Sei sulla pagina 1di 40

4.

Determine the approximate length of wire and


ELECTRICAL DESIGN 1 conduct for the panel homerun to the main
THIS COURSE DEALS WITH THE STUDY OF ELECTRICAL SYSTEM panel or main distribution panel.
DESIGN, INSTALLATION AND COST ESTIMATION FOR SINGLE AND 4.1 Conduits – measure the length of the run. Check the
MULTI-FAMILY DWELLING UNITS GUIDED BY THE PROVISIONS OF shortest possible route and avoid obstructions. Total
THE PHILIPPINE ELECTRICAL CODE (PEC) AND OTHER RELEVANT
length divide 3 and add 5%
LAWS AND STNDARDS.
4.2 Wire – multiply the length of conduct by the
COST ESTIMATION following constants
ESTIMATION GUIDE a. 2- for two-wire single phase
1. Prepare paper, pencils, scale and rulers. Mark b. 3- for two-wire single phase with neutral
papers indicating the panel no., circuit number c. 3- for three-wire, 3-phase
and the location of the circuit run. d. 4- for 3-phase, 4 wire
2. Study plans, drawing and specifications. 5. Boxes
2.1 Coordinate with Civil, Mechanical and Architectural 5.1 Octagonal boxes – provide one box for each lighting
Estimators about the following fixtures
2.1.1 Height between floors 5.2 Utility box 4”x 2” – provide one box for each switch,
2.1.2 Drop ceilings and ceiling supports duplex outlet or special outlet (small)
2.1.3 Height between finish floor and ceilings 5.3 Square box 4” – provide one box if the conduits
2.1.4 Major beams and columns thru which conduits terminating exceed 4 conduits or special big outlets.
may not pass 5.4 Square box 4 11/16 – provide one box for one-inch
2.1.5 Other architectural/civil/mechanical drawings diameter conduits or for special purpose outlets. Also
indicating positions of the lights, special outlets or provide one box for multiple (6 or more) terminations.
aircon unit equipment. 5.5 Pull boxes – provide one box for every 18 meters of
2.2 Check and make a physical count of the following conduits length depending upon the length of run.
2.2.1 Lighting fixtures – number of each type of fixtures Other pull boxes may be designated by plans. Check
2.2.2 Convenience outlets – duplex with the designer/consultant about the sizes.
2.2.3 Special outlet 6. Fittings
2.2.4 Panel boards – make a complete description of 6.1 For PVC pipes
each panel board. 6.1.1 Couplings – provide 1 coupling for every length
The description should include: plus 1 coupling for every termination.
a. main breaker rating or lugs only 6.1.2 Elbows – provide 1-900 elbow for every quarter
b. no. of branches per ampere trip turn for sizes of 32 mm (1 1/4”) and above.
c. kAIC 6.1.3 Cement – provide 1 can for every 10 length of
2.2.5 Other electrical equipment to be supplied by conduit.
contractor 6.1.4 End bells – provide 1 for every termination.
2.3 Study carefully the circuit runs and the riser diagram 6.2 For RSC conduits
together with the schedule of load. 6.2.1 Coupling – provide 1 additional coupling for every
3. Determine the approximate length of wire and 5 lengths
conduit per circuit. 6.2.2 Elbows- provide one 90-degree elbow every 90-
3.1 For the conduit (each circuit) - measure the length degree turn for sizes of 25 mm (1”) diameter above.
from the last outlet to the panel using the scale. The 6.2.3 Locknut and bushing – provide one pair for every
trace of the route must be followed as per drawing. termination.
3.2 For the wire – measure the length between outlets 6.3 For electrical metallic tubing
and the length shall be multiplied by the no. of wires. 6.3.1 Couplings- one set for every length
The sum of the products (lengths x the no of wires) shall 6.3.2 Elbows- use on site bended EMT
be the approximate length of wire. 6.3.3 Adapters w/ locknut and bushing- for every
3.3 Sum up the total length of conduit per size and termination are 1 adapter and 1 pair of locknut and
divide by 3. Round off and add 10%. bushings.
3.4 Sum up the total length of wire for each size and 6.4 Straps – two (2) straps for every length of conduit.
divide by 150 to get the no of rolls. Round off and add In sizes of 25 mm diameter and above use clamps
10%. especially for RSC or EMT conduits.
3.5 Set aside the papers and data temporarily. 6.5 Other fittings
6.5.1 Wire trays/cable trays – check with drawings and 10.2 If the conduits and most materials are locally
consultant/designer available
6.5.2 Cable trough / duets – check w/ drawings a. Labor cost is 25 % to 30% of subtotal A
especially that the drawings may have specific sizes. b. Supervision cost is 4% to 5% of subtotal A
7. Other Considerations c. Mark up cost is 2 % of subtotal A
7.1 for lighting fixtures – add 1 m of wire for every 10.3 Contingencies – an allowance of 5% to 7% of the
termination or lighting fixtures total cost of materials and labor
7.2 for convenience outlets 10.4 Overhead – this include the cost of transportation,
a. Add 0.8 m. for every C.0. to the length of pipe and 1m office staff tools and equipment depreciation, papers
of wire for every termination and office supplies to representation, and cost of
b. Add 0.4 m above the height of counters if the C.O. is money.
above the counter in addition to the height of the - Normally 7% to 10% of the cost of materials is the cost
counter. Add also 1 m of wire for every termination. of overhead.
7.3 for homeruns terminating a panel boards add 2 10.5 Permits – show the plans to the municipal
meters of wires for every circuit. electrical engineer or his assistant and request for an
7.4 provide an empty conduit for every spare circuit per estimate. Add 5% to cover the exingencies.
panel 10.6 a. the sum cost as computed in 10.1 and 10.5 is to
7.5 normally the electronic and communication circuits be multiplied by 0.03 to get the contractor’s tax.
will be in separate sheets and have an ECE estimate b. Add the contractor’s tax to the sum of sections 10.1
7.6 provide 1 connector for every termination # 6 up. to 10.5 and round off. This will be your bid price.
8. Summarize the lists of materials as follows
8.1 conduits – total of each size ELECTRIC MOTOR AND OVERCURRENT PROTECTION
8.2 fittings - total of each type/size Parts of a Motor Branch Circuit
8.3 boxes - total of each type/size A - Motor circuit conductor 125 % of current full load
8.4 panels – per panel and lowest canvassed price
8.5 Wires - total length of each wire size B' - Motor disconnecting means
8.6 Connectors – (solderless less) total termination of
each size for wire #6 wire and above. B - Motor Branch Circuit; over current protection
8.7 Tape – 1 roll PVC tape for every 100 m of wire plus 1 usually 300% of full load current for safety switch (SS) or
roll of rubber tape for every 200m of wire. 250% of full load current for air circuit breaker (ACB)
8.8 other materials must be itemized.
9. Costing NOTE: These values are for general purposes motor
9.1 get the unit cost for each item and deduct all only, values of B will depend on type and class of motor.
discounts. The range is from 150% to 300% of the full load current,
9.2 from the total cost add 5% to 10% mark up and shall in no case exceed 400% of full load current.
9.3 For all others materials like duets, panels, transfer
switches, safety switches, and etc.- get the price from C - Motor Controller - rated according to motor
the fabricator net (less discounts) and add 5% markup. horsepower
10. Preparation of Bid or Asking Price
10.1 Material cost D - Motor Running Over current and overload
Conduits Fitting Boxes__________________________ protection: setting is from 115% to 125% of full load
Wires and wiring Devices________________________ current. Value of 1.15 nd 1.25 is called service factor
Lighting fixtures _______________________________ (SF)
Safety Devices_________________________________
Service Entrance and Mains_______________________ 1. Circuit Conductor - for the size of conductor having a
Others________________________________________ maximum ampacity greater than the calculated value to
_______________________ protect the conductor from burning due to overheating.
Subtotal A Faulty wiring is caused by the undersized conductor
10.2 Labor Cost wire.
10.1 If materials are imported
a. Labor Cost is 20 % of subtotal A 2. Branch Circuit Over current Protection - for
b. Supervision is 3% of subtotal A protection against short circuit ground fault which
c. Mark-up is 1.25 % of subtotal A
cause over current flow. It should be capable of carrying 3. Determine the Motor feeder. The current load of a
the starting current of the motor. motor multiplied by 125% (Code requirements)

3. Motor - controller ( magnetic contactor ) - used to 4. Find the size of the conductor wire. Refer to Table,
start and stop the motor. It includes any switch or for 80.56 A, use any of the following:
device capable of interrupting the stalled rotor current
of motor. 3 - 38 mm2 THW or RHW copper wire
3 - 50 mm2 TW copper wire
4. Running Over current and Overload Protection - used 3 - 80 mm2 TW aluminum or copper clad alum
to protect motor controller and motor against excessive 3 - 50 mm2 THW or RHW aluminum or copper clad
heating due to motor overload and failure to start. aluminum

The allowable ampacities of the above wires in Table


CIRCUIT FOR MOTOR LOAD was derated by 80% to carry the 80.56 A current load.

Name plate of the motor 5. Solve for the size of conduit pipe. Refer to Table, use
50 mm diameter pipe.
25 hp,220 volts, 3 phase; 3 wires
60 Hz, 0.84 power factor 90.5% efficiency 6. Determine the size or rating of the over current
protection. The Code provides "The maximum over
current protection for a single motor or a combination
of motors should be, 250% of the ampacity of the
SOLUTION: largest motor plus the sum of the full load current of
the other motors.
1. Solve for the current load:
Therefore:
1 horsepower = 746 watts 64.45 A x 250% = 161.15 A minimum

I = (load in hp x 746 w)/ (k x E x pf x n) 7. Refer to Table. Use 150 A fuse or trip breaker. It is the
nearest standard rating which does not exceed the
where: 161.12 A current load as computed.

k - 1.0 for 2 wire single phase DC


1.73 for 3 wire, 3 phase AC
2.0 for 3 wire single phase AC or DC MATERIALS FOR MOTOR INSTALLATION:
3.0 for 4 wires, 3 phase AC
1. 25 hp Induction motor 230 volts, 3 phase, 1800 rpm,
E - voltage between the neutral and live wire or 60 Hz at 40 degree temperature rise
between two live wires if no neutral line exists
2. Magnetic thermal overload control with contractors.
I - Current in any live wire except Neutral Line
3. Service entrance cap 50 mm with locknut
pf - power factor
4. 38 mm2 THW or RHW copper wire.
N - efficiency
5. 50 mm2 diameter IMT or RSC conduit pipe
2. Applying the formula
6. Conduit clamp with screw, 50 mm conduit pipe
I = (25 hp x 746)/(1.73 x 220 volts x .84 x 90.5%)
7. TPST safety switch or circuit breaker 150 or 250 volts
= 64.45 A
The quantity of materials depends upon the area and
choice of the designing Engineer
circuit leaves the normal current carrying path of the
circuit and takes a “short cut” around the load and back
CALCULATION PROCEDURES IN FINDING THE SIZE OF to the power source. Motors can be damaged by both
FEEDER AND THE OVERLOAD CURRENT PROTECTION types of currents.Single-phasing, overworking and
FOR A GROUP OF MOTORS locked rotor conditions are
just a few of the situations that can be protected
Four 3 - phase motor 220 volts squirrel cage induction against with the careful choice of protective devices. If
motor designed for 40 degree Celsius temperature rise left unprotected, motors will continue to operate even
at 1800 rpm, 60 Hz under abnormal conditions. The excessive current
causes the motor to overheat, which in turn causes the
motor winding insulation to deteriorate and ultimately
SOLUTION: fail. Good motor overload protection can greatly extend
the useful life of a motor. Because of a motor’s
1. Determine the main feeder of the motors. Apply 25% characteristics, many common overcurrent devices
of the biggest motor current load plus the sum of the actually offer limited or no protection.
other motors.

(45 x 1.25) + 39 + 29 +21 Motor Starting Currents


= 145.25 A
When an AC motor is energized, a high inrush current
2. Refer to Table. For the 145.25 A current load use any occurs. Typically, during the initial half cycle, the inrush
of the following conductor wires: current is often higher than 20 times the normal full
load current. After the first halfcycle the motor begins
3 - 80 mm2 THW or RHW copper wire to rotate and the starting current subsides to 4 to 8
3 - 100 mm2 TW copper wire times the normal current for several seconds. As a
3- 125 mm2 THW or RHW aluminum or copper clad motor reaches running speed, the current subsides to
aluminum its normal running level. Typical motor starting
3 - 150 mm2 TW clad aluminum characteristics are shown in Curve 1.

3. Determine the main over current protection. The


National Electrical Code provides that:

" The protection rating or setting of a motor shall be Because of this inrush, motors require special overload
250 % percent (maximum) of the full load current of the protective devices that can withstand the temporary
biggest motor being served plus the sum of the full load overloads associated with starting currents and yet
current of the other motors." protect the motor from sustained overloads. There are
four major types. Each offers varying degrees of
(45 x 125%) x (250% +39 + 29 + 21) protection.
140.625 + 89 = 229.625 A (maximum)
Fast Acting Fuses
4. Refer to Table. Select a fuse or trip breaker that is To offer overload protection, a protective device,
nearest to standard rating that will not exceed 229.62 depending on its application and the motor’s service
A. Use 200 A. factor (S.F.), should be sized at 115% or less of motor
VERLOAD PROTECTION F.L.A. for 1.0 S.F. or 125% or less of motor F.L.A. for 1.15
Overcurrents or greater S.F. However, as shown in Curve 2, when
An overcurrent exists when the normal load current for fast-acting, non-time-delay fuses are sized to the
a circuit is exceeded. It can be in the form of an recommended level the motors inrush will cause
overload or short-circuit. When applied to motor nuisance openings.
circuits an overload is any current, flowing within the
normal circuit path, that is higher than the motor’s A fast-acting, non-time-delay fuse sized at 300% will
normal full load amperes (F.L.A.). A short-circuit is an allow the motor to start but sacrifices the overload
overcurrent which greatly exceeds the normal full load protection of the motor. As shown by Curve 3 below, a
current of the circuit. Also, as its name infers, a short-
sustained overload will damage the motor before the (6) Where incandescent lighting is provided, lighting
fuse can open. equal to one watt per square metre of floor area shall
be considered to meet the requirement in Subsection
ILLUMINATION CALCULATION AND DESIGN FOR B(5)(e).
MULTI-FAMILY DWELLING UNIT
(7) Where self-contained emergency lighting units are
used, they shall conform to CSA C22.2 No. 141-M, “Unit
Equipment for Emergency Lighting”.
(8) Every public or service area in buildings, including a
recreational camp and a camp for housing of workers,
shall have lighting outlets with fixtures controlled by a
wall switch or panel.
Interior lighting. (9) When provided by incandescent lighting,
(1) Within all buildings of three or fewer storeys in illumination required in Sentence (1) shall conform to
building height, having a building area not exceeding Table § 629-36B(1).
600 square metres and used for residential occupancies, (j) When other types of lighting are used, illumination
business and personal services occupancies, mercantile equivalent to that
occupancies or medium and low industrial occupancies. shown in Table 36.B.(1) shall be provided.
(1) Every exit (except those serving not more than one (2) Within all buildings exceeding three storeys in
dwelling unit), public corridor or corridor providing building height or having a building area exceeding 600
access to exit for the public shall be equipped to square metres or used for other occupancies not
provide illumination to an average level of not less than described in Subsection B(1).
50 lux at floor or tread level and at all points such as (a) An exit, a public corridor, a corridor providing access
angles and to exit for the public, a corridor serving patients or
intersections at changes of level where there are stairs residents in a Care and Treatment occupancy or Care
or ramps. occupancy, a corridor serving
classrooms, an electrical equipment room, a
(2) Emergency lighting shall be provided in: transformer vault and a hoistway pit shall be equipped
to provide illumination to an average level not less than
(a) Exits; 50 lux at floor or tread level and at angles and
intersections at changes of level where there are stairs
(b) Principal routes providing access to exit in an open or ramps.
floor area; (b) Rooms and spaces used by the public shall be
illuminated as described in Subsection B(1)(h),(i) and (j).
(c) Corridors used by the public; (c) Elevator machine rooms shall be equipped to
provide illumination to an average level of not less than
(d) Underground walkways; and 100 lux at floor level.
(d) Every place of assembly intended for the viewing of
(e) Public corridors. motion pictures or the performing arts, shall be
equipped to provide an average level of illumination at
(3) Emergency lighting required in Subsection B(1)(b) floor level in the aisles of not less than two lux during
shall be provided from a source of energy separate from the viewing.
the electrical supply for the building. (e) Every area where food is intended to be processed,
prepared or manufactured and where equipment or
(4) Lighting required in Subsection B(2)(b) shall be utensils are intended to be
designed to be automatically actuated for a period of
not less than 30 minutes when the electric lighting in (2) Within all buildings exceeding three storeys in
the affected area is interrupted. building height or having a building area exceeding 600
square metres or used for other occupancies not
(5) Illumination from lighting required in Subsection described in Subsection B(1).
B(2)(b) shall be provided to average levels of not less
than 10 lx at floor or tread level. (a) An exit, a public corridor, a corridor providing access
to exit for the public, a corridor serving patients or
residents in a Care and Treatment occupancy or Care The lumen method is applied only to square or
occupancy, a corridor serving rectangular rooms with a regular array luminaires as
classrooms, an electrical equipment room, a shown in Figure 2.
transformer vault and a hoistway pit shall be equipped 2. Lumen Method Calculations
to provide illumination to an average level not less than The lumen method is based on fundamental lighting
50 lux at floor or tread level and at angles and calculations. The lumen method formula is easiest to
intersections at changes of level where there are stairs appreciate in the following form.
or ramps. (1)
where E = average illuminance over the horizontal
(b) Rooms and spaces used by the public shall be working plane
illuminated asdescribed in Subsection B(1)(h),(i) and (j). n = number of lamps in each luminaire
N = number of luminaire
(c) Elevator machine rooms shall be equipped to F = lighting design lumens per lamp, i.e. initial bare lamp
provide illumination to an average level of not less than luminous
100 lux at floor level. flux
UF = utilisation factor for the horizontal working plane
(d) Every place of assembly intended for the viewing of LLF = light loss factor
motion pictures or the performing arts, shall be A = area of the horizontal working plane
equipped to provide an average levelof illumination at
floor level in the aisles of not less than two lux during
the viewing. 2.1 Light Loss Factor

(e) Every area where food is intended to be processed, Light loss factor (LLF) is the ratio of the illuminance
prepared or manufactured and where equipment or produced by the lighting installation at the some
utensils are intended to be specified time to the illuminance produced by the same
installation when new. It allows for effects such as
In a service space in which facilites are included to decrease in light output caused by
permit a person to enter and to undertake maintenance (a) the fall in lamp luminous flux with hours of use,
and other operations; and On a shelf and rack storage (b) the deposition of dirt on luminaire, and
system, which includes walkways, platforms, (c) reflectances of room surfaces over time.
unenclosed egress stairs and exits providing means of
egress. In fact, light loss factor is the product of three other
factors:
(j) The minimum value of the illumination required by
Subsections B(2) (h) and (i) shall be not less than one (2)
lux. where LLMF = lamp lumen maintenance factor

(k) In addition to the requirements of Subsections LMF = luminaire maintenance factor


B(2)(h) to (j), the installation of battery-operated
emergency lighting in health care facilities shall conform RSMF = room surface maintenance factor
to the appropriate requirements of CSA Z32, “Electrical
Safety and Essential Electrical Systems in Health Care
Facilities”. C. For parking lots, walkways, stairs, porches, 2.1.1 Lamp Lumen Maintenance Factor
verandas, loading docks, ramps or other similar areas, a
minimum level of illumination of ten lux (0.90 foot- Lamp lumen maintenance factor (LLMF) is the
candle) at ground or tread level and at angles and proportion of the initial light output of a lamp produced
intersections at changes of level where there are stairs after a set time to those produced when new. It allows
or ramps. for the decline in lumen output from a lamp with age.
Introduction to the Lumen Method Its value can be determined in two ways:
The lumen method is applicable to design of a uniform
(general) lighting scheme in a space where flexibility of (a) by consulting a lamp manufacturer's catalog for a
working locations or other activities is required. lumen depreciation chart, and
(b) by dividing the maintained lumens by the initial
lamps.

2.1.2 Luminaire Maintenance Factor

Luminaire maintenance factor (LMF) is the proportion Amount of light energy absorbed in luminaire = 100 - 80
of the initial light output from a luminaire after a set = 20 %
time to the initial light output from a lamp after a set
time. It constitutes the greatest loss in light output and A greater DLOR usually means a higher UF.
is mainly due to the accumulation of atmospheric dirt
on luminaire. Three factors must be considered in its A simple classification of luminaires according to their
determination: distribution is based on flux fractions, as shown in
Figure 5. Upward flux fraction (UFF) and downward flux
(a) the type of luminaire, fraction (DFF) are used as a basis of comparison.

(b) atmospheric conditions, and Example 2


(c) maintenance interval.
2.1.3 Room Surface Maintenance Factor For data given in Example 1 determine upward flux
Room surface maintenance factor (RSMF) is the fraction (UFF), downward flux fraction (DFF) and flux
proportion of the illuminance provided by a lighting fraction ratio (FRR).
installation in a room after a set time compared with
that occurred when the room was clean. It takes into
account that dirt accumulates on room surfaces and
reduces surface reflectance. Figure 4 shows the typical
changes in the illuminance from an installation that
occur with time due to dirt deposition on the room
surfaces.
2.2 Utilisation Factor
Utilisation factor (UF) is the proportion of the luminous
flux emitted by the lamps which reaches the working
plane. It is a measure of the effectiveness of the lighting Figure 5 Flux Fraction of Various Luminaires
scheme. Factors that affect the value of UF are as
follows:
(a) light output ratio of luminaire
(b) flux distribution of luminaire 2. Lumen Method Calculations
(c) room proportions
(d) room reflectances
(e) spacing/mounting height ratio The lumen method is based on fundamental lighting
2.2.1 Light Output Ratio of Luminaire calculations. The lumen method formula is easiest to
Light output ratio of luminaire (LOR) takes into account appreciate in the following form.
for the loss of light energy both inside and by
transmission through light fittings. It is given by the (1)
following expression.
(3) where E = average illuminance over the horizontal
Example 1 working plane
The total, upward and downward lamp output from a n = number of lamps in each luminaire
lamp are 1000 lm, 300 lm and 500 lm respectively. N = number of luminaire
Calculate upward light output ratio (ULOR), downward F = lighting design lumens per lamp, i.e. initial bare lamp
light output ratio (DLOR), light output ratio (LOR) of luminous
luminaire and percentage of light energy absorbed in flux
luminaire. UF = utilisation factor for the horizontal working plane
LLF = light loss factor
A = area of the horizontal working plane (a) the type of luminaire,
2.1 Light Loss Factor
(b) atmospheric conditions, and
Light loss factor (LLF) is the ratio of the illuminance
produced by the lighting installation at the some (c) maintenance interval.
specified time to the illuminance produced by the same
installation when new. It allows for effects such as
decrease in light output caused by 2.1.3 Room Surface Maintenance Factor

(a) the fall in lamp luminous flux with hours of use, Room surface maintenance factor (RSMF) is the
proportion of the illuminance provided by a lighting
(b) the deposition of dirt on luminaire, and installation in a room after a set time compared with
that occurred when the room was clean. It takes into
(c) reflectances of room surfaces over time. account that dirt accumulates on room surfaces and
reduces surface reflectance. Figure 4 shows the typical
In fact, light loss factor is the product of three other changes in the illuminance from an installation that
factors: occur with time due to dirt deposition on the room
surfaces.
(2)

where LLMF = lamp lumen maintenance factor 2.2 Utilisation Factor

LMF = luminaire maintenance factor Utilisation factor (UF) is the proportion of the luminous
flux emitted by the lamps which reaches the working
RSMF = room surface maintenance factor plane. It is a measure of the effectiveness of the lighting
scheme. Factors that affect the value of UF are as
follows:
2.1.1 Lamp Lumen Maintenance Factor
(a) light output ratio of luminaire
Lamp lumen maintenance factor (LLMF) is the
proportion of the initial light output of a lamp produced (b) flux distribution of luminaire
after a set time to those produced when new. It allows
for the decline in lumen output from a lamp with age. (c) room proportions
Its value can be determined in two ways:
(d) room reflectances
(a) by consulting a lamp manufacturer's catalog for a
lumen depreciation chart, and (e) spacing/mounting height ratio

(b) by dividing the maintained lumens by the initial


lamps. 2.2.1 Light Output Ratio of Luminaire

Light output ratio of luminaire (LOR) takes into account


2.1.2 Luminaire Maintenance Factor for the loss of light energy both inside and by
transmission through light fittings. It is given by the
following expression.
Luminaire maintenance factor (LMF) is the proportion (3) Example 1
of the initial light output from a luminaire after a set The total, upward and downward lamp output from a
time to the initial light output from a lamp after a set lamp are 1000 lm, 300 lm and 500 lm respectively.
time. It constitutes the greatest loss in light output and Calculate upward light output ratio (ULOR), downward
is mainly due to the accumulation of atmospheric dirt light output ratio (DLOR), light output ratio (LOR) of
on luminaire. Three factors must be considered in its luminaire and percentage of light energy absorbed in
determination: luminaire.
Amount of light energy absorbed in luminaire = 100 - 80 2.2.3 Room Proportion
= 20 %

A greater DLOR usually means a higher UF. Room index (RI) is the ratio of room plan area to half
the wall area between the working and luminaire
A simple classification of luminaires according to their planes.
distribution is based on flux fractions, as shown in
Figure 5. Upward flux fraction (UFF) and downward flux (4)
fraction (DFF) are used as a basis of comparison.
where L = length of room
Example 2
W = width of room
For data given in Example 1 determine upward flux
fraction (UFF), downward flux fraction (DFF) and flux Hm = mounting height, i.e. the vertical distance
fraction ratio (FRR). between the working plane and the luminaire.

2.2.4 Room Reflectances

The room is considered to consist of three main


surfaces:

(a) the ceiling cavity,

(b) the walls, and


Figure 5 Flux Fraction of Various Luminaires
(c) the floor cavity (or the horizontal working plane).

2.2.2 Flux Distribution of Luminaire The effective reflectances of the above three surfaces
affect the quantity of reflected light received by the
Direct ratio is the proportion of the total downward working plane.
luminous flux from a conventional installation of
luminaires which his directly incident on the working
plane. It is used to assess the flux distribution of 2.2.5 Spacing to Height Ratio
luminaire. Since the intensity distribution pattern of the
light radiated from a luminaire in the lower hemisphere Spacing to Height ratio (SHR or S/Hm) is defined as the
will affect: ratio of the distance between adjacent luminaires
(centre to centre), to their height above the working
(a) the quantity of the downward flux falls directly on plane. For a rectangular arrangement of luminaires and
the working plane and by approximation,

(b) the quantity of flux available for reflection from the (5)
walls in a given room,
where A = total floor area
Direct ratio depends on both the room proportions and
the luminaires. Direct ratio has a low value with a N = number of luminaires
narrow room (small room index) and a luminaire which
emits most of its light sideways (BZ 10), and on the Hm = mounting height
contrary, a high value with a wide room (large room
index) and a luminaire which emits most of its light Under a regular array of luminaires the illuminance on
downwards (BZ 1). the working plane is not uniform. The closer spaced the
luminaires for a given mounting height, the higher the
uniformity; or the greater the mounting height for a
given spacing, the greater the uniformity. If uniformity Design a lighting installation for a college seminar room
of illuminance is to be acceptable for general lighting, so that the average illuminance is 500 lux on the
horizontal working plane, using the data listed below.
(a) SHR should not exceed maximum spacing to height Suggest the layout and check appropriate spacing to
ratio (SHR MAX) of the given luminaire as quoted by the mounting height.
manufacturer, and
Room dimensions: 12 m long x 8 m wide x 3.2 m high
(b) geometric mean spacing to height ratio of the
luminaire layout should be within the range of nominal Working plane at 0.7 m above floor
spacing to height ratio (SHR NOM) of the given
luminaire as quoted by the manufacturer, i.e. Reflection factors: Ceiling 70 %

(6) Walls 50 %

Working plane 20 %

3. Summary of Procedures for Lumen Design Method Light Loss factor: 0.779

(a) Calculate the room index. Luminaires: 1800 mm twin tube with opal diffuser

(b) Determine the effective reflectances of the ceiling Ceiling mounted


cavity, walls and floor cavity.
Downward light output ratio 36 %
(c) Determine the utilisation factor from the
manufacturer's data sheet, using the room index and SHR MAX 1.60 : 1
effective surface reflectances as found in (a) and (b)
above. SHR NOM 1.50 : 1

(d) Determine the light loss factor. Dimensions : 1800 mm long x 200 mm wide

(e) Inert the appropriate variables into the lumen Lamps: 1800 mm 75 W plus white
method formula to obtain the number of luminaires
required. 5800 average initial lumens per lamp

(f) Determine a suitable layout. 2 lamps per luminaire

(g) Check that the geometric mean spacing to height


ratio of the layout is within the SHR NOM range:
Solution

(a) Initial calculation


(h) Check that the proposed layout does not exceed the
maximum spacing to height ratios (SHR MAX).

(i) Calculate the illuminance that will be achieved by the From manufacturer's photometric data sheet (Table 3),
final layout and check against the standard. utilisation factor (UF) is 0.5336 by interpolation.

Therefore, the number of luminairs is 10.


Example 3
Initial check on S/Hm ratio gives:
the light source and no direct light from the source is
visible. The shielding angle is the angle, measured from
From the manufacture's photometric data, maximum horizontal, through which the fixture provides shielding
S/Hm is 1.6 : 1. Therefore, it should be possible to use to prevent direct viewing of the light source. The
10 luminaires. shielding and cut-off angles add up to 90 degrees.
The lighting upgrade products mentioned in this
(b) Proposed layout document are described in more detail in Lighting
Upgrade Technologies.
A 5 x 2 array is proposed fro the lighting installation. (A
10 x 1 array is an alternative.) WIRING CALCULATION FOR MULTI-FAMILY DWELLING

(c) Checking the proposed layout Multi - Family Dwelling


4 - door apartment
Since 2 x 1.8 m = 3.6 m < 8 m (width of room), the Types of Service: 230 V
proposed layout will fit. 2 wire, Line to Ground System
Floor Area per unit: 80 sq. m
(Usually checking only the linear dimension of the fitting Total Floor Area: 320 sq. m
for space is enough as the other dimension (i.e. 200 mm
in this case) is much smaller.) Determine the branch circuit protection, size of
For long axis, conductor wires and the main header.
For short axis,
Note that if the checks had worked out to be
unsatisfactory, the number of luminaires should be SOLUTION:
reconsidered and the calculations on the illuminance
should be repeated. For example, a 3x3 array for lower Assume that the dwelling unit is equipped with one 5.1
lux level or a 4x4 array for higher lux level. kW cooking unit; one unit laundry ckt. at 1.5 kW
Distribution
One of the primary functions of a luminaire is to direct A. Circuit - 1 For Lighting Load per unit (see plan)
the light to where it is needed. The light distribution
produced by luminaires is characterized by the 1. By the area method, refer to Table, General Lighting
Illuminating Engineering Society as follows: Load by occupancy for dwelling units.
Direct ( 90 to 100 percent of the light is directed
downward for maximum use. 80 sq. m x 24 watts per sq. m = 1920 watts
Indirect ( 90 to 100 percent of the light is directed to the
ceilings and upper walls and is reflected to all parts of a
room. 2. Compute for the Lighting Load. Divide:
Semi-Direct ( 60 to 90 percent of the light is directed
downward with the remainder directed upward. 1920 watts/230 volts = 8.35 A
General Diffuse or Direct-Indirect ( equal portions of the
light are directed upward and downward. 3. Determine the size of the Branch Circuit conductor
Highlighting ( the beam projection distance and wire. Refer to Table. For 8.35 A load, use 2 pieces 2.0
focusing ability characterize this luminaire. mm2 or No. 14 TW AWG copper wire
The lighting distribution that is characteristic of a given
luminaire is described using the candela distribution 4. Determine the size of the conduit pipe. For number
provided by the luminaire manufacturer (see diagram 14 AWG , TW wire use 13 mm minimum size of conduit
on next page). The candela distribution is represented pipe.
by a curve on a polar graph showing the relative
luminous intensity 360 around the fixture ( looking at a 5. Determine the size or rating of the branch circuit
cross-section of the fixture. This information is useful protection. Refer again to Table. For 8.35 A load on a
because it shows how much light is emitted in each 2.0 mm2 wire conductor size, use 15 A fuse or trip
direction and the relative proportions of downlighting breaker.
and uplighting. The cut-off angle is the angle, measured
from straight down, where the fixture begins to shield
B. Circuit - 2 For Convenience Outlet Load 2. Refer to Table Demand load for household. For
electric range, apply 80% demand factor.
1. Solve for the total current load.
Total load x demand factor (Df)
8 receptacles x 2 gang per outlet x 180 watts = 2880 5100 watts x .80 = 4080 watts
watts
3. Compute for the line current load. Divide:
2. Solve for the appliance current load. Divide.
4080 watts/230 volts = 17.74 A
I = 2880 watts/230 volts = 12.52 A
4. Find the size of the branch Circuit wire. Refer to Table
3. Determine the size of the Branch Circuit conductor. 0.1 or 11.1. For 17.74 A line current, use 5.5 mm2 or
Refer to Table 9.1 or 11.1. For a 12.52 A load, a 2.0 No.10 TW copper wire.
mm2 or No.14 TW AWG wire would be sufficient
considering its 15 A ampacity that is bigger than 12.52 A 5. Determine the size of the conduit pipe. From Table,
as computed for No.10 TW wire, use 20 mm diameter pipe.

4. But the National Electrical Code limits the size of 6. Find the size of the branch circuit fuse protection.
convenience outlet wire to minimum of 3.5 mm2 or No. Refer to Table, for 17.74 A current load, use 30 A fuse or
12 AWG copper wire. The code must prevail. Use No. 12 trip breaker.
TW.

5. Determine the size of the conduit pipe. Refer to Table E. Determine the sub-feeder per dwelling
. For No. 12 TW wire, use 13 mm diameter pipe.
1. Solve for the total connected load per dwelling.
6. Find the Size of the Branch Circuit fuse protection.
Refer to table. For 12.53 A non continuous load on Lighting load ........................................ 1920 watts
convenience outlet, use 20 AT breaker. Convenience Load ,............................... 2880 watts
Other loads 5.1 + 1.5 kW........................ 6600 watts

C. Circuit - 3 Other Load TOTAL....................................11400 watts

1. Laundry Circuit at 1500 watts per circuit (PEC 2. Apply 80% demand factor (see Table)
provision)
TOTAL LINE CURRENT = (11400 watts x.80 df)/230 volts
1500 watts/230 volys = 6.52 A
= 39.65 A
2. Find the size of the branch circuit conductor. From
Table, use 3.5 mm2 or No. 12 TW copper wire, the 3. Determine the Size of the sub-feeder and protection
minimum size for convenience outlet. per dwelling for 39.65 A. For Table 9.1 or 11.1, use 8.0
mm2 or No. 8 wire THW copper wire.
3. Find the size of the conduit pipe. From Table, use 13
mm diameter pipe. 4. Find the size of the conduit pipe. For 8.0 mm2 wire,
specify 25 mm diameter pipe.
4. Find the size of the branch circuit fuse protection.
From Table. The 6.52 A load on convenience outlet 5. Determine the size or rating of the fuse protection.
requires 20 A fuse or trip breaker. From Table, use 60 A molded Circuit breaker 2- wire 250
volts with solid bus.

D. Circuit - 4 Cooking Unit

1. Total Load is 5.1 kW = 5100 watts F. Determine the Size of the Main Feeder
2. The quality of light
1. Solve for the Total connected Load on 4 dwelling
units at 11400 watts each. Multiply:
Quantity of Light – refers to the amount of illumination
11400 watts x 4 = 45600 watts or luminous flux per unit area.
Quantity of light can be measured and easily handled
2. Refer to Table. For 4 dwelling units apply 45% because it deals with the number of light fixtures
demand factor. Multiply: required for a certain area.

45600 watts x .45 = 20520 watts


Quality of Light – refers to the distribution of brightness
3. Solve for the line current: in the lighting installation. It deals with the essential
nature or characteristics of light. In short, quality of light
I = 20520 watts/230 volts = 89.22 A is the mixture of all the items related to illumination
other than the quantity of light which includes several
4. Determine the Size of the Conductor wire. Refer to elements such as:
Table. For 89.22 A, use 2- 50 mm2 TW copper wire or 2-
38 mm2 THW copper wire. 1. Brightness
2. Brightness ratio or contrast
COMMENT: 3. Glare
4. Diffuseness
IT will be noted in Table, that the 89.22 A as computed 5. Color
does not exceed 80 % of the 120 allowable ampacity of 6. Aesthetics
50 mm2 TW copper wire or 125 ampacity of 38 mm2 7. Psychological reaction to color and fixtures
THW copper wire. Therefore, any one of these two 8. Economics
types of wire could be used for main feeder.

5. Find the size of conduit pipe. Refer to Table. Use 38 There are four factors that affect illumination, namely:
nn diameter RSC or IMT pipe 1. Brightness
2. Glare
6. Find the size or rating of the over-current protection. 3. Contrast
Refer to Table. Use 125 A safety switch,250 volts, 2 4. Diffuseness
pole.

ILLUMINATION CALCULATION AND DESIGN FOR SINGLE Brightness is the light that seems to radiate from an
FAMILY DWELLING object being viewed. Brightness or luminance is the
PRINCIPLES OF ILLUMINATION luminous flux (light) emitted, transmitted or reflected
6 – 1 INTRODUCTION from a surface.

Illumination is defined as the intensity of light per unit Contrast is the difference in brightness or the brightness
area. When we talk of illumination, or simply lighting, ratio between an object and its background. The
we are referring to man made lighting. Daylight being recommended brightness ratio between an object being
excellent is not included, thus, we assume a night time viewed and its background is normally 3:1.
condition.
If a print on a white paper can be clearly seen on a light
background, it is due to the effect called contrast.
Electric Illumination is the production of light by means Likewise, if a light object is placed on a dark
of electricity and its applications to provide efficient, background, the light object reflects more light and
comfortable and safe vision. Specifically, when one looks brighter although bought have equal illumination.
speaks of lighting design, he refers to only two things: It is for this reason that office furniture are generally
light colored, tan or light green for eye comfort.

1. The quantity of light


Glare is a strong, steady, dazzling light or reflection. 1. The Comparator type which requires the operator to
There are two types of glare: make a brightness equivalence judgment between the
1. Direct Glare is an annoying brightness of light in a target and the background.
person’s normal field of vision. 2. The Direct Reading type is basically an illumination
2. Indirect or Reflected Glare is much more serious and meter equipped with a hooded cell arranged to block
difficult to control. Technically, reflected glare is a oblique light.
glossy object. 3. The Accurate Laboratory Instrument which unsuitable
for field work.

Diffuseness refers to the control of shadows cast by The quantity of light level of illumination can be easily
light. Diffuseness is the degree to which light is measured or calculated with the aid of portable foot
shadowless and is therefore a function of the number of candle meter.
directions to which light collides with a particular point
and the comparative intensities. Footcandle (fc) is the amount of light flux density. It is
the unit of measure used when describing the amount
of light in a room and is expressed in lumens per square
Perfect Diffusion is an equal intensities of light clashing foot.
from all directions producing no shadows. A single lamp
will cast sharp and deep shadows. A luminous ceiling
provides a satisfactory diffuse illumination and less Footlambert (fl) is defined as “the luminance of a
shadows. surface reflecting. Transmitting or emitting one lumen
(lm) of illumination per square foot of area in the
direction being viewed or the conventional unit of
The color of lighting and the corresponding color of the brightness or luminance. In the same manner, the
object within a space is an important consideration in lumens (lm) is the light output generated continuously
producing a quality of light. by a standard wax candle
There are three characteristics that define a particular
coloration. They are:
In our study of light, we are interested in the amount of
light that fall on the areas that we want to illuminate.
a. Hue – is the quality attribute by which we recognize We also want to know the lumens per square foot or
and describe colors as red, blue, yellow, green, violet square meter in a space.
and so on. This quantity called Light Flux Density is the common
b. Brilliance or Value – is the difference between the term Foot-candle (fc) represented by the formula:
resultant colors of the same hue, such as: white is the Footcandle = Lumens
most brilliant of the neutral colors while black is the Area
last.
c. Saturation or Chroma – is the difference from the ILLUSTRATION 6 – 1
purity of the colors. Colors of high saturation must be A 40 – watt fluorescent lamp 120 centimeters long
used in well lit spaces. produces 3,200 lumens of light in a room having a
general dimension of 10 x 20ft. Find the illumination on
the floor.
6 – 2 ESTIMATING ILLUMINATION AND BRIGHTNESS
In many respect, it is more important to know
luminance measurements than illumination because the SOLUTION
eye is more sensitive to brightness than simple Footcandle = Lumens
illumination. However, it is more difficult to measure Area
luminance than illumination. fc = 3,200 lm. = 16 footcandle
10 x 20 ft.
The footcandle is an important unit of measure in
There are three types of luminance meter, namely: calculating the desired illumination and layout of
fixtures. In the absence of Tables of equivalent
footcandles for a particular fixture, a rule of thumb of Table 6 – 2 TABLE OF COMPARISON
10-30-50 illumination level is here presented.

10 – footcandle is adequate for halls and corridors


30 – footcande is sufficient for areas between work ILLUSTRATION 6 – 3
stations such as in offices other than desk areas. A 40 – watts x 120 centimeters long fluorescent lamp
50 – footcandle is satisfactory on spaces where office produces 3,200 lumens of light in a room having a
work is done. general dimension of 10ft. x 20ft. Compute the
illumination on the floor comparing the English and the
Metric units.
However, providing an adequate quantity of light alone SOLUTION BY COMPARISON
is not a guarantee for an efficient and comfortable English Metric (SI)
vision. In fact, the quality of light is very important Light Flux = 3,200 lm. …………………. 3,200 lm
especially where difficult visual needs are required. The Area = 10’ x 20’ …………………. 10 x 20
luminance or brightness of a diffusely reflecting surface 10.76
is equal to the product of the illumination and the = 200 sq. ft. ………………… 18.59 sq. m.
reflectance. Thus; Illumination = 16 fc ……………………… 172.16 lux
Another SOLUTION
Luminance = Illumination x Reflectance factor or Convert: 10 feet to meter = 3.048 m.
Footlambert = Footcandle x Reflectance factor 20……………. = 6.097 m.
Lux = 3,200 = 172.19 Lux
ILLUSTRATION 6 – 2 3.048 x 6.097
From illustration 6 – 1, find the luminance if the ILLUSTRATION 6 – 4
reflectance factor of the wall is 40%. Compute for the brightness of a fixture with a 1’x 4’
plastic diffuser having a transmittance of .6 and
SOLUTION illuminated by 2 pieces 3,200 lm. lamp assuming 100%
1. Footlambert = Footcandle x Reflectance factor use of light flux.
= 16 x 40% = 6.4
SOLUTION
Metric Lighting Units 1. Luminance = Total lumens x transmission factor
In English System of measure, the distance is expressed Area of diffuser
in feet and the area is in square feet. Under the Metric = 2pcs. x 3,200 x .6
System (SI) the distance and area are expressed in 1’ x 4’
meters and square meters respectively. = 960 footlambert
1. To obtain the metric equivalent, multiply:
Meanwhile, Lumens flux remains in Lumens but Millilambert = Footlambert x 1.076
illumination or light flux is expressed in Lux. Thus: = 960 x 1.076
Lux = Lumens = 1032.96 millilambert
Area (sq. m.)
The Watts per Square Meter
Another method used in determining the illumination is
Table 6 -1 APPROXIMATE REFLECTANCE FACTOR the watts per square meter wherein the floor area is
computed from the outside dimensions of the building
excluding open porches.
In the metric system, Luminance or Brightness is
expressed in Lambert which is defined as “the
luminance or brightness of a surface reflecting, Depending upon the size of the room, color of wall and
transmitting or emitting one lumen per square ceiling, types of lighting units and methods of lighting
centimeter. Millilambert is more conveniently used than used, the watts per square meter method is may
the lambert because the value of lambert is greater produce 50 to 100 lux which is approximately 5 to 10
than what is usually encountered. footcandles.
1. Twenty watts (20) per square meter will provide an
illumination of 100 to 150 lux which is approximately 10
to 15 fc in industrial areas. TABLE 6 – 4 MAINTENANCE FACTOR
2. For commercial areas, two (2) watts per square foot
or 22 watts per square meter is will provide from 80 to ILLUSTRATION 6 – 5
120 lux when used with standard quality equipment. A school classroom with a general dimension of 24 x 30
3. Forty (40) watts per square meter will provide about ft. is lighted with 10 fluorescent of 4F 40 T12 WW rapid
200 lux which is approximately 20 fc wherein greater start lamp. Calculate the initial and maintained
illumination is required illumination in footcandles (English) and Lux (Metric)
4. Sixty (60) watts per square meter will provide about assuming that (cu) is 0.35 and (mf) is 0.70.
300 lux or approximately 30 fc which is recommended
for many conventional, industrial and commercial SOLUTION – 1 (English Measure)
requirements. 1. Refer to Table 5 – 3. An F 40 T12 WW watts
5. Eighty (80) watts per square meter will provide from fluorescent lamp has 3,200 lm. output. Multiply:
300 to 350 lux and in excess of supplementary lighting is Lamp lumens = 10 fixturesX 4 lamps per fixture X 3,200
necessary. lumens per lamp
= 128,000 lumens
Initial footcandle = 128,000 x 0.35
6 – 3 COEFFICIENT OF UTILIZATION AND MAINTENANCE 24 x 30 ft.
FACTOR = 62.22 fc x 0.70 mf
= 43.55 footcandle
The usable Initial footcandle or lux is equal to the SOLUTION – 2 By Metric Measure (SI)
footcandle produced by the coefficient of utilization Convert feet to meter: 24 ft. = 7.32 m.
(cu). 30 ft = 9.14 m.
Lux = Lumens x cu x mf
Initial was emphasized because the output is of a light Area
fixture is reduced with time as the lamp fixture is = 10 x 4 x 3,200 x 0.35 x 0.70
becomes old and dirty. Lamp output normally drops and 7.32 m. x 9.14 m.
is termed as Maintenance factor (mf). And to find the = 468.75 lux
average maintained illumination, we reduce the initial Check the answer:
illumination by the maintenance factor. One lux = .09294
468.75 x .09294 = 43.56 fc.
The efficiency of a light fixture is equals the ratio of Sometimes when the size of the room and the
fixture output lumens to lamp output lumens. What we footcandle are given, the problem is how to find the
need is to determine a number indicating the efficiency number of lamps required in each fixture. The following
of the fixture room combination, or how a particular example is offered.
light fixture lights a particular room. This number is
normally expressed in decimal value called coefficient ILLUSTRATION 6 – 6
of utilization represented by letter (cu). An office room having a general dimension of 8 x 20
meters is to be lghted at an averaged maintained
The usable initial footcandle is equal to the footcandle footcandle of 50 fc, How many 3-lamp fixtures of 120
produced by the coefficient of utilization (cu). centimeters long F40 T12 WW rapid start fluorescent
lamps are required assuming the cu is 0.38 and the mf is
a.) Initial Footcandle = footcandle x cu. 0.75?
Area
b.) Maintenance illumination = Lamp lumens x cu x mf SOLUTION
Area 1. Lamp lumens = maintained footcandle x area
* Lamp lumen therefore is simply the rated output of cu x mf
the lamp. = 50 fc x (8m. x 20 m.)
0.38 x 0.75
= 28,070 lumens
TABLE 6 – 3 COEFFICIENT OF UTILIZATION 2. Each 40 watt fluorescent lamp has an output of 3,200
lumens, the number of lamps will be:
Number of lamps = 28,070 2.87
3,200 6 – 4 MEASURING FOOTCANDLE
= 8.77 lamps The unit measure of illumination is the footcandle or lux
3. Since there are 3 lamps for each fixture, divide: in the Metric System which is frequently used when
8.77 = 2.93 say 3 lamps in ach fixture describing the amount of light in a room. It is not
3 enough to know how to calculate the illumination level
Calculation involving a wide area is more confusing than but it is also equally important to know how to measure
by computing the number of lamp fixtures per bay or them in enclosed space. In measuring illumination level,
per row which is more meaningful and interesting. the footcandle meter is held horizontally with its
This could be done easily by using the following sensitive surface at least 30 centimeters from the body
formula: of the person holding the meter, The meter could be
Number of mixtures = Illumination x area placed on a table and read from a distance to avoid
Lamp per fixture x lumens x cu x mf obstruction of the light.
In conducting a general illumination check inside a
This means that the area lighted by a single area is: room, the meter is held at least 80 centimeters above
Area per fixture = lamp per fixture x lumens per lamp x the floor. Reading is undertaken throughout the room
cu x mf and the results are recorded on the plan of the room.
Illumination

TABLE 6 – 6 EFFICACY OF VARIOUS LAMPS

a. All dimensions in meters


ILLUSTRATION 6 – 7 b. These spacing apply where desks and benches are
An entire office floor is lighted at an averaged next to wall, otherwise, one third the spacing between
maintained 538 lux or 50 fc. The floor measures 20 units is satisfactory.
meters by 50 meters and is divided into bays measuring c. The actual spacing of luminaries is usually less the
4 m. x 5 m. Using 2-lamp of F40 T12 CW rapid start maximum spacing to suit bay or room dimensions.
preheat lamp, find the number of fixtures required. d. For mounting height of general diffusing and direct-
Assume an economy grade fixture with a lo cu of 0.35 indirect fixtures.
and mf of 0.70
SOLUTION – 1 6-5 Uniformity of Light
Solve for the number of fixtures per bay. The purpose of lighting calculations, by the foot-candle
Refer to Table 5-3 for F40 T12 CW = 3,150 lm. or lux, is to determine the average illumination in a
No. of Fixtures = Illumination x area room or lux, is to determine the average illumination in
Lamp per fixture x lumens x cu x mf a room to a working level condition. This working level
Fixtures = 538 lux x (4 m. x 5m. ) condition refers to the height of 75 centimeters above
2-lamps x 3,150 lm. x 0.35 x 0.70 the floor being the approximate height of the table. The
= 10,760 = 6.9 fixtures average illumination at the working level is directly
1,543 related to the maximum spacing of the light to the
Accept 6 pieces per bay to make it symmetrical mounting height ratio represented by the formula.
SOLUTION – 2
1. From the following Formula, substitute the values: S/mh where: S = Spacing of light fixtures
Area per Fixtures = Lamp per fixture x lumen/ lamp x cu mh = mounting height
x mf Normally, the manufacture of light provides data with
Illumination respect to spacing and mounting ratio. However, in the
Fixtures = 2-lamps per fixture x 3,150 lm. x 0.35 x 0.70 event that the manufacturer failed to provide these
538 lux data, Table 6-8 was presented shoeing the spacing and
= 1,543.5 = 2.87 sq.m. per fixture mounting height ratio for particular lighting conditions.
538
2. Therefore, the number of fixture per bay is: Table 6-8 SPACING AND MOUNTING HEIGHT RATIO
4 m x 5m = 6.9 say 6 pcs. Per bay for symmetry
ILLUSTRATION 6-8 Indirect Lighting. When the light is diffused and
A room with a ceiling height of 3 meters is to be lighted reflected from a wide ceiling area. This kind of lighting
with direct concentrating fluorescent light. What is the produces a soft and subdued effect due to low
maximum fixtures spacing? brightness and absence of sharp shadows.
SOLUTION:
1. For spacing and mounting ratio, refer to 6-8. The
mounting height ratio od direct concentrating light is
0.40.
Therefore: FIGURE 6-6
2. Substituting the given values, wherein mh is the CHART FOR ESTIMATING LIGHTING LOAD AND
ceiling height, ILLUMINATION LEVEL CALCULATED FOR FAIRLY LARGE
ROOM
S = 0.40 x 3.00
Spacing: S = 1.20 meters maximum side to side of the
fixtures.
ILLUSTRATION 6-9 6-7 Street Lighting
A warehouse will install pendant dome incandescent The Institute of Integrated Electrical Engineers
lamps at a mounting ratio of 1.50 meters. The lamp will instituted guidelines for adequate and acceptable
be mounted on a grid measuring 5.00 x 5.00 meters. illumination of the streets in order to promote safety.
What is the minimum mounting height of the lamps? This concept was brought about by the continuously
Solution: increasing speed of motor vehicles using the road.
Mounting height is; mh = Spacing The Philippine Electrical Code Committee prepared the
Ratio guidelines for a standard practice on design of street
mh = 5.00 m. = 3.30 meters lighting installation recommending the proper quantity
1.50 and quality of light for traffic routes.
6-6 Classification of Lighting System Definition of Terms
Lighting system is classified into four types, namely: Lighting Installation – is defined as the whole of the
1. Direct lighting 2. Semi-direct lighting equipment provided for lighting the roadway
3. Semi-indirect-lighting 4. Indirect Lighting comprising the lamps luminaries, means of support and
Direct Lighting. When the light on an illuminated area is electrical installations including other auxiliaries.
focused downward coming directly from the lighting Lighting System – refers to an array of luminaires having
fixtures. a characteristic of light distribution.
Luminaire – is a housing for one or more lamps
comprising a body and any refractor, diffuser or
enclosure associated with the lamps.
Road Width – is the distance between the edges of the
Semi-Direct Lighting. When the predominant light on road curbs measured at right angles to the length of the
the illuminated area is fed directly from the lighting roadway.
units wherein the greater amount of light is obtained Outreach – is the distance measured horizontally
from the ceiling through the reflection. between the outer of the column or wall face or lamp
post and the center of the luminaries.
Overhang – is the horizontal distance between the
center of luminaires and the adjacent edge of the road.
Mounting Height – refers to the vertical distance
between the center of the luminaire and the surface of
Semi-Indirect Lighting. A lighting arrangement wherein the roadway.
5% to 25% of the light is directed downward with more Spacing – is the distance between the successive
than half of the light focused upward and reflected from luminaries in an installation.
the ceiling.
minimum light levels are raised. The increasing motor
Maximum Light Utilization – In order to attain the vehicle speed and the incerasing congestiin in the street
maximum utilization of light from the fixtures, the requires higher level of highway lighting. Therefore,
luminaires should be mounted under the following future needs for light should be considered in the
specifications. design.
ILLUSTRATION 6-10
Considering the data as presented on Figure 6-7 when
the night pedestrian traffic is estimated oto be light and
the night vehicular traffic is to be medium, determine
the required lumens if theroad concrete is a pavement.
SOLUTION
Refering to Table 6- 9, E= 6.46 for light pedestrian
Working Voltage medium traffic classifications. For concrete road, the
Luminance are properly selected and mounted on a reflectance will be higher but let us accept the value of
location most feasible and effective with minimum cost. 6.46 lumens.
For a 230 volt system, a voltage drop of 5% is allowed Determine the average pole distance.
although in extreme cases 15% voltage drop is E= 6.46 lumens per sq.m.
sometimes tolerated. w= 7.00 meters
For street illumination, the following formula is d= 50 meters
adopted. mf= 0.9
cu= 0.29 (type A fixture)

Where:
E=The illumination in lux
Al=Average lumens with a typical value of:
20 500 lumens for 40 watts
11 500 lumens for 250 watts Under the Working Voltage, the mean lamp lumens of a
5 400 lumens for 125 watts 250 watts lamp is 11, 500 lumens, this is the nearest
The value of Al varies depending upon the type of lamp value to 8,662.83 average lumens. Therfore, a 250 watts
specified. lamp is acceptable.
mf- is the maintenance factor which depends on the Computing for the new actual illumination E
following:
a). Maintenance practice of the company
b). Operation of light sources at rate current and
voltage This is higher than the 6.46 recommended in table 6-
c). Regular replacement of depreciated lamp 11. Therefore, the road is considered as adequeately
d). Periodic cleaning of the luminaires either 0.8-0.9 lighted.
w = Width of the roadway
d = Distance between luminaires
cu = Coefficient of utilization which is dependent on the
type of fixture, mounting height, width of roadway and WIRING CALCULATIONS FOR SINGLE FAMILY DWELLING
the lenght of mast arm or outreach. UNIT
SINGLE FAMILY DWELLING
Type of Service - 230 V
Single Phase 2 wire 60 Hz
Line to ground Current system
The values given are based on the favorable
reflectances for asphalt road, the recommended
illumination should be increased by 50%. For concrete
road, the recommended value could be decreased by
25%.
In decreasing street illumination, consider the modern PROBLEM:
lighting today that will be obsolete tomorrow when the
A single family dwelling is to be circuited with the maximum 100 watts per light outlet. therefore the use
following requirements as shown on the figure above. of 2.0 mm2 or No.14 TW is safe.
Determine the:

size of the branch circuit wire for lighting outlets


size of the conduit pipes B, Circuit - 2 For Small Appliance load
size or rating of the fuse protective device
SOLUTION
SOLUTION
The National Electrical Code provides that:
A. Circuit - 1 for lighting load
"For each single receptacle shall be considered at no
1. From the Figure above, determine the number of less than 180 watts rating."
lighting outlets. By direct counting, there are 8 light
outlets.
It simply mean that, each convenience outlet, is
The National Electrical Code provides that: considered to have a maximum load of not less than
"100 watts shall be the maximum load for each 180 watts per plug or gang. thus:
household lighting outlet."
1. From Figure above, there are 6 convenience
Adopting the 100 watts per lighting outlet we have: receptacles for small appliance load. considering that
there are two plug outlet, the total number of plug will
8 outlets x 100 = 800 watts be:

2. Determine the Total Current load 6 outlets x 2 plug = 12 pieces

800 watts/230 volts = 3.48 amperes 2. Solve for the Total Estimated Load

3. Determine the size of conductor wire for circuit - 1 . 12 x 180 watts per outlet = 2,160 watts
Refer to Table 9.1 or 11.1. use 2 pieces 2.0 mm2 or No.
14 TW copper wire having an ampacity of 15 amperes 3. Determine the Maximum Expected Current Load:
that is much largr than the 3.48 amperes computed
maximum load. 2,160 watts / 230 volts = 9.39 amperes

4. Determine the size of the Conduit Pipe. Refer to 4. Determine the Size of the Conductor wire . Refer to
Table . The smallest diameter of a conduit pipe that Table 9.1 or 11.1. For 9.39 amperes, use 2 pieces 3.5
could accommodate up to 3 pieces of No.14 TW mm2 or No. 12 TW copper wire for Circuit no.2
conductor wire is 13 mm diameter. therefore, specify
13 mm diameter conduit pipe. 5. Determine the Size of the conduit pipe. for the 2 - No.
12 TW wire, refer to Table . Use 13 mm conduit pipe.
5. determine the size or rating of the fuse protective 6. Determine the Over Current fuse protection. Refer to
device. Refer to Table . Use 15 amperes fuse Table . under the column of fuse and breaker rating, the
20 amperes fuse can safely carry a maximum load of 16
The National Electrical Code provides that: amperes the 80 % of 20 amperes fuse can safely carry a
"Ampacity of the connected load shall not exceed 80% maximum load of 16 amperes the 80% of 20 amperes
of the amperage capacity of the conductor and the load permitted by the National Electrical Code on No.
fuse." 12 circuit wire.

In Table , the maximum ampacity load of a or 2.0 mm2


No.14 AWG copper wire is 15 amperes. 80 % of 15 is 12, COMMENT:
the maximum allowable load of the circuit sufficient
enough to carry the 3.48 amperes computed load for a
1. On convenience outlet receptacle, the National The fuse rating is 20 amperes. Granting that it will be
Electrical Code provides that, " Each single receptacle derated at 80 % x 20, the 16 amperes derated value is
shall be considered at no less than 180 watts rating." still higher than the computed load of 15.65 amperes.
Therefore, the 20 amperes fuse over current protection
2. Examining the values given on Table , the 2.0 mm2 or is accepted.
No. 14 AWG TW copper wire has an allowable ampacity
rating of 15 amperes. Granting that only 80 % of this 15
amperes is considered the derated value, still 12 FINDING THE SIZE OF SERVICE ENTRANCE
amperes is very much larger than the 9.36 amperes
computed as maximum load for 6-convenience outlet. The size of service entrance being the supply conductor
Why specify a bigger 3.5 mm2or No. 12 AWG conductor and equipment for delivering energy from the electricity
wire? supply to the wiring system of the building, is also
computed based on the total load supplied by the
3. Although the 2.0 mm2or No. 14 AWG wire conductor branch circuit. Continuing the solution, we have the
could safely carry the 9.36 amperes computed load, following:
considering its 15 amperes ampacity rating,yet, we
cannot do so because the Code specifically mandated 1. Solve for the total load of circuit 1 to circuit 3.
the use of 3.5 mm2or No. 12 AWG copper wire as the
minimum size for all types of convenience outlet wiring Total current load = Total connected load / voltage
except, for an appliance with limited load wherein a 2.0 rating
mm2or No.14 AWG wire is permitted.
= (800 W + 2,160 W + 3,600 W) / 230 V
= 28.52 amperes
C. Circuit - 3 for other loads

SOLUTION 2. Apply 80% demand factor as permitted by the


National Electrical Code.
1. Examining Figure above, other loads are:
28.52 x .80 = 22.8 amperes
1 - unit electric stove at 1.1 kw = 1,1oo watts
1 - unit water heater at 2.5 kw = 2,500 watts 3. Find the Size of the Service Wire. Refer 22.8 amperes
Total Load..........3,600 watts to Table . Use 2- 8.0 mm2or No.8 TW copper wire
2. Compute for the current load. Divide:
4. Determine the size of conduit pipe for the service
3,600 watts / 230 volts = 15.65 amperes wire. Refer Table , for No.8 TW copper wire, use 20 mm
diameter conduit pipe.
3. Determine the size of the service conductor wire. COMMENT:
Refer to Table 9.1 or 11.1.
1. A demand factor of 80% was applied considering that
4. For the 15.65 amperes load, use 2 pieces 3.5mm2or not all receptacles and outlets are being used
No.12 AWG TW copper wire simultaneously.

5. Determine the Size of the Conduit Pipe (if reqd) to 2. These type of loads are classified as non-continuous
Table. Two pieces No. 12 AWG wire can be load. From Table 9.1, the 5.5 mm2or
accommodated comfortably in a 13 mm diameter No.10 AWG copper wire conductor has 30 amperes
conduit pipe. Specify 13 mm diameter conduit pipe. ampacity which is bigger than 22.8 amperes as
computed. However, we do not specify the use of No.10
6. Determine the size or rating of the Over-current AWG wire because the code limits the use of 8.0 mm2or
Protection. Refer to Table . For the 15.65 amperes load No.8 AWG, conductor as minimum size for Service
use 20 amperes fuse rating. Entrance.

COMMENTS:
3. The National Electrical Code on Service Entrance NOTE:
provides that: The quantity of materials is subject to change
depending upon the area and the choice of the
" Service entrance shall have sufficient ampacity to designing engineers. For open onstallation, conduit pipe
carry the building load. They shall have the adequate can be changed to split knobs or PDX wires.
mechanical strength and shall not be smaller than 8.0
mm2or 3.2 mm diameter except for installation to
supply limited load of a single branch circuit such as
small poly-phase power, controlled water heaters and
the like and they shall not be smaller than 3.5 mm2or SINGLE FAMILY DWELLING
2.0 mm diameter copper or equivalent. Type of Service - 115/230 V
Single Phase 3 wire 60 Hz
Line to Line system
THE MAIN DISCONNECTING MEANS OR SAFETY SWITCH

Find the total computed load

Circuit - 1 ........ 3.48 amperes SOLUTION:


Circuit - 2 ........9.39 amperes
Circuit - 3 ........15.65 amperes Examining the lighting plan of the above figure, there
TOTAL........28.52 amperes are 19 lighting outlets. Split the 19 outlets into two
circuits A and B.
2. Use 2 pieces 30 amperes fuse parallel connection 60
amperes 2 pole single throw (PST) 250 volts safety
switch A. Circuit - 1 Lighting Load (10 light outlets)

3. Provide 2-double branch circuit cut out with two 15 1. The PEC provides that 100 watts be the maximum
and 2-20 amperes fuse respectively. load per light outlet. thus, for 10 light outlets at 100
watts, multiply:

10 outlets x 100 watts = 1000 watts

2. Compute The Current Load


MULTI-ground system and line to line service
1000 watts/230 volts = 4.35 amperes

The protection of branch circuit is tapped to the hot line 3. Find the size of Branch circuit wire. Refer to Table 9.1
of live wire. The grounded line being in neutral zero or 11.1. For 4.35 amperes, use 2.0 mm2 TW copper
voltage is not protected with fuse. this is one advantage wire.
of the MULTI-GROUND SYSTEM being adopted by the 4. Find the rating of overcurrent protection. Refer to
electric cooperative implemented by the RURAL Table. for 4.35 A, use 15 amperes trip breaker.
ELECTRIFICATION PROGRAM of the government. The
branch circuit and cutout should be doubled because 5. Determine the size of conduit pipe. Refer to Table ,
the engaged voltage in the line is only 230 V while the for No. 14 TW copper wire, use 13 mm conduit pipe.
other is zero being grounded ( see figure)
B. Circuit - 2 Lighting Load (9 light outlets)

Other electric service system on the other hand, are 1. For 9 outlets, find the Total load in watts.
classified as LINE TO LINE SERVICE wherein the engaged
voltage is 115/230 volts which requires FUSE 9 outlets x 100 watts per outlet = 900 watts
PROTECTIO FOR BOTH LINES. Divide : 900 watts/230 volts = 3.91 amperes
2. Determine the Size of the Branch circuit Wire. Refer 4. Determine the Size of the Branch Circuit wire. Refer
to Table 9.1 or 11.1. For 3.91 A load, use 2.0 mm2or to Table 9.1 or 11.1. For the 27.82 A, use 8.0 mm2 or
No.14 TW copper wire. No. 8 TW copper wire.
3. Determine the size of the conduit pipe. Refer to
Table. For 2 pieces No. 14 TW copper wire, use the 13 5. Determine the Size of Conduit pipe. Refer to Table.
mm minimum size of conduit pipe. For 2 pieces No.8 wire use 200 mm diameter pipe.
4. Determine the size or rating of the overcurrent
Protection. Refer to Table. For 3.91 A load, use 15 A 6. Find the Size or Rating of the Fuse or Trip Breaker.
load fuse of trip breaker. Refer to Table. For appliance load, use 40 A fuse or trip
C. Circuit - 3 For small appliance load breaker.

Section 3.3.1.2 of the the PEC specif 180 watts load limit F. Circuit - 6 for Water heater Load
per convenience outlet. Thus,
1. one unit water heater at 2.5 kW = 2500 watts
1. Find the number of appliance load outlet and the 2. The current load will be:
current load.
2500 watts/230 volts = 10.86 A
6 outlets x 2 gang per outlet x 180 watts
12 x 180 = 2,160 watts 3. Solve for the Size of the Branch circuit wire. Refer to
Divide: 2160 watts/230 volts = 9.39 A Table 9.1 or 11.1 . For 10.86 A convenience outlet use 2
pcs 3.5 mm2 or No. 12 TW copper wire.
2. Determine the Size of the Service Wire conductor. 4. Determine the Size of the conduit pipe. Refer to
Refer to Table 9.1 or 11.1. For the 9.39 A load, specify Table. For 2 - No.12 Tw copper wire, use 13 mm conduit
the minimum wire gauge for convenience outlet. pipe.
5. Find the Size or Rating of the Over Current
2 pieces 3.5 mm2or No.12 TW copper wire Protection. For the 10.86 A load, use 20 A fuse fuse or
trip breaker.
3. Determine the Size of the conduit pipe. Refer to
Table. For 2 pieces No.12 TW copper wire. Use 13 mm
diameter conduit pipe. G. Circuit 7 and 8 with 1 - unit ACU each
4. Solve for the Size or Rating of the Over current
Protection. Refer to Table. For 9.39 A on No. 12 TW 1. One unit ACU at 1.5 Hp is
copper wire specify:
20 A fuse or trip breaker. 1.5 Hp x 746 = 1119 watts

Article 6.7 of the Philippine Electrical Code provides


D. Circuit- 4 for Small Appliance Load that: "BRANCH CIRCUIT CONDUCTOR SUPPLYING A
MOTOR SHALL HAVE AN AMPACITY NOT LESS THAN
1. The load of circuit 4 is identical with circuit . Use the 125% OF THE FULL LOAD CURRENT."
same size of wire, conduit, and wire protection rating.
2. Current Load: 1119 watts/230 V = 4.86 A
E. Circuit - 5 for Range Load
4.86 A x 125% = 6.07 A
1. Range load (appliance rating) at 8.0 kW = 8000 watts
3. Find the Size of the Branch circuit service wire. Refer
2. Solve for the Line current. to Table. The 6.7 A can be served by a 2.0 No.14 TW
copper wire, but the Code limits the size of convenience
8000 watts / 230 V= 34.78 A outlet to No. 12 AWG copper wire. Specify No.12 THW
copper wire for circuit 7 and 8.
3. Refer to Table , apply 80% demand load factor . 4. Find the Size of the conduit pipe. Refer to Table. For
two No.12 wire, use 13 mm conduit pipe.
34.78 x .80df = 27.82 A
5. Find the Size and Rating of the Branch Circuit 4. Determine the Size of the Conduit pipe. Refer to
Protection. The Code on branch circuit protection for a Table , use 32 mm diameter pipe.
single motor provides that" It shall be increased by
250% of the full load current of the motor." thus, 5. For main Breaker, refer to Table . Use 2 - 100 A 2 -
wires 250 V, 2 pole molded air circuity breaker.
4.86 x 250% = 12.15 A. From Table for a continuous load
use 2-30 AT breaker. COMMENT:

The total computed load is 63.37 A. The 30 mm2 copper


CALCULATING THE AMPACITY OF THE SERVICE wire could be used considering its 90 A capacity.
ENTRANCE CONDUCTOR AND THE MAIN However, The NEC provides that:
DISCONNECTING MEANS
" If the computed load exceeds 10000 watts, the
conductor and overcurrent protection shall be rated not
1. Find The total current load of circuit 1 to circuit 8: less than 100 A.

lighting load Ct. 1 and Ct.2 ....................1900 watts


small appliance load Ct. 3 and Ct. 4.......4320 watts THEREFORE USE 2 - 38 mm2 TW WIRE FOR THE MAIN
other loads Ct.5 and Ct 6.,......................10500 watts FEEDER AND 2 - 100 A FOR THE MAIN BREAKER.

TOTAL LOAD(except the ACU)....16720 watts

2. From Table , OPTIONAL CALCULATION for dwelling


Unit, apply demand factor.
Small Family Dwelling
for the first 10000 w at 100%(df)...........10000 watts Type of Service - 230 volts; two wire
Line to Ground system
subtract: 16720 - 10000 = 6720 watts

for other load, multiply by 40% A single family dwelling with a floor area of 80 square
6720 x .4 .........................................2688 watts meters has the following receptacles and outlets load.

Aircon unit at 100% demand factor


2-units at 1119 watts........................2238 watts LIGHTING:

TOTAL .....................14, 926 watts 7 pcs. - 40 watts fluorescent lamps


2 pcs. - 20 watts Incandescent lamps
TOTAL CONNECTED LOAD PLUS 25% OF THE LARGEST
MOTOR CONVENIENCE OUTLET:

1. Ampere I = 14.926w + (25% of 1.119w)/230 V 1 - Electric Iron .............................................. 1000 watts


= 63.37 A 1 - Electric stove.............................................. 1100
watts
2. Find the Size of Main feeder and the Neutral line. 2 - Electric fan ................................................ 500 watts
- Use 2 - 3.8 mm2 TW copper wire 1 - 7 cu. ft Refrigerator .................................... 175 watts
1 - Portable stereo ........................................... 100 watts
3. The Neutral Conductor of a 3 - wire line to line supply 1 - 20" TV set ................................................... 300 watts
system shall have an ampacity of not less than 70% of
the ungrounded(live wire) conductor or TWO TRADE
SIZE SMALLER SIZE THAN THE UNGROUNDED
CONDUCTOR. (PEC specs) Therefore use 1- 22 mm2 Tw SOLUTION:
copper wire for the Neutral line.
A. Circuit 1 - Lighting Load by the Area method
1. Determine the wattage required per square meter COMMENT:
area. From, the wattage required per square meter for
dwelling units is 24 watts. Multiply: It is interesting to note that only one 20 A fuse
protection was used because the current is a LINE TO
80 sq.m x 24 watts = 1920 watts GROUND OR MULTI-GROUND SYSTEM where one line is
zero voltage being grounded. Unlike the LINE TO LINE
2. Determine the current load. Divide: SYSTEM of current supply, it is necessary to provide 2
fuses to protect the two line branch circuit.
1920 watts/ 230 volts = 8.35 A

3. Compute the actual lighting load. Multiply: FINDING THE SIZE OF THE SERVICE ENTRANCE OR
FEEDER
7 - Fluorescent lamps x 40 watts = 280 watts
2 - Incandescent bulb x 60 watts = 120 watts 1. Get the sum total of connected load. Add:
TOTAL............ 400 watts
Lighting Load.................................... 1920 watts
4. Solve the actual current load. Divide: Small appliance load ......................... 3175 watts
TOTAL.................................. 5095 watts
400 watts/230 volts = 1.74 A
2. Solve for the total connected load current. Divide:
5. Determine th Size of the Branch Circuit wire. From ,
the 1.74 A is very small load to be carried by 2.0 mm2 or 5095 watts/230 volts = 22.15 A
No. 14 TW copper wire. Therefore, the No. 14 wire is
safe. 3. Find the size of Service Entrance. Refer to Table. For
22.15 A, use No. 8 TW copper wire, the minimum size
6. Determine the Size of the conduit pipe. Refer to for service entrance.
table, for 2- No.14 wire, use 13 mm conduit pipe.
4. For Main Protection, use 1-safety switch, 2 pole, 2
7. Determine the size or rating of the branch circuit wires, 250 volts.
protection. Refer to table. For 2.0 mm2 or No.14 copper Under the preceding set-up, one safety switch could
wire conductor, use 15 A fuse or trip breaker. supply both lighting and convenience outlet at different
branch circuit without the use of fuse cutout. This is
only applicable to the line to ground or multi-ground
B. Circuit - 2 For small appliance load system being used by the electric cooperative.

1. Solve for the total appliance current load. PEC REQUIREMENTS FOR ADEQUATE WIRING IN SINGLE
AND MULTI-FAMILY DWELLING UNIT
LOAD CURRENT = ( 1000 + 1100 + 500 + 175 + 300 + GENERAL LIGHTING LOADS BY OCCUPANCIES
100) / 230 volts (Table 1.1)
= 3175 watts/230 volts
= 13.81 A * All receptacle outlets of 20-ampere or less in one-
family, two-family and multifamily dwellings and in
2. Determine the size of the Branch circuit wire guest rooms of hotels and motels shall be considered as
conductor. Refer to Table. For a convenience load of outlets for general illumination, and no additional load
13.81 A specify 3.5 mm2 or No. 12 TW copper wire, the calculations shall be required for such outlets.
minimum size required for convenience outlet.
** In addition a unit load of 8 volt-amperes per square
3. Find the size of the conduit pipe. Refer to Table, for 2 meter shall be included for general purpose receptacle
pieces No.12 TW copper wire, use 13 mm diameter outlets when the actual number of general purpose
pipe. receptacle outlets is unknown.
4. Find the Size or rating of the Protection device. See
Table, for 13.81 A, use 1 - 20 A fuse.
FEEDER DEMAND FACTORS FOR GENERAL LIGHTING Note 3: Over 1.75 kW through 8.75 kW. In lieu of the
LOAD AND SMALL APPLIANCE LOAD method provided in column A, it shall be permissible to
(Table 2.1) add the nameplate ratings of all ranges rated more than
1.75 kW but not more than 8.75 kW and multiply the
sum by the demand factors specified in column B or C
*The demand factors of this table shall not apply to the for the given numbers of appliances.
computed load of feeders to areas in hospitals, hotels,
and motels where the entire lighting is likely to be used Note 4: Branch circuit load. It shall be permissible to
at one time, as in operating rooms, ballrooms, or dining compute the branch-circuit load for one range In
rooms. accordance with Table 3.3.2.10. the branch-circuit load
for one wall-mounted oven or one counter-mounted
cooking unit shall be the nameplate rating of the
appliance. The branch-circuit load for a counter-
mounted cooking unit and not more than two wall-
DEMAND FACTOR FOR HOUSEHOLD ELECTRIC CLOTHES mounted ovens, all supplied from a single branch circuit
DRYER and located in the same room, shall be computed by
(Table 3.1) adding the nameplate ratings of the individual
appliances and treating this total as equivalent to one
range.

Note 5: This table also applies to household cooking


appliances rated over 1.75 kW and used in instructional
programs.
DEMAND LOADS FOR HOUSEHOLD ELECTRIC RANGES,
WALL-MOUNTED OVENS, COUNTER-MOUNTED
COOKING UNITS, AND OTHER HOUSEHOLD COOKING
APPLIANCES OVER 1.75 KW RATING.
COLUMN A TO BE USED IN ALL CASES EXCEPT AS
OTHERWISE PERMITTED ON NOTE 3 BELOW FULL LOAD CURRENT IN AMPERES
(Table 4.1) SINGLE PHASE ALTERNATING - CURRENT MOTORS
(Table 4.1)

Note: Over 12 kW through 27 kW ranges all of same


rating. For ranges individually rated more than 12 kW
but not more than 27 kW, the maximum demand in FULL-LOAD CURRENT
Column A shall be increased 5 % for each additional kW TWO-PHASE ALTERNATING CURRENT MOTORS (4-WIRE)
of rating of major fraction thereof by which the rating of (Table 5.1)
individual ranges exceeds 12 kW.

Note 2: Over 8.75 kW through 27 kW ranges of unequal


ratings. For ranges individually rated more than 8.75 kW FULL-LOAD CURRENT
and of different ratings but no exceeding 27 kW, an THREE-PHASE ALTERNATING-CURRENT MOTORS
average of value of rating shall be computed by adding (Table 6.1)
together the ratings of all ranges to obtain the total
connected load (using 12 kW for any range rated less
than 12 kW) and dividing by the total number of ranges;
and then the maximum demand in column A shall be
increased 5 percent for each kW or major fraction
thereof by which this average value exceeds 12 kW.
CONVERSION TABLE OF LOCKED-ROTOR CURRENTS
FOR SELECTION OF DISCONNECTING MEANS AND
CONTROLLERS
AS DETERMINED FROM HORSEPOWER AND VOLTAGE
RATING
(Table 7.1)

ALLOWABLE AMPACITIES OF THREE SINGLE INSULATED


CONDUCTORS, RATED 0-2000VOLTS, 150º TO 250ºC, IN
RACEWAY OR CABLE BASED ON AMBIENT AIR
MAXIMUM RATING OR SETTING OF MOTOR BRANCH- TEMPERATURE OF 40ºC
CIRCUIT (Table 13.1)
SHORT-CIRCUIT AND GROUND-FAULT PROTECTIVE
DEVICES
(Table 8.1)

AMPACITY CORRECTION FACTORS

(Table 14.1)
ALLOWABLE AMPACITIES OF INSULATED CONDUCTORS
RATED 0-2000 VOLTS, 60º C TO 90ºC
NOT MORE THAN THREE CONDUCTORS IN RACEWAY OR
CABLE OR EARTH (DIRECTLY BURIED), BASED ON
AMBIENT ALLOWABLE AMPACITIES FOR SINGLE INSULATED
TEMPERATURE OF 30ºC CONDUCTORS, RATED 0-2000VOLTS, 150º TO 250ºC, IN
(Table 9.1) FREE AIR BASED ON AMBIENT AIR
TEMPERATURE OF 40ºC

(Table 15.1)
AMPACITY CORRECTION FACTORS
(Table 10.1)

AMPACITY CORRECTION FACTORS

(Table 16.1)
ALLOWABLE AMPACITIES OF SINGLE INSULATED
CONDUCTORS, RATED 0-2000VOLTS, IN FREE AIR
BASED ON AMBIENT AIR TEMPERATURE OF 30ºC
(Table 11.1) EXCEPTIONS (based on PEC requirements)

1. The small appliance appliance branch circuit required


in a dwelling unit shall supply only the receptacle
outlets specified in that section.
AMPACITY CORRECTION FACTORS (b.) 25- and 30-Ampere Branch Circuits. A 25- or 30-
(Table 12.1) ampere branch circuit shall be permitted to supply fixed
lightning units with heavy-duty lamp holders in other
dwelling unit(s) or appliances shall not exceed 80
+ Unless otherwise specifically permitted elsewhere in percent of the branch-circuit ampere rating.
this Code, the over current protection for conductor (c.) 40- and 50-Ampere Branch Circuits. A 40- and 50-
types marked with an obelisk (+) shall not exceeds 15 ampere branch circuit shall be permitted to supply fixed
amperes for 2.0 mm2, 20 amperes for 3.5 mm2, and 30 lighting units with heavy-duty lamp holders or infrared
amperes for 5.5 mm2 copper; or 15 amperes for 3.5 heating units in other than dwelling units or cooking
mm and 25 amperes for 5.5 mm2 aluminum and copper appliances that are fastened in place in any occupancy.
clad aluminum.
At least one receptacle outlet shall be installed for the
Receptacle Outlets required laundry.
(a) General. where flexible cords are used.
3. In a dwelling unit that is an apartment or living area
2. where flexible cords are specifically permitted to be in a multifamily dwelling where laundry facilities are
permanently connected, and are so connected in boxes provided on the premises that are available to all
or fittings approved for the purpose, it shall be building occupancies, a laundry receptacle shall not be
acceptable to omit receptacles on such equipment. required.

(b) Dwelling units. In every kitchen, family room, dining 4.In other than one-family dwellings where laundry
room, breakfast room, living room, parlor, library, den, facilities are not be installed or permitted, a laundry
sun room, bedroom, recreation room, or similar rooms, receptacle shall not be required.
receptacle outlets shall be installed so that no point
along the floor kine in any wall space is more than 1800 As used in this section, a "wall space" shall be
mm, measured horizontally, from an outlet in that considered a wall unbroken along the floor line by
space, including any wall space 600 mm or more in doorways, fireplaces, and similar openings. Each wall
width and the wall space occupied by sliding panels in space 600 or more mm wide shall be treated
exterior walls. The wall space afforded by fixed room individually and separately from the other wall spaces
dividers, such a free-standing bar type counters, shall be within the room. A wall space shall be permitted to
included in the 2 meter measurement. include two or more walls or a room(around corners)
where unbroken at the floor line.
In kitchen and dining areas, a receptacle outlet shall be
installed at each counter space wider than 300 mm. The receptacle outlets required by this section shall be
Counter top spaces separated by range tops, in addition to any receptacle that is part of any lighting
refrigerators, or sinks shall be considered as separate fixture or appliances, located within cabinet or
counter top spaces. Receptacles rendered inaccessible cupboard, or located over 1600 mm above the floor.
by appliances fastened in place or appliances occpying
dedicated space shall not be considered as these 5. Permanently installed electric baseboard heaters
requires outlets. equipped with factory installed receptacle outlets, or
outlets provided as a separate assembly by the
Receptacles outlets shall, in so far as practicable, be manufacture, shall be permitted as the required outlet
spaced equal distances apart. Receptacle outlets in or outlets for the wall space utilized by such
floors shall not be counted as part of the required permanently installed heaters. Such receptacle outlets
number of receptacle outlet unless located close to the shall not be connected to the heater circuits.
wall.
Lighting Outlets Required:
At least one wall receptacle shall be installed in the
bathroom adjacent in the basin location. (a) Dwelling units: At least one wall switch controlled
lighting outlet shall be installed in every habitable room,
For a one-family dwelling, at least one receptacle outlet in bathrooms, hallways, stairways and attached garage:
shall be installed outdoors. and at outdoor entrances

For a one-family dwelling, at least one receptacle outlet At least one lighting outlet shall be installed in an attic,
in addition to any provided for laundry equipment, shall underfloor space, utility room and basement only wher
be installed in each basement and in each attached these spaces are used for storage or containing
garage. equipment requiring servicing.

Outlets in other section of the dwelling unit for special 6. In habitable rooms, other than the kitchen, one or
appliances, such as laundry equipment, shall be placed more receptacles controlled by a wall switch shall be
within 1800 mm of the intended location of the permitted in lieu of light outlets
appliance.
7. In hallways, stairways, and at outdoor entrances shall be permitted to have the neutral load determined
remote, central, or automatic control of lighting shall be by this section
permitted.
the connected load to which the demand factors apply
shall include the following:
FEEDERS:
(1)1500 watts for each 2-wire, 20 A small appliance
Minimum size or rating. Feeder conductors shall have branch circuit and each laundry branch circuit
an ampacity not lower than required to supply the load
. The minimum sizes shall be as specified in (a) and (b) (2) 24 watts per square meter for general lighting and
below under the conditions stipulated. Feeder general use receptacles
conductors for a one family dwelling or amobile home
need not be larger than service entrance conductors. (3) The nameplate rating of all appliances that are
fastened in place, permanently connected or located to
(a) For specified circuits. The feeder conductors shall be on a specific circuit, ranges, wall mounted ovens,
not be smaller than 5.5 square mm where the load counter-mounted cooking units, clothes dryer, water
supplied consists of the following number and types of heaters and space heaters
circuits: (1) Two or more 2-wire branch circuits supplied
by a 2-wire feeder. (2) MOre than two 2-wire branch If water heater elements are so interlocked that all
circuits supplied by a 3-wire feeder (3) Two or more 3- elements cannot be used at the same time, the
wire branch circuits supplied by a 3-wire feeder maximum possible load shall be considered the
nameplate load.
(b) ampacity relative to service entrance conductors.
The feeder conductor ampacity shall not be lower than (4)The nameplate A or kVA rating of all motors and of
that of the service-entrance conductors 14 square mm all low-power factor load.
or smaller.
(5) The larger of the air conditioning load or the space
(c) Overload feeders. Where at any time feeder heating load.
conductors are or will be overloaded the feeder
conductors shall be increased in ampacity to
accommodate the ctual load served. BASIC CONCEPT IN ELECTRICAL DESIGN
RECEPTACLES AND WIRING DEVICES
OPTIONAL CALCULATION - MULTIFAMILY DWELLING
(a) It shall be permissible to compute the feeder or
service load of a multifamily dwelling where all the ELECTRICAL CONDUCTORS AND INSULATORS
following conditions are met:
Electrical Conductors are substances that offer a very
(1) No dwelling unit is supplied by more than one feeder low resistance to current flow.
(2) Each dwelling unit is equipped with electric cooking
equipment. Insulators are substances that offer a very high
resistance to current flow.
EXCEPTION: When the computed load for multifamily
dwelling under the section without cooking load
exceeds that computed under this section for the List of some good electrical conductors:
identical load plus electric cooking exceeds that
computed for the identical load plus the electric Silver
cooking, the lesser of the loads may be used. Zinc
Copper
(3) Each dwelling unit is equipped with either electric Platinum
space heating or air conditioning or both Aluminum
Iron
Feeders and service-entrance conductors whose Nickel
demand load is determined by this optional calculation Tin
Brass SQUARE MIL. It is the area of a square having its side
Lead equal to 1 mil.
Square mil = ( sides )2 = ( 1 mil )2 = ( 0.001 in.)2 = 1 x 10-
6 in.2
List of some insulating materials: Square mil = 0.7854 x circular mils
Rubber
Asbestos
Porcelain
Thermoplastics CONDUCTOR AREAS:
Varnish
Paper CONVERSION FACTOR
Slate
Oils Square inch = square mil x 0.000001
Glass Square mil = square inch x 1,000,000
Wax Square mil = circular mils x 0.7854
Mica Circular mil = square mils x 1.273
Dry air Millimeter = inches x 25.4
Latex Square mm = circular mils x 0.0005067

WIRES AND CABLES

Wires are those electrical conductors which are 8 mm2


(AWG no. 8) or smaller, while cables are those larger
than the wires. They are either solid or stranded.

Stranded wire - consists of a group of wires twisted to


form metallic string. The total circular-mil area of a
stranded wire is found by multiplying the circular mil
area of each strand by the total number of strand.

Cord is the term given to an insulated stranded wire.

CIRCULAR MIL. This is the unit of cross section in the DIFFERENT TYPES OF CABLES
American wire gauge. The term “mil” means one-
thousandth of an inch (0.001 in.). It is the area of a
circular wire having a diameter of one mil. To find the 1. Armored Cable. This type of cable, the type AC is a
number of circular mils in a circle of a given diameter, fabricated assembly of insulated conductors enclosed in
we have to square the number of mils in the diameter. flexible metalsheath. Armored cable is used in both
exposed and concealed work.

Area in circular mil = ( diameter in mils )2


1 inch = 1,000 mils 2. Metal Clad Cable. Cable of the type MC is a factory
MCM = 1,000 circular mils assembled cable of one or more conductors, each
individually insulated and enclosed in a metallic sheath
of interlocking tape, or a smooth or corrugated tube.
This type is used specifically for services, feeders,
branch circuits, either exposed or concealed and for web designed specifically for field installation in metal
indoor or outdoor work. surface raceway. Cables of this type are the types FC.

3. Mineral Insulated Cable. This type of cable, type MI, 10. Flat Conductor Cable. This type of cable, type FCC
is a factory assembly of one or more conductors consists of three or more flat conductors placed edge to
insulated with a highly compressed refractory mineral edge, separated and enclosed within an insulating
insulation and enclosed in liquid-tight and gas-tight assembly. This used for general purpose, appliance
continuous copper sheath. The type MI is used in dry, branch circuits and for individual branch circuits
wet or continuously moist location as service, feeders or specifically on hard, smooth, continuous floor surfaces,
branch circuit. etc.

4. Nonmetallic Sheathed Cable. Types NM and NMC are 12.Medium Voltage Cables. MV cable is a single or
factory assembled two or more insulated conductors multiconductor solid dielectric insulated cable rated
having a moisture-resistant outer sheath, flame- 2,001 volts or higher and is used for power systems up
retardant and non-metallic material. These types are to 35,000 volts. The MV cables are of different types
used specifically for one or two dwelling not exceeding and characteristics.
3 storey buildings.

5. Shielded Nonmetallic Sheathed Cable. This type of RACEWAYS


cable, the type SNM, is a factory assembly of two or
more insulated conductors in an extruded core or
moisture-resistant and flame-retardant material, Raceways are channels designed for holding wires,
covered with an overlapping spiral metal tape. This type cables or bus-bars, which are either made of metal or
is used in hazardous locations and in cable trays or in insulating materials. The common types of raceways in
raceways. household wiring are the a) conduits, b) connectors,
and c) others.

6. Service Entrance Cable. This is a single conductor or


multiconductor assembly provided with or without an a) Conduits
over-all covering, primarily used for services and of the
types SE and USE. Conduits, pipes or tubings are the most common
electrical raceway.

7. Underground Feeder and Brach Circuit Cables. This According to the type of materials used, conduit maybe
type of cable, the type UF cable is a moisture-resistant classified as either metallic such as steel pipes or
cable used for underground, including direct burial in nonmetallic such as PVC, and the like.
the ground, as feeder or branch circuit.
According to its make, conduits maybe classified as:
rigid metal, flexible metal, rigid nonmetal and flexible
8. Power and Control Tray Cable. Type TC cable is a nonmetal.
factory assembly of two or more insulated conductors
with or without associated bare or covered grounding b) Connectors
under a metallic sheath. This is used for installation in
cable trays, raceways or where supported by a A connector is a metal sleeve usually made of copper
messenger wire. that is slipped over and secured to the butted ends of
conductors in making joint. A connector is also called a
splicing sleeve.
9. Flat Cable Assemblies. This is an assembly of parallel
conductors formed integrally with an insulating material c) Other Raceways
Aside from the conduits and connectors there are still These are comparatively new types of wire, consisting
numerous types and kinds of raceways, among these of the basic Type THH and THW but with less
are the a) conduit couplings, elbows and other fittings; thermoplastic insulation, and with a final extruded
b) conduit supports, such as clamps, hangers,etc; c) jacket of nylon. Nylon has exceptional insulating
cable trays, cablebus; d) metal raceways;e) nonmetal qualities and great mechanical strength, all of which
raceways. results in a wire which is smaller in diameter than
ordinary Types T, TW, TW of corresponding size.

OUTLETS, RECEPTACLES and other WIRING DEVICES


C. TYPE XHHW

In appearance, it resembles Types T, TW, THW but


OUTLETS. An outlet is a point in the wiring system at because of somewhat thinner layer of insulation, the
which current is taken to supply utilization equipment. over-all diameter is smaller. The insulation is “cross-
The kinds of outlets are: convenience outlet or linked synthetic polymer,” which has an extraordinary
attachment cap, lighting outlet, and receptacle outlet. properties as to insulating value, heat resistance, and
moisture resistance. It may be used in dry or wet
locations. While at present, it is an expensive wire, it
A convenience outlet or attachment cap is a device would be no surprise if in due course of time, this one
which by insertion in a receptacle, establishes single type will replace all the many types and subtypes
connection between the conductor of the flexible cord of Type T or R now recognized by the Code.
and the conductors connected permanently to the
receptacle.
D. RUBBER-COVERED WIRE

A lighting outlet is an outlet intended for direct


connection of a lampholder, a lighting fixture, or a It consists of copper conductor, tinned to make it easier
pendant cord terminating in a lampholder. to remove the insulation, and for easy soldering. Over
the copper is a layer of rubber, the thickness of which
depends on the size of the wire. Then follows an outer
A receptacle outlet is an outlet where one or more fabric braid which is saturated with moisture-and-fire-
receptacles are installed. resistant compounds; if it is set on fire with a blowtorch,
the flame dies out when the torch is removed.

E. OTHER TYPES
TYPES OF WIRES
Other types such as the basic Type R, which is suitable
for only in dry locations, is no longer being made. The
A. TYPES T, TW, THW most ordinary kind is Type RHW, which may be used for
dry or wet locations. Types RH and RHH have insulation
The most ordinary type of plastic insulated wire is the which withstands more heat and therefore have a
“type T”. It may be used only in dry locations. Some higher ampacity in the larger size. They may be used
manufactures no longer make the ordinary Type T, only in dry locations.
instead produce Type TW, which is identical in
appearance, but may be used in wet or dry locations.
Also available is Type THW, is similar to Type TW but
withstand a greater degree of heat, and consequently KINDS OF LOCATIONS
has a higher ampacity rating in the larger sizes.

DAMP LOCATION
B. TYPES THHN, THWN
Partially protected locations under canopies, marquees, which the liquids, vapors, or gases will normally be
roofed open porches, and like locations, and interior confines within closed containers or closed systems
locations subjected to moderate degree of moisture, from which they can escape only in case of accidental
such as some basements, some barns, and some cold- rupture or breakdown of such containers or systems, or
storage warehouses. in case of abnormal operation of equipment; or ii) in
which ignitible concentrations of gases or vapors are
normally prevented by positive mechanical ventilation,
DRY LOCATION and which might become hazardous through failure or
abnormal operation of the ventilating equipment; iii)
A location not normally subject to dampness or that is adjacent to Class I, Division 1 location, and to
wetness. A location classified as dry may be temporarily which ignitible concentrations of gases or vapors might
subject to dampness or wetness, as in the case of a occasionally be communicated unless such
building under construction. communication is prevented by adequate positive
ventilation from a source of clean air, and effective
safeguards against ventilation failure are provided.
WET LOCATION

Installations underground or in concrete slabs or Class II Locations. Class II locations are those that are
masonry in direct contact with the earth, and location hazardous because of the presence of combustible dust.
subject to saturation with water or other liquids, such
as vehicle washing areas, and locations exposed to a) Class II, Division 1. A class II, Division 1 location is a
weather and unprotected. location: I) in which combustible dust is in the air
normal operating conditions in quantities sufficient to
produce explosive or ignitible mixtures; or ii) where
mechanical failure or abnormal operation of machinery
HAZARDOUS (CLASSIFIED) LOCATIONS or equipment might cause such explosive or ignitible
mixtures to be produced, and might also provide a
Locations where fire or explosion hazards may exist due source of ignition through simultaneous failure of
to flammable gases or vapors, flammable liquids, electric equipment, operation devices, or from other
combustible dust, or ignitible fibers or flyings. causes; or iii) in which combustible dusts of an
electrically conductive nature may be present in
1. Class I Locations. Class I locations are those in which hazardous quantities.
flammable gases or vapors are or may be present in the
air in quantities sufficient to produce explosive or
ignitible mixtures. b) Class II, Division 2. A Class II, Division 2 location is a
location where combustible dust is not normally in the
air in quantities sufficient to produce explosive or
a) Class I, Division 1. A Class I, Division 1 location is a ignitible mixtures, and dust accumulations are normally
location: I) in which igntible concentrations of insufficient to interfere with the normal operation of
flammable gases or vapors can exist under normal electrical equipment or other apparatus, but
operating conditions; or ii) in which ignitible combustible dust may be in suspension in the air as a
concentrations of such gas vapors may exist frequently result of infrequent malfunctioning of handling or
because of repair or maintenance operations or processing equipment and where combustible dust
because of leakage; or iii) in which breakdown or faulty accumulations on, in, or in the vicinity of the electrical
operation of equipment or processes might release equipment may be sufficient to interfere with the safe
ignitible concentrations of flammable gases or vapors, dissipation of heat from electrical equipment or may be
and might also cause simultaneous failure of electric ignitible by abnormal operation or failure of electrical
equipment. equipment.

b) Class I, Division 2. A Class I, Division 2 location is a 3. Class III Locations. Class III locations are those that
location: I) in which volatile flammable liquids or are hazardous because of the presence of easily
flammable gases are handled, processes, or used, but in combustible fibers or flyings, but in which such fibers or
flyings are not likely to be in suspension in the air in
quantities sufficient to produce ignitible mixtures.
THE OVERHEAD SERVICE-DROP CONDUCTOR

a) Class III, Division 1. A Class III, Divisions 1 location is a


location in which easily ignitible fibers or materials
producing combustible flyings are handled, This is the overhead service conductor from the last
manufactured, or used. pole or other aerial support to and including the splices
if any, connecting the service entrance conductors at
the building or other structure.
b) Class III, Division 2. A Class III, Division 2 location is a
location in which easily ignitible fibers are stored or
handled. SIZE AND RATING:

a) General. Service drop shall have sufficient ampacity


to carry the load without a temperature rise
detrimental to the covering or insulation of the
ELECTRIC CIRCUITS IN BUILDING conductors and shall have adequate mechanical
* SERVICES * strength.

No. of Service:
b) Minimum Size. The conductors shall not be smaller
A building or other structure served shall be supplied by than 8 mm2 copper, 14 mm2 aluminum or copper-clad
only one service. aluminum.

*EXCEPTIONS* CLEARANCES:

1. For fire pump where a separate service is required. a) Above Roofs. Conductors shall have a vertical
clearance of not less than 2,500 mm from the roof
2. For emergency electrical system where a separate surface.
service is required.
b) Vertical Clearance from Ground.
3. Multiple-Occupancy building
3,100 mm - at the electric service entrance to buildings,
4. Capacity Requirements. Two or more services shall be or at the drip loop of the building electric entrance, or
permitted: above areas or sidewalks

3,700 mm - for those areas listed in the 4,600 mm


a) Where the capacity requirements are in excess of classification when the voltage is limited to 600 volts to
2,000 amperes at a supply voltage of 600 volts or less; ground.
or
4,600 mm - over residential property and driveways,
b) Where the load requirements of a single-phase and those commercial areas not subject to truck traffic.
installation are greater than the serving agency
normally supplies through one service; or 5,500 mm - over public streets, alleys, roads, parking
areas subject to truck traffic, driveways on other than
5. Building of Large Area ( 10,000 m2 or more Total Area residential property, and other land transversed by
). vehicles such as cultivated, grazing, forest, and orchard.

6. For different voltage characteristics, such as for


different voltage, frequencies, or phases, or for UNDERGROUND SERVICE-LATERAL CONDUCTOR
different uses, such as for different rate schedules.
power, controlled water heaters and the like, they shall
not be smaller than 3.5 mm2 copper or 5.0 mm2
This is the underground service conductor between the aluminum or copper-clad aluminum.
street main, including any risers at a pole or other
structure or from transformers, and the first point of
any connection to the service-entrance conductors in a SERVICE ENTRANCE
terminal box or meter or other enclosure with adequate
space, inside or outside the building wall.
Service is defined as the portion of the supply which
extends from the street main duct or transformer to the
INSULATION. Service-lateral conductor shall withstand service switch or switchboard of the building supply.
exposure to atmospheric and other conditions of use
without detrimental leakage of current. -it is the conductor and equipment for delivering energy
from the electricity supply system to the wiring system
of the premises served.
*EXCEPTIONS*

A grounded conductor shall be permitted to be TYPES:


uninsulated as follows:

a) Bare copper used in a raceway. 1. Overhead Service Entrance

b) Bare copper for direct burial where bare copper is The most common type of service entrance employed
judged to be suitable for the soil conditions. by the power companies supplying electricity which is
either a 2, 3 or 4-wire connection. Generally, the
c) Bare copper for direct burial without regard to soil overhead service cable between the building property
conditions where part of cable assembly identified for line and the supply point is supplied by electric
underground use. company to a limit of 30 meters.

d) Aluminum or copper-clad aluminum without


insulation or covering where part of a cable assembly 2. The Underground Service Entrance
identified for underground use in a raceway or for
direct burial. The underground service entrance consists of a raceway
conduit extending from the building to the property line
where it is tapped to the main. The type of cable
SIZE AND RATING recommended is the underground service entrance
cable commonly referred to as USE.
a) General. Service lateral conductors shall have
sufficient ampacity to carry the current for the load and
shall have adequate mechanical strength.

b) Minimum Size. The conductors shall not be smaller SERVICE - ENTRANCE CONDUCTORS
than 5.5 mm2 copper or 8.0 mm2 aluminum or copper-
clad aluminum.

Where two to six service disconnecting means in No. of Service-Entrance Conductor Sets
separate enclosures supply separate loads from one Each service drop or lateral shall supply only one set of
service drop or lateral, one set of service entrance service-entrance conductors.
conductors shall be permitted to supply each or several
such service equipment enclosures.
*EXCEPTIONS:
EXCEPTION: For installations to supply only limited
loads of a single branch circuit such as small polyphase 1. Buildings with more than one occupancy.
PROTECTION:
2. Where two to six service disconnecting means in a
separate enclosures are grouped at one location and Service entrance conductors subjected to physical
supply separate loads from one service drop or lateral. damage shall be protected in any of the following ways
or methods:

SIZE AND RATING: Service entrance conductors shall be 1. By RMC


of sufficient size to carry the computed loads. 2. By IMC
3. By RNMC suitable for the location
Ungrounded conductors shall not be smaller than: 4. By EMT
5. Type MC cable or other approved means
1. 100 A ---- For one family dwelling with six or more 2-
wire branch circuits.
2. 60 A ---- For one family dwelling with an initial THE SERVICE EQUIPMENT-DISCONNECTING MEANS
computed load of 10 kVA above.
3. 40 A ---- For other loads.
GENERAL:
The service-disconnecting means shall be provided to
EXCEPTIONS: disconnect all conductors in a building or other
structures from the service-entrance conductor.
1. For loads consisting of not more than 2 - wire branch
circuits, 5.5 mm2 copper or 8.0 mm2 aluminum or NUMBER OF DISCONNECTING MEANS:
copper-clad aluminum. The service disconnecting means for each set or each
subset of service entrance conductor shall consist of not
2. By special permission, for loads limited by demand or more than six switches or six circuit breakers mounted
by the source of supply, 5.5 mm2 copper or 8.0 mm2 in a single enclosure, or in a switchboard.
aluminum or copper-clad aluminum.

3. For limited loads of single branch circuit, 3.5 mm2 LOCATION:


copper or 5.5 mm2 aluminum or copper-clad aluminum. The service disconnecting means shall be installed
either inside or outside the building or other structure
at a readily accessible location nearest the point of
INSTALLATION OF SERVICE CONDUCTORS entrance of the service entrance conductor

Service entrance conductors shall be installed in


accordance with the applicable requirements of this RATING:
Code covering the type of wiring method used and The service disconnecting means shall have a rating of
limited to the following methods: not less than the load to be carried. In no case shall the
rating be lower than specified through:
1. Open-wiring on insulators
2. Rigid Metal Conduit (RMC) 1. One circuit installation -- The service disconnecting
3. Intermediate Metallic Tubing (IMT) means shall have a rating of not less than 15 amperes.
4. Electrical Metallic Tubing (EMT)
5. Service-Entrance Cables 2. Two circuit installation -- The service disconnecting
6. Wireways means shall have a rating of not less than 30 amperes.
7. Busways
8. Auxiliary gutters 3. One family dwelling -- The service disconnecting
9. Rigid Non-Metallic Conduit (RNMC) means shall have a rating of:
10. Cable Bus
11. Mineral-Insulated Metal-Sheated Cable 60 A -- where the initial computed loads is 10 kVA or
12. Type MC Cables more
100 A -- where the initial installations consist of six or
more 2-wire branch circuit.
1. One of its major advantage is its reliability and
4. Others -- For all other installations, the service stability. It can stay on its position for years and act
disconnecting means shall have a rating of not less than when called on to act as designed, unlike the circuit
40 amperes. breaker which requires proper maintenance and
periodic testing to keep it into a tip-top condition.

NOTES: 2. The cost of a fuse is less than that of a circuit breaker.


The service disconnecting means shall simultaneously
disconnect all ungrounded conductors and shall be Standard Ampere Ratings of Fuses and Inverse time
capable of being closed on a fault equal to or greater circuit breakers
than the maximum available short-circuit current.
15, 20, 25, 30, 40, 45, 60, 70, 80, 90, 100, 110, 125, 150,
Service entrance conductor shall have a short-circuit 200, 225, 250, 300, 350, 400, 450, 500, 600, 700, 800,
protective device in each ungrounded conductors. 1000, 1200, 1600, 2000, 2500, 3000, 4000, 5000 and
6000
Fuses shall have an Interrupting Rating no less than the
maximum available short circuit current in the circuit at Fuses, circuit breakers or combinations shall not be
their supply terminals. connected in parallel.
Exception: Circuit breakers or fuses, factory assembled
Circuit breakers shall be free to open in case the circuit in parallel, and approved as a unit.
is closed on an overload. Circuit breakers shall have an
interrupting rating not less than the maximum available
short-circuit current at its supply terminals.

Position of Knife Switches


THE CIRCUIT BREAKER AND THE FUSE
a) Single-throw Knife Switches. Single-throw knife
switches shall be so placed that gravity will not tend to
A circuit breaker is an overcurrent protective device close them. Single-throw knife switches, approved for
also designed to function as a switch. It is equipped with use in the inverted position, shall be provided with a
an automatic tripping device to protect the branch locking device that will ensure that the blades remain in
circuit from overload and ground fault. the open position when so set.

A fuse is also an overcurrent protective device with a b) Double-throw Knife Switches. Double-throw knife
circuit opening fusible element which opens when there switches shall be permitted to be mounted so that the
is an overcurrent in the circuit. It is considered as the throw will be either vertical or horizontal. Where the
simplest and the most common circuit protective device throw is vertical, a locking device shall be provided to
used into the house wiring connection. hold the blades in the open position when so set.

Advantages of circuit breaker over a fuse


FEEDERS AND MAIN
1. The circuit breaker acts as a switch aside from its
being an overcurrent device. Essential considerations being adapted or followed.

2. When there is an overcurrent, the circuit breaker 1. On large installation, one feeder is provided for each
trips automatically and after correcting the fault, it is floor.
ready to be switched on again, unlike the fuse which
has to be discarded and replaced after it is busted. 2. In small installations, one or two feeders is
satisfactory.
Advantages of fuse over a circuit breaker
3. Feeder for motor must be separate and independent Principles applied in installing panel board
from the light circuits. 1. The approach should be accessible and convenient.

4. Feeders requiring more than 50 mm diameter 2. The panelboard must be centrally located to shorten
conduit should not be used. the home wiring runs.
3. It must be installed near the load center. As in most
5.Feeders should be subdivided if there are several cases, panelboard is installed near the kitchen and the
bends or offsets because a 50 mm conduit is the largest laundry where heavy loads are expected.
that could be economically used.
MAIN- is the feeder interior wiring extending from
6. Feeders radiating from the distributing panel should service switch, generator bus, or converter bus to the
be provided each with a properly rated switch and main distribution.
circuit breaker.
BRANCH CIRCUIT- is defined as the circuit conductors
7. Good practice dictates that feeders and main shall be between the final overcurrent device protecting the
installed inside a conduit pipe as it carries high voltage circuit and the outlets. This means that the branch
that should be well protected. circuit is only the wiring between the circuit overcurrent
protection device such as fuses or circuit breaker and
the outlets. However, it is a common knowledge and
practice that the branch circuit comprises the entire
circuit including the outlet receptacles and other wiring
GROUNDING PROTECTION devices.

A ground is an electrical connection which may either PROTECTION OF THE BRANCH CIRCUIT
be intentional or accidental between an electric circuit
or equipment and the earth, or to some conducting Any current in excess of the rated current capacity of
body that serves in place of the earth. The purpose of the equipment or the rated ampacity of the conductor
grounding a circuit is to fix permanently a zero voltage is called overcurrent.
point in the system. The grounded line of a circuit
should not be broken nor fused to maintain a solid and The causes of overcurrent are:
uninterrupted connection to the ground. 1. Overload in the equipment conductors.

Grounding could be accomplished in the following 2. Short circuit or ground fault


manner: As per PEC requirement, conductors shall be protected
1. Connection to a buried cold water main. against overcurrent in accordance with their ampacities
(Art. 4.5.1.3)
2. Connection to a rod or group of rods.
Ampacity - is the current-carrying capacity of an electric
3. Connection to a buried ground plate. conductor.

THE PANELBOARD CIRCUITRY DESIGN

Circuitry design varies according to the number of


A panelboard is a single panel or group of panel units designers. However, good circuitry design is based on
designed for assembly in the form of a single panel. This the following considerations:
includes buses, automatic overcurrent protective
devices, and with or without switches for the control of
light, heat or power circuit. It is designed to be placed in flexibility of the circuit
a cabinet or cutout box placed in or against a wall or It means that the installation can accommodate all
partition and accessible only from the front. probable pattern arrangements and location of the
loads for expansion, or future development
· reliability and efficiency of service It supplies outlets for lighting and appliances, including
It means to have a continuous service and supply of convenience receptacles
power that are all dependent on the wiring system.
Reliability of electric power in a facility is determined by Appliance branch circuit
two factors:
o utility service It supplies outlets intended for feeding appliances.
o building electric system
· safety of the circuitry Individual branch circuit
SAFETY means that independent service can be used in
lieu of emergency equipment as backup for normal It is designed to supply a single specific item.
services. For reliability of the circuitry, the following
principles should be considered:
o to provide double emergency power equipment at
selected weak points in the system ·
o that the electrical service and the building distribution CIRCUITING GUIDELINES:
system must act together so that the power can reach
the desired point of service There are many ways of doing circuitry but there is no
o critical loads within the best way to serve them by optimum or perfect way of doing it. However, there are
providing a reliable power either from the outside certain rules and guidelines promulgated by the NEC for
source, or by standby power package for them flexibility, economical, and convenient way of installing
o the system design must readily detect any equipment a circuitry.
failure and to be corrected automatically,
· economy as to cost
ECONOMY refers to the initial cost as well as the 1. The Code requires sufficient circuitry to supply
operating costs. These two cost-factors stand in inverse residential load of 30 watts per square meter in
relationship to one another. OVER DESIGN is as bad as buildings excluding porches, garages, and basements.
under design. It is wasteful both on initial and operating 2. The requirement of 30 watts per square meter is up
costs. to 80 sq. m for a 20 amperes circuit (2400 watts) or 60
The effect of acquiring low cost equipment: sq. m for 15 ampere circuit (1800 circuit).
o high energy cost 3. Good practice suggests that the load should not
o higher maintenance cost exceed 1600 watts for a 20 amperes circuit and 1200
o shorter life watts for a 15 amperes circuit.
· energy consideration a. Observe a minimum load of 1200 watts on a 15
It is a complex one considering the following factors: amperes circuit with a maximum area of 40 sq. m
o energy laws and codes b. A maximum load of 1600 watts on a 20 amperes
o budget circuit with a maximum area of 53 sq. m
o energy conservation technique 4. The Code requires a minimum of 20 amperes
o energy control application branch circuit to feed all small appliance
· space allocation outlets in the kitchen, pantry, dining, and family room
It must consider the following: 5. The general purpose branch circuit shall be rated at
o easy maintenance 20 amperes circuit, wired with No. 12 AWG being the
o ventilation minimum size of conductor wire required for all
o expandability convenience outlets.
o centrality 6. Plug outlets or convenience receptacles shall be
o limitation of access counted in computing the load if it is not included in the
load for general lighting circuit. To find the number of
outlets for 9 and 12 A loading on a 20 A circuit
respectively, we have:
BRANCH CIRCUIT
The branch circuit is classified into: a. For 15 A ckt : 91.5 = 6 outlets
General purpose branch circuit b. For 20 A ckt : 121.5 = 8 outlets
7. Convenience receptacles should be planned properly,
so that in case of failure by any one of the circuitry, the
entire area will not be deprived of power supply.
8. All kitchen outlets should be fed from at least two of
these circuits
9. The Code further stipulated that: “all receptacles are
potential appliance outlet and at least two circuits shall
be supplied to serve them.”
10. Certain outlets in the room should be designed as
appliance outlet like:
a. All kitchen receptacles
b. Dining room receptacles
c. One in the living room
11. The Code requires that, “at least one 20 A ckt.
Supply the laundry outlets.”
12. If air conditioner is anticipated, provide a separate
circuit for this particular appliance

OTHER GOOD PRACTICES IN CIRCUITING

1. Lighting and receptacles should not be combined in a


single circuit.
2. Avoid connecting all building lights on a single circuit
3. Lighting and receptacles should be supplied with
current from at least 2 ckt. so that if a single line is out,
the entire area is not deprived of power.
4. Do not allow combination switch and receptacle
outlets
5. Provide at least one receptacle in the bathroom, and
one outside the house. Both must be Ground Fault
Circuit Interrupter (GFCI) type
6. Provide switch control for closet lights. Pull chain
switch is nuisance
7. Convenience outlet though counted as part of the
general lighting load shall be limited to 6 convenience
outlets on a 15 A ckt and 8 convenience outlet on a 20 A
ckt.
8. The Code requires that, at least one 20 A ckt supply
shall be installed to the laundry outlets
9. Convenience outlet shall be laid out in such a manner
that no point on a wall is more than 2 meters from an
outlet. Use a grounding type receptacle only

Potrebbero piacerti anche