E(7'-0), T(3'-0)
11 10'-2 24.97 0.8740
11'-5 3.611

23.019 Total(Pt) Route 5

© M.E.P.CAD, Inc. AutoSPRINK 2018 v14.1.4.0 1 3/23/2018 2:08:11PM Page 7


Job Name: HOME 2 SUITES RICHMOND
Remote Area Number: 1 Date: 3/23/2018
Equivalent Pipe Lengths of Valves and Fittings (C=120 only) C Value Multiplier

Actual Inside Diameter 4.87 Value Of C 100 130 140 150


( Schedule 40 Steel Pipe Inside Diameter ) = Factor
Multiplying Factor 0.713 1.16 1.33 1.51

Fittings Legend

ALV Alarm Valve AngV Angle Valve b Bushing


BalV Ball Valve BFP Backflow Preventer BV Butterfly Valve
C Cross Flow Turn 90° cplg Coupling Cr Cross Run
CV Check Valve DelV Deluge Valve DPV Dry Pipe Valve
E 90° Elbow EE 45° Elbow Ee1 11¼° Elbow
Ee2 22½° Elbow f Flow Device fd Flex Drop
FDC Fire Department Connection fE 90° FireLock(TM) Elbow fEE 45° FireLock(TM) Elbow
flg Flange FN Floating Node fT FireLock(TM) Tee
g Gauge GloV Globe Valve GV Gate Valve
Ho Hose Hose Hose HV Hose Valve
Hyd Hydrant LtE Long Turn Elbow mecT Mechanical Tee
Noz Nozzle P1 Pump In P2 Pump Out
PIV Post Indicating Valve PO Pipe Outlet PrV Pressure Relief Valve
PRV Pressure Reducing Valve red Reducer/Adapter S Supply
sCV Swing Check Valve SFx Seismic Flex Spr Sprinkler
St Strainer T Tee Flow Turn 90° Tr Tee Run
U Union WirF Wirsbo WMV Water Meter Valve
Z Cap

© M.E.P.CAD, Inc. AutoSPRINK 2018 v14.1.4.0 1 3/23/2018 2:08:11PM Page 8