PROJECT : YCP

PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

OFFICE BUILDING 0.00 0.00 0

OA TR1 (2,500KVA) ST-1 BD 4000 4W Cu-Fe 40 m 400 V ACB TPN 4,000 A 4,271.86 kVA 0.497 2,124.00 kVA 3,065.82 A 4000

OB ST-1 (Busduct No.1-1) BD 1000 4W Cu-Fe 30 m 400 V ACB TPN 1,000 A 515.56 kVA 0.75 386.67 kVA 558.13 A 1000
OB-1 Tap Off Unit 1-1 LO1-D1 3C 70sqmm XLPE/PVC 9 m 400 V MCCB TPN 200 A 97.36 kVA 0.75 73.02 kVA 105.40 A 279
From Transformer to LO1-D1 (OA+OB+OB-1)
LO1-D1 LO1-T1-1 4C 4sqmm XLPE/PVC 18 m 400 V MCCB TPN 30 A 11.10 kVA 0.80 8.88 kVA 12.82 A 41
LO1-T1-1 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO1-T101-1 : Fin
LO1-D1 LO1-T1-2 4C 4sqmm XLPE/PVC 19 m 400 V MCCB TPN 30 A 13.00 kVA 0.80 10.40 kVA 15.01 A 41
LO1-T1-2 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO1-T1-2 : Fin
LO1-D1 LO1-T2-1 4C 4sqmm XLPE/PVC 23 m 400 V MCCB TPN 30 A 11.20 kVA 0.80 8.96 kVA 12.93 A 41
LO1-T2-1 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO1-T2-1 : Fin
LO1-D1 LO1-T2-2 4C 4sqmm XLPE/PVC 24 m 400 V MCCB TPN 30 A 12.80 kVA 0.80 10.24 kVA 14.78 A 41
LO1-T2-2 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO1-T2-2 : Fin
LO1-D1 LO1-T3 4C 4sqmm XLPE/PVC 28 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO1-T3 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO1-T3 : Fin
LO1-D1 LO1-T4 4C 4sqmm XLPE/PVC 28 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO1-T4 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO1-T4 : Fin
LO1-D1 LO1-C1 4C 6sqmm XLPE/PVC 8 m 400 V MCCB TPN 40 A 20.33 kVA 0.80 16.26 kVA 23.47 A 53
LO1-C1 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO1-C1 : Fin
LO1-D1 P-O-1-01 4C 4sqmm XLPE/PVC 11 m 400 V MCCB TPN 20 A 4.23 kVA 0.70 2.96 kVA 4.27 A 41

Voltage Drop shall be less than 3%. - 1 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

P-O-1-01 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V P-O-1-01 : Fin

Voltage Drop shall be less than 3%. - 2 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

OC ST-1 (Busduct No.1-2) BD 1000 4W Cu-Fe 4 m 400 V ACB TPN 1,000 A 418.20 kVA 0.75 313.65 kVA 452.73 A 1000
OC-1 Tap Off Unikt 1-2 LO2-D1 4x1C 120sqmm XLPE/PVC 9 m 400 V MCCB TPN 250 A 139.40 kVA 0.75 104.55 kVA 150.91 A 398
From Transformer to LO2-D1 (OA+OB+OC+OC-1)
LO2-D1 LO2-T1-1 4C 4sqmm XLPE/PVC 18 m 400 V MCCB TPN 30 A 11.10 kVA 0.80 8.88 kVA 12.82 A 41
LO2-T1-1 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO2-T1-1 : Fin
LO2-D1 LO2-T1-2 4C 4sqmm XLPE/PVC 19 m 400 V MCCB TPN 30 A 12.80 kVA 0.80 10.24 kVA 14.78 A 41
LO2-T1-2 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO2-T1-2 : Fin
LO2-D1 LO2-T2 4C 4sqmm XLPE/PVC 19 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO2-T2 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO2-T2 : Fin
LO2-D1 LO2-T15 4C 4sqmm XLPE/PVC 23 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO2-T15 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO2-T15 : Fin
LO2-D1 LO2-T16 4C 4sqmm XLPE/PVC 23 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO2-T16 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO2-T16 : Fin
LO2-D1 LO2-T3 4C 4sqmm XLPE/PVC 24 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO2-T3 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO2-T3 : Fin
LO2-D1 LO2-T4 4C 4sqmm XLPE/PVC 23 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO2-T4 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO2-T4 : Fin
LO2-D1 LO2-T5-1 4C 4sqmm XLPE/PVC 24 m 400 V MCCB TPN 30 A 11.10 kVA 0.80 8.88 kVA 12.82 A 41
LO2-T5 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO2-T5 : Fin

Voltage Drop shall be less than 3%. - 3 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

LO2-D1 LO2-T5-2 4C 4sqmm XLPE/PVC 28 m 400 V MCCB TPN 30 A 12.80 kVA 0.80 10.24 kVA 14.78 A 41
LO2-T5-2 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO2-T5-2 : Fin
LO2-D1 LO2-T6 4C 4sqmm XLPE/PVC 28 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO2-T6 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO2-T6 : Fin

Voltage Drop shall be less than 3%. - 4 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

LO2-D1 LO2-C1 4C 6sqmm XLPE/PVC 8 m 400 V MCCB TPN 40 A 16.27 kVA 0.80 13.02 kVA 18.79 A 53
LO2-C1 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO2-C1 : Fin
LO2-D1 P-O-2-01 4C 4sqmm XLPE/PVC 11 m 400 V MCCB TPN 20 A 4.23 kVA 0.70 2.96 kVA 4.27 A 41
P-O-2-01 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V P-O-2-01 : Fin

OD ST-1 (Busduct No.1-3) BD 1000 4W Cu-Fe 4 m 400 V ACB TPN 1,000 A 278.80 kVA 0.75 209.10 kVA 301.82 A 1000
OD-1 Tap Off Unikt 1-3 LO3-D1 4x1C 120sqmm XLPE/PVC 9 m 400 V MCCB TPN 250 A 139.40 kVA 0.75 104.55 kVA 150.91 A 398
From Transformer to LO3-D1 (OA+OB+OC+OD+OD-1)
LO3-D1 LO3-T1-1 4C 4sqmm XLPE/PVC 18 m 400 V MCCB TPN 30 A 11.10 kVA 0.80 8.88 kVA 12.82 A 41
LO3-T1-1 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO3-T1-1 : Fin
LO3-D1 LO3-T1-2 4C 4sqmm XLPE/PVC 19 m 400 V MCCB TPN 30 A 12.80 kVA 0.80 10.24 kVA 14.78 A 41
LO3-T1-2 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO3-T1-2 : Fin
LO3-D1 LO3-T2 4C 4sqmm XLPE/PVC 19 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO3-T2 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO3-T2: Fin
LO3-D1 LO3-T15 4C 4sqmm XLPE/PVC 23 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO3-T15 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO3-T15 : Fin
LO3-D1 LO3-T16 4C 4sqmm XLPE/PVC 23 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO3-T16 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO3-T16 : Fin
LO3-D1 LO3-T3 4C 4sqmm XLPE/PVC 24 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO3-T3 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V

Voltage Drop shall be less than 3%. - 5 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

400 V LO3-T3 : Fin


LO3-D1 LO3-T4 4C 4sqmm XLPE/PVC 23 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO3-T4 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO3-T4 : Fin
LO3-D1 LO3-T5-1 4C 4sqmm XLPE/PVC 24 m 400 V MCCB TPN 30 A 11.10 kVA 0.80 8.88 kVA 12.82 A 41
LO3-T5-1 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO3-T5-1 : Fin

Voltage Drop shall be less than 3%. - 6 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

LO3-D1 LO3-T5-2 4C 4sqmm XLPE/PVC 28 m 400 V MCCB TPN 30 A 12.80 kVA 0.80 10.24 kVA 14.78 A 41
LO3-T5-2 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO3-T5-2 : Fin
LO3-D1 LO3-T6 4C 4sqmm XLPE/PVC 28 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO3-T6 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO3-T6 : Fin
LO3-D1 LO3-C1 4C 6sqmm XLPE/PVC 8 m 400 V MCCB TPN 40 A 16.27 kVA 0.80 13.02 kVA 18.79 A 53
LO3-C1 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO3-C1 : Fin
LO3-D1 P-O-3-01 4C 4sqmm XLPE/PVC 11 m 400 V MCCB TPN 20 A 4.23 kVA 0.70 2.96 kVA 4.27 A 41
P-O-3-01 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V P-O-3-01 : Fin

OE ST-1 (Busduct No.1-4) BD 1000 4W Cu-Fe 4 m 400 V ACB TPN 1,000 A 139.40 kVA 0.75 104.55 kVA 150.91 A 1000
OE1 Tap Off Unikt 1-4 LO4-D1 4x1C 120sqmm XLPE/PVC 9 m 400 V MCCB TPN 250 A 139.40 kVA 0.75 104.55 kVA 150.91 A 398
From Transformer to LO4-D1 (OA+OB+OC+OD+OE+OE-1)
LO4-D1 LO4-T1-1 4C 4sqmm XLPE/PVC 18 m 400 V MCCB TPN 30 A 11.10 kVA 0.80 8.88 kVA 12.82 A 41
LO4-T1-1 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO4-T1-1 : Fin
LO4-D1 LO4-T1-2 4C 4sqmm XLPE/PVC 19 m 400 V MCCB TPN 30 A 12.80 kVA 0.80 10.24 kVA 14.78 A 41
LO4-T1-2 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO4-T1-2 : Fin
LO4-D1 LO4-T2 4C 4sqmm XLPE/PVC 19 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO4-T2 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO4-T2 : Fin
LO4-D1 LO4-T15 4C 4sqmm XLPE/PVC 23 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO4-T15 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V

Voltage Drop shall be less than 3%. - 7 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

400 V LO4-T15 : Fin


LO4-D1 LO4-T16 4C 4sqmm XLPE/PVC 23 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO4-T16 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO4-T16 : Fin
LO4-D1 LO4-T3 4C 4sqmm XLPE/PVC 24 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO4-T3 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO4-T3 : Fin

Voltage Drop shall be less than 3%. - 8 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

LO4-D1 LO4-T4 4C 4sqmm XLPE/PVC 23 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO4-T4 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO4-T4 : Fin
LO4-D1 LO4-T5-1 4C 4sqmm XLPE/PVC 24 m 400 V MCCB TPN 30 A 11.10 kVA 0.80 8.88 kVA 12.82 A 41
LO4-T5-1 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO4-T5-1 : Fin
LO4-D1 LO4-T5-2 4C 4sqmm XLPE/PVC 28 m 400 V MCCB TPN 30 A 12.80 kVA 0.80 10.24 kVA 14.78 A 41
LO4-T5-2 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO4-T5-2 : Fin
LO4-D1 LO4-T6 4C 4sqmm XLPE/PVC 28 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO4-T1-1 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO4-T1-1 : Fin
LO4-D1 LO4-C1 4C 6sqmm XLPE/PVC 8 m 400 V MCCB TPN 40 A 16.27 kVA 0.80 13.02 kVA 18.79 A 53
LO4-C1 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO4-C1: Fin
LO4-D1 P-O-4-01 4C 4sqmm XLPE/PVC 11 m 400 V MCCB TPN 20 A 4.23 kVA 0.70 2.96 kVA 4.27 A 41
P-O-4-01 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V P-O-4-01 : Fin
0.00 0.00 0

Voltage Drop shall be less than 3%. - 9 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

OF ST-1 (Busduct No.2-1) BD 1000 4W Cu-Fe 49 m 400 V ACB TPN 1,000 A 557.60 kVA 0.75 418.20 kVA 603.64 A 1000
OF-1 Tap Off Unikt 2-1 LO5-D1 4x1C 120sqmm XLPE/PVC 9 m 400 V MCCB TPN 250 A 139.40 kVA 0.75 104.55 kVA 150.91 A 398
From Transformer to LO5-D1 (OA+OF+OF-1)
LO5-D1 LO5-T1-1 4C 4sqmm XLPE/PVC 18 m 400 V MCCB TPN 30 A 11.10 kVA 0.80 8.88 kVA 12.82 A 41
LO5-T1-1 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO5-T1-1 : Fin
LO5-D1 LO5-T1-2 4C 4sqmm XLPE/PVC 19 m 400 V MCCB TPN 30 A 12.80 kVA 0.80 10.24 kVA 14.78 A 41
LO5-T1-2 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO5-T1-2 : Fin
LO5-D1 LO5-T2 4C 4sqmm XLPE/PVC 19 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO5-T2 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO5-T2 : Fin
LO5-D1 LO5-T15 4C 4sqmm XLPE/PVC 23 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO5-T15 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO5-T15 : Fin
LO5-D1 LO5-T16 4C 4sqmm XLPE/PVC 23 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO5-T16 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO5-T16 : Fin
LO5-D1 LO5-T3 4C 4sqmm XLPE/PVC 24 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO5-T3 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO5-T3 : Fin
LO5-D1 LO5-T4 4C 4sqmm XLPE/PVC 23 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO5-T4 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO5-T4 : Fin
LO5-D1 LO5-T5-1 4C 4sqmm XLPE/PVC 24 m 400 V MCCB TPN 30 A 11.10 kVA 0.80 8.88 kVA 12.82 A 41
LO5-T5-1 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO5-T5-1 : Fin

Voltage Drop shall be less than 3%. - 10 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

LO5-D1 LO5-T5-2 4C 4sqmm XLPE/PVC 28 m 400 V MCCB TPN 30 A 12.80 kVA 0.80 10.24 kVA 14.78 A 41
LO5-T5-2 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO5-T5-2 : Fin
LO5-D1 LO5-T6 4C 4sqmm XLPE/PVC 28 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO5-T6 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO5-T6 : Fin

Voltage Drop shall be less than 3%. - 11 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

LO5-D1 LO5-C1 4C 6sqmm XLPE/PVC 8 m 400 V MCCB TPN 40 A 16.27 kVA 0.80 13.02 kVA 18.79 A 53
LO5-C1 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO5-C1 : Fin
LO5-D1 P-O-5-01 4C 4sqmm XLPE/PVC 11 m 400 V MCCB TPN 20 A 4.23 kVA 0.70 2.96 kVA 4.27 A 41
P-O-5-01 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V P-O-5-01 : Fin

OG ST-1 (Busduct No.2-2) BD 1000 4W Cu-Fe 4 m 400 V ACB TPN 1,000 A 418.20 kVA 0.75 313.65 kVA 452.73 A 1000
OG-1 Tap Off Unikt 2-2 LO6-D1 4x1C 120sqmm XLPE/PVC 9 m 400 V MCCB TPN 250 A 139.40 kVA 0.75 104.55 kVA 150.91 A 398
From Transformer to LO6-D1 (OA+OF+OG+OG-1)
LO6-D1 LO6-T1-1 4C 4sqmm XLPE/PVC 18 m 400 V MCCB TPN 30 A 11.10 kVA 0.80 8.88 kVA 12.82 A 41
LO6-T1-1 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO6-T1-1 : Fin
LO6-D1 LO6-T1-2 4C 4sqmm XLPE/PVC 19 m 400 V MCCB TPN 30 A 12.80 kVA 0.80 10.24 kVA 14.78 A 41
LO6-T1-2 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO6-T1-2 : Fin
LO6-D1 LO6-T2 4C 4sqmm XLPE/PVC 19 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO6-T2 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO6-T2 : Fin
LO6-D1 LO6-T15 4C 4sqmm XLPE/PVC 23 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO6-T15 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO6-T15 : Fin
LO6-D1 LO6-T16 4C 4sqmm XLPE/PVC 23 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO6-T16 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO6-T16 : Fin
LO6-D1 LO6-T3 4C 4sqmm XLPE/PVC 24 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO6-T3 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V

Voltage Drop shall be less than 3%. - 12 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

400 V LO6-T3 : Fin


LO6-D1 LO6-T4 4C 4sqmm XLPE/PVC 23 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO6-T4 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO6-T4 : Fin
LO6-D1 LO6-T5-1 4C 4sqmm XLPE/PVC 24 m 400 V MCCB TPN 30 A 11.10 kVA 0.80 8.88 kVA 12.82 A 41
LO6-T5-1 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO6-T5-1 : Fin

Voltage Drop shall be less than 3%. - 13 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

LO6-D1 LO6-T5-2 4C 4sqmm XLPE/PVC 28 m 400 V MCCB TPN 30 A 12.80 kVA 0.80 10.24 kVA 14.78 A 41
LO6-T5-2 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO6-T5-2 : Fin
LO6-D1 LO6-T6 4C 4sqmm XLPE/PVC 28 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO6-T6 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO6-T6 : Fin
LO6-D1 LO6-C1 4C 6sqmm XLPE/PVC 8 m 400 V MCCB TPN 40 A 16.27 kVA 0.80 13.02 kVA 18.79 A 53
LO6-C1 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO6-C1 : Fin
LO6-D1 P-O-6-01 4C 4sqmm XLPE/PVC 11 m 400 V MCCB TPN 20 A 4.23 kVA 0.70 2.96 kVA 4.27 A 41
P-O-6-01 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V P-O-6-01 : Fin

OH ST-1 (Busduct No.2-3) BD 1000 4W Cu-Fe 4 m 400 V ACB TPN 1,000 A 278.80 kVA 0.75 209.10 kVA 301.82 A 1000
OH-1 Tap Off Unikt 2-3 LO7-D1 4x1C 120sqmm XLPE/PVC 9 m 400 V MCCB TPN 250 A 139.40 kVA 0.75 104.55 kVA 150.91 A 398
From Transformer to LO7-D1 (OA+OF+OG+OH+OH-1)
LO7-D1 LO7-T1-1 4C 4sqmm XLPE/PVC 18 m 400 V MCCB TPN 30 A 11.10 kVA 0.80 8.88 kVA 12.82 A 41
LO7-T1-1 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO7-T1-1 : Fin
LO7-D1 LO7-T1-2 4C 4sqmm XLPE/PVC 19 m 400 V MCCB TPN 30 A 12.80 kVA 0.80 10.24 kVA 14.78 A 41
LO7-T1-2 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO7-T1-2 : Fin
LO7-D1 LO7-T2 4C 4sqmm XLPE/PVC 19 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO7-T2 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO7-T2 : Fin
LO7-D1 LO7-T15 4C 4sqmm XLPE/PVC 23 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO7-T15 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V

Voltage Drop shall be less than 3%. - 14 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

400 V LO7-T15 : Fin


LO7-D1 LO7-T16 4C 4sqmm XLPE/PVC 23 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO7-T16 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO7-T16 : Fin
LO7-D1 LO7-T3 4C 4sqmm XLPE/PVC 24 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO7-T3 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO7-T3 : Fin

Voltage Drop shall be less than 3%. - 15 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

LO7-D1 LO7-T4 4C 4sqmm XLPE/PVC 23 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO7-T4 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO7-T4: Fin
LO7-D1 LO7-T5-1 4C 4sqmm XLPE/PVC 24 m 400 V MCCB TPN 30 A 11.10 kVA 0.80 8.88 kVA 12.82 A 41
LO7-T5-1 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO7-T5-1 : Fin
LO7-D1 LO7-T5-2 4C 4sqmm XLPE/PVC 28 m 400 V MCCB TPN 30 A 12.80 kVA 0.80 10.24 kVA 14.78 A 41
LO7-T5-2 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO7-T5-2 : Fin
LO7-D1 LO7-T6 4C 4sqmm XLPE/PVC 28 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO7-T6 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO7-T6 : Fin
LO7-D1 LO7-C1 4C 6sqmm XLPE/PVC 8 m 400 V MCCB TPN 40 A 16.27 kVA 0.80 13.02 kVA 18.79 A 53
LO7-C1 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO7-C1 : Fin
LO7-D1 P-O-7-01 4C 4sqmm XLPE/PVC 11 m 400 V MCCB TPN 20 A 4.23 kVA 0.70 2.96 kVA 4.27 A 41
P-O-7-01 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V P-O-7-01 : Fin

OI ST-1 (Busduct No.2-4) BD 1000 4W Cu-Fe 4 m 400 V ACB TPN 1,000 A 139.40 kVA 0.75 104.55 kVA 150.91 A 1000
OI-1 Tap Off Unikt 2-4 LO8-D1 4x1C 120sqmm XLPE/PVC 9 m 400 V MCCB TPN 250 A 139.40 kVA 0.75 104.55 kVA 150.91 A 398
From Transformer to LO8-D1 (OA+OF+OG+OH+OI+OI-1)
LO8-D1 LO8-T1-1 4C 4sqmm XLPE/PVC 18 m 400 V MCCB TPN 30 A 11.10 kVA 0.80 8.88 kVA 12.82 A 41
LO8-T1-1 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO8-T1-1 : Fin
LO8-D1 LO8-T1-2 4C 4sqmm XLPE/PVC 19 m 400 V MCCB TPN 30 A 12.80 kVA 0.80 10.24 kVA 14.78 A 41
LO8-T1-2 to Final Point 2X1C 2.5sqmm PVC 25 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V

Voltage Drop shall be less than 3%. - 16 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

400 V LO8-T1-2 : Fin


LO8-D1 LO8-T2 4C 4sqmm XLPE/PVC 19 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO8-T2 to Final Point 2X1C 2.5sqmm PVC 25 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO8-T2 : Fin
LO8-D1 LO8-T15 4C 4sqmm XLPE/PVC 23 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO8-T15 to Final Point 2X1C 2.5sqmm PVC 25 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO8-T15 : Fin

Voltage Drop shall be less than 3%. - 17 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

LO8-D1 LO8-T16 4C 4sqmm XLPE/PVC 23 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO8-T16 to Final Point 2X1C 2.5sqmm PVC 25 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO8-T16 : Fin
LO8-D1 LO8-T3 4C 4sqmm XLPE/PVC 24 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO8-T3 to Final Point 2X1C 2.5sqmm PVC 25 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO8-T3 : Fin
LO8-D1 LO8-T4 4C 4sqmm XLPE/PVC 23 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO8-T4 to Final Point 2X1C 2.5sqmm PVC 25 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO8-T4 : Fin
LO8-D1 LO8-T5-1 4C 4sqmm XLPE/PVC 24 m 400 V MCCB TPN 30 A 11.10 kVA 0.80 8.88 kVA 12.82 A 41
LO8-T5-1 to Final Point 2X1C 2.5sqmm PVC 25 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO8-T5-1 : Fin
LO8-D1 LO8-T5-2 4C 4sqmm XLPE/PVC 28 m 400 V MCCB TPN 30 A 12.80 kVA 0.80 10.24 kVA 14.78 A 41
LO8-T5-2 to Final Point 2X1C 2.5sqmm PVC 25 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO8-T5-2 : Fin
LO8-D1 LO8-T6 4C 4sqmm XLPE/PVC 28 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO8-T6 to Final Point 2X1C 2.5sqmm PVC 25 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO8-T6 : Fin
LO8-D1 LO8-C1 4C 6sqmm XLPE/PVC 8 m 400 V MCCB TPN 40 A 16.27 kVA 0.80 13.02 kVA 18.79 A 53
LO8-C1 to Final Point 2X1C 2.5sqmm PVC 25 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO8-C1 : Fin
LO8-D1 P-O-8-01 4C 4sqmm XLPE/PVC 11 m 400 V MCCB TPN 20 A 4.23 kVA 0.70 2.96 kVA 4.27 A 41
LO8-T1-1 to Final Point 2X1C 2.5sqmm PVC 25 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO8-T1-1 : Fin
0.00 0.00 0

Voltage Drop shall be less than 3%. - 18 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

OJ ST-1 (Busduct No.3-1) BD 1000 4W Cu-Fe 34 m 400 V ACB TPN 1,000 A 470.52 kVA 0.75 352.88 kVA 509.35 A 1000
OJ-1 Tap Off Unikt 3-1 LO1-D2 4C 70sqmm XLPE/PVC 8 m 400 V MCCB TPN 200 A 100.23 kVA 0.75 75.17 kVA 108.50 A 279
From Transformer to LO1-D2 (OA+OJ+OJ-1)
LO1-D2 LO1-T5 4C 4sqmm XLPE/PVC 20 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO1-T5 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO1-T5 : Fin
LO1-D2 LO1-T6-2 4C 4sqmm XLPE/PVC 20 m 400 V MCCB TPN 30 A 13.30 kVA 0.80 10.64 kVA 15.36 A 41
LO1-T6-2 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO1-T6-2 : Fin
LO1-D2 LO1-T6-1 4C 4sqmm XLPE/PVC 16 m 400 V MCCB TPN 30 A 11.20 kVA 0.80 8.96 kVA 12.93 A 41
LO1-T6-1 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO1-T6-1 : Fin
LO1-D2 LO1-T7 4C 4sqmm XLPE/PVC 15 m 400 V MCCB TPN 30 A 11.10 kVA 0.80 8.88 kVA 12.82 A 41
LO1-T7 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO1-T7 : Fin
LO1-D2 LO1-T8 4C 4sqmm XLPE/PVC 16 m 400 V MCCB TPN 30 A 11.10 kVA 0.80 8.88 kVA 12.82 A 41
LO1-T8 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO1-T8 : Fin
LO1-D2 LO1-T9 4C 4sqmm XLPE/PVC 21 m 400 V MCCB TPN 30 A 11.10 kVA 0.80 8.88 kVA 12.82 A 41
LO1-T9 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO1-T9 : Fin
LO1-D2 LO1-T10-1 4C 4sqmm XLPE/PVC 20 m 400 V MCCB TPN 30 A 11.10 kVA 0.80 8.88 kVA 12.82 A 41
LO1-T10-1 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO1-T10-1 : Fin
LO1-D2 LO1-T10-2 4C 4sqmm XLPE/PVC 21 m 400 V MCCB TPN 30 A 13.40 kVA 0.80 10.72 kVA 15.47 A 41
LO1-T10-2 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO1-T10-2 : Fin

Voltage Drop shall be less than 3%. - 19 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

LO1-D2 P-O-1-06 4C 4sqmm XLPE/PVC 11 m 400 V MCCB TPN 20 A 4.23 kVA 0.70 2.96 kVA 4.27 A 41
P-O-1-06 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V P-O-1-06 : Fin

Voltage Drop shall be less than 3%. - 20 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

OK ST-1 (Busduct No.3-2) BD 1000 4W Cu-Fe 4 m 400 V ACB TPN 1,000 A 370.29 kVA 0.75 277.71 kVA 400.85 A 1000
OK-1 Tap Off Unikt 3-2 LO2-D2 4x1C 120sqmm XLPE/PVC 8 m 400 V MCCB TPN 250 A 123.43 kVA 0.75 92.57 kVA 133.62 A 398
From Transformer to LO2-D2 (OA+OJ+OK+OK-1)
LO2-D2 LO2-T7 4C 4sqmm XLPE/PVC 20 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO2-T7 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO2-T7 : Fin
LO2-D2 LO2-T8 4C 4sqmm XLPE/PVC 20 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO2-T8 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO2-T8 : Fin
LO2-D2 LO2-T9-2 4C 4sqmm XLPE/PVC 16 m 400 V MCCB TPN 30 A 13.30 kVA 0.80 10.64 kVA 15.36 A 41
LO2-T9-2 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO2-T9-2 : Fin
LO2-D2 LO2-T9-1 4C 4sqmm XLPE/PVC 15 m 400 V MCCB TPN 30 A 11.20 kVA 0.80 8.96 kVA 12.93 A 41
LO2-T9-1 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO2-T9-1 : Fin
LO2-D2 LO2-T10 4C 4sqmm XLPE/PVC 16 m 400 V MCCB TPN 30 A 11.10 kVA 0.80 8.88 kVA 12.82 A 41
LO2-T10 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO2-T10 : Fin
LO2-D2 LO2-T11 4C 4sqmm XLPE/PVC 21 m 400 V MCCB TPN 30 A 11.10 kVA 0.80 8.88 kVA 12.82 A 41
LO2-T11 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO2-T11 : Fin
LO2-D2 LO2-T12 4C 4sqmm XLPE/PVC 20 m 400 V MCCB TPN 30 A 11.10 kVA 0.80 8.88 kVA 12.82 A 41
LO2-T12 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO2-T12 : Fin
LO2-D2 LO2-T13-1 4C 4sqmm XLPE/PVC 21 m 400 V MCCB TPN 30 A 11.20 kVA 0.80 8.96 kVA 12.93 A 41
LO2-T13-1 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO2-T13-1 : Fin

Voltage Drop shall be less than 3%. - 21 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

LO2-D2 LO2-T13-2 4C 4sqmm XLPE/PVC 25 m 400 V MCCB TPN 30 A 13.30 kVA 0.80 10.64 kVA 15.36 A 41
LO2-T13-2 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO2-T13-2 : Fin
LO2-D2 LO2-T14 4C 4sqmm XLPE/PVC 25 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO2-T14 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO2-T14 : Fin

Voltage Drop shall be less than 3%. - 22 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

LO2-D2 P-O-2-02 4C 4sqmm XLPE/PVC 11 m 400 V MCCB TPN 20 A 4.23 kVA 0.70 2.96 kVA 4.27 A 41
P-O-2-02 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V P-O-2-02 : Fin

OL ST-1 (Busduct No.3-3) BD 1000 4W Cu-Fe 4 m 400 V ACB TPN 1,000 A 246.86 kVA 0.75 185.14 kVA 267.23 A 1000
OL-1 Tap Off Unikt 3-3 LO3-D2 4x1C 120sqmm XLPE/PVC 8 m 400 V MCCB TPN 250 A 123.43 kVA 0.75 92.57 kVA 133.62 A 398
From Transformer to LO3-D2 (OA+OJ+OK+OL+OL-1)
LO3-D2 LO3-T7 4C 4sqmm XLPE/PVC 20 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO3-T7 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO3-T7 : Fin
LO3-D2 LO3-T8 4C 4sqmm XLPE/PVC 20 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO3-T8 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO3-T8 : Fin
LO3-D2 LO3-T9-2 4C 4sqmm XLPE/PVC 16 m 400 V MCCB TPN 30 A 13.30 kVA 0.80 10.64 kVA 15.36 A 41
LO3-T9-2 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO3-T9-2 : Fin
LO3-D2 LO3-T9-1 4C 4sqmm XLPE/PVC 15 m 400 V MCCB TPN 30 A 11.20 kVA 0.80 8.96 kVA 12.93 A 41
LO3-T9-1 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO3-T9-1 : Fin
LO3-D2 LO3-T10 4C 4sqmm XLPE/PVC 16 m 400 V MCCB TPN 30 A 11.10 kVA 0.80 8.88 kVA 12.82 A 41
LO3-T10 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO3-T10 : Fin
LO3-D2 LO3-T11 4C 4sqmm XLPE/PVC 21 m 400 V MCCB TPN 30 A 11.10 kVA 0.80 8.88 kVA 12.82 A 41
LO3-T11 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO3-T11 : Fin
LO3-D2 LO3-T12 4C 4sqmm XLPE/PVC 20 m 400 V MCCB TPN 30 A 11.10 kVA 0.80 8.88 kVA 12.82 A 41
LO3-T12 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V

Voltage Drop shall be less than 3%. - 23 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

400 V LO3-T12 : Fin


LO3-D2 LO3-T13-1 4C 4sqmm XLPE/PVC 21 m 400 V MCCB TPN 30 A 11.20 kVA 0.80 8.96 kVA 12.93 A 41
LO3-T13-1 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO3-T13-1 : Fin
LO3-D2 LO3-T13-2 4C 4sqmm XLPE/PVC 25 m 400 V MCCB TPN 30 A 13.30 kVA 0.80 10.64 kVA 15.36 A 41
LO3-T13-2 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO3-T13-2 : Fin

Voltage Drop shall be less than 3%. - 24 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

LO3-D2 LO3-T14 4C 4sqmm XLPE/PVC 25 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO3-T14 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO3-T14 : Fin
LO3-D2 P-O-3-02 4C 4sqmm XLPE/PVC 11 m 400 V MCCB TPN 20 A 4.23 kVA 0.70 2.96 kVA 4.27 A 41
P-O-3-02 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V P-O-3-02 : Fin

OM ST-1 (Busduct No.3-4) BD 1000 4W Cu-Fe 4 m 400 V ACB TPN 1,000 A 123.43 kVA 0.75 92.57 kVA 133.62 A 1000
OM-1 Tap Off Unikt 3-4 LO4-D2 4x1C 120sqmm XLPE/PVC 8 m 400 V MCCB TPN 250 A 123.43 kVA 0.75 92.57 kVA 133.62 A 398
From Transformer to LO4-D2 (OA+OJ+OK+OL+OM+OM-1)
LO4-D2 LO4-T7 4C 4sqmm XLPE/PVC 20 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO4-T7 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO4-T7 : Fin
LO4-D2 LO4-T8 4C 4sqmm XLPE/PVC 20 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO4-T8 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO4-T8 : Fin
LO4-D2 LO4-T9-2 4C 4sqmm XLPE/PVC 16 m 400 V MCCB TPN 30 A 13.30 kVA 0.80 10.64 kVA 15.36 A 41
LO4-T9-2 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO4-T9-2 : Fin
LO4-D2 LO4-T9-1 4C 4sqmm XLPE/PVC 15 m 400 V MCCB TPN 30 A 11.20 kVA 0.80 8.96 kVA 12.93 A 41
LO4-T9-1 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO4-T9-1 : Fin
LO4-D2 LO4-T10 4C 4sqmm XLPE/PVC 16 m 400 V MCCB TPN 30 A 11.10 kVA 0.80 8.88 kVA 12.82 A 41
LO4-T10 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO4-T10 : Fin
LO4-D2 LO4-T11 4C 4sqmm XLPE/PVC 21 m 400 V MCCB TPN 30 A 11.10 kVA 0.80 8.88 kVA 12.82 A 41
LO4-T11 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V

Voltage Drop shall be less than 3%. - 25 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

400 V LO4-T11 : Fin


LO4-D2 LO4-T12 4C 4sqmm XLPE/PVC 20 m 400 V MCCB TPN 30 A 11.10 kVA 0.80 8.88 kVA 12.82 A 41
LO4-T12 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO4-T12 : Fin
LO4-D2 LO4-T13-1 4C 4sqmm XLPE/PVC 21 m 400 V MCCB TPN 30 A 11.20 kVA 0.80 8.96 kVA 12.93 A 41
LO4-T13-1 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO4-T13-1 : Fin

Voltage Drop shall be less than 3%. - 26 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

LO4-D2 LO4-T13-2 4C 4sqmm XLPE/PVC 25 m 400 V MCCB TPN 30 A 13.30 kVA 0.80 10.64 kVA 15.36 A 41
LO4-T13-2 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO4-T13-2 : Fin
LO4-D2 LO4-T14 4C 4sqmm XLPE/PVC 25 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO4-T14 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO4-T14 : Fin
LO4-D2 P-O-4-02 4C 4sqmm XLPE/PVC 11 m 400 V MCCB TPN 20 A 4.23 kVA 0.70 2.96 kVA 4.27 A 41
P-O-4-02 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V P-O-4-02 : Fin
0.00 0.00 0

Voltage Drop shall be less than 3%. - 27 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

ON ST-1 (Busduct No.4-1) BD 1000 4W Cu-Fe 53 m 400 V ACB TPN 1,000 A 498.97 kVA 0.75 374.22 kVA 540.16 A 1000
ON-1 Tap Off Unikt 4-1 LO5-D2 4x1C 120sqmm XLPE/PVC 8 m 400 V MCCB TPN 250 A 123.43 kVA 0.75 92.57 kVA 133.62 A 398
From Transformer to LO5-D2 (OA+ON+ON-1)
LO5-D2 LO5-T7 4C 4sqmm XLPE/PVC 20 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO5-T7 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO5-T7 : Fin
LO5-D2 LO5-T8 4C 4sqmm XLPE/PVC 20 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO5-T8 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO5-T8 : Fin
LO5-D2 LO5-T9-2 4C 4sqmm XLPE/PVC 16 m 400 V MCCB TPN 30 A 13.30 kVA 0.80 10.64 kVA 15.36 A 41
LO5-T9-2 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO5-T9-2 : Fin
LO5-D2 LO5-T9-1 4C 4sqmm XLPE/PVC 15 m 400 V MCCB TPN 30 A 11.20 kVA 0.80 8.96 kVA 12.93 A 41
LO5-T9-1 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO5-T9-1 : Fin
LO5-D2 LO5-T10 4C 4sqmm XLPE/PVC 16 m 400 V MCCB TPN 30 A 11.10 kVA 0.80 8.88 kVA 12.82 A 41
LO5-T10 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO5-T10 : Fin
LO5-D2 LO5-T11 4C 4sqmm XLPE/PVC 21 m 400 V MCCB TPN 30 A 11.10 kVA 0.80 8.88 kVA 12.82 A 41
LO5-T11 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO5-T11 : Fin
LO5-D2 LO5-T12 4C 4sqmm XLPE/PVC 20 m 400 V MCCB TPN 30 A 11.10 kVA 0.80 8.88 kVA 12.82 A 41
LO5-T12 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO5-T12 : Fin
LO5-D2 LO5-T13-1 4C 4sqmm XLPE/PVC 21 m 400 V MCCB TPN 30 A 11.20 kVA 0.80 8.96 kVA 12.93 A 41
LO5-T13-1 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO5-T13-1 : Fin

Voltage Drop shall be less than 3%. - 28 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

LO5-D2 LO5-T13-2 4C 6sqmm XLPE/PVC 25 m 400 V MCCB TPN 30 A 13.30 kVA 0.80 10.64 kVA 15.36 A 53
LO5-T13-2 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO5-T13-2 : Fin
LO5-D2 LO5-T14 4C 4sqmm XLPE/PVC 25 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO5-T14 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO5-T14 : Fin

Voltage Drop shall be less than 3%. - 29 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

LO5-D2 P-O-5-02 4C 4sqmm XLPE/PVC 11 m 400 V MCCB TPN 20 A 4.23 kVA 0.70 2.96 kVA 4.27 A 41
P-O-5-02 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V P-O-5-02 : Fin

OO ST-1 (Busduct No.4-2) BD 1000 4W Cu-Fe 4 m 400 V ACB TPN 1,000 A 375.54 kVA 0.75 281.65 kVA 406.54 A 1000
OO-1 Tap Off Unikt 4-2 LO6-D2 4x1C 120sqmm XLPE/PVC 8 m 400 V MCCB TPN 250 A 123.43 kVA 0.75 92.57 kVA 133.62 A 398
From Transformer to LO6-D2 (OA+ON+OO+OO-1)
LO6-D2 LO6-T7 4C 4sqmm XLPE/PVC 20 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO6-T7 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO6-T7 : Fin
LO6-D2 LO6-T8 4C 4sqmm XLPE/PVC 20 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO6-T8 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO6-T8 : Fin
LO6-D2 LO6-T9-2 4C 4sqmm XLPE/PVC 16 m 400 V MCCB TPN 30 A 13.30 kVA 0.80 10.64 kVA 15.36 A 41
LO6-T9-2 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO6-T9-2 : Fin
LO6-D2 LO6-T9-1 4C 4sqmm XLPE/PVC 15 m 400 V MCCB TPN 30 A 11.20 kVA 0.80 8.96 kVA 12.93 A 41
LO6-T9-1 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO6-T9-1 : Fin
LO6-D2 LO6-T10 4C 4sqmm XLPE/PVC 16 m 400 V MCCB TPN 30 A 11.10 kVA 0.80 8.88 kVA 12.82 A 41
LO6-T10 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO6-T10 : Fin
LO6-D2 LO6-T11 4C 4sqmm XLPE/PVC 21 m 400 V MCCB TPN 30 A 11.10 kVA 0.80 8.88 kVA 12.82 A 41
LO6-T11 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO6-T11 : Fin
LO6-D2 LO6-T12 4C 4sqmm XLPE/PVC 20 m 400 V MCCB TPN 30 A 11.10 kVA 0.80 8.88 kVA 12.82 A 41
LO6-T12 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V

Voltage Drop shall be less than 3%. - 30 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

400 V LO6-T12 : Fin


LO6-D2 LO6-T13-1 4C 4sqmm XLPE/PVC 21 m 400 V MCCB TPN 30 A 11.20 kVA 0.80 8.96 kVA 12.93 A 41
LO6-T13-1 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO6-T13-1 : Fin
LO6-D2 LO6-T13-2 4C 4sqmm XLPE/PVC 25 m 400 V MCCB TPN 30 A 13.30 kVA 0.80 10.64 kVA 15.36 A 41
LO6-T13-2 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO6-T13-2 : Fin

Voltage Drop shall be less than 3%. - 31 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

LO6-D2 LO6-T14 4C 4sqmm XLPE/PVC 25 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO6-T14 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO6-T14 : Fin
LO6-D2 P-O-6-02 4C 4sqmm XLPE/PVC 11 m 400 V MCCB TPN 20 A 4.23 kVA 0.70 6.72 kVA 9.70 A 41
P-O-6-02 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V P-O-6-02 : Fin

OP ST-1 (Busduct No.4-3) BD 1000 4W Cu-Fe 4 m 400 V ACB TPN 1,000 A 252.11 kVA 0.75 189.08 kVA 272.92 A 1000
OP-1 Tap Off Unikt 4-3 LO7-D2 4x1C 120sqmm XLPE/PVC 8 m 400 V MCCB TPN 250 A 123.43 kVA 0.75 92.57 kVA 133.62 A 398
From Transformer to LO7-D2 (OA+ON+OO+OP+OP-1)
LO7-D2 LO7-T7 4C 4sqmm XLPE/PVC 20 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO7-T7 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO7-T7 : Fin
LO7-D2 LO7-T8 4C 4sqmm XLPE/PVC 20 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO7-T8 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO7-T8 : Fin
LO7-D2 LO7-T9-2 4C 4sqmm XLPE/PVC 16 m 400 V MCCB TPN 30 A 13.30 kVA 0.80 10.64 kVA 15.36 A 41
LO7-T9-2 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO7-T9-2 : Fin
LO7-D2 LO7-T9-1 4C 4sqmm XLPE/PVC 15 m 400 V MCCB TPN 30 A 11.20 kVA 0.80 8.96 kVA 12.93 A 41
LO7-T9-1 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO7-T9-1 : Fin
LO7-D2 LO7-T10 4C 4sqmm XLPE/PVC 16 m 400 V MCCB TPN 30 A 11.10 kVA 0.80 8.88 kVA 12.82 A 41
LO7-T10 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO7-T10 : Fin
LO7-D2 LO7-T11 4C 4sqmm XLPE/PVC 21 m 400 V MCCB TPN 30 A 11.10 kVA 0.80 8.88 kVA 12.82 A 41
LO7-T11 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V

Voltage Drop shall be less than 3%. - 32 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

400 V LO7-T11 : Fin


LO7-D2 LO7-T12 4C 4sqmm XLPE/PVC 20 m 400 V MCCB TPN 30 A 11.10 kVA 0.80 8.88 kVA 12.82 A 41
LO7-T12 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO7-T12 : Fin
LO7-D2 LO7-T13-1 4C 4sqmm XLPE/PVC 21 m 400 V MCCB TPN 30 A 11.20 kVA 0.80 8.96 kVA 12.93 A 41
LO7-T13-1 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO7-T13-1 : Fin

Voltage Drop shall be less than 3%. - 33 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

LO7-D2 LO7-T13-2 4C 4sqmm XLPE/PVC 25 m 400 V MCCB TPN 30 A 13.30 kVA 0.80 10.64 kVA 15.36 A 41
LO13-2-T7 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO7-T13-2 : Fin
LO7-D2 LO7-T14 4C 4sqmm XLPE/PVC 25 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO7-T14 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO7-T14 : Fin
LO7-D2 P-O-7-02 4C 4sqmm XLPE/PVC 11 m 400 V MCCB TPN 20 A 4.23 kVA 0.70 2.96 kVA 4.27 A 41
P-O-7-02 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V P-O-7-02 : Fin

OQ ST-1 (Busduct No.4-4) BD 1000 4W Cu-Fe 4 m 400 V ACB TPN 1,000 A 128.68 kVA 0.75 96.51 kVA 139.30 A 1000
OQ-1 Tap Off Unikt 4-4 LO8-D2 4x1C 120sqmm XLPE/PVC 8 m 400 V MCCB TPN 250 A 128.68 kVA 0.75 96.51 kVA 139.30 A 398
From Transformer to LO8-D2 (OA+ON+OO+OP+OQ+OQ-1)
LO8-D2 LO8-T7 4C 4sqmm XLPE/PVC 20 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO8-T7 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO8-T7 : Fin
LO8-D2 LO8-T8 4C 4sqmm XLPE/PVC 20 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO8-T8 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO8-T8 : Fin
LO8-D2 LO8-T9-2 4C 4sqmm XLPE/PVC 16 m 400 V MCCB TPN 30 A 13.30 kVA 0.80 10.64 kVA 15.36 A 41
LO8-T9-2 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO8-T9-2 : Fin
LO8-D2 LO8-T9-1 4C 4sqmm XLPE/PVC 15 m 400 V MCCB TPN 30 A 11.20 kVA 0.80 8.96 kVA 12.93 A 41
LO8-T9-1 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO8-T9-1 : Fin
LO8-D2 LO8-T10 4C 4sqmm XLPE/PVC 16 m 400 V MCCB TPN 30 A 11.10 kVA 0.80 8.88 kVA 12.82 A 41
LO8-T10 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V

Voltage Drop shall be less than 3%. - 34 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

400 V LO8-T10 : Fin


LO8-D2 LO8-T11 4C 4sqmm XLPE/PVC 21 m 400 V MCCB TPN 30 A 11.10 kVA 0.80 8.88 kVA 12.82 A 41
LO8-T11 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO8-T11 : Fin
LO8-D2 LO8-T12 4C 4sqmm XLPE/PVC 20 m 400 V MCCB TPN 30 A 11.10 kVA 0.80 8.88 kVA 12.82 A 41
LO8-T12 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO8-T12 : Fin

Voltage Drop shall be less than 3%. - 35 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

LO8-D2 LO8-T13-1 4C 4sqmm XLPE/PVC 21 m 400 V MCCB TPN 30 A 11.20 kVA 0.80 8.96 kVA 12.93 A 41
LO8-T13-1 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO8-T13-1 : Fin
LO8-D2 LO8-T13-2 4C 4sqmm XLPE/PVC 25 m 400 V MCCB TPN 30 A 13.30 kVA 0.80 10.64 kVA 15.36 A 41
LO8-T13-2 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO8-T13-2 : Fin
LO8-D2 LO8-T14 4C 4sqmm XLPE/PVC 25 m 400 V MCCB TPN 30 A 11.30 kVA 0.80 9.04 kVA 13.05 A 41
LO8-T14 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO8-T14 : Fin
LO8-D2 P-O-8-02 4C 4sqmm XLPE/PVC 11 m 400 V MCCB TPN 20 A 4.23 kVA 0.70 2.96 kVA 4.27 A 41
P-O-8-02 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V P-O-8-02 : Fin
LO8-D2 LOR-C1 4C 4sqmm XLPE/PVC 11 m 400 V MCCB TPN 30 A 4.95 kVA 0.70 3.47 kVA 5.01 A 41
LO8-T7 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LO8-T7 : Fin

Voltage Drop shall be less than 3%. - 36 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

0.00 0.00 0
ST-1 P-O-B1-01 4C 10sqmm XLPE/PVC 73 m 400 V MCCB TPN 30 A 8.94 kVA 1.00 8.94 kVA 8.60 A 73
P-O-B1-01 To P-O-B1-02 (M Scope) 4C 6sqmm XLPE/PVC 7 m 400 V MCCB TPN 15 A 6.00 kVA 0.75 4.50 kVA 6.50 A 53
P-O-B1-02 To Final Point (M Scope) 4C 2.5sqmm XLPE/PVC 50 m 400 V MCCB TPN 15 A 2.98 kVA 1.00 2.98 kVA 4.30 A 31
400 V P-O-B1-01 : Fin
ST-1 P-O-B1-03 4C 95sqmm XLPE/PVC 78 m 400 V MCCB TPN 250 A 115.84 kVA 1.00 115.84 kVA 167.21 A 341
P-O-B1-02 To Final Point (M Scope) 4C 16sqmm XLPE/PVC 50 m 400 V MCCB TPN 60 A 37.41 kVA 1.00 37.41 kVA 54.00 A 85
400 V P-O-B1-03 : Fin
ST-1 LOB1-C1 4C 4sqmm XLPE/PVC 55 m 400 V MCCB TPN 20 A 2.74 kVA 1.00 2.74 kVA 3.95 A 41
LOG-C1 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LOG-B1 : Fin
0.00 0.00 0
OR ST-1 LOG-D1 4C 35sqmm XLPE/PVC 43 m 400 V MCCB TPN 125 A 60.60 kVA 0.65 39.17 kVA 56.54 A 176
From Transformer to LOG-D1 (OA+OR)
LOG-D1 LOG-C1 4C 25sqmm XLPE/PVC 5 m 400 V MCCB TPN 75 A 30.75 kVA 0.60 18.45 kVA 26.63 A 140
LOG-C1 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LOG-C1 : Fin
LOG-D1 LOG-T1 4C 6sqmm XLPE/PVC 24 m 400 V MCCB TPN 40 A 15.50 kVA 0.60 9.30 kVA 13.42 A 53
LOG-T1 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LOG-T1 : Fin
LOG-D1 Well pump-1 4C 25sqmm XLPE/PVC 38 m 400 V MCCB 3P 75 A 13.75 kVA 0.80 11.00 kVA 15.88 A 140
400 V Well Pump1 : Fin
0.00 0.00 0
OS ST-1 LOG-D2 4C 25sqmm XLPE/PVC 52 m 400 V MCCB TPN 100 A 50.39 kVA 0.60 30.23 kVA 43.63 A 140
From Transformer to LOG-D2 (OA+OS)
LOG-D2 P-O-GF-01 4C 10sqmm XLPE/PVC 35 m 400 V MCCB TPN 40 A 16.81 kVA 0.80 13.45 kVA 19.41 A 73
To Final Point (M Scope) 3C 6sqmm XLPE/PVC 20 m 230 V MCCB SP 15 A 2.95 kVA 1.00 2.95 kVA 12.83 A 38
400 V
400 V P-O-GF-01 : Fin
LOG-D2 P-O-GF-02 4C 4sqmm XLPE/PVC 14 m 400 V MCCB TPN 15 A 4.23 kVA 0.80 3.38 kVA 4.88 A 41
LOG-D1 To Final Point (M Scope) 4C 4sqmm XLPE/PVC 20 m 400 V MCCB TPN 15 A 3.57 kVA 1.00 3.57 kVA 8.93 A 41
400 V P-O-GF-02 : Fin

Voltage Drop shall be less than 3%. - 37 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

LOG-D2 LOG-C2 4C 10sqmm XLPE/PVC 5 m 400 V MCCB TPN 50 A 22.83 kVA 0.60 13.70 kVA 19.77 A 73
LOG-C2 to Final Point 2X1C 2.5sqmm PVC 50 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V LOG-C2 : Fin
0.00 0.00 0
10 ST-1 P-O-GF-09 4C 35sqmm XLPE/PVC 49 m 400 V MCCB TPN 125 A 54.04 kVA 0.75 40.53 kVA 58.50 A 176
From Transformer to P-O-GF-09
To Final Point (M Scope) 3C 16sqmm XLPE/PVC 20 m 400 V MCCB TPN 60 A 24.94 kVA 1.00 24.94 kVA 36.00 A 85
400 V P-O-GF-09 : Fin
P-O-GF-09 P-O-GF-06 4C 4sqmm XLPE/PVC 10 m 400 V MCCB TPN 20 A 5.96 kVA 0.80 4.77 kVA 6.89 A 41
To Final Point (M Scope) 3C 2.5sqmm XLPE/PVC 20 m 400 V MCCB TPN 15 A 2.90 kVA 1.00 2.90 kVA 4.19 A 31
400 V P-O-1-06 : Fin
P-O-GF-09 P-O-GF-07 4C 16sqmm XLPE/PVC 10 m 400 V MCCB TPN 60 A 24.94 kVA 0.80 19.95 kVA 28.80 A 85
To Final Point (M Scope) 3C 10sqmm XLPE/PVC 20 m 400 V MCCB TPN 15 A 12.47 kVA 1.00 12.47 kVA 18.00 A 73
400 V P-O-1-07 : Fin
P-O-GF-09 P-O-GF-08 4C 16sqmm XLPE/PVC 10 m 400 V MCCB TPN 60 A 24.94 kVA 0.80 19.95 kVA 28.80 A 85
To Final Point (M Scope) 3C 10sqmm XLPE/PVC 20 m 400 V MCCB TPN 15 A 12.47 kVA 1.00 12.47 kVA 18.00 A 73
400 V P-O-1-08 : Fin

11 ST-1 P-O-1-03 4x1C 185sqmm XLPE/PVC 41 m 400 V MCCB TPN 350 A 210.35 kVA 0.00 0.00 0.00 530
To Final Point (M Scope) 4C 70sqmm XLPE/PVC 20 m 400 V MCCB TPN 125 A 76.90 kVA 1.00 76.90 kVA 111.00 A 279
400 V P-O-1-03 : Fin
12 ST-1 P-O-1-05 4C 50sqmm XLPE/PVC 41 m 400 V MCCB TPN 75 A 46.80 kVA 0.75 35.10 kVA 50.66 A 215
To Final Point (M Scope) 4C 4sqmm XLPE/PVC 20 m 400 V MCCB TPN 20 A 7.16 kVA 1.00 7.16 kVA 10.33 A 41
400 V P-O-1-03 : Fin
13 ST-1 P-O-RF-01 4C 70sqmm XLPE/PVC 78 m 400 V MCCB TPN 150 A 67.97 kVA 0.75 50.98 kVA 73.59 A 279
To Final Point (M Scope) 3C 16sqmm XLPE/PVC 50 m 400 V MCCB TPN 60 A 18.70 kVA 1.00 18.70 kVA 27.00 A 85
400 V P-O-RF-01 : Fin
14 ST-1 P-O-RF-02 4x1C 300sqmm XLPE/PVC 71 m 400 V MCCB TPN 600 A 391.99 kVA 0.75 293.99 kVA 424.35 A 730
To Final Point (M Scope) Busduct 50 m 400 V MCCB TPN 125 A 55.75 kVA 1.00 55.75 kVA 80.47 A 400
400 V P-O-RF-02 : Fin
15 ST-1 P-O-RF-03 4C 70sqmm XLPE/PVC 72 m 400 V MCCB TPN 150 A 66.37 kVA 0.75 49.78 kVA 71.85 A 279
To Final Point (M Scope) 3C 16sqmm XLPE/PVC 50 m 400 V MCCB TPN 60 A 18.70 kVA 1.00 18.70 kVA 27.00 A 85
400 V P-O-RF-03 : Fin
16 ST-1 P-O-RF-04 4x1C 185sqmm XLPE/PVC 74 m 400 V MCCB TPN 400 A 228.47 kVA 0.75 171.35 kVA 247.33 A 530

Voltage Drop shall be less than 3%. - 38 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

To Final Point (M Scope) 4C 25sqmm XLPE/PVC 30 m 400 V MCCB TPN 75 A 24.00 kVA 1.00 24.00 kVA 34.64 A 140
400 V P-O-RF-04 : Fin
17 ST-1 P-O-RF-05 8x1C 185sqmm XLPE/PVC 78 m 400 V MCCB TPN 800 A 412.49 kVA 0.75 309.36 kVA 446.54 A 1060
To Final Point (M Scope) Busduct 50 m 400 V MCCB TPN 125 A 55.75 kVA 1.00 55.75 kVA 80.47 A 400
400 V P-O-RF-02 : Fin

18 ST-1 ELV-1 4C 25sqmm XLPE/PVC 86 m 400 V MCCB TPN 100 A 20.50 kVA 1.00 20.50 kVA 29.59 A 140
400 V ELV-1 : Fin
19 ST-1 ELV-2 4C 25sqmm XLPE/PVC 86 m 400 V MCCB TPN 100 A 20.50 kVA 1.00 20.50 kVA 29.59 A 140
400 V ELV-2 : Fin
20 ST-1 ELV-3 4C 25sqmm XLPE/PVC 86 m 400 V MCCB TPN 100 A 20.50 kVA 1.00 20.50 kVA 29.59 A 140
400 V ELV-3 : Fin
21 ST-1 ELV-4 4C 25sqmm XLPE/PVC 72 m 400 V MCCB TPN 100 A 20.50 kVA 1.00 20.50 kVA 29.59 A 140
400 V ELV-4 : Fin
22 ST-1 ELV-5 4C 25sqmm XLPE/PVC 72 m 400 V MCCB TPN 100 A 20.50 kVA 1.00 20.50 kVA 29.59 A 140
400 V ELV-5 : Fin
23 ST-1 ELV-6 4C 25sqmm XLPE/PVC 72 m 400 V MCCB TPN 100 A 20.50 kVA 1.00 20.50 kVA 29.59 A 140
400 V ELV-6 : Fin
24 ST-1 ELV-7 4C 25sqmm XLPE/PVC 0 400 V MCCB TPN 100 A 20.50 kVA 1.00 20.50 kVA 29.59 A 140
400 V ELV-7 : Fin
25 ST-1 ELV-9 4C 10sqmm XLPE/PVC 50 m 400 V MCCB TPN 50 A 12.50 kVA 1.00 12.50 kVA 18.04 A 73
400 V ELV-9 : Fin
0.00 0.00 0

Voltage Drop shall be less than 3%. - 39 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage
Factor Voltage Drop (v) Judge
Cap (A) Cap (A) Drop (%)
mV/A/m

0 0.00

A 1.00 4,000 A 0.02 2.73 V OK V%= 0.68%

A 1.00 1,000 A 0.10 1.64 V OK V%= 0.41%


A 0.85 237 A 0.62 0.59 V OK V%= 0.15%
Total Voltage Drop 4.96 V
A 0.85 35 A 10.00 7.24 V OK V%= 1.81%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO1-T101-1 : Final Point Voltage Drop (Less than 4%) 13.62 V V%= 3.41%
A 0.85 35 A 10.00 2.82 V OK V%= 0.71%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO1-T1-2 : Final Point Voltage Drop (Less than 4%) 9.20 V V%= 2.3%
A 0.85 35 A 10.00 2.91 V OK V%= 0.73%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO1-T2-1 : Final Point Voltage Drop (Less than 4%) 9.29 V V%= 2.32%
A 0.85 35 A 10.00 3.47 V OK V%= 0.87%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO1-T2-2 : Final Point Voltage Drop (Less than 4%) 9.85 V V%= 2.46%
A 0.85 35 A 10.00 3.59 V OK V%= 0.9%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO1-T3 : Final Point Voltage Drop (Less than 4%) 9.97 V V%= 2.49%
A 0.85 35 A 10.00 3.59 V OK V%= 0.9%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO1-T4 : Final Point Voltage Drop (Less than 4%) 9.97 V V%= 2.49%
A 0.85 45 A 6.80 1.28 V OK V%= 0.32%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO1-C1 : Final Point Voltage Drop (Less than 4%) 7.66 V V%= 1.92%
A 0.85 35 A 10.00 0.45 V OK V%= 0.11%

Voltage Drop shall be less than 3%. - 40 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage
Factor Voltage Drop (v) Judge
Cap (A) Cap (A) Drop (%)
mV/A/m

A 0.85 20 A 18.00 0.82 V ###


Convert to 3Phase 1.42 V
P-O-1-01 : Final Point Voltage Drop (Less than 4%) 6.83 V V%= 1.71%

Voltage Drop shall be less than 3%. - 41 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage
Factor Voltage Drop (v) Judge
Cap (A) Cap (A) Drop (%)
mV/A/m

A 1.00 1,000 A 0.10 0.18 V OK V%= 0.05%


A 0.85 338 A 0.38 0.52 V OK V%= 0.13%
Total Voltage Drop 5.07 V
A 0.85 35 A 10.00 2.28 V OK V%= 0.57%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO2-T1-1 : Final Point Voltage Drop (Less than 4%) 8.77 V V%= 2.19%
A 0.85 35 A 10.00 2.78 V OK V%= 0.7%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO2-T1-2 : Final Point Voltage Drop (Less than 4%) 9.27 V V%= 2.32%
A 0.85 35 A 10.00 2.45 V OK V%= 0.61%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO2-T2 : Final Point Voltage Drop (Less than 4%) 8.94 V V%= 2.24%
A 0.85 35 A 10.00 2.98 V OK V%= 0.75%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO2-T15 : Final Point Voltage Drop (Less than 4%) 9.47 V V%= 2.37%
A 0.85 35 A 10.00 2.98 V OK V%= 0.75%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO2-T16 : Final Point Voltage Drop (Less than 4%) 9.47 V V%= 2.37%
A 0.85 35 A 10.00 3.07 V OK V%= 0.77%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO2-T3 : Final Point Voltage Drop (Less than 4%) 9.56 V V%= 2.39%
A 0.85 35 A 10.00 2.94 V OK V%= 0.74%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO2-T4 : Final Point Voltage Drop (Less than 4%) 9.43 V V%= 2.36%
A 0.85 35 A 10.00 3.01 V OK V%= 0.75%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO2-T5 : Final Point Voltage Drop (Less than 4%) 9.50 V V%= 2.38%

Voltage Drop shall be less than 3%. - 42 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage
Factor Voltage Drop (v) Judge
Cap (A) Cap (A) Drop (%)
mV/A/m

A 0.85 35 A 10.00 4.06 V OK V%= 1.02%


A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO2-T5-2 : Final Point Voltage Drop (Less than 4%) 10.55 V V%= 2.64%
A 0.85 35 A 10.00 3.59 V OK V%= 0.9%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO2-T6 : Final Point Voltage Drop (Less than 4%) 10.08 V V%= 2.52%

Voltage Drop shall be less than 3%. - 43 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage
Factor Voltage Drop (v) Judge
Cap (A) Cap (A) Drop (%)
mV/A/m

A 0.85 45 A 6.80 1.02 V OK V%= 0.26%


A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO2-C1 : Final Point Voltage Drop (Less than 4%) 7.51 V V%= 1.88%
A 0.85 35 A 10.00 0.45 V OK V%= 0.11%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
P-O-2-01 : Final Point Voltage Drop (Less than 4%) 6.94 V V%= 1.74%

A 1.00 1,000 A 0.10 0.12 V OK V%= 0.03%


A 0.85 338 A 0.38 0.52 V OK V%= 0.13%
Total Voltage Drop 5.19 V
A 0.85 35 A 10.00 2.28 V OK V%= 0.57%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO3-T1-1 : Final Point Voltage Drop (Less than 4%) 8.89 V V%= 2.22%
A 0.85 35 A 10.00 2.78 V OK V%= 0.7%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO3-T1-2 : Final Point Voltage Drop (Less than 4%) 9.39 V V%= 2.35%
A 0.85 35 A 10.00 2.45 V OK V%= 0.61%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO3-T2: Final Point Voltage Drop (Less than 4%) 9.06 V V%= 2.27%
A 0.85 35 A 10.00 2.98 V OK V%= 0.75%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO3-T15 : Final Point Voltage Drop (Less than 4%) 9.59 V V%= 2.4%
A 0.85 35 A 10.00 2.98 V OK V%= 0.75%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO3-T16 : Final Point Voltage Drop (Less than 4%) 9.59 V V%= 2.4%
A 0.85 35 A 10.00 3.07 V OK V%= 0.77%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V

Voltage Drop shall be less than 3%. - 44 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage
Factor Voltage Drop (v) Judge
Cap (A) Cap (A) Drop (%)
mV/A/m

LO3-T3 : Final Point Voltage Drop (Less than 4%) 9.68 V V%= 2.42%
A 0.85 35 A 10.00 2.94 V OK V%= 0.74%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO3-T4 : Final Point Voltage Drop (Less than 4%) 9.55 V V%= 2.39%
A 0.85 35 A 10.00 3.01 V OK V%= 0.75%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO3-T5-1 : Final Point Voltage Drop (Less than 4%) 9.62 V V%= 2.41%

Voltage Drop shall be less than 3%. - 45 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage
Factor Voltage Drop (v) Judge
Cap (A) Cap (A) Drop (%)
mV/A/m

A 0.85 35 A 10.00 4.06 V OK V%= 1.02%


A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO3-T5-2 : Final Point Voltage Drop (Less than 4%) 10.67 V V%= 2.67%
A 0.85 35 A 10.00 3.59 V OK V%= 0.9%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO3-T6 : Final Point Voltage Drop (Less than 4%) 10.20 V V%= 2.55%
A 0.85 45 A 6.80 1.02 V OK V%= 0.26%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO3-C1 : Final Point Voltage Drop (Less than 4%) 7.63 V V%= 1.91%
A 0.85 35 A 10.00 0.45 V OK V%= 0.11%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
P-O-3-01 : Final Point Voltage Drop (Less than 4%) 7.06 V V%= 1.77%

A 1.00 1,000 A 0.10 0.06 V OK V%= 0.02%


A 0.85 338 A 0.38 0.52 V OK V%= 0.13%
Total Voltage Drop 5.25 V
A 0.85 35 A 10.00 2.28 V OK V%= 0.57%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO4-T1-1 : Final Point Voltage Drop (Less than 4%) 8.95 V V%= 2.24%
A 0.85 35 A 10.00 2.78 V OK V%= 0.7%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO4-T1-2 : Final Point Voltage Drop (Less than 4%) 9.45 V V%= 2.36%
A 0.85 35 A 10.00 2.45 V OK V%= 0.61%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO4-T2 : Final Point Voltage Drop (Less than 4%) 9.12 V V%= 2.28%
A 0.85 35 A 10.00 2.98 V OK V%= 0.75%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V

Voltage Drop shall be less than 3%. - 46 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage
Factor Voltage Drop (v) Judge
Cap (A) Cap (A) Drop (%)
mV/A/m

LO4-T15 : Final Point Voltage Drop (Less than 4%) 9.65 V V%= 2.41%
A 0.85 35 A 10.00 2.98 V OK V%= 0.75%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO4-T16 : Final Point Voltage Drop (Less than 4%) 9.65 V V%= 2.41%
A 0.85 35 A 10.00 3.07 V OK V%= 0.77%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO4-T3 : Final Point Voltage Drop (Less than 4%) 9.74 V V%= 2.44%

Voltage Drop shall be less than 3%. - 47 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage
Factor Voltage Drop (v) Judge
Cap (A) Cap (A) Drop (%)
mV/A/m

A 0.85 35 A 10.00 2.94 V OK V%= 0.74%


A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO4-T4 : Final Point Voltage Drop (Less than 4%) 9.61 V V%= 2.4%
A 0.85 35 A 10.00 3.01 V OK V%= 0.75%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO4-T5-1 : Final Point Voltage Drop (Less than 4%) 9.68 V V%= 2.42%
A 0.85 35 A 10.00 4.06 V OK V%= 1.02%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO4-T5-2 : Final Point Voltage Drop (Less than 4%) 10.73 V V%= 2.68%
A 0.85 35 A 10.00 3.59 V OK V%= 0.9%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO4-T1-1 : Final Point Voltage Drop (Less than 4%) 10.26 V V%= 2.57%
A 0.85 45 A 6.80 1.02 V OK V%= 0.26%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO4-C1: Final Point Voltage Drop (Less than 4%) 7.69 V V%= 1.92%
A 0.85 35 A 10.00 0.45 V OK V%= 0.11%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
P-O-4-01 : Final Point Voltage Drop (Less than 4%) 7.12 V V%= 1.78%
0 0.00

Voltage Drop shall be less than 3%. - 48 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage
Factor Voltage Drop (v) Judge
Cap (A) Cap (A) Drop (%)
mV/A/m

A 1.00 1,000 A 0.10 2.90 V OK V%= 0.73%


A 0.85 338 A 0.38 0.52 V OK V%= 0.13%
Total Voltage Drop 6.15 V
A 0.85 35 A 10.00 2.28 V OK V%= 0.57%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO5-T1-1 : Final Point Voltage Drop (Less than 4%) 9.85 V V%= 2.46%
A 0.85 35 A 10.00 2.78 V OK V%= 0.7%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO5-T1-2 : Final Point Voltage Drop (Less than 4%) 10.35 V V%= 2.59%
A 0.85 35 A 10.00 2.45 V OK V%= 0.61%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO5-T2 : Final Point Voltage Drop (Less than 4%) 10.02 V V%= 2.51%
A 0.85 35 A 10.00 2.98 V OK V%= 0.75%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO5-T15 : Final Point Voltage Drop (Less than 4%) 10.55 V V%= 2.64%
A 0.85 35 A 10.00 2.98 V OK V%= 0.75%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO5-T16 : Final Point Voltage Drop (Less than 4%) 10.55 V V%= 2.64%
A 0.85 35 A 10.00 3.07 V OK V%= 0.77%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO5-T3 : Final Point Voltage Drop (Less than 4%) 10.64 V V%= 2.66%
A 0.85 35 A 10.00 2.94 V OK V%= 0.74%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO5-T4 : Final Point Voltage Drop (Less than 4%) 10.51 V V%= 2.63%
A 0.85 35 A 10.00 3.01 V OK V%= 0.75%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO5-T5-1 : Final Point Voltage Drop (Less than 4%) 10.58 V V%= 2.65%

Voltage Drop shall be less than 3%. - 49 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage
Factor Voltage Drop (v) Judge
Cap (A) Cap (A) Drop (%)
mV/A/m

A 0.85 35 A 10.00 4.06 V OK V%= 1.02%


A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO5-T5-2 : Final Point Voltage Drop (Less than 4%) 11.63 V V%= 2.91%
A 0.85 35 A 10.00 3.59 V OK V%= 0.9%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO5-T6 : Final Point Voltage Drop (Less than 4%) 11.16 V V%= 2.79%

Voltage Drop shall be less than 3%. - 50 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage
Factor Voltage Drop (v) Judge
Cap (A) Cap (A) Drop (%)
mV/A/m

A 0.85 45 A 6.80 1.02 V OK V%= 0.26%


A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO5-C1 : Final Point Voltage Drop (Less than 4%) 8.59 V V%= 2.15%
A 0.85 35 A 10.00 0.45 V OK V%= 0.11%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
P-O-5-01 : Final Point Voltage Drop (Less than 4%) 8.02 V V%= 2.01%

A 1.00 1,000 A 0.10 0.18 V OK V%= 0.05%


A 0.85 338 A 0.38 0.52 V OK V%= 0.13%
Total Voltage Drop 6.33 V
A 0.85 35 A 10.00 2.28 V OK V%= 0.57%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO6-T1-1 : Final Point Voltage Drop (Less than 4%) 10.03 V V%= 2.51%
A 0.85 35 A 10.00 2.78 V OK V%= 0.7%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO6-T1-2 : Final Point Voltage Drop (Less than 4%) 10.53 V V%= 2.63%
A 0.85 35 A 10.00 2.45 V OK V%= 0.61%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO6-T2 : Final Point Voltage Drop (Less than 4%) 10.20 V V%= 2.55%
A 0.85 35 A 10.00 2.98 V OK V%= 0.75%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO6-T15 : Final Point Voltage Drop (Less than 4%) 10.73 V V%= 2.68%
A 0.85 35 A 10.00 2.98 V OK V%= 0.75%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO6-T16 : Final Point Voltage Drop (Less than 4%) 10.73 V V%= 2.68%
A 0.85 35 A 10.00 3.07 V OK V%= 0.77%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V

Voltage Drop shall be less than 3%. - 51 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage
Factor Voltage Drop (v) Judge
Cap (A) Cap (A) Drop (%)
mV/A/m

LO6-T3 : Final Point Voltage Drop (Less than 4%) 10.82 V V%= 2.71%
A 0.85 35 A 10.00 2.94 V OK V%= 0.74%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO6-T4 : Final Point Voltage Drop (Less than 4%) 10.69 V V%= 2.67%
A 0.85 35 A 10.00 3.01 V OK V%= 0.75%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO6-T5-1 : Final Point Voltage Drop (Less than 4%) 10.76 V V%= 2.69%

Voltage Drop shall be less than 3%. - 52 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage
Factor Voltage Drop (v) Judge
Cap (A) Cap (A) Drop (%)
mV/A/m

A 0.85 35 A 10.00 4.06 V OK V%= 1.02%


A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO6-T5-2 : Final Point Voltage Drop (Less than 4%) 11.81 V V%= 2.95%
A 0.85 35 A 10.00 3.59 V OK V%= 0.9%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO6-T6 : Final Point Voltage Drop (Less than 4%) 11.34 V V%= 2.84%
A 0.85 45 A 6.80 1.02 V OK V%= 0.26%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO6-C1 : Final Point Voltage Drop (Less than 4%) 8.77 V V%= 2.19%
A 0.85 35 A 10.00 0.45 V OK V%= 0.11%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
P-O-6-01 : Final Point Voltage Drop (Less than 4%) 8.20 V V%= 2.05%

A 1.00 1,000 A 0.10 0.12 V OK V%= 0.03%


A 0.85 338 A 0.38 0.52 V OK V%= 0.13%
Total Voltage Drop 9.76 V
A 0.85 35 A 10.00 2.28 V OK V%= 0.57%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO7-T1-1 : Final Point Voltage Drop (Less than 4%) 13.46 V V%= 3.37%
A 0.85 35 A 10.00 2.78 V OK V%= 0.7%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO7-T1-2 : Final Point Voltage Drop (Less than 4%) 13.96 V V%= 3.49%
A 0.85 35 A 10.00 2.45 V OK V%= 0.61%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO7-T2 : Final Point Voltage Drop (Less than 4%) 13.63 V V%= 3.41%
A 0.85 35 A 10.00 2.98 V OK V%= 0.75%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V

Voltage Drop shall be less than 3%. - 53 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage
Factor Voltage Drop (v) Judge
Cap (A) Cap (A) Drop (%)
mV/A/m

LO7-T15 : Final Point Voltage Drop (Less than 4%) 14.16 V V%= 3.54%
A 0.85 35 A 10.00 2.98 V OK V%= 0.75%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO7-T16 : Final Point Voltage Drop (Less than 4%) 14.16 V V%= 3.54%
A 0.85 35 A 10.00 3.07 V OK V%= 0.77%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO7-T3 : Final Point Voltage Drop (Less than 4%) 14.25 V V%= 3.56%

Voltage Drop shall be less than 3%. - 54 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage
Factor Voltage Drop (v) Judge
Cap (A) Cap (A) Drop (%)
mV/A/m

A 0.85 35 A 10.00 2.94 V OK V%= 0.74%


A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO7-T4: Final Point Voltage Drop (Less than 4%) 14.12 V V%= 3.53%
A 0.85 35 A 10.00 3.01 V OK V%= 0.75%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO7-T5-1 : Final Point Voltage Drop (Less than 4%) 14.19 V V%= 3.55%
A 0.85 35 A 10.00 4.06 V OK V%= 1.02%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO7-T5-2 : Final Point Voltage Drop (Less than 4%) 15.24 V V%= 3.81%
A 0.85 35 A 10.00 3.59 V OK V%= 0.9%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO7-T6 : Final Point Voltage Drop (Less than 4%) 14.77 V V%= 3.69%
A 0.85 45 A 6.80 1.02 V OK V%= 0.26%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO7-C1 : Final Point Voltage Drop (Less than 4%) 12.20 V V%= 3.05%
A 0.85 35 A 10.00 0.45 V OK V%= 0.11%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
P-O-7-01 : Final Point Voltage Drop (Less than 4%) 11.63 V V%= 2.91%

A 1.00 1,000 A 0.10 0.06 V OK V%= 0.02%


A 0.85 338 A 0.38 0.52 V OK V%= 0.13%
Total Voltage Drop 6.51 V
A 0.85 35 A 10.00 2.28 V OK V%= 0.57%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO8-T1-1 : Final Point Voltage Drop (Less than 4%) 10.21 V V%= 2.55%
A 0.85 35 A 10.00 2.78 V OK V%= 0.7%
A 0.85 20 A 18.00 0.41 V ###
Convert to 3Phase 0.71 V

Voltage Drop shall be less than 3%. - 55 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage
Factor Voltage Drop (v) Judge
Cap (A) Cap (A) Drop (%)
mV/A/m

LO8-T1-2 : Final Point Voltage Drop (Less than 4%) 10.00 V V%= 2.5%
A 0.85 35 A 10.00 2.45 V OK V%= 0.61%
A 0.85 20 A 18.00 0.41 V ###
Convert to 3Phase 0.71 V
LO8-T2 : Final Point Voltage Drop (Less than 4%) 9.67 V V%= 2.42%
A 0.85 35 A 10.00 2.98 V OK V%= 0.75%
A 0.85 20 A 18.00 0.41 V ###
Convert to 3Phase 0.71 V
LO8-T15 : Final Point Voltage Drop (Less than 4%) 10.20 V V%= 2.55%

Voltage Drop shall be less than 3%. - 56 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage
Factor Voltage Drop (v) Judge
Cap (A) Cap (A) Drop (%)
mV/A/m

A 0.85 35 A 10.00 2.98 V OK V%= 0.75%


A 0.85 20 A 18.00 0.41 V ###
Convert to 3Phase 0.71 V
LO8-T16 : Final Point Voltage Drop (Less than 4%) 10.20 V V%= 2.55%
A 0.85 35 A 10.00 3.07 V OK V%= 0.77%
A 0.85 20 A 18.00 0.41 V ###
Convert to 3Phase 0.71 V
LO8-T3 : Final Point Voltage Drop (Less than 4%) 10.29 V V%= 2.57%
A 0.85 35 A 10.00 2.94 V OK V%= 0.74%
A 0.85 20 A 18.00 0.41 V ###
Convert to 3Phase 0.71 V
LO8-T4 : Final Point Voltage Drop (Less than 4%) 10.16 V V%= 2.54%
A 0.85 35 A 10.00 3.01 V OK V%= 0.75%
A 0.85 20 A 18.00 0.41 V ###
Convert to 3Phase 0.71 V
LO8-T5-1 : Final Point Voltage Drop (Less than 4%) 10.23 V V%= 2.56%
A 0.85 35 A 10.00 4.06 V OK V%= 1.02%
A 0.85 20 A 18.00 0.41 V ###
Convert to 3Phase 0.71 V
LO8-T5-2 : Final Point Voltage Drop (Less than 4%) 11.28 V V%= 2.82%
A 0.85 35 A 10.00 3.59 V OK V%= 0.9%
A 0.85 20 A 18.00 0.41 V ###
Convert to 3Phase 0.71 V
LO8-T6 : Final Point Voltage Drop (Less than 4%) 10.81 V V%= 2.7%
A 0.85 45 A 6.80 1.02 V OK V%= 0.26%
A 0.85 20 A 18.00 0.41 V ###
Convert to 3Phase 0.71 V
LO8-C1 : Final Point Voltage Drop (Less than 4%) 8.24 V V%= 2.06%
A 0.85 35 A 10.00 0.45 V OK V%= 0.11%
A 0.85 20 A 18.00 0.41 V ###
Convert to 3Phase 0.71 V
LO8-T1-1 : Final Point Voltage Drop (Less than 4%) 7.67 V V%= 1.92%
0 0.00

Voltage Drop shall be less than 3%. - 57 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage
Factor Voltage Drop (v) Judge
Cap (A) Cap (A) Drop (%)
mV/A/m

A 1.00 1,000 A 0.10 1.70 V OK V%= 0.43%


A 0.85 237 A 0.62 0.54 V OK V%= 0.14%
Total Voltage Drop 4.97 V
A 0.85 35 A 10.00 2.61 V OK V%= 0.65%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO1-T5 : Final Point Voltage Drop (Less than 4%) 9.00 V V%= 2.25%
A 0.85 35 A 10.00 3.07 V OK V%= 0.77%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO1-T6-2 : Final Point Voltage Drop (Less than 4%) 9.46 V V%= 2.37%
A 0.85 35 A 10.00 2.07 V OK V%= 0.52%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO1-T6-1 : Final Point Voltage Drop (Less than 4%) 8.46 V V%= 2.12%
A 0.85 35 A 10.00 1.92 V OK V%= 0.48%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO1-T7 : Final Point Voltage Drop (Less than 4%) 8.31 V V%= 2.08%
A 0.85 35 A 10.00 2.05 V OK V%= 0.51%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO1-T8 : Final Point Voltage Drop (Less than 4%) 8.44 V V%= 2.11%
A 0.85 35 A 10.00 2.73 V OK V%= 0.68%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO1-T9 : Final Point Voltage Drop (Less than 4%) 9.12 V V%= 2.28%
A 0.85 35 A 10.00 2.60 V OK V%= 0.65%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO1-T10-1 : Final Point Voltage Drop (Less than 4%) 8.99 V V%= 2.25%
A 0.85 35 A 10.00 3.30 V OK V%= 0.83%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO1-T10-2 : Final Point Voltage Drop (Less than 4%) 9.69 V V%= 2.42%

Voltage Drop shall be less than 3%. - 58 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage
Factor Voltage Drop (v) Judge
Cap (A) Cap (A) Drop (%)
mV/A/m

A 0.85 35 A 10.00 0.45 V OK V%= 0.11%


A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
P-O-1-06 : Final Point Voltage Drop (Less than 4%) 6.84 V V%= 1.71%

Voltage Drop shall be less than 3%. - 59 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage
Factor Voltage Drop (v) Judge
Cap (A) Cap (A) Drop (%)
mV/A/m

A 1.00 1,000 A 0.10 0.16 V OK V%= 0.04%


A 0.85 338 A 0.38 0.41 V OK V%= 0.1%
Total Voltage Drop 5.00 V
A 0.85 35 A 10.00 2.61 V OK V%= 0.65%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO2-T7 : Final Point Voltage Drop (Less than 4%) 9.03 V V%= 2.26%
A 0.85 35 A 10.00 2.61 V OK V%= 0.65%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO2-T8 : Final Point Voltage Drop (Less than 4%) 9.03 V V%= 2.26%
A 0.85 35 A 10.00 2.46 V OK V%= 0.62%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO2-T9-2 : Final Point Voltage Drop (Less than 4%) 8.88 V V%= 2.22%
A 0.85 35 A 10.00 1.94 V OK V%= 0.49%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO2-T9-1 : Final Point Voltage Drop (Less than 4%) 8.36 V V%= 2.09%
A 0.85 35 A 10.00 2.05 V OK V%= 0.51%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO2-T10 : Final Point Voltage Drop (Less than 4%) 8.47 V V%= 2.12%
A 0.85 35 A 10.00 2.73 V OK V%= 0.68%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO2-T11 : Final Point Voltage Drop (Less than 4%) 9.15 V V%= 2.29%
A 0.85 35 A 10.00 2.60 V OK V%= 0.65%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO2-T12 : Final Point Voltage Drop (Less than 4%) 9.02 V V%= 2.26%
A 0.85 35 A 10.00 2.75 V OK V%= 0.69%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO2-T13-1 : Final Point Voltage Drop (Less than 4%) 9.17 V V%= 2.29%

Voltage Drop shall be less than 3%. - 60 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage
Factor Voltage Drop (v) Judge
Cap (A) Cap (A) Drop (%)
mV/A/m

A 0.85 35 A 10.00 3.81 V OK V%= 0.95%


A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO2-T13-2 : Final Point Voltage Drop (Less than 4%) 10.23 V V%= 2.56%
A 0.85 35 A 10.00 3.24 V OK V%= 0.81%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO2-T14 : Final Point Voltage Drop (Less than 4%) 9.66 V V%= 2.42%

Voltage Drop shall be less than 3%. - 61 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage
Factor Voltage Drop (v) Judge
Cap (A) Cap (A) Drop (%)
mV/A/m

A 0.85 35 A 10.00 0.45 V OK V%= 0.11%


A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
P-O-2-02 : Final Point Voltage Drop (Less than 4%) 6.87 V V%= 1.72%

A 1.00 1,000 A 0.10 0.10 V OK V%= 0.03%


A 0.85 338 A 0.38 0.41 V OK V%= 0.1%
Total Voltage Drop 5.10 V
A 0.85 35 A 10.00 2.61 V OK V%= 0.65%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO3-T7 : Final Point Voltage Drop (Less than 4%) 9.13 V V%= 2.28%
A 0.85 35 A 10.00 2.61 V OK V%= 0.65%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO3-T8 : Final Point Voltage Drop (Less than 4%) 9.13 V V%= 2.28%
A 0.85 35 A 10.00 2.46 V OK V%= 0.62%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO3-T9-2 : Final Point Voltage Drop (Less than 4%) 8.98 V V%= 2.25%
A 0.85 35 A 10.00 1.94 V OK V%= 0.49%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO3-T9-1 : Final Point Voltage Drop (Less than 4%) 8.46 V V%= 2.12%
A 0.85 35 A 10.00 2.05 V OK V%= 0.51%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO3-T10 : Final Point Voltage Drop (Less than 4%) 8.57 V V%= 2.14%
A 0.85 35 A 10.00 2.73 V OK V%= 0.68%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO3-T11 : Final Point Voltage Drop (Less than 4%) 9.25 V V%= 2.31%
A 0.85 35 A 10.00 2.60 V OK V%= 0.65%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V

Voltage Drop shall be less than 3%. - 62 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage
Factor Voltage Drop (v) Judge
Cap (A) Cap (A) Drop (%)
mV/A/m

LO3-T12 : Final Point Voltage Drop (Less than 4%) 9.12 V V%= 2.28%
A 0.85 35 A 10.00 2.75 V OK V%= 0.69%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO3-T13-1 : Final Point Voltage Drop (Less than 4%) 9.27 V V%= 2.32%
A 0.85 35 A 10.00 3.81 V OK V%= 0.95%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO3-T13-2 : Final Point Voltage Drop (Less than 4%) 10.33 V V%= 2.58%

Voltage Drop shall be less than 3%. - 63 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage
Factor Voltage Drop (v) Judge
Cap (A) Cap (A) Drop (%)
mV/A/m

A 0.85 35 A 10.00 3.24 V OK V%= 0.81%


A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO3-T14 : Final Point Voltage Drop (Less than 4%) 9.76 V V%= 2.44%
A 0.85 35 A 10.00 0.45 V OK V%= 0.11%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
P-O-3-02 : Final Point Voltage Drop (Less than 4%) 6.97 V V%= 1.74%

A 1.00 1,000 A 0.10 0.05 V OK V%= 0.01%


A 0.85 338 A 0.38 0.41 V OK V%= 0.1%
Total Voltage Drop 5.15 V
A 0.85 35 A 10.00 2.61 V OK V%= 0.65%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO4-T7 : Final Point Voltage Drop (Less than 4%) 9.18 V V%= 2.3%
A 0.85 35 A 10.00 2.61 V OK V%= 0.65%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO4-T8 : Final Point Voltage Drop (Less than 4%) 9.18 V V%= 2.3%
A 0.85 35 A 10.00 2.46 V OK V%= 0.62%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO4-T9-2 : Final Point Voltage Drop (Less than 4%) 9.03 V V%= 2.26%
A 0.85 35 A 10.00 1.94 V OK V%= 0.49%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO4-T9-1 : Final Point Voltage Drop (Less than 4%) 8.51 V V%= 2.13%
A 0.85 35 A 10.00 2.05 V OK V%= 0.51%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO4-T10 : Final Point Voltage Drop (Less than 4%) 8.62 V V%= 2.16%
A 0.85 35 A 10.00 2.73 V OK V%= 0.68%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V

Voltage Drop shall be less than 3%. - 64 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage
Factor Voltage Drop (v) Judge
Cap (A) Cap (A) Drop (%)
mV/A/m

LO4-T11 : Final Point Voltage Drop (Less than 4%) 9.30 V V%= 2.33%
A 0.85 35 A 10.00 2.60 V OK V%= 0.65%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO4-T12 : Final Point Voltage Drop (Less than 4%) 9.17 V V%= 2.29%
A 0.85 35 A 10.00 2.75 V OK V%= 0.69%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO4-T13-1 : Final Point Voltage Drop (Less than 4%) 9.32 V V%= 2.33%

Voltage Drop shall be less than 3%. - 65 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage
Factor Voltage Drop (v) Judge
Cap (A) Cap (A) Drop (%)
mV/A/m

A 0.85 35 A 10.00 3.81 V OK V%= 0.95%


A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO4-T13-2 : Final Point Voltage Drop (Less than 4%) 10.38 V V%= 2.6%
A 0.85 35 A 10.00 3.24 V OK V%= 0.81%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO4-T14 : Final Point Voltage Drop (Less than 4%) 9.81 V V%= 2.45%
A 0.85 35 A 10.00 0.45 V OK V%= 0.11%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
P-O-4-02 : Final Point Voltage Drop (Less than 4%) 7.02 V V%= 1.76%
0 0.00

Voltage Drop shall be less than 3%. - 66 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage
Factor Voltage Drop (v) Judge
Cap (A) Cap (A) Drop (%)
mV/A/m

A 1.00 1,000 A 0.10 2.81 V OK V%= 0.7%


A 0.85 338 A 0.38 0.41 V OK V%= 0.1%
Total Voltage Drop 5.95 V
A 0.85 35 A 10.00 2.61 V OK V%= 0.65%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO5-T7 : Final Point Voltage Drop (Less than 4%) 9.98 V V%= 2.5%
A 0.85 35 A 10.00 2.61 V OK V%= 0.65%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO5-T8 : Final Point Voltage Drop (Less than 4%) 9.98 V V%= 2.5%
A 0.85 35 A 10.00 2.46 V OK V%= 0.62%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO5-T9-2 : Final Point Voltage Drop (Less than 4%) 9.83 V V%= 2.46%
A 0.85 35 A 10.00 1.94 V OK V%= 0.49%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO5-T9-1 : Final Point Voltage Drop (Less than 4%) 9.31 V V%= 2.33%
A 0.85 35 A 10.00 2.05 V OK V%= 0.51%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO5-T10 : Final Point Voltage Drop (Less than 4%) 9.42 V V%= 2.36%
A 0.85 35 A 10.00 2.73 V OK V%= 0.68%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO5-T11 : Final Point Voltage Drop (Less than 4%) 10.10 V V%= 2.53%
A 0.85 35 A 10.00 2.60 V OK V%= 0.65%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO5-T12 : Final Point Voltage Drop (Less than 4%) 9.97 V V%= 2.49%
A 0.85 35 A 10.00 2.75 V OK V%= 0.69%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO5-T13-1 : Final Point Voltage Drop (Less than 4%) 10.12 V V%= 2.53%

Voltage Drop shall be less than 3%. - 67 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage
Factor Voltage Drop (v) Judge
Cap (A) Cap (A) Drop (%)
mV/A/m

A 0.85 45 A 6.80 2.59 V OK V%= 0.65%


A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO5-T13-2 : Final Point Voltage Drop (Less than 4%) 9.96 V V%= 2.49%
A 0.85 35 A 10.00 3.24 V OK V%= 0.81%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO5-T14 : Final Point Voltage Drop (Less than 4%) 10.61 V V%= 2.65%

Voltage Drop shall be less than 3%. - 68 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage
Factor Voltage Drop (v) Judge
Cap (A) Cap (A) Drop (%)
mV/A/m

A 0.85 35 A 10.00 0.45 V OK V%= 0.11%


A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
P-O-5-02 : Final Point Voltage Drop (Less than 4%) 7.82 V V%= 1.96%

A 1.00 1,000 A 0.10 0.16 V OK V%= 0.04%


A 0.85 338 A 0.38 0.41 V OK V%= 0.1%
Total Voltage Drop 6.11 V
A 0.85 35 A 10.00 2.61 V OK V%= 0.65%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO6-T7 : Final Point Voltage Drop (Less than 4%) 10.14 V V%= 2.54%
A 0.85 35 A 10.00 2.61 V OK V%= 0.65%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO6-T8 : Final Point Voltage Drop (Less than 4%) 10.14 V V%= 2.54%
A 0.85 35 A 10.00 2.46 V OK V%= 0.62%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO6-T9-2 : Final Point Voltage Drop (Less than 4%) 9.99 V V%= 2.5%
A 0.85 35 A 10.00 1.94 V OK V%= 0.49%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO6-T9-1 : Final Point Voltage Drop (Less than 4%) 9.47 V V%= 2.37%
A 0.85 35 A 10.00 2.05 V OK V%= 0.51%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO6-T10 : Final Point Voltage Drop (Less than 4%) 9.58 V V%= 2.4%
A 0.85 35 A 10.00 2.73 V OK V%= 0.68%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO6-T11 : Final Point Voltage Drop (Less than 4%) 10.26 V V%= 2.57%
A 0.85 35 A 10.00 2.60 V OK V%= 0.65%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V

Voltage Drop shall be less than 3%. - 69 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage
Factor Voltage Drop (v) Judge
Cap (A) Cap (A) Drop (%)
mV/A/m

LO6-T12 : Final Point Voltage Drop (Less than 4%) 10.13 V V%= 2.53%
A 0.85 35 A 10.00 2.75 V OK V%= 0.69%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO6-T13-1 : Final Point Voltage Drop (Less than 4%) 10.28 V V%= 2.57%
A 0.85 35 A 10.00 3.81 V OK V%= 0.95%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO6-T13-2 : Final Point Voltage Drop (Less than 4%) 11.34 V V%= 2.84%

Voltage Drop shall be less than 3%. - 70 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage
Factor Voltage Drop (v) Judge
Cap (A) Cap (A) Drop (%)
mV/A/m

A 0.85 35 A 10.00 3.24 V OK V%= 0.81%


A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO6-T14 : Final Point Voltage Drop (Less than 4%) 10.77 V V%= 2.69%
A 0.85 35 A 10.00 1.02 V OK V%= 0.26%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
P-O-6-02 : Final Point Voltage Drop (Less than 4%) 8.55 V V%= 2.14%

A 1.00 1,000 A 0.10 0.11 V OK V%= 0.03%


A 0.85 338 A 0.38 0.41 V OK V%= 0.1%
Total Voltage Drop 6.22 V
A 0.85 35 A 10.00 2.61 V OK V%= 0.65%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO7-T7 : Final Point Voltage Drop (Less than 4%) 10.25 V V%= 2.56%
A 0.85 35 A 10.00 2.61 V OK V%= 0.65%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO7-T8 : Final Point Voltage Drop (Less than 4%) 10.25 V V%= 2.56%
A 0.85 35 A 10.00 2.46 V OK V%= 0.62%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO7-T9-2 : Final Point Voltage Drop (Less than 4%) 10.10 V V%= 2.53%
A 0.85 35 A 10.00 1.94 V OK V%= 0.49%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO7-T9-1 : Final Point Voltage Drop (Less than 4%) 9.58 V V%= 2.4%
A 0.85 35 A 10.00 2.05 V OK V%= 0.51%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO7-T10 : Final Point Voltage Drop (Less than 4%) 9.69 V V%= 2.42%
A 0.85 35 A 10.00 2.73 V OK V%= 0.68%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V

Voltage Drop shall be less than 3%. - 71 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage
Factor Voltage Drop (v) Judge
Cap (A) Cap (A) Drop (%)
mV/A/m

LO7-T11 : Final Point Voltage Drop (Less than 4%) 10.37 V V%= 2.59%
A 0.85 35 A 10.00 2.60 V OK V%= 0.65%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO7-T12 : Final Point Voltage Drop (Less than 4%) 10.24 V V%= 2.56%
A 0.85 35 A 10.00 2.75 V OK V%= 0.69%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO7-T13-1 : Final Point Voltage Drop (Less than 4%) 10.39 V V%= 2.6%

Voltage Drop shall be less than 3%. - 72 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage
Factor Voltage Drop (v) Judge
Cap (A) Cap (A) Drop (%)
mV/A/m

A 0.85 35 A 10.00 3.81 V OK V%= 0.95%


A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO7-T13-2 : Final Point Voltage Drop (Less than 4%) 11.45 V V%= 2.86%
A 0.85 35 A 10.00 3.24 V OK V%= 0.81%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO7-T14 : Final Point Voltage Drop (Less than 4%) 10.88 V V%= 2.72%
A 0.85 35 A 10.00 0.45 V OK V%= 0.11%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
P-O-7-02 : Final Point Voltage Drop (Less than 4%) 8.09 V V%= 2.02%

A 1.00 1,000 A 0.10 0.05 V OK V%= 0.01%


A 0.85 338 A 0.38 0.42 V OK V%= 0.11%
Total Voltage Drop 6.28 V
A 0.85 35 A 10.00 2.61 V OK V%= 0.65%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO8-T7 : Final Point Voltage Drop (Less than 4%) 10.31 V V%= 2.58%
A 0.85 35 A 10.00 2.61 V OK V%= 0.65%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO8-T8 : Final Point Voltage Drop (Less than 4%) 10.31 V V%= 2.58%
A 0.85 35 A 10.00 2.46 V OK V%= 0.62%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO8-T9-2 : Final Point Voltage Drop (Less than 4%) 10.16 V V%= 2.54%
A 0.85 35 A 10.00 1.94 V OK V%= 0.49%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO8-T9-1 : Final Point Voltage Drop (Less than 4%) 9.64 V V%= 2.41%
A 0.85 35 A 10.00 2.05 V OK V%= 0.51%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V

Voltage Drop shall be less than 3%. - 73 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage
Factor Voltage Drop (v) Judge
Cap (A) Cap (A) Drop (%)
mV/A/m

LO8-T10 : Final Point Voltage Drop (Less than 4%) 9.75 V V%= 2.44%
A 0.85 35 A 10.00 2.73 V OK V%= 0.68%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO8-T11 : Final Point Voltage Drop (Less than 4%) 10.43 V V%= 2.61%
A 0.85 35 A 10.00 2.60 V OK V%= 0.65%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO8-T12 : Final Point Voltage Drop (Less than 4%) 10.30 V V%= 2.58%

Voltage Drop shall be less than 3%. - 74 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage
Factor Voltage Drop (v) Judge
Cap (A) Cap (A) Drop (%)
mV/A/m

A 0.85 35 A 10.00 2.75 V OK V%= 0.69%


A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO8-T13-1 : Final Point Voltage Drop (Less than 4%) 10.45 V V%= 2.61%
A 0.85 35 A 10.00 3.81 V OK V%= 0.95%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO8-T13-2 : Final Point Voltage Drop (Less than 4%) 11.51 V V%= 2.88%
A 0.85 35 A 10.00 3.24 V OK V%= 0.81%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO8-T14 : Final Point Voltage Drop (Less than 4%) 10.94 V V%= 2.74%
A 0.85 35 A 10.00 0.45 V OK V%= 0.11%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
P-O-8-02 : Final Point Voltage Drop (Less than 4%) 8.15 V V%= 2.04%
A 0.85 35 A 10.00 0.53 V OK V%= 0.13%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LO8-T7 : Final Point Voltage Drop (Less than 4%) 8.23 V V%= 2.06%

Voltage Drop shall be less than 3%. - 75 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage
Factor Voltage Drop (v) Judge
Cap (A) Cap (A) Drop (%)
mV/A/m

0 0.00
A 0.85 62 A 4.00 2.51 V OK V%= 0.63%
A 0.85 45 A 6.80 0.31 V OK V%= 0.08%
A 0.85 26 A 16.00 3.44 V OK V%= 0.86%
P-O-B1-01 : Final Point Voltage Drop (Less than 4%) 8.99 V V%= 2.25%
A 0.85 290 A 0.46 6.01 V OK V%= 1.5%
A 0.85 72 A 2.50 6.75 V OK V%= 1.69%
P-O-B1-03 : Final Point Voltage Drop (Less than 4%) 15.49 V V%= 3.87%
A 0.85 35 A 10.00 2.19 V OK V%= 0.55%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LOG-B1 : Final Point Voltage Drop (Less than 4%) 6.34 V V%= 1.59%
0 0.00
A 0.85 150 A 1.15 2.81 V OK V%= 0.7%
Total Voltage Drop 5.54 V
A 0.85 119 A 1.60 0.21 V OK V%= 0.05%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LOG-C1 : Final Point Voltage Drop (Less than 4%) 7.17 V V%= 1.79%
A 0.85 45 A 6.80 2.17 V OK V%= 0.54%
A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LOG-T1 : Final Point Voltage Drop (Less than 4%) 9.13 V V%= 2.28%
A 0.85 119 A 1.60 0.97 V OK V%= 0.24%
Well Pump1 : Final Point Voltage Drop (Less than 4%) 6.51 V V%= 1.63%
0 0.00
A 0.85 119 A 1.60 3.62 V OK V%= 0.91%
Total Voltage Drop 6.35 V
A 0.85 62 A 4.00 2.73 V OK V%= 0.68%
A 0.85 32 A 7.30 1.87 V OK V%= 0.81%
Convert to 3Phase 3.24 V
P-O-GF-01 : Final Point Voltage Drop (Less than 4%) 12.32 V V%= 3.08%
A 0.85 35 A 10.00 0.69 V OK V%= 0.17%
A 0.85 35 A 10.00 1.79 V OK V%= 0.45%
P-O-GF-02 : Final Point Voltage Drop (Less than 4%) 8.83 V V%= 2.21%

Voltage Drop shall be less than 3%. - 76 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage
Factor Voltage Drop (v) Judge
Cap (A) Cap (A) Drop (%)
mV/A/m

A 0.85 62 A 4.00 0.40 V OK V%= 0.1%


A 0.85 20 A 18.00 0.82 V ###
Convert to 3Phase 1.42 V
LOG-C2 : Final Point Voltage Drop (Less than 4%) 8.17 V V%= 2.04%
0 0.00
A 0.85 150 A 1.15 3.31 V OK V%= 0.83%
Total Voltage Drop 6.04 V
A 0.85 72 A 2.50 1.80 V OK V%= 0.45%
P-O-GF-09 : Final Point Voltage Drop (Less than 4%) 7.84 V V%= 1.96%
A 0.85 35 A 10.00 0.69 V OK V%= 0.17%
A 0.85 26 A 16.00 1.34 V OK V%= 0.34%
P-O-1-06 : Final Point Voltage Drop (Less than 4%) 8.07 V V%= 2.02%
A 0.85 72 A 2.50 0.72 V OK V%= 0.18%
A 0.85 62 A 4.00 1.44 V OK V%= 0.36%
P-O-1-07 : Final Point Voltage Drop (Less than 4%) 8.20 V V%= 2.05%
A 0.85 72 A 2.50 0.72 V OK V%= 0.18%
A 0.85 62 A 4.00 1.44 V OK V%= 0.36%
P-O-1-08 : Final Point Voltage Drop (Less than 4%) 8.20 V V%= 2.05%

A 0.85 451 A 0.28 0.00 OK V%= 0%


A 0.85 237 A 0.62 1.38 V OK V%= 0.35%
P-O-1-03 : Final Point Voltage Drop (Less than 4%) 7.73 V V%= 1.93%
A 0.85 183 A 0.87 1.82 V OK V%= 0.46%
A 0.85 35 A 10.00 2.07 V OK V%= 0.52%
P-O-1-03 : Final Point Voltage Drop (Less than 4%) 10.24 V V%= 2.56%
A 0.85 237 A 0.62 3.56 V OK V%= 0.89%
A 0.85 72 A 2.50 3.38 V OK V%= 0.85%
P-O-RF-01 : Final Point Voltage Drop (Less than 4%) 13.29 V V%= 3.32%
A 0.85 621 A 0.21 6.34 V OK V%= 1.59%
A 0.85 340 A 0.24 0.96 V OK V%= 0.24%
P-O-RF-02 : Final Point Voltage Drop (Less than 4%) 13.65 V V%= 3.41%
A 0.85 237 A 0.62 3.23 V OK V%= 0.81%
A 0.85 72 A 2.50 3.38 V OK V%= 0.85%
P-O-RF-03 : Final Point Voltage Drop (Less than 4%) 12.96 V V%= 3.24%
A 0.85 451 A 0.28 5.12 V OK V%= 1.28%

Voltage Drop shall be less than 3%. - 77 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage
Factor Voltage Drop (v) Judge
Cap (A) Cap (A) Drop (%)
mV/A/m

A 0.85 119 A 1.60 1.66 V OK V%= 0.42%


P-O-RF-04 : Final Point Voltage Drop (Less than 4%) 13.13 V V%= 3.28%
A 0.85 901 A 0.14 4.85 V OK V%= 1.21%
A 0.85 340 A 0.24 0.96 V OK V%= 0.24%
P-O-RF-02 : Final Point Voltage Drop (Less than 4%) 12.16 V V%= 3.04%

A 0.85 119 A 1.60 4.07 V OK V%= 1.02%


ELV-1 : Final Point Voltage Drop (Less than 4%) 6.80 V V%= 1.7%
A 0.85 119 A 1.60 4.07 V OK V%= 1.02%
ELV-2 : Final Point Voltage Drop (Less than 4%) 6.80 V V%= 1.7%
A 0.85 119 A 1.60 4.07 V OK V%= 1.02%
ELV-3 : Final Point Voltage Drop (Less than 4%) 6.80 V V%= 1.7%
A 0.85 119 A 1.60 3.41 V OK V%= 0.85%
ELV-4 : Final Point Voltage Drop (Less than 4%) 6.14 V V%= 1.54%
A 0.85 119 A 1.60 3.41 V OK V%= 0.85%
ELV-5 : Final Point Voltage Drop (Less than 4%) 6.14 V V%= 1.54%
A 0.85 119 A 1.60 3.41 V OK V%= 0.85%
ELV-6 : Final Point Voltage Drop (Less than 4%) 6.14 V V%= 1.54%
A 0.85 119 A 1.60 0.00 OK V%= 0%
ELV-7 : Final Point Voltage Drop (Less than 4%) 2.73 V V%= 0.68%
A 0.85 62 A 4.00 3.61 V OK V%= 0.9%
ELV-9 : Final Point Voltage Drop (Less than 4%) 6.34 V V%= 1.59%
0 0.00

Voltage Drop shall be less than 3%. - 78 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (COPPER CABLE)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

0.00 0.00 0

TR2 (2.500KVA) ST-2 BD 4000 4W Cu-Fe 40 m 400 V ACB TPN 4,000 A 4,919.58 kVA 0.49 2,400.00 kVA 3,464.20 A 4000
0.00 0.00 0
F1 ST-2 PF-O-B1-02 (Emergency) 4C-240sqmm FR Cable 110 m 400 V MCCB TPN 500 A 144.11 kVA 1.00 144.11 kVA 208.01 A 607
To Final Point (M-Scope) 3C-185sqmm FR Cable 20 m 400 V MCCB 3P 450 A 144.11 kVA 1.00 144.11 kVA 208.01 A 510
(FR-1 Standby) 400 V

F2 ST-2 PF-O-B1-04 (Emergency) 4C-10sqmm FR Cable 110 m 400 V MCCB TPN 30 A 10.69 kVA 1.00 10.69 kVA 15.43 A 74
To Final Point (M-Scope) 3C-2.5sqmm FR Cable 20 m 400 V MCCB 3P 15 A 4.66 kVA 1.00 4.66 kVA 6.73 A 31
(FR-1 Duty) 400 V

F3 ST-2 P-O-RF-01 (Emergency) 4C-10sqmm FR Cable 78 m 400 V MCCB TPN 40 A 12.47 kVA 1.00 12.47 kVA 18.00 A 74
To Final Point M-Scope) 3C-10sqmm FR Cable 20 m 400 V MCCB TPN 40 A 12.47 kVA 1.00 12.47 kVA 18.00 A 74
400 V

F4 ST-2 P-O-RF-03 (Emergency) 4C-10sqmm FR Cable 72 m 400 V MCCB TPN 50 A 11.71 kVA 1.00 11.71 kVA 16.90 A 74
To Final Point M-Scope) 3C-6.0sqmm FR Cable 20 m 400 V MCCB TPN 30 A 9.70 kVA 1.00 9.70 kVA 14.00 A 54
400 V

F5 ST-2 ELV-8 4C-25sqmm FR Cable 86 m 400 V MCCB TPN 100 A 20.50 kVA 1.00 20.50 kVA 29.59 A 135
400 V
F6 ST-2 ELV-15 4C-25sqmm FR Cable 191 m 400 V MCCB TPN 75 A 15.50 kVA 1.00 15.50 kVA 22.37 A 135
400 V
F7 ST-2 ELV-18 4C-25sqmm FR Cable 95 m 400 V MCCB TPN 75 A 15.50 kVA 1.00 15.50 kVA 22.37 A 135
400 V

F8 ST-2 P-H-B2-14 (Emergency) 4C-95sqmm FR Cable 170 m 400 V MCCB TPN 225 A 90.69 kVA 1.00 90.69 kVA 130.90 A 328
To Final Point M-Scope) 2sets -3C 25sqmm FR Cable 20 m 400 V MCCB 3P 125 A 35.33 kVA 1.00 35.33 kVA 51.00 A 414
400 V

F9 ST-2 P-H-B1-01 4C-120sqmm FR Cable 200 m 400 V MCCB TPN 250 A 117.16 kVA 0.70 82.01 kVA 118.37 A 383
To Final Point M-Scope) 3C-50sqmm FR Cable 20 m 400 V MCCB 3P 125 A 35.33 kVA 1.00 35.33 kVA 51.00 A 207
400 V

F10 ST-2 P-H-B1-02 (Emergency) 4C-70sqmm FR Cable 164 m 400 V MCCB TPN 175 A 61.04 kVA 0.70 42.73 kVA 61.68 A 268

Voltage Drop shall be less than 3%. - 79 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (COPPER CABLE)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

To Final Point (M-Scope) 3C-50sqmm FR Cable 20 m 400 V MCCB 3P 125 A 35.33 kVA 1.00 35.33 kVA 51.00 A 207
400 V

Voltage Drop shall be less than 3%. - 80 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (COPPER CABLE)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor
Tap Off Unit
F11 ST-2
(To P-H-GF-01)
4C-6.0sqmm FR Cable 55 m 400 V MCCB TPN 20 A 1.80 kVA 0.70 1.26 kVA 1.82 A 54

From Transformer to Tap Off Unit (To P-H-GF-01)


P-H-GF-01 (Tap off) P-H-GF-01(Emergency) 2C-2.5sqmm FR Cable 10 m 230 V MCB 2P 15 A 1.13 kVA 0.70 0.79 kVA 1.98 A 34
To Final Point (M-Scope) 2C-2.5sqmm FR Cable 20 m 230 V MCB 2P 15 A 1.13 kVA 1.00 1.13 kVA 4.91 A 34
400 V
400 V PF-O
Tap Off Unit
F11 Tap Off Unit
(KDP-H-GF-1)
4C-4.0sqmm FR Cable 38 m 400 V MCCB TPN 15 A 0.67 kVA 0.70 0.47 kVA 0.68 A 41

P-H-GF-01 (Tap off) KDP-H-GF-1 (Emergency) 2C-2.5sqmm FR Cable 10 m 230 V MCB 2P 15 A 0.34 kVA 0.70 0.24 kVA 0.60 A 34
To Final Point (M-Scope) 2C-2.5sqmm FR Cable 20 m 230 V MCB 2P 15 A 0.34 kVA 1.00 0.34 kVA 1.48 A 34
400 V
400 V PF-O
Tap Off Unit
F11 Tap Off Unit
(KDP-H-M1-1)
4C-4.0sqmm FR Cable 20 m 400 V MCCB TPN 20 A 0.33 kVA 0.70 0.23 kVA 0.33 A 41

P-H-GF-01 (Tap off) KDP-H-M1-1 (Emergency) 2C-2.5sqmm FR Cable 10 m 230 V MCB 2P 15 A 0.11 kVA 1.00 0.11 kVA 0.28 A 34
To Final Point (M-Scope) 2C-2.5sqmm FR Cable 20 m 230 V MCB 2P 15 A 0.11 kVA 1.00 0.11 kVA 0.48 A 34
400 V
400 V PF-O
Tap Off Unit
F11 Tap Off Unit
(P-H-GF-03)
4C-4.0sqmm FR Cable 26 m 400 V MCCB TPN 20 A 0.22 kVA 0.70 0.15 kVA 0.22 A 41

P-H-GF-01 (Tap off) P-H-GF-03 (Emergency) 2C-2.5sqmm FR Cable 10 m 230 V MCB 2P 15 A 0.16 kVA 1.00 0.16 kVA 0.40 A 34
To Final Point (M-Scope) 2C-2.5sqmm FR Cable 20 m 230 V MCB 2P 15 A 0.16 kVA 1.00 0.16 kVA 0.70 A 34
400 V
400 V PF-O

F11 Tap Off Unit P-H-GF-05 (Emergency) 2C-2.5sqmm FR Cable 68 m 230 V MCB 2P 20 A 0.06 kVA 1.00 0.06 kVA 0.15 A 34

To Final Point (M-Scope) 2C-2.5sqmm FR Cable 20 m 230 V MCB 2P 15 A 0.06 kVA 1.00 0.06 kVA 0.26 A 34
400 V
400 V PF-O

F12 ST-2 P-H-1-01 (Emergency) 4C-10sqmm FR Cable 83 m 400 V MCCB TPN 40 A 12.47 kVA 1.00 12.47 kVA 18.00 A 74
To Final Point (M-Scope) 3C-10sqmm FR Cable 20 m 400 V MCCB 3P 40 A 12.47 kVA 1.00 12.47 kVA 18.00 A 74
400 V

F13 ST-2 P-H-3-01 4C-10sqmm FR Cable 83 m 400 V MCCB TPN 50 A 13.60 kVA 1.00 13.60 kVA 19.63 A 74
To Final Point (M-Scope) 3C-6.0sqmm FR Cable 20 m 400 V MCCB 3P 30 A 9.70 kVA 1.00 9.70 kVA 14.00 A 54
400 V

Voltage Drop shall be less than 3%. - 81 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (COPPER CABLE)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

F14 ST-2 P-H-RF-01 (Emergency) 4C-50sqmm FR Cable 197 m 400 V MCCB TPN 100 A 38.26 kVA 1.00 38.26 kVA 55.23 A 207
To Final Point (M-Scope) 3C-10sqmm FR Cable 20 m 400 V MCCB 3P 40 A 12.48 kVA 1.00 12.48 kVA 18.01 A 74
400 V

F15 ST-2 P-H-RF-02 (Emergency) 3C 70sqmm XLPE/PVC 192 m 400 V MCCB TPN 60 A 21.99 kVA 1.00 21.99 kVA 31.74 A 279
To Final Point (M-Scope) 3C-10sqmm FR Cable 20 m 400 V MCCB 3P 40 A 12.48 kVA 1.00 12.48 kVA 18.01 A 74
400 V

F16 ST-2 P-H-RF-04 4C-16sqmm FR Cable 85 m 400 V MCCB TPN 60 A 24.62 kVA 0.70 17.23 kVA 24.87 A 99
To Final Point (M-Scope) 3C-10sqmm FR Cable 20 m 400 V MCCB 3P 40 A 12.48 kVA 1.00 12.48 kVA 18.01 A 74
400 V

F17 ST-2 P-O-GF-03 4C-6.0sqmm FR Cable 56 m 400 V MCCB TPN 30 A 6.37 kVA 0.70 4.46 kVA 6.44 A 54
To Final Point M-Scope) 3C-2.5sqmm FR Cable 20 m 400 V MCCB 3P 15 A 1.59 kVA 1.00 1.59 kVA 2.30 A 31
400 V

F18 ST-2 P-O-GF-04 4C-50sqmm FR Cable 55 m 400 V MCCB TPN 150 A 82.33 kVA 0.70 57.63 kVA 83.18 A 207
To Final Point M-Scope) 3C-50sqmm FR Cable 20 m 400 V MCCB 3P 125 A 74.82 kVA 1.00 74.82 kVA 108.00 A 207
400 V
P-O-GF-04 P-O-GF-05 3C-50sqmm FR Cable 10 m 400 V MCCB 3P 125 A 74.82 kVA 0.70 52.37 kVA 75.59 A 207
To Final Point M-Scope) 3C-4.0sqmm FR Cable 20 m 400 V MCCB 3P 20 A 6.72 kVA 1.00 6.72 kVA 9.70 A 41
400 V

P-O-GF-06 OMIT

F19 ST-2 P-O-1-02 4C-4.0sqmm FR Cable 23 m 400 V MCCB TPN 30 A 7.58 kVA 1.00 7.58 kVA 10.94 A 41
To Final Point M-Scope) 3C-2.5sqmm FR Cable 20 m 400 V MCCB TPN 15 A 2.50 kVA 1.00 2.50 kVA 3.61 A 31
400 V

F20 ST-2 LOG-C3 4C-10sqmm FR Cable 73 m 400 V MCCB TPN 40 A 18.21 kVA 1.00 18.21 kVA 26.28 A 74
LOG-C3 to Final Point 2X1C 2.5sqmm PVC 12 m 230 V MCB SP 20 A 1.00 kVA 1.00 1.00 kVA 4.35 A 24
400 V
400 V

Voltage Drop shall be less than 3%. - 82 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (COPPER CABLE)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

F21 ST-2 LHG-C3 4C-16sqmm FR Cable 100 m 400 V MCCB TPN 40 A 15.52 kVA 1.00 15.52 kVA 22.40 A 99
LHG-C3 to Final Point 2X1C 2.5sqmm PVC 20 m 230 V MCB SP 20 A 1.00 kVA 1.00 1.00 kVA 4.35 A 24
400 V
400 V
0.00 0.00 0
F22 ST-2 P-H-1-02 4C-4.0sqmm FR Cable 106 m 400 V MCCB TPN 15 A 0.64 kVA 1.00 0.64 kVA 0.92 A 41
To Final Point M-Scope) 4C-2.5sqmm FR Cable 20 m 400 V MCCB TPN 15 A 0.35 kVA 1.00 0.35 kVA 0.51 A 31
400 V

F23 ST-2 P-H-2-01 4C-400sqmm FR Cable 70 m 400 V MCCB TPN 600 A 266.04 kVA 1.00 266.04 kVA 384.01 A 823
To Final Point M-Scope) 2x3C-70sqmm FR Cable 20 m 400 V MCCB 3P 300 A 88.68 kVA 1.00 88.68 kVA 128.00 A 536
400 V

F24 ST-2 P-H-B2-28 4C-150sqmm FR Cable 116 m 400 V MCCB TPN 300 A 141.34 kVA 1.00 141.34 kVA 204.01 A 444
To Final Point M-Scope) 2x3C-50sqmm FR Cable 20 m 400 V MCCB 3P 125 A 35.33 kVA 1.00 35.33 kVA 51.00 A 414
400 V

1 ST-2 P-WT-B1-01 4C 70sqmm XLPE/PVC 65 m 400 V MCCB TPN 100 A 40.38 kVA 1.00 40.38 kVA 58.29 A 279
400 V P-WT
2 ST-2 P-WT-B1-02 4C 95sqmm XLPE/PVC 65 m 400 V MCCB TPN 250 A 121.75 kVA 1.00 121.75 kVA 175.74 A 341
400 V P-WT
0.00 0.00 0
3 ST-2 P-H-B1-02 12x1C 240sqmm XLPE/PVC 164 m 400 V ACB TPN 1,200 A 636.72 kVA 0.70 445.70 kVA 643.33 A 1890
To Final Point M-Scope) 3C 150sqmm XLPE/PVC 20 m 400 V MCCB 3P 250 A 71.36 kVA 1.00 71.36 kVA 103.00 A 461
400 V
4 ST-2 P-H-B2-14 24x1C 300sqmm XLPE/PVC 170 m 400 V ACB TPN 3,000 A 1,305.56 kVA 0.70 913.89 kVA 1,319.13 A 4380
To Final Point M-Scope) 4 x (4x1C 185sqmm XLPE/PVC) 20 m 400 V MCCB 3P 1,000 A 318.89 kVA 1.00 318.89 kVA 460.29 A 1260
400 V
5 ST-2 P-H-2-04 4C 35sqmm XLPE/PVC 83 m 400 V MCCB TPN 100 A 52.80 kVA 0.70 36.96 kVA 53.35 A 176
To Final Point M-Scope) 3C 2.5sqmm XLPE/PVC 20 m 400 V MCCB 3P 15 A 5.56 kVA 1.00 5.56 kVA 8.03 A 31
400 V
6 ST-2 P-H-RF-01 4x1C 120sqmm XLPE/PVC 197 m 400 V MCCB TPN 250 A 131.91 kVA 0.70 92.34 kVA 133.29 A 398
To Final Point M-Scope) 3C 25sqmm XLPE/PVC 20 m 400 V MCCB 3P 75 A 23.56 kVA 1.00 23.56 kVA 34.01 A 280
400 V
7 ST-2 P-H-RF-03 4x1C 120sqmm XLPE/PVC 85 m 400 V MCCB TPN 250 A 137.31 kVA 0.70 96.12 kVA 138.74 A 398

Voltage Drop shall be less than 3%. - 83 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (COPPER CABLE)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

To Final Point M-Scope) 3C 2.5sqmm XLPE/PVC 20 m 400 V MCCB 3P 15 A 7.19 kVA 1.00 7.19 kVA 10.38 A 31
400 V
8 ST-2 P-H-RF-04 4C 95sqmm XLPE/PVC 85 m 400 V MCCB TPN 175 A 112.00 kVA 0.70 78.40 kVA 113.16 A 341
To Final Point M-Scope) 4C 4sqmm XLPE/PVC 20 m 400 V MCCB TPN 20 A 7.19 kVA 1.00 7.19 kVA 10.38 A 41
400 V

9 ST-2 ELV-10 4C 25sqmm XLPE/PVC 90 m 400 V MCCB TPN 75 A 15.50 kVA 1.00 15.50 kVA 22.37 A 140
400 V
10 ST-2 ELV-11 4C 25sqmm XLPE/PVC 90 m 400 V MCCB TPN 75 A 15.50 kVA 1.00 15.50 kVA 22.37 A 140
400 V
11 ST-2 ELV-12 4C 25sqmm XLPE/PVC 170 m 400 V MCCB TPN 75 A 15.50 kVA 1.00 15.50 kVA 22.37 A 140
400 V
12 ST-2 ELV-13 4C 25sqmm XLPE/PVC 170 m 400 V MCCB TPN 75 A 15.50 kVA 1.00 15.50 kVA 22.37 A 140
400 V
13 ST-2 ELV-14 4C 25sqmm XLPE/PVC 170 m 400 V MCCB TPN 75 A 15.50 kVA 1.00 15.50 kVA 22.37 A 140
400 V
14 ST-2 ELV-16 4C 25sqmm XLPE/PVC 191 m 400 V MCCB TPN 75 A 15.50 kVA 1.00 15.50 kVA 22.37 A 140
400 V
15 ST-2 ELV-17 4C 25sqmm XLPE/PVC 191 m 400 V MCCB TPN 75 A 15.50 kVA 1.00 15.50 kVA 22.37 A 140
400 V
16 ST-2 ELV-19 4C 25sqmm XLPE/PVC 95 m 400 V MCCB TPN 75 A 15.50 kVA 1.00 15.50 kVA 22.37 A 140
400 V
17 ST-2 ELV-20 4C 10sqmm XLPE/PVC 67 m 400 V MCCB TPN 50 A 12.50 kVA 1.00 12.50 kVA 18.04 A 73
400 V
18 ST-2 ELV-22 4C 10sqmm XLPE/PVC 149 m 400 V MCCB TPN 50 A 10.60 kVA 1.00 10.60 kVA 15.30 A 73
400 V
19 ST-2 ES-1 4C 10sqmm XLPE/PVC 70 m 400 V MCCB TPN 50 A 11.00 kVA 0.70 7.70 kVA 11.11 A 73
400 V
20 ST-2 ES-2 4C 10sqmm XLPE/PVC 70 m 400 V MCCB TPN 50 A 11.00 kVA 0.70 7.70 kVA 11.11 A 73
400 V
0.00 0.00 0
0.00 0.00 0
0.00 0.00 0

Voltage Drop shall be less than 3%. - 84 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage Drop Total Voltage
Judge Factor Judge Voltage Drop (v) Judge
Cap (A) Cap (A) (v) Drop (%)
mV/A/m

0 0.00

A OK 1.00 4,000 A OK 0.02 3.09 V 3.09 V OK V%= 0.77%


0 0.00
A OK 0.85 516 A OK 0.21 4.81 V 7.90 V OK V%= 1.2%
A OK 0.85 434 A False 0.26 1.08 V 7.94 V OK V%=0.27%
PF-O-B1-02 : Final Point Voltage Drop (Less than 4%) 8.98 V V%= 2.25%

A OK 0.85 63 A OK 4.00 6.79 V 9.88 V OK V%= 1.7%


A OK 0.85 26 A OK 16.00 2.15 V 9.01 V OK V%=0.54%
PF-O-B1-02 : Final Point Voltage Drop (Less than 4%) 12.03 V V%= 3.01%

A OK 0.85 63 A OK 4.00 5.62 V 8.71 V OK V%= 1.41%


A OK 0.85 63 A OK 4.00 1.44 V 8.30 V OK V%=0.36%
PF-O-B1-02 : Final Point Voltage Drop (Less than 4%) 10.15 V V%= 2.54%

A OK 0.85 63 A OK 4.00 4.89 V 7.98 V OK V%= 1.22%


A OK 0.85 46 A OK 6.80 1.90 V 8.76 V OK V%=0.48%
PF-O-B1-02 : Final Point Voltage Drop (Less than 4%) 9.88 V V%= 2.47%

A OK 0.85 115 A OK 1.65 4.20 V 7.29 V OK V%= 1.05%


ELV-8 : Final Point Voltage Drop (Less than 4%) 7.29 V V%= 1.82%
A OK 0.85 115 A OK 1.65 7.05 V 10.14 V OK V%= 1.76%
ELV-15 : Final Point Voltage Drop (Less than 4%) 10.14 V V%= 2.54%
A OK 0.85 115 A OK 1.65 3.51 V 6.60 V OK V%= 0.88%
ELV-16 : Final Point Voltage Drop (Less than 4%) 6.60 V V%= 1.65%

A OK 0.85 279 A OK 0.45 10.01 V 13.10 V OK V%= 2.5%


A OK 0.85 352 A OK 0.44 0.44 V 7.30 V OK V%=0.11%
P-H-B2-14 : Final Point Voltage Drop (Less than 4%) 13.54 V V%= 3.39%

A OK 0.85 326 A OK 0.37 8.76 V 11.85 V OK V%= 2.19%


A OK 0.85 176 A OK 0.87 0.89 V 7.75 V OK V%=0.22%
P-H-B1-01 : Final Point Voltage Drop (Less than 4%) 12.74 V V%= 3.19%

A OK 0.85 228 A OK 0.60 6.06 V 9.15 V OK V%= 1.52%

Voltage Drop shall be less than 3%. - 85 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage Drop Total Voltage
Judge Factor Judge Voltage Drop (v) Judge
Cap (A) Cap (A) (v) Drop (%)
mV/A/m

A OK 0.85 176 A OK 0.87 0.89 V 7.75 V OK V%=0.22%


PF-O-B1-02 : Final Point Voltage Drop (Less than 4%) 10.04 V V%= 2.51%

Voltage Drop shall be less than 3%. - 86 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage Drop Total Voltage
Judge Factor Judge Voltage Drop (v) Judge
Cap (A) Cap (A) (v) Drop (%)
mV/A/m

A OK 0.85 46 A OK 6.80 0.68 V 3.77 V OK V%= 0.17%

Total Voltage Drop 3.77 V


A OK 0.85 29 A OK 19.00 0.38 V 3.47 V OK V%= 0.17%
A OK 0.85 29 A OK 19.00 1.87 V 8.73 V OK V%=0.81%
Convert to 3Phase 3.90 V
PF-O-GF-01 : Final Point Voltage Drop (Less than 4%) 7.67 V V%= 1.92%

A OK 0.85 35 A OK 10.00 0.26 V 3.35 V OK V%= 0.07%

A OK 0.85 29 A OK 19.00 0.11 V 3.20 V OK V%= 0.05%


A OK 0.85 29 A OK 19.00 0.56 V 7.42 V OK V%=0.24%
Convert to 3Phase 1.16 V
PF-O-GF-03 : Final Point Voltage Drop (Less than 4%) 5.19 V V%= 1.3%

A OK 0.85 35 A OK 10.00 0.07 V 3.16 V OK V%= 0.02%

A OK 0.85 29 A OK 19.00 0.05 V 3.14 V OK V%= 0.02%


A OK 0.85 29 A OK 19.00 0.18 V 7.04 V OK V%=0.08%
Convert to 3Phase 0.40 V
PF-O-GF-04 : Final Point Voltage Drop (Less than 4%) 4.50 V V%= 1.12%

A OK 0.85 35 A OK 10.00 0.06 V 3.15 V OK V%= 0.02%

A OK 0.85 29 A OK 19.00 0.08 V 3.17 V OK V%= 0.03%


A OK 0.85 29 A OK 19.00 0.26 V 7.12 V OK V%=0.11%
Convert to 3Phase 0.59 V
PF-O-GF-04 : Final Point Voltage Drop (Less than 4%) 4.75 V V%= 1.19%

A OK 0.85 29 A OK 19.00 0.19 V 3.28 V OK V%= 0.08%

A OK 0.85 29 A OK 19.00 0.10 V 6.96 V OK V%=0.04%


Convert to 3Phase 0.50 V
PF-O-GF-05 : Final Point Voltage Drop (Less than 4%) 4.66 V V%= 1.17%

A OK 0.85 63 A OK 4.00 5.98 V 9.07 V OK V%= 1.5%


A OK 0.85 63 A OK 4.00 1.44 V 8.30 V OK V%=0.36%
PF-O-1-03 : Final Point Voltage Drop (Less than 4%) 10.51 V V%= 2.63%

A OK 0.85 63 A OK 4.00 6.51 V 9.60 V OK V%= 1.63%


A OK 0.85 46 A OK 6.80 1.90 V 8.76 V OK V%=0.48%
PF-O-3-01 : Final Point Voltage Drop (Less than 4%) 11.50 V V%= 2.88%

Voltage Drop shall be less than 3%. - 87 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage Drop Total Voltage
Judge Factor Judge Voltage Drop (v) Judge
Cap (A) Cap (A) (v) Drop (%)
mV/A/m

A OK 0.85 176 A OK 0.87 9.47 V 12.56 V OK V%= 2.37%


A OK 0.85 63 A OK 4.00 1.44 V 8.30 V OK V%=0.36%
P-H-RF-01 : Final Point Voltage Drop (Less than 4%) 14.00 V V%= 3.5%

A OK 0.85 237 A OK 0.62 3.77 V 6.86 V OK V%= 0.94%


A OK 0.85 63 A OK 4.00 1.44 V 8.30 V OK V%=0.36%
P-H-RF-02 : Final Point Voltage Drop (Less than 4%) 8.30 V V%= 2.08%

A OK 0.85 84 A OK 2.50 5.27 V 8.36 V OK V%= 1.32%


A OK 0.85 63 A OK 4.00 1.44 V 8.30 V OK V%=0.36%
P-H-RF-04 : Final Point Voltage Drop (Less than 4%) 9.80 V V%= 2.45%

A OK 0.85 46 A OK 6.80 2.46 V 5.55 V OK V%= 0.62%


A OK 0.85 26 A OK 16.00 0.73 V 7.59 V OK V%=0.18%
P-O-GF-03 : Final Point Voltage Drop (Less than 4%) 6.28 V V%= 1.57%

A OK 0.85 176 A OK 0.87 3.98 V 7.07 V OK V%= 1%


A OK 0.85 176 A OK 0.87 1.88 V 8.74 V OK V%=0.47%
P-O-GF-03 : Final Point Voltage Drop (Less than 4%) 8.95 V V%= 2.24%
A OK 0.85 176 A OK 0.87 0.66 V 3.75 V OK V%= 0.17%
A OK 0.85 35 A OK 10.00 1.94 V 8.80 V OK V%=0.49%
P-O-GF-03 : Final Point Voltage Drop (Less than 4%) 6.58 V V%= 1.65%

###

A OK 0.85 35 A OK 10.00 2.47 V 5.56 V OK V%= 0.62%


A OK 0.85 26 A OK 16.00 1.15 V 8.01 V OK V%=0.29%
P-O-1-02 : Final Point Voltage Drop (Less than 4%) 6.71 V V%= 1.68%

A OK 0.85 63 A OK 4.00 7.68 V 10.77 V OK V%= 1.92%


A OK 0.85 20 A OK 18.00 0.94 V 9.92 V ###
Convert to 3Phase 1.63 V
P-O-2-01 : Final Point Voltage Drop (Less than 4%) 12.40 V V%= 3.1%

Voltage Drop shall be less than 3%. - 88 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage Drop Total Voltage
Judge Factor Judge Voltage Drop (v) Judge
Cap (A) Cap (A) (v) Drop (%)
mV/A/m

A OK 0.85 84 A OK 2.50 5.60 V 8.69 V OK V%= 1.4%


A OK 0.85 20 A OK 18.00 1.57 V 10.55 V ###
Convert to 3Phase 2.72 V
P-O-2-01 : Final Point Voltage Drop (Less than 4%) 11.41 V V%= 2.85%
0 0.00
A OK 0.85 35 A OK 10.00 0.98 V 4.07 V OK V%= 0.25%
A OK 0.85 26 A OK 16.00 0.16 V 7.02 V OK V%=0.04%
P-H-1-02 : Final Point Voltage Drop (Less than 4%) 4.23 V V%= 1.06%

A OK 0.85 700 A OK 0.17 4.44 V 7.53 V OK V%= 1.11%


A OK 0.85 456 A OK 0.30 0.77 V 7.63 V OK V%=0.19%
P-H-1-02 : Final Point Voltage Drop (Less than 4%) 8.30 V V%= 2.08%

A OK 0.85 377 A OK 0.30 7.10 V 10.19 V OK V%= 1.78%


A OK 0.85 352 A OK 0.44 0.44 V 7.30 V OK V%=0.11%
P-H-1-02 : Final Point Voltage Drop (Less than 4%) 10.63 V V%= 2.66%

A OK 0.85 237 A OK 0.62 2.35 V 5.44 V OK V%= 0.59%


P-WT-B1-01 : Final Point Voltage Drop (Less than 4%) 5.44 V V%= 1.36%
A OK 0.85 290 A OK 0.46 5.25 V 8.34 V OK V%= 1.31%
P-WT-B1-02 : Final Point Voltage Drop (Less than 4%) 8.34 V V%= 2.09%
0 0.00
A OK 0.85 1,607 A OK 0.08 8.43 V 11.52 V OK V%= 2.11%
A OK 0.85 392 A OK 0.32 0.66 V 7.52 V OK V%=0.17%
P-H-B1-02 : Final Point Voltage Drop (Less than 4%) 12.18 V V%= 3.05%
A OK 0.85 3,723 A OK 0.04 7.85 V 10.94 V OK V%= 1.96%
A OK 0.85 1,071 A OK 0.12 1.10 V 7.96 V OK V%=0.28%
P-H-B2-14 : Final Point Voltage Drop (Less than 4%) 12.04 V V%= 3.01%
A OK 0.85 150 A OK 1.15 5.09 V 8.18 V OK V%= 1.27%
A OK 0.85 26 A OK 16.00 2.57 V 9.43 V OK V%=0.64%
P-H-2-04 : Final Point Voltage Drop (Less than 4%) 10.75 V V%= 2.69%
A OK 0.85 338 A OK 0.38 9.99 V 13.08 V OK V%= 2.5%
A OK 0.85 238 A OK 0.80 0.54 V 7.40 V OK V%=0.14%
P-H-RF-01 : Final Point Voltage Drop (Less than 4%) 13.62 V V%= 3.41%
A OK 0.85 338 A OK 0.38 4.47 V 7.56 V OK V%= 1.12%

Voltage Drop shall be less than 3%. - 89 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage Drop Total Voltage
Judge Factor Judge Voltage Drop (v) Judge
Cap (A) Cap (A) (v) Drop (%)
mV/A/m

A OK 0.85 26 A OK 16.00 3.32 V 10.18 V OK V%=0.83%


P-H-RF-03 : Final Point Voltage Drop (Less than 4%) 10.88 V V%= 2.72%
A OK 0.85 290 A OK 0.46 4.41 V 7.5 V OK V%= 1.1%
A OK 0.85 35 A OK 10.00 2.08 V 8.94 V OK V%=0.52%
P-H-RF-04 : Final Point Voltage Drop (Less than 4%) 9.58 V V%= 2.4%

A OK 0.85 119 A OK 1.60 3.22 V 6.31 V OK V%= 0.81%


ELV-10 : Final Point Voltage Drop (Less than 4%) 6.31 V V%= 1.58%
A OK 0.85 119 A OK 1.60 3.22 V 6.31 V OK V%= 0.81%
ELV-11 : Final Point Voltage Drop (Less than 4%) 6.31 V V%= 1.58%
A OK 0.85 119 A OK 1.60 6.09 V 9.18 V OK V%= 1.52%
ELV-12 : Final Point Voltage Drop (Less than 4%) 9.18 V V%= 2.3%
A OK 0.85 119 A OK 1.60 6.09 V 9.18 V OK V%= 1.52%
ELV-13 : Final Point Voltage Drop (Less than 4%) 9.18 V V%= 2.3%
A OK 0.85 119 A OK 1.60 6.09 V 9.18 V OK V%= 1.52%
ELV-14 : Final Point Voltage Drop (Less than 4%) 9.18 V V%= 2.3%
A OK 0.85 119 A OK 1.60 6.84 V 9.93 V OK V%= 1.71%
ELV-16 : Final Point Voltage Drop (Less than 4%) 9.93 V V%= 2.48%
A OK 0.85 119 A OK 1.60 6.84 V 9.93 V OK V%= 1.71%
ELV-17 : Final Point Voltage Drop (Less than 4%) 9.93 V V%= 2.48%
A OK 0.85 119 A OK 1.60 3.40 V 6.49 V OK V%= 0.85%
ELV-18 : Final Point Voltage Drop (Less than 4%) 6.49 V V%= 1.62%
A OK 0.85 62 A OK 4.00 4.84 V 7.93 V OK V%= 1.21%
ELV-19 : Final Point Voltage Drop (Less than 4%) 7.93 V V%= 1.98%
A OK 0.85 62 A OK 4.00 9.12 V 12.21 V OK V%= 2.28%
ELV-22 : Final Point Voltage Drop (Less than 4%) 12.21 V V%= 3.05%
A OK 0.85 62 A OK 4.00 3.11 V 6.2 V OK V%= 0.78%
ES-1 : Final Point Voltage Drop (Less than 4%) 6.20 V V%= 1.55%
A OK 0.85 62 A OK 4.00 3.11 V 6.20 V OK V%= 0.78%
ES-2 : Final Point Voltage Drop (Less than 4%) 6.20 V V%= 1.55%
0 0.00
0 0.00
0 0.00

Voltage Drop shall be less than 3%. - 90 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

0.00 0.00 0

FA TR3 TR-3 (2,500KVA) BD 4000 4W Cu-Fe 40 m 400 V ACB TPN 4,000 A 6,169.67 kVA 0.34 2,122.00 kVA 3,062.93 A 4000
HOTEL 客室 0.00 0.00 0
FB-1 ST-3 12x1C 300sqmm XLPE/PVC 162 m 400 V ACB TPN 1,250 A 649.46 kVA 0.75 487.12 kVA 703.12 A 2190
FB-2 BD 1250 4W Cu-Fe (5-1) 4 m 400 V ACB TPN 1,250 A 649.46 kVA 0.75 487.12 kVA 703.12 A 1250
FB-3 Tap Off Unit (5-1) LH2-D1 4C 50sqmm XLPE/PVC 6 m 400 V MCCB TPN 175 A 89.72 kVA 0.75 67.29 kVA 97.13 A 215
From Transformer to LH2-D1 (FA+FB-1+FB-2+FB-3)
LH2-D1 P-H-GF-05 4C 4sqmm XLPE/PVC 26 m 400 V MCCB 3P 30 A 5.72 kVA 0.70 4.00 kVA 5.77 A 41
To Final Point M-Scope) 3C 4sqmm XLPE/PVC 25 m 400 V MCCB 3P 20 A 4.23 kVA 1.00 4.23 kVA 6.11 A 41
400 V
LH2-D1 Standard (24rooms) 4C 4sqmm XLPE/PVC 60 m 400 V MCCB TPN 15 A 3.00 kVA 0.70 2.10 kVA 3.03 A 41
Standard to Final Point 2X1C 2.5sqmm PVC 10 m 230 V MCB SP 20 A 0.10 kVA 1.00 0.10 kVA 0.43 A 24
400 V
400 V
LH2-D1 Deluxe (2rooms) 4C 6sqmm XLPE/PVC 60 m 400 V MCCB TPN 15 A 6.00 kVA 0.70 4.20 kVA 6.06 A 53
Deluxe to Final Point 2X1C 2.5sqmm PVC 10 m 230 V MCB SP 20 A 0.10 kVA 1.00 0.10 kVA 0.43 A 24
400 V
400 V

FC BD 1250 4W Cu-Fe (5-2) 4 m 400 V ACB TPN 1,250 A 559.74 kVA 0.75 419.83 kVA 605.99 A 1250
FC-1 Tap Off Unit (5-2) LH3-D1 4C 50sqmm XLPE/PVC 6 m 400 V MCCB TPN 175 A 98.46 kVA 0.75 73.85 kVA 106.60 A 215
From Transformer to LH3-D1 (FA+FB-1+FB-2+FC+FC-1)
LH3-D1 P-H-3-03 4C 6sqmm XLPE/PVC 25 m 400 V MCCB 3P 30 A 4.23 kVA 0.70 2.96 kVA 4.27 A 53
To Final Point (M-Scope) 3C 2.5sqmm XLPE/PVC 25 m 400 V MCCB 3P 15 A 4.23 kVA 1.00 4.23 kVA 6.11 A 31
400 V
LH3-D1 P-H-3-04 4C 6sqmm XLPE/PVC 19 m 400 V MCCB 3P 30 A 4.23 kVA 0.70 2.96 kVA 4.27 A 53
To Final Point M-Scope) 3C 2.5sqmm XLPE/PVC 25 m 400 V MCCB 3P 15 A 4.23 kVA 1.00 4.23 kVA 0.54 A 31
400 V
LH3-D1 Standard (22rooms) 4C 4sqmm XLPE/PVC 60 m 400 V MCCB TPN 15 A 3.00 kVA 0.70 2.10 kVA 3.03 A 41
Standard to Final Point 2X1C 2.5sqmm PVC 10 m 230 V MCB SP 20 A 0.10 kVA 1.00 0.10 kVA 0.43 A 24
400 V
400 V
LH3-D1 Deluxe (4rooms) 4C 6sqmm XLPE/PVC 60 m 400 V MCCB TPN 15 A 6.00 kVA 0.70 4.20 kVA 6.06 A 53
Deluxe to Final Point 2X1C 2.5sqmm PVC 10 m 230 V MCB SP 20 A 0.10 kVA 1.00 0.10 kVA 0.43 A 24
400 V

Voltage Drop shall be less than 3%. - 91 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

400 V

Voltage Drop shall be less than 3%. - 92 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

FD BD 1250 4W Cu-Fe (5-3) 4 m 400 V ACB TPN 1,250 A 461.28 kVA 0.75 345.98 kVA 499.39 A 1250
FD-1 Tap Off Unit (5-3) LH4-D1 4C 50sqmm XLPE/PVC 6 m 400 V MCCB TPN 175 A 98.46 kVA 0.75 73.85 kVA 106.60 A 215
From Transformer to LH4-D1 (FA+FB-1+FB-2+FC+FD+FD-1)
LH4-D1 P-H-4-01 4C 6sqmm XLPE/PVC 25 m 400 V MCCB 3P 30 A 4.23 kVA 0.70 2.96 kVA 4.27 A 53
To Final Point M-Scope) 3C 2.5sqmm XLPE/PVC 10 m 400 V MCCB 3P 15 A 4.23 kVA 1.00 4.23 kVA 6.10 A 31
400 V
LH4-D1 P-H-4-02 4C 6sqmm XLPE/PVC 19 m 400 V MCCB 3P 30 A 4.23 kVA 0.70 2.96 kVA 4.27 A 53
To Final Point M-Scope) 3C 2.5sqmm XLPE/PVC 10 m 400 V MCCB 3P 15 A 4.23 kVA 1.00 4.23 kVA 6.10 A 31
400 V
LH4-D1 Standard (22rooms) 4C 4sqmm XLPE/PVC 60 m 400 V MCCB TPN 15 A 3.00 kVA 0.70 2.10 kVA 3.03 A 41
Standard to Final Point 2X1C 2.5sqmm PVC 10 m 230 V MCB SP 20 A 0.10 kVA 1.00 0.10 kVA 0.43 A 24
400 V
400 V
LH4-D1 Deluxe (4rooms) 4C 6sqmm XLPE/PVC 60 m 400 V MCCB TPN 15 A 6.00 kVA 0.70 4.20 kVA 6.06 A 53
Deluxe to Final Point 2X1C 2.5sqmm PVC 10 m 230 V MCB SP 20 A 0.10 kVA 1.00 0.10 kVA 0.43 A 24
400 V
400 V

FE BD 1250 4W Cu-Fe (5-4) 4 m 400 V ACB TPN 1,250 A 362.82 kVA 0.75 272.13 kVA 392.80 A 1250
FE-1 Tap Off Unit (5-4) LH5-D1 4C 50sqmm XLPE/PVC 6 m 400 V MCCB TPN 175 A 92.46 kVA 0.75 69.35 kVA 100.10 A 215
From Transformer to LH5-D1 (FA+FB-1+FB-2+FC+FD+FE+FE-1)
LH5-D1 P-H-5-01 4C 6sqmm XLPE/PVC 25 m 400 V MCCB 3P 30 A 4.23 kVA 0.70 2.96 kVA 4.27 A 53
To Final Point M-Scope) 3C 2.5sqmm XLPE/PVC 10 m 400 V MCCB 3P 15 A 4.23 kVA 1.00 4.23 kVA 6.10 A 31
400 V
LH5-D1 P-H-5-02 4C 6sqmm XLPE/PVC 19 m 400 V MCCB 3P 30 A 4.23 kVA 0.70 2.96 kVA 4.27 A 53
To Final Point M-Scope) 3C 2.5sqmm XLPE/PVC 10 m 400 V MCCB 3P 15 A 4.23 kVA 1.00 4.23 kVA 6.10 A 31
400 V
LH5-D1 Standard (20rooms) 4C 4sqmm XLPE/PVC 60 m 400 V MCCB TPN 15 A 3.00 kVA 0.70 2.10 kVA 3.03 A 41
Standard to Final Point 2X1C 2.5sqmm PVC 10 m 230 V MCB SP 20 A 0.10 kVA 1.00 0.10 kVA 0.43 A 24
400 V
400 V
LH5-D1 Deluxe or Suit(4rooms) 4C 6sqmm XLPE/PVC 60 m 400 V MCCB TPN 15 A 6.00 kVA 0.70 4.20 kVA 6.06 A 53
Deluxe or Suitto Final Point 2X1C 2.5sqmm PVC 10 m 230 V MCB SP 20 A 0.10 kVA 1.00 0.10 kVA 0.43 A 24
400 V
400 V Deluxe

Voltage Drop shall be less than 3%. - 93 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

Voltage Drop shall be less than 3%. - 94 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

FG BD 1250 4W Cu-Fe (5-5) 18 m 400 V ACB TPN 1,250 A 270.36 kVA 0.75 202.78 kVA 292.70 A 1250
FG-1 Tap Off Unit (5-5) LH6-D1 4C 50sqmm XLPE/PVC 6 m 400 V MCCB TPN 175 A 92.46 kVA 0.75 69.35 kVA 100.10 A 215
From Transformer to LH6-D1 (FA+FB-1+FB-2+FC+FD+FE+FG+FG-1)
LH6-D1 P-H-6-01 4C 6sqmm XLPE/PVC 25 m 400 V MCCB 3P 30 A 4.23 kVA 0.70 2.96 kVA 4.27 A 53
To Final Point M-Scope) 3C 2.5sqmm XLPE/PVC 10 m 400 V MCCB 3P 15 A 4.23 kVA 1.00 4.23 kVA 6.10 A 31
400 V
LH6-D1 P-H-6-02 4C 6sqmm XLPE/PVC 19 m 400 V MCCB 3P 30 A 4.23 kVA 0.70 2.96 kVA 4.27 A 53
To Final Point M-Scope) 3C 2.5sqmm XLPE/PVC 10 m 400 V MCCB 3P 15 A 4.23 kVA 1.00 4.23 kVA 6.10 A 31
400 V
LH6-D1 Standard (20rooms) 4C 4sqmm XLPE/PVC 60 m 400 V MCCB TPN 15 A 3.00 kVA 0.70 2.10 kVA 3.03 A 41
Standard to Final Point 2X1C 2.5sqmm PVC 10 m 230 V MCB SP 20 A 0.10 kVA 1.00 0.10 kVA 0.43 A 24
400 V
400 V
LH6-D1 Deluxe or Suit(4rooms) 4C 6sqmm XLPE/PVC 60 m 400 V MCCB TPN 15 A 6.00 kVA 0.70 4.20 kVA 6.06 A 53
Deluxe or Suitto Final Point 2X1C 2.5sqmm PVC 10 m 230 V MCB SP 20 A 0.10 kVA 1.00 0.10 kVA 0.43 A 24
400 V
400 V Deluxe

FH BD 1250 4W Cu-Fe (5-6) 4 m 400 V ACB TPN 1,250 A 177.90 kVA 0.75 133.43 kVA 192.60 A 1250
FH-1 Tap Off Unit (5-6) LH7-D1 4C 50sqmm XLPE/PVC 6 m 400 V MCCB TPN 175 A 92.46 kVA 0.75 69.35 kVA 100.10 A 215
From Transformer to LH7-D1 (FA+FB-1+FB-2+FC+FD+FE+FG+FH+FH-1)
LH7-D1 P-H-7-01 4C 6sqmm XLPE/PVC 25 m 400 V MCCB 3P 30 A 4.23 kVA 0.70 2.96 kVA 4.27 A 53
To Final Point M-Scope) 3C 2.5sqmm XLPE/PVC 10 m 400 V MCCB 3P 15 A 4.23 kVA 1.00 4.23 kVA 6.10 A 31
400 V
LH7-D1 P-H-7-02 4C 6sqmm XLPE/PVC 19 m 400 V MCCB 3P 30 A 4.23 kVA 0.70 2.96 kVA 4.27 A 53
To Final Point M-Scope) 3C 2.5sqmm XLPE/PVC 10 m 400 V MCCB 3P 15 A 4.23 kVA 1.00 4.23 kVA 6.10 A 31
400 V
LH7-D1 Standard (20rooms) 4C 4sqmm XLPE/PVC 60 m 400 V MCCB TPN 15 A 3.00 kVA 0.70 2.10 kVA 3.03 A 41
Standard to Final Point 2X1C 2.5sqmm PVC 10 m 230 V MCB SP 20 A 0.10 kVA 1.00 0.10 kVA 0.43 A 24
400 V
400 V
LH7-D1 Deluxe or Suit(4rooms) 4C 6sqmm XLPE/PVC 60 m 400 V MCCB TPN 15 A 6.00 kVA 0.70 4.20 kVA 6.06 A 53
Deluxe or Suitto Final Point 2X1C 2.5sqmm PVC 10 m 230 V MCB SP 20 A 0.10 kVA 1.00 0.10 kVA 0.43 A 24
400 V
400 V Deluxe

Voltage Drop shall be less than 3%. - 95 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

Voltage Drop shall be less than 3%. - 96 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

FI BD 1250 4W Cu-Fe (5-7) 4 m 400 V ACB TPN 1,250 A 85.44 kVA 0.75 64.08 kVA 92.49 A 1250
FI-1 Tap Off Unit (5-7) LH8-D1 4C 50sqmm XLPE/PVC 6 m 400 V MCCB TPN 175 A 85.44 kVA 0.75 64.08 kVA 92.49 A 215
From Transformer to LH8-D1 (FA+FB-1+FB-2+FC+FD+FE+FG+FH+FI+FI-1)
LH8-D1 P-H-8-01 4C 6sqmm XLPE/PVC 29 m 400 V MCCB 3P 30 A 6.72 kVA 0.70 4.70 kVA 6.78 A 53
To Final Point M-Scope) 3C 2.5sqmm XLPE/PVC 10 m 400 V MCCB 3P 15 A 4.23 kVA 1.00 4.23 kVA 6.10 A 31
400 V
LH8-D1 P-H-RF-02 4C 4sqmm XLPE/PVC 10 m 400 V MCCB 3P 20 A 6.72 kVA 1.00 6.72 kVA 9.70 A 41
To Final Point M-Scope) 3C 2.5sqmm XLPE/PVC 10 m 400 V MCCB 3P 20 A 6.72 kVA 1.00 6.72 kVA 9.70 A 31
400 V
LH8-D1 Standard (18rooms) 4C 4sqmm XLPE/PVC 60 m 400 V MCCB TPN 15 A 3.00 kVA 0.70 2.10 kVA 3.03 A 41
Standard to Final Point 2X1C 2.5sqmm PVC 10 m 230 V MCB SP 20 A 0.10 kVA 1.00 0.10 kVA 0.43 A 24
400 V
400 V
LH8-D1 Deluxe or Suit(4rooms) 4C 6sqmm XLPE/PVC 60 m 400 V MCCB TPN 15 A 6.00 kVA 0.70 4.20 kVA 6.06 A 53
Deluxe or Suitto Final Point 2X1C 2.5sqmm PVC 10 m 230 V MCB SP 20 A 0.10 kVA 1.00 0.10 kVA 0.43 A 24
400 V
400 V Deluxe

0.00 0.00 0
FJ ST-3 8x1C 400sqmm XLPE/PVC 162 m 400 V ACB TPN 800 A 450.94 kVA 0.75 338.21 kVA 488.18 A 1698
FJ-1 BD 1250 4W Cu-Fe (6-1) 4 m 400 V ACB TPN 800 A 450.94 kVA 0.75 338.21 kVA 488.18 A 800
FJ-2 Tap Off Unit (6-1) LH2-D2 4C 35sqmm XLPE/PVC 6 m 400 V MCCB TPN 125 A 65.43 kVA 0.75 49.07 kVA 70.83 A 176
From Transformer to LH2-D2 (FA+FJ-1+FJ-2)
LH2-D2 LH2-C1 4C 6sqmm XLPE/PVC 6 m 400 V MCCB TPN 40 A 20.43 kVA 0.70 14.30 kVA 20.64 A 53
LH2-C1 to Final Point 2X1C 2.5sqmm PVC 30 m 230 V MCB SP 20 A 1.20 kVA 0.50 0.60 kVA 2.61 A 24
400 V
400 V
LH2-D2 Standard (10rooms) 4C 4sqmm XLPE/PVC 60 m 400 V MCCB TPN 15 A 3.00 kVA 0.70 2.10 kVA 3.03 A 41
Standard to Final Point 2X1C 2.5sqmm PVC 10 m 230 V MCB SP 20 A 0.10 kVA 1.00 0.10 kVA 0.43 A 24
400 V
400 V

FK BD 1250 4W Cu-Fe (6-2) 4 m 400 V ACB TPN 800 A 385.51 kVA 0.75 289.14 kVA 417.35 A 800
FK-1 Tap Off Unit (6-2) LH3-D2 4C 35sqmm XLPE/PVC 6 m 400 V MCCB TPN 125 A 66.30 kVA 0.75 49.73 kVA 71.78 A 176
From Transformer to LH3-D2 (FA+FJ+FJ-1+FK+FK-1)

Voltage Drop shall be less than 3%. - 97 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

LH3-D2 LH3-C1 4C 6sqmm XLPE/PVC 6 m 400 V MCCB TPN 30 A 18.30 kVA 0.70 12.81 kVA 18.49 A 53
LH3-C1 to Final Point 2X1C 2.5sqmm PVC 30 m 230 V MCB SP 20 A 1.20 kVA 0.50 0.60 kVA 2.61 A 24
400 V
400 V
LH3-D2 Standard (16rooms) 4C 4sqmm XLPE/PVC 60 m 400 V MCCB TPN 15 A 3.00 kVA 0.70 2.10 kVA 3.03 A 41
Standard to Final Point 2X1C 2.5sqmm PVC 10 m 230 V MCB SP 20 A 1.50 kVA 1.00 1.50 kVA 6.52 A 24
400 V
400 V

Voltage Drop shall be less than 3%. - 98 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

FL BD 1250 4W Cu-Fe (6-3) 4 m 400 V ACB TPN 800 A 319.21 kVA 0.75 239.41 kVA 345.57 A 800
FL-1 Tap Off Unit (6-3) LH4-D2 4C 35sqmm XLPE/PVC 6 m 400 V MCCB TPN 125 A 66.30 kVA 0.75 49.73 kVA 71.78 A 176
From Transformer to LH4-D2 (FA+FJ+FJ-1+FK+FL+FL-1)
LH4-D2 LH4-C1 4C 6sqmm XLPE/PVC 6 m 400 V MCCB TPN 30 A 18.30 kVA 0.70 12.81 kVA 18.49 A 53
LH4-C1 to Final Point 2X1C 2.5sqmm PVC 30 m 230 V MCB SP 20 A 1.20 kVA 0.50 0.60 kVA 2.61 A 24
400 V
400 V
LH4-D2 Standard (16rooms) 4C 4sqmm XLPE/PVC 60 m 400 V MCCB TPN 15 A 3.00 kVA 0.70 2.10 kVA 3.03 A 41
Standard to Final Point 2X1C 2.5sqmm PVC 10 m 230 V MCB SP 20 A 1.50 kVA 1.00 1.50 kVA 6.52 A 24
400 V
400 V

FM BD 1250 4W Cu-Fe (6-4) 4 m 400 V ACB TPN 800 A 252.91 kVA 0.75 189.68 kVA 273.79 A 800
FM-1 Tap Off Unit (6-4) LH5-D2 4C 35sqmm XLPE/PVC 6 m 400 V MCCB TPN 125 A 66.15 kVA 0.75 49.61 kVA 71.61 A 176
From Transformer to LH5-D2 (FA+FJ+FJ-1+FK+FL+FM+FM-1)
LH5-D2 LH5-C1 4C 6sqmm XLPE/PVC 6 m 400 V MCCB TPN 30 A 18.15 kVA 0.70 12.71 kVA 18.35 A 53
LH5-C1 to Final Point 2X1C 2.5sqmm PVC 30 m 230 V MCB SP 20 A 1.20 kVA 0.50 0.60 kVA 2.61 A 24
400 V
400 V
LH5-D2 Standard (13rooms) 4C 4sqmm XLPE/PVC 60 m 400 V MCCB TPN 15 A 3.00 kVA 0.70 2.10 kVA 3.03 A 41
Standard to Final Point 2X1C 2.5sqmm PVC 10 m 230 V MCB SP 20 A 0.10 kVA 1.00 0.10 kVA 0.43 A 24
400 V
400 V
LH5-D2 Suit(1rooms) 4C 6sqmm XLPE/PVC 60 m 400 V MCCB TPN 15 A 6.00 kVA 0.70 4.20 kVA 6.06 A 53
Deluxe or Suitto Final Point 2X1C 2.5sqmm PVC 10 m 230 V MCB SP 20 A 0.10 kVA 1.00 0.10 kVA 0.43 A 24
400 V
400 V

FN BD 1250 4W Cu-Fe (6-5) 4 m 400 V ACB TPN 800 A 186.76 kVA 0.75 140.07 kVA 202.18 A 800
FN-1 Tap Off Unit (6-5) LH6-D2 4C 35sqmm XLPE/PVC 6 m 400 V MCCB TPN 125 A 66.15 kVA 0.75 49.61 kVA 71.61 A 176
From Transformer to LH6-D2 (FA+FJ+FJ-1+FK+FL+FM+FN+FN-1)
LH6-D2 LH6-C1 4C 6sqmm XLPE/PVC 6 m 400 V MCCB TPN 30 A 18.15 kVA 0.70 12.71 kVA 18.35 A 53
LH6-C1 to Final Point 2X1C 2.5sqmm PVC 30 m 230 V MCB SP 20 A 1.20 kVA 0.50 0.60 kVA 2.61 A 24
400 V
400 V

Voltage Drop shall be less than 3%. - 99 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

LH6-D2 Standard (13rooms) 4C 4sqmm XLPE/PVC 60 m 400 V MCCB TPN 15 A 3.00 kVA 0.70 2.10 kVA 3.03 A 41
Standard to Final Point 2X1C 2.5sqmm PVC 10 m 230 V MCB SP 20 A 0.10 kVA 1.00 0.10 kVA 0.43 A 24
400 V
400 V
LH6-D2 Suit(1rooms) 4C 6sqmm XLPE/PVC 60 m 400 V MCCB TPN 15 A 6.00 kVA 0.70 4.20 kVA 6.06 A 53
Deluxe or Suitto Final Point 2X1C 2.5sqmm PVC 10 m 230 V MCB SP 20 A 0.10 kVA 1.00 0.10 kVA 0.43 A 24
400 V
400 V

Voltage Drop shall be less than 3%. - 100 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

FO BD 1250 4W Cu-Fe (6-6) 4 m 400 V ACB TPN 800 A 120.61 kVA 0.75 90.46 kVA 130.57 A 800
FO-1 Tap Off Unit (6-6) LH7-D2 4C 35sqmm XLPE/PVC 6 m 400 V MCCB TPN 125 A 63.15 kVA 0.75 47.36 kVA 68.36 A 176
From Transformer to LH7-D2 (FA+FJ+FJ-1+FK+FL+FM+FN+FO+FO-1)
LH7-D2 LH7-C1 4C 6sqmm XLPE/PVC 6 m 400 V MCCB TPN 30 A 18.15 kVA 0.70 12.71 kVA 18.35 A 53
LH7-C1 to Final Point 2X1C 2.5sqmm PVC 30 m 230 V MCB SP 20 A 1.20 kVA 0.50 0.60 kVA 2.61 A 24
400 V
400 V
LH7-D2 Standard (12rooms) 4C 4sqmm XLPE/PVC 60 m 400 V MCCB TPN 15 A 3.00 kVA 0.70 2.10 kVA 3.03 A 41
Standard to Final Point 2X1C 2.5sqmm PVC 10 m 230 V MCB SP 20 A 0.10 kVA 1.00 0.10 kVA 0.43 A 24
400 V
400 V
LH7-D2 Suit(1rooms) 4C 6sqmm XLPE/PVC 60 m 400 V MCCB TPN 15 A 6.00 kVA 0.70 4.20 kVA 6.06 A 53
Deluxe or Suitto Final Point 2X1C 2.5sqmm PVC 10 m 230 V MCB SP 20 A 0.10 kVA 1.00 0.10 kVA 0.43 A 24
400 V
400 V

FP BD 1250 4W Cu-Fe (6-7) 4 m 400 V ACB TPN 800 A 57.46 kVA 0.75 43.10 kVA 62.21 A 800
FP-1 Tap Off Unit (6-7) LH8-D2 4C 35sqmm XLPE/PVC 6 m 400 V MCCB TPN 125 A 57.46 kVA 0.75 43.10 kVA 62.21 A 176
From Transformer to LH8-D2 (FA+FJ+FJ-1+FK+FL+FM+FN+FO+FP+FP-1)
LH8-D2 LH8-C1 4C 6sqmm XLPE/PVC 6 m 400 V MCCB TPN 40 A 19.54 kVA 0.70 13.68 kVA 19.75 A 53
LH8-C1 to Final Point 2X1C 2.5sqmm PVC 30 m 230 V MCB SP 20 A 1.20 kVA 0.50 0.60 kVA 2.61 A 24
400 V
400 V
LH8-D2 LHR-C1 4C 6sqmm XLPE/PVC 47 m 400 V MCCB TPN 20 A 7.92 kVA 0.70 5.54 kVA 8.00 A 53
To Final Point (M Scope) 3C 16sqmm XLPE/PVC 40 m 230 V MCCB SP 20 A 1.01 kVA 1.00 1.01 kVA 4.39 A 69
400 V
400 V
LH7-D2 Standard (7rooms) 4C 4sqmm XLPE/PVC 60 m 400 V MCCB TPN 15 A 3.00 kVA 0.70 2.10 kVA 3.03 A 41
Standard to Final Point 2X1C 2.5sqmm PVC 10 m 230 V MCB SP 20 A 0.10 kVA 1.00 0.10 kVA 0.43 A 24
400 V
400 V
LH8-D2 Suit(1rooms) 4C 6sqmm XLPE/PVC 60 m 400 V MCCB TPN 15 A 6.00 kVA 0.70 4.20 kVA 6.06 A 53
Deluxe or Suitto Final Point 2X1C 2.5sqmm PVC 10 m 230 V MCB SP 20 A 0.10 kVA 1.00 0.10 kVA 0.43 A 24
400 V
400 V

Voltage Drop shall be less than 3%. - 101 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

SA 客室

FQ ST-3 12x1C 240sqmm XLPE/PVC 50 m 400 V ACB TPN 1,600 A 926.20 kVA 0.75 694.66 kVA 1,002.68 A 1890
FQ-1 BD 1250 4W Cu-Fe (7-1) 5 m 400 V ACB TPN 1,600 A 926.20 kVA 0.75 694.66 kVA 1,002.68 A 1600
FQ-2 Tap Off Unit (7-1) LS2-D1 4C 70sqmm XLPE/PVC 6 m 400 V MCCB TPN 200 A 158.39 kVA 0.75 118.79 kVA 171.46 A 279
From Transformer to LS2-D1 (FA+FQ+FQ-1+FQ-2)
LS2-D1 LSG-C1 4C 6sqmm XLPE/PVC 22 m 400 V MCCB TPN 20 A 11.00 kVA 0.70 7.70 kVA 11.11 A 53
LSG-C1 to Final Point 2X1C 2.5sqmm PVC 35 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V
LS2-D1 LS1-C1 4C 4sqmm XLPE/PVC 15 m 400 V MCCB TPN 30 A 14.25 kVA 0.70 9.98 kVA 14.41 A 41
LS1-C1 to Final Point 2X1C 2.5sqmm PVC 35 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V
LS2-D1 LS2-C1 4C 4sqmm XLPE/PVC 6 m 400 V MCCB TPN 30 A 8.54 kVA 0.70 5.98 kVA 8.63 A 41
LS1-C1 to Final Point 2X1C 2.5sqmm PVC 35 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V
LS2-D1 LSB1-C1 4C 4sqmm XLPE/PVC 33 m 400 V MCCB TPN 30 A 15.15 kVA 0.70 10.61 kVA 15.31 A 41
LS1-C1 to Final Point 2X1C 2.5sqmm PVC 35 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V
1Bed or Stadio type
LS2-D1 4C 6sqmm XLPE/PVC 80 m 400 V MCCB TPN 15 A 5.00 kVA 0.70 3.50 kVA 5.05 A 53
(11rooms)
1Bed/Stadio to Final Point 2X1C 2.5sqmm PVC 10 m 230 V MCB SP 20 A 0.10 kVA 1.00 0.10 kVA 0.43 A 24
400 V
400 V 1Bed or Stadi
LS2-D1 2Bed (6rooms) 4C 6sqmm XLPE/PVC 70 m 400 V MCCB TPN 15 A 7.00 kVA 0.70 4.90 kVA 7.07 A 53
2Bed to Final Point 2X1C 2.5sqmm PVC 10 m 230 V MCB SP 20 A 0.10 kVA 1.00 0.10 kVA 0.43 A 24
400 V
400 V
LS2-D1 3Bed 4C 6sqmm XLPE/PVC 30 m 400 V MCCB TPN 20 A 9.00 kVA 0.70 6.30 kVA 9.09 A 53
3Bed to Final Point 2X1C 2.5sqmm PVC 10 m 230 V MCB SP 20 A 0.10 kVA 1.00 0.10 kVA 0.43 A 24
400 V
400 V

FR BD 1250 4W Cu-Fe (7-2) 4 m 400 V ACB TPN 1,600 A 767.81 kVA 0.75 575.87 kVA 831.22 A 1600

Voltage Drop shall be less than 3%. - 102 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

FR-1 Tap Off Unit (7-2) LS3-D1 4C 70sqmm XLPE/PVC 6 m 400 V MCCB TPN 200 A 132.21 kVA 0.75 99.16 kVA 143.13 A 279
From Transformer to LS3-D1 (FA+FQ+FQ-1+FR+FR-1)
LS3-D1 LS3-C1 4C 4sqmm XLPE/PVC 6 m 400 V MCCB TPN 20 A 8.21 kVA 0.70 5.75 kVA 8.30 A 41
LS3-C1 to Final Point 2X1C 2.5sqmm PVC 35 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V

Voltage Drop shall be less than 3%. - 103 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor
1Bed or Stadio type
LS3-D1 4C 6sqmm XLPE/PVC 80 m 400 V MCCB TPN 15 A 5.00 kVA 0.70 3.50 kVA 5.05 A 53
(13rooms)
1Bed/Stadio to Final Point 2X1C 2.5sqmm PVC 10 m 230 V MCB SP 20 A 0.10 kVA 1.00 0.10 kVA 0.43 A 24
400 V
400 V 1Bed or Stadi
LS3-D1 2Bed (6rooms) 4C 6sqmm XLPE/PVC 70 m 400 V MCCB TPN 15 A 7.00 kVA 0.70 4.90 kVA 7.07 A 53
2Bed to Final Point 2X1C 2.5sqmm PVC 10 m 230 V MCB SP 20 A 0.10 kVA 1.00 0.10 kVA 0.43 A 24
400 V
400 V
LS3-D1 3Bed (3rooms) 4C 6sqmm XLPE/PVC 30 m 400 V MCCB TPN 20 A 9.00 kVA 0.70 6.30 kVA 9.09 A 53
3Bed to Final Point 2X1C 2.5sqmm PVC 10 m 230 V MCB SP 20 A 0.10 kVA 1.00 0.10 kVA 0.43 A 24
400 V
400 V

FS BD 1250 4W Cu-Fe (7-3) 4 m 400 V ACB TPN 1,600 A 635.60 kVA 0.75 476.71 kVA 688.09 A 1600
FS-1 Tap Off Unit (7-3) LS4-D1 4C 70sqmm XLPE/PVC 6 m 400 V MCCB TPN 200 A 132.21 kVA 0.75 99.16 kVA 143.13 A 279
From Transformer to LS4-D1 (FA+FQ+FQ-1+FR+FS+FS-1)
LS4-D1 LS4-C1 4C 4sqmm XLPE/PVC 6 m 400 V MCCB TPN 20 A 8.21 kVA 0.70 5.75 kVA 8.30 A 41
LS4-C1 to Final Point 2X1C 2.5sqmm PVC 35 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V
1Bed or Stadio type
LS4-D1 4C 6sqmm XLPE/PVC 80 m 400 V MCCB TPN 15 A 5.00 kVA 0.70 3.50 kVA 5.05 A 53
(11rooms)
1Bed/Stadio to Final Point 2X1C 2.5sqmm PVC 10 m 230 V MCB SP 20 A 0.10 kVA 1.00 0.10 kVA 0.43 A 24
400 V
400 V 1Bed or Stadi
LS4-D1 2Bed (6rooms) 4C 6sqmm XLPE/PVC 70 m 400 V MCCB TPN 15 A 7.00 kVA 0.70 4.90 kVA 7.07 A 53
2Bed to Final Point 2X1C 2.5sqmm PVC 10 m 230 V MCB SP 20 A 0.10 kVA 1.00 0.10 kVA 0.43 A 24
400 V
400 V
LS4-D1 3Bed (3rooms) 4C 6sqmm XLPE/PVC 30 m 400 V MCCB TPN 20 A 9.00 kVA 0.70 6.30 kVA 9.09 A 53
3Bed to Final Point 2X1C 2.5sqmm PVC 10 m 230 V MCB SP 20 A 0.10 kVA 1.00 0.10 kVA 0.43 A 24
400 V
400 V

FT BD 1250 4W Cu-Fe (7-4) 4 m 400 V ACB TPN 1,600 A 503.39 kVA 0.75 377.55 kVA 544.96 A 1600

Voltage Drop shall be less than 3%. - 104 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

FT-1 Tap Off Unit (7-4) LS5-D1 4C 70sqmm XLPE/PVC 6 m 400 V MCCB TPN 200 A 132.21 kVA 0.75 99.16 kVA 143.13 A 279
From Transformer to LS5-D1 (FA+FQ+FQ-1+FR+FS+FT+FT-1)
LS5-D1 LS5-C1 4C 4sqmm XLPE/PVC 6 m 400 V MCCB TPN 20 A 8.21 kVA 0.70 5.75 kVA 8.30 A 41
LS5-C1 to Final Point 2X1C 2.5sqmm PVC 35 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V

Voltage Drop shall be less than 3%. - 105 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor
1Bed or Stadio type
LS5-D1 4C 6sqmm XLPE/PVC 80 m 400 V MCCB TPN 15 A 5.00 kVA 0.70 3.50 kVA 5.05 A 53
(11rooms)
1Bed/Stadio to Final Point 2X1C 2.5sqmm PVC 10 m 230 V MCB SP 20 A 0.10 kVA 1.00 0.10 kVA 0.43 A 24
400 V
400 V 1Bed or Stadi
LS5-D1 2Bed (6rooms) 4C 6sqmm XLPE/PVC 70 m 400 V MCCB TPN 15 A 7.00 kVA 0.70 4.90 kVA 7.07 A 53
2Bed to Final Point 2X1C 2.5sqmm PVC 10 m 230 V MCB SP 20 A 0.10 kVA 1.00 0.10 kVA 0.43 A 24
400 V
400 V
LS5-D1 3Bed (3rooms) 4C 6sqmm XLPE/PVC 30 m 400 V MCCB TPN 20 A 9.00 kVA 0.70 6.30 kVA 9.09 A 53
3Bed to Final Point 2X1C 2.5sqmm PVC 10 m 230 V MCB SP 20 A 0.10 kVA 1.00 0.10 kVA 0.43 A 24
400 V
400 V

FU BD 1250 4W Cu-Fe (7-5) 19 m 400 V ACB TPN 1,600 A 371.18 kVA 0.75 278.39 kVA 401.83 A 1600
FU-1 Tap Off Unit (7-5) LS6-D1 4C 70sqmm XLPE/PVC 6 m 400 V MCCB TPN 200 A 132.21 kVA 0.75 99.16 kVA 143.13 A 279
From Transformer to LS6-D1 (FA+FQ+FQ-1+FR+FS+FT+FU+FU-1)
LS6-D1 LS6-C1 4C 4sqmm XLPE/PVC 6 m 400 V MCCB TPN 20 A 8.21 kVA 0.70 5.75 kVA 8.30 A 41
LS6-C1 to Final Point 2X1C 2.5sqmm PVC 35 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V
1Bed or Stadio type
LS6-D1 4C 6sqmm XLPE/PVC 80 m 400 V MCCB TPN 15 A 5.00 kVA 0.70 3.50 kVA 5.05 A 53
(11rooms)
1Bed/Stadio to Final Point 2X1C 2.5sqmm PVC 10 m 230 V MCB SP 20 A 0.10 kVA 1.00 0.10 kVA 0.43 A 24
400 V
400 V 1Bed or Stadi
LS6-D1 2Bed (6rooms) 4C 6sqmm XLPE/PVC 70 m 400 V MCCB TPN 15 A 7.00 kVA 0.70 4.90 kVA 7.07 A 53
2Bed to Final Point 2X1C 2.5sqmm PVC 10 m 230 V MCB SP 20 A 0.10 kVA 1.00 0.10 kVA 0.43 A 24
400 V
400 V
LS6-D1 3Bed (3rooms) 4C 6sqmm XLPE/PVC 30 m 400 V MCCB TPN 20 A 9.00 kVA 0.70 6.30 kVA 9.09 A 53
3Bed to Final Point 2X1C 2.5sqmm PVC 10 m 230 V MCB SP 20 A 0.10 kVA 1.00 0.10 kVA 0.43 A 24
400 V
400 V

FV BD 1250 4W Cu-Fe (7-6) 4 m 400 V ACB TPN 1,600 A 238.97 kVA 0.75 179.23 kVA 258.70 A 1600

Voltage Drop shall be less than 3%. - 106 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

FV-1 Tap Off Unit (7-6) LS7-D1 4C 70sqmm XLPE/PVC 6 m 400 V MCCB TPN 200 A 132.21 kVA 0.75 99.16 kVA 143.13 A 279
From Transformer to LS7-D1 (FA+FQ+FQ-1+FR+FS+FT+FU+FV+FV-1)
LS7-D1 LS7-C1 4C 4sqmm XLPE/PVC 6 m 400 V MCCB TPN 20 A 8.21 kVA 0.70 5.75 kVA 8.30 A 41
LS6-C1 to Final Point 2X1C 2.5sqmm PVC 35 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V

Voltage Drop shall be less than 3%. - 107 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor
1Bed or Stadio type
LS7-D1 4C 6sqmm XLPE/PVC 80 m 400 V MCCB TPN 15 A 5.00 kVA 0.70 3.50 kVA 5.05 A 53
(11rooms)
1Bed/Stadio to Final Point 2X1C 2.5sqmm PVC 10 m 230 V MCB SP 20 A 0.10 kVA 1.00 0.10 kVA 0.43 A 24
400 V
400 V 1Bed or Stadi
LS7-D1 2Bed (6rooms) 4C 6sqmm XLPE/PVC 70 m 400 V MCCB TPN 15 A 7.00 kVA 0.70 4.90 kVA 7.07 A 53
2Bed to Final Point 2X1C 2.5sqmm PVC 10 m 230 V MCB SP 20 A 0.10 kVA 1.00 0.10 kVA 0.43 A 24
400 V
400 V
LS7-D1 3Bed (3rooms) 4C 6sqmm XLPE/PVC 30 m 400 V MCCB TPN 20 A 9.00 kVA 0.70 6.30 kVA 9.09 A 53
3Bed to Final Point 2X1C 2.5sqmm PVC 10 m 230 V MCB SP 20 A 0.10 kVA 1.00 0.10 kVA 0.43 A 24
400 V
400 V

FW-1 BD 1250 4W Cu-Fe (7-7) 4 m 400 V ACB TPN 1,600 A 106.76 kVA 0.75 80.07 kVA 115.57 A 1600
FW-1 Tap Off Unit (7-7) LS8-D1 4C 70sqmm XLPE/PVC 6 m 400 V MCCB TPN 200 A 106.76 kVA 0.75 80.07 kVA 115.57 A 279
From Transformer to LS8-D1 (FA+FQ+FQ-1+FR+FS+FT+FU+FV+FW+FW-1)
LS8-D1 LS8-C1 4C 4sqmm XLPE/PVC 6 m 400 V MCCB TPN 20 A 7.76 kVA 0.70 5.43 kVA 7.84 A 41
LS6-C1 to Final Point 2X1C 2.5sqmm PVC 35 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V
1Bed or Stadio type
LS7-D1 4C 6sqmm XLPE/PVC 80 m 400 V MCCB TPN 15 A 5.00 kVA 0.70 3.50 kVA 5.05 A 53
(11rooms)
1Bed/Stadio to Final Point 2X1C 2.5sqmm PVC 10 m 230 V MCB SP 20 A 0.10 kVA 1.00 0.10 kVA 0.43 A 24
400 V
400 V 1Bed or Stadi
LS7-D1 2Bed (6rooms) 4C 6sqmm XLPE/PVC 70 m 400 V MCCB TPN 15 A 7.00 kVA 0.70 4.90 kVA 7.07 A 53
2Bed to Final Point 2X1C 2.5sqmm PVC 10 m 230 V MCB SP 20 A 0.10 kVA 1.00 0.10 kVA 0.43 A 24
400 V
400 V
LS7-D1 3Bed (3rooms) 4C 6sqmm XLPE/PVC 30 m 400 V MCCB TPN 20 A 9.00 kVA 0.70 6.30 kVA 9.09 A 53
3Bed to Final Point 2X1C 2.5sqmm PVC 10 m 230 V MCB SP 20 A 0.10 kVA 1.00 0.10 kVA 0.43 A 24
400 V
400 V
0.00 0.00 0
HOTEL 空調盤 0.00 0.00 0

Voltage Drop shall be less than 3%. - 108 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

4 ST-3 P-H-B2-04 4C 35sqmm XLPE/PVC 197 m 400 V MCCB TPN 50 A 26.88 kVA 0.75 20.16 kVA 29.10 A 176
From Transformer to P-H-B2-04
P-H-B2-04 P-H-B2-03 3C 6sqmm XLPE/PVC 5 m 400 V MCCB 3P 30 A 13.44 kVA 0.75 10.08 kVA 14.55 A 53
To Final Point (M Scope) 3C 4sqmm XLPE/PVC 30 m 400 V MCCB 3P 20 A 6.72 kVA 1.00 6.72 kVA 9.70 A 41
400 V
P-H-B2-04 P-H-B2-05 3C 6sqmm XLPE/PVC 5 m 400 V MCCB 3P 30 A 13.44 kVA 0.75 10.08 kVA 14.55 A 53
To Final Point (M Scope) 3C 4sqmm XLPE/PVC 30 m 400 V MCCB 3P 20 A 6.72 kVA 1.00 6.72 kVA 9.70 A 41
400 V

Voltage Drop shall be less than 3%. - 109 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

5 ST-3 P-H-B2-07 4C 50sqmm XLPE/PVC 169 m 400 V MCCB TPN 125 A 59.31 kVA 0.75 44.48 kVA 64.20 A 215
From Transformer to P-H-B2-07
P-H-B2-07 P-H-B2-06 3C 6sqmm XLPE/PVC 5 m 400 V MCCB 3P 30 A 13.44 kVA 0.75 10.08 kVA 14.55 A 53
To Final Point (M Scope) 3C 4sqmm XLPE/PVC 30 m 400 V MCCB 3P 20 A 6.72 kVA 1.00 6.72 kVA 9.70 A 41
400 V
P-H-B2-07 P-H-B2-08 4C 35sqmm XLPE/PVC 5 m 400 V MCCB 3P 75 A 37.42 kVA 0.75 28.07 kVA 40.52 A 176
To Final Point (M Scope) 3C 16sqmm XLPE/PVC 30 m 400 V MCCB 3P 60 A 18.70 kVA 1.00 18.70 kVA 26.99 A 85
400 V
P-H-B2-07 P-H-B2-09 3C 6sqmm XLPE/PVC 5 m 400 V MCCB 3P 30 A 8.45 kVA 0.75 6.34 kVA 9.15 A 53
To Final Point (M Scope) 3C 2.5sqmm XLPE/PVC 30 m 400 V MCCB 3P 15 A 4.22 kVA 1.00 4.22 kVA 6.09 A 31
400 V

6 ST-3 P-H-B2-11 4C 35sqmm XLPE/PVC 183 m 400 V MCCB TPN 75 A 40.32 kVA 0.75 30.24 kVA 43.65 A 176
From Transformer to P-H-B2-11
P-H-B2-11 P-H-B2-10 3C 6sqmm XLPE/PVC 5 m 400 V MCCB 3P 30 A 13.44 kVA 0.75 10.08 kVA 14.55 A 53
To Final Point (M Scope) 3C 4sqmm XLPE/PVC 30 m 400 V MCCB 3P 20 A 6.72 kVA 1.00 6.72 kVA 9.70 A 41
400 V
P-H-B2-11 P-H-B2-12 3C 6sqmm XLPE/PVC 5 m 400 V MCCB 3P 30 A 13.44 kVA 0.75 10.08 kVA 14.55 A 53
To Final Point (M Scope) 3C 4sqmm XLPE/PVC 30 m 400 V MCCB 3P 15 A 6.72 kVA 1.00 6.72 kVA 9.70 A 41
400 V
P-H-B2-11 P-H-B2-13 3C 6sqmm XLPE/PVC 5 m 400 V MCCB 3P 30 A 13.44 kVA 1.00 13.44 kVA 19.40 A 53
To Final Point (M Scope) 3C 4sqmm XLPE/PVC 30 m 400 V MCCB 3P 20 A 6.72 kVA 1.00 6.72 kVA 9.70 A 41
400 V

7 ST-3 P-H-B2-18 4C 70sqmm XLPE/PVC 128 m 400 V MCCB TPN 175 A 93.30 kVA 0.75 69.98 kVA 101.01 A 279
From Transformer to P-H-B2-18
P-H-B2-18 P-H-B2-15 3C 6sqmm XLPE/PVC 5 m 400 V MCCB 3P 30 A 5.04 kVA 0.75 3.78 kVA 5.46 A 53
To Final Point (M Scope) 3C 2.5sqmm XLPE/PVC 15 m 400 V MCCB 3P 15 A 0.90 kVA 1.00 0.90 kVA 1.30 A 31
400 V
P-H-B2-18 P-H-B2-16 3C 6sqmm XLPE/PVC 5 m 400 V MCCB 3P 30 A 13.44 kVA 0.75 10.08 kVA 14.55 A 53
To Final Point (M Scope) 3C 4sqmm XLPE/PVC 30 m 400 V MCCB 3P 15 A 6.72 kVA 1.00 6.72 kVA 9.70 A 41
400 V
P-H-B2-18 P-H-B2-17 3C 35sqmm XLPE/PVC 5 m 400 V MCCB 3P 100 A 37.41 kVA 1.00 37.41 kVA 54.00 A 176
To Final Point (M Scope) 3C 16sqmm XLPE/PVC 30 m 400 V MCCB 3P 60 A 18.71 kVA 1.00 18.71 kVA 27.01 A 85
400 V

Voltage Drop shall be less than 3%. - 110 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

P-H-B2-18 P-H-B2-19 3C 35sqmm XLPE/PVC 5 m 400 V MCCB 3P 100 A 37.41 kVA 1.00 37.41 kVA 54.00 A 176
To Final Point (M Scope) 3C 16sqmm XLPE/PVC 30 m 400 V MCCB 3P 60 A 18.71 kVA 1.00 18.71 kVA 27.01 A 85
400 V

Voltage Drop shall be less than 3%. - 111 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

8 ST-3 P-H-B2-23 4C 50sqmm XLPE/PVC 102 m 400 V MCCB TPN 175 A 81.06 kVA 0.75 60.80 kVA 87.76 A 215
From Transformer to P-H-B2-23
P-H-B2-23 P-H-B2-20 3C 50sqmm XLPE/PVC 5 m 400 V MCCB 3P 125 A 56.12 kVA 0.75 42.09 kVA 60.75 A 215
To Final Point (M Scope) 3C 16sqmm XLPE/PVC 15 m 400 V MCCB 3P 20 A 18.71 kVA 1.00 18.71 kVA 27.01 A 85
400 V
P-H-B2-23 P-H-B2-21(STANDBY) 3C 50sqmm XLPE/PVC 5 m 400 V MCCB 3P 125 A 56.12 kVA 0.75 42.09 kVA 60.75 A 215
To Final Point (M Scope) 3C 16sqmm XLPE/PVC 30 m 400 V MCCB 3P 20 A 18.71 kVA 1.00 18.71 kVA 27.01 A 85
400 V
P-H-B2-23 P-H-B2-22 3C 16sqmm XLPE/PVC 5 m 400 V MCCB 3P 60 A 24.94 kVA 1.00 24.94 kVA 36.00 A 85
To Final Point (M Scope) 3C 10sqmm XLPE/PVC 30 m 400 V MCCB 3P 40 A 12.47 kVA 1.00 12.47 kVA 18.00 A 73
400 V

9 ST-3 P-H-B2-26 4C 16sqmm XLPE/PVC 88 m 400 V MCCB TPN 50 A 26.88 kVA 0.75 20.16 kVA 29.10 A 85
From Transformer to P-H-B2-26
P-H-B2-26 P-H-B2-24 3C 6sqmm XLPE/PVC 5 m 400 V MCCB 3P 30 A 13.44 kVA 0.75 10.08 kVA 14.55 A 53
To Final Point (M Scope) 3C 4sqmm XLPE/PVC 15 m 400 V MCCB 3P 15 A 6.72 kVA 1.00 6.72 kVA 9.70 A 41
400 V
P-H-B2-26 P-H-B2-25 3C 6sqmm XLPE/PVC 5 m 400 V MCCB 3P 30 A 13.44 kVA 0.75 10.08 kVA 14.55 A 53
To Final Point (M Scope) 3C 4sqmm XLPE/PVC 30 m 400 V MCCB 3P 15 A 6.72 kVA 1.00 6.72 kVA 9.70 A 41
400 V

10 ST-3 P-H-2-01 4x1C 150sqmm XLPE/PVC 70 m 400 V MCCB TPN 350 A 147.32 kVA 0.75 110.49 kVA 159.48 A 461
To Final Point (M Scope) 3C 95sqmm XLPE/PVC 30 m 400 V MCCB 3P 175 A 58.00 kVA 1.00 58.00 kVA 83.72 A 341
400 V
11 ST-3 P-H-2-02 4C 4sqmm XLPE/PVC 191 m 400 V MCCB TPN 20 A 2.98 kVA 0.75 2.24 kVA 3.23 A 41
To Final Point (M Scope) 4C 2.5sqmm XLPE/PVC 10 m 400 V MCCB 3P 15 A 2.98 kVA 1.00 2.98 kVA 4.30 A 31
400 V
12 ST-3 P-H-2-03 4C 50sqmm XLPE/PVC 178 m 400 V MCCB TPN 100 A 56.53 kVA 0.75 42.40 kVA 61.20 A 215
To Final Point (M Scope) 3C 10sqmm XLPE/PVC 20 m 400 V MCCB 3P 40 A 12.47 kVA 1.00 12.47 kVA 18.00 A 73
400 V
13 ST-3 P-H-3-01 4C 50sqmm XLPE/PVC 83 m 400 V MCCB TPN 150 A 78.35 kVA 0.75 58.76 kVA 84.82 A 215
To Final Point (M Scope) 3C 6sqmm XLPE/PVC 20 m 400 V MCCB 3P 30 A 9.70 kVA 1.00 9.70 kVA 14.00 A 53
400 V

HOTEL 厨房盤 0.00 0.00 0

Voltage Drop shall be less than 3%. - 112 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

14 ST-3 LHG-K1(Pre Kitchen) 4C 70sqmm XLPE/PVC 220 m 400 V MCCB TPN 150 A 84.02 kVA 0.75 63.02 kVA 90.96 A 279
LHG-K1 to Final Point 3C 16sqmm XLPE/PVC 20 m 230 V MCCB sp 20 A 0.74 kVA 1.00 0.74 kVA 3.22 A 85
400 V
400 V

15 ST-3 LHG-K2(Baker) 4C 95sqmm XLPE/PVC 194 m 400 V MCCB TPN 225 A 120.07 kVA 0.75 90.05 kVA 129.98 A 341

LHG-K2 to Final Point 3C 16sqmm XLPE/PVC 20 m 230 V MCCB sp 20 A 3.00 kVA 1.00 3.00 kVA 13.04 A 85
400 V
400 V

Voltage Drop shall be less than 3%. - 113 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor
16 ST-3 LHG-K31 4C 70sqmm XLPE/PVC 114 m 400 V MCCB TPN 175 A 95.61 kVA 0.75 71.71 kVA 103.51 A 279
LHG-K31 to Final Point 3C 6sqmm XLPE/PVC 20 m 230 V MCCB sp 20 A 3.80 kVA 1.00 3.80 kVA 16.52 A 53
400 V
400 V
17 ST-3 LHG-K31 3C 120+1C 70sqmm XLPE/PVC 114 m 400 V MCCB TPN 250 A 141.87 kVA 0.75 106.40 kVA 153.58 A 398
LHG-K31 to Final Point 4C 25sqmm XLPE/PVC 20 m 400 V MCCB TPN 75 A 33.90 kVA 1.00 33.90 kVA 48.93 A 140
400 V
18 ST-3 LHG-K32 4C 16sqmm XLPE/PVC 90 m 400 V MCCB TPN 40 A 24.07 kVA 0.75 18.05 kVA 26.05 A 85
LHG-K32 to Final Point 2X1C 2.5sqmm PVC 20 m 230 V MCB SP 20 A 0.90 kVA 1.00 0.90 kVA 3.91 A 24
400 V
400 V
19 ST-3 LHG-K4(Lounge) 4C 50sqmm XLPE/PVC 180 m 400 V MCCB TPN 100 A 55.96 kVA 0.75 41.97 kVA 60.58 A 215
LHG-K4 to Final Point 4C 2.5sqmm XLPE/PVC 20 m 400 V MCCB TPN 20 A 6.80 kVA 1.00 6.80 kVA 9.82 A 31
400 V
20 ST-3 LHM-K1(Canteen) 4C 25sqmm XLPE/PVC 115 m 400 V MCCB TPN 75 A 34.90 kVA 0.75 26.18 kVA 37.79 A 140
LHG-K1 to Final Point 4C 4sqmm XLPE/PVC 20 m 400 V MCCB TPN 20 A 10.10 kVA 1.00 10.10 kVA 14.58 A 41
400 V
21 ST-3 LH1-K1(JPN Rest.) 3C 185+1C 95sqmm XLPE/PVC 156 m 400 V MCCB TPN 400 A 210.33 kVA 0.75 157.75 kVA 227.70 A 530
LH1-K1 to Final Point 3C 10sqmm XLPE/PVC 20 m 230 V MCCB sp 20 A 3.40 kVA 1.00 3.40 kVA 14.78 A 73
400 V
400 V
22 ST-3 LH1-K1(JPN Rest.) 4C 50sqmm XLPE/PVC 156 m 400 V MCCB TPN 125 A 68.68 kVA 0.75 51.51 kVA 74.35 A 215
LH1-K1 to Final Point 4C 25sqmm XLPE/PVC 20 m 400 V MCCB TPN 75 A 33.90 kVA 1.00 33.90 kVA 48.93 A 140
400 V
23 ST-3 LH1-K2(Banquet Kitchen) 4C 35sqmm XLPE/PVC 161 m 400 V MCCB TPN 100 A 49.37 kVA 0.75 37.03 kVA 53.45 A 176
LH1-K2 to Final Point 3C 16sqmm XLPE/PVC 20 m 230 V MCCB sp 20 A 5.60 kVA 1.00 5.60 kVA 24.35 A 85
400 V
400 V
24 ST-3 LH1-K2(Banquet Kitchen) 3C 150+1C 70sqmm XLPE/PVC 161 m 400 V MCCB TPN 350 A 188.94 kVA 0.75 141.71 kVA 204.55 A 461
LH1-K2 to Final Point 4C 25sqmm XLPE/PVC 20 m 400 V MCCB TPN 60 A 36.50 kVA 1.00 36.50 kVA 52.68 A 140
400 V
25 ST-3 LH2-K1(GYM) 4C 95sqmm XLPE/PVC 171 m 400 V MCCB TPN 150 A 76.95 kVA 0.75 57.71 kVA 83.30 A 341
LH2-K1 to Final Point 2X1C 2.5sqmm PVC 20 m 230 V MCB SP 20 A 1.50 kVA 1.00 1.50 kVA 6.52 A 24
400 V
400 V
26 ST-3 LH8-K1(Lounge) 4C 70sqmm XLPE/PVC 203 m 400 V MCCB TPN 150 A 82.89 kVA 0.75 62.17 kVA 89.74 A 279

Voltage Drop shall be less than 3%. - 114 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

LH8-K1 to Final Point 4C 10sqmm XLPE/PVC 20 m 400 V MCCB TPN 30 A 13.00 kVA 1.00 13.00 kVA 18.76 A 73
400 V
27 ST-3 LHB1-L1 4C 70sqmm XLPE/PVC 164 m 400 V MCCB TPN 225 A 103.07 kVA 0.75 77.30 kVA 111.58 A 279
LHB1-L1 to Final Point 4C 25sqmm XLPE/PVC 20 m 400 V MCCB TPN 100 A 12.20 kVA 1.00 12.20 kVA 17.61 A 140
400 V

Voltage Drop shall be less than 3%. - 115 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

CA ST-3 LHM-D1 4x1C 300sqmm XLPE/PVC 35 m 400 V MCCB TPN 600 A 391.40 kVA 0.75 293.55 kVA 423.72 A 730
From Transformer to LHM-D1 (FA+CA)
LHM-D1 LHG-T2 4C 35sqmm XLPE/PVC 21 m 400 V MCCB TPN 125 A 84.00 kVA 0.75 63.00 kVA 90.94 A 176
LHG-T2 to Final Point 2X1C 2.5sqmm PVC 60 m 230 V MCB SP 20 A 0.10 kVA 1.00 0.10 kVA 0.43 A 24
400 V
400 V
LHM-D1 LHG-T3 4C 4sqmm XLPE/PVC 29 m 400 V MCCB TPN 30 A 19.00 kVA 0.75 14.25 kVA 20.57 A 41
LHG-T3 to Final Point 2X1C 2.5sqmm PVC 60 m 230 V MCB SP 20 A 0.10 kVA 1.00 0.10 kVA 0.43 A 24
400 V
400 V
LHM-D1 LHG-T4 4C 6sqmm XLPE/PVC 31 m 400 V MCCB TPN 40 A 21.80 kVA 0.75 16.35 kVA 23.60 A 53
LHG-T4 to Final Point 2X1C 2.5sqmm PVC 60 m 230 V MCB SP 20 A 0.10 kVA 1.00 0.10 kVA 0.43 A 24
400 V
400 V
LHM-D1 LHG-T5 4C 35sqmm XLPE/PVC 34 m 400 V MCCB TPN 150 A 87.50 kVA 0.75 65.63 kVA 94.73 A 176
LHG-T5 to Final Point 2X1C 2.5sqmm PVC 60 m 230 V MCB SP 20 A 0.10 kVA 1.00 0.10 kVA 0.43 A 24
400 V
400 V
LHM-D1 LHG-T6 4C 50sqmm XLPE/PVC 37 m 400 V MCCB TPN 175 A 119.50 kVA 0.75 89.63 kVA 129.37 A 215
LHG-T6 to Final Point 2X1C 2.5sqmm PVC 60 m 230 V MCB SP 20 A 0.10 kVA 1.00 0.10 kVA 0.43 A 24
400 V
400 V
LHM-D1 LHG-T7 4C 10sqmm XLPE/PVC 42 m 400 V MCCB TPN 50 A 27.80 kVA 0.75 20.85 kVA 30.10 A 73
LHG-T7 to Final Point 2X1C 2.5sqmm PVC 60 m 230 V MCB SP 20 A 0.10 kVA 1.00 0.10 kVA 0.43 A 24
400 V
400 V
LHM-D1 LHG-T8 4C 10sqmm XLPE/PVC 60 m 400 V MCCB TPN 30 A 19.30 kVA 0.75 14.48 kVA 20.90 A 73
LHG-T8 to Final Point 2X1C 2.5sqmm PVC 60 m 230 V MCB SP 20 A 0.10 kVA 1.00 0.10 kVA 0.43 A 24
400 V
400 V
LHM-D1 LHG-T9 4C 10sqmm XLPE/PVC 75 m 400 V MCCB TPN 20 A 12.50 kVA 0.75 9.38 kVA 13.54 A 73
LHG-T9 to Final Point 2X1C 2.5sqmm PVC 60 m 230 V MCB SP 20 A 1.50 kVA 0.40 0.60 kVA 2.61 A 24
(S.S.O) 400 V
400 V
0.00 0.00 0

Voltage Drop shall be less than 3%. - 116 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

CB ST-3 LHB1-D1 4C 95sqmm XLPE/PVC 70 m 400 V MCCB TPN 150 A 80.62 kVA 0.75 60.47 kVA 87.28 A 341
From Transformer to LHB1-D1 (FA+CB)
LHB1-D1 LHB2-P1 4C 4sqmm XLPE/PVC 39 m 400 V MCCB TPN 20 A 12.30 kVA 0.75 9.23 kVA 13.32 A 41
LHB2-P1 to Final Point 2X1C 2.5sqmm PVC 30 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V

Voltage Drop shall be less than 3%. - 117 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

400 V
LHB1-D1 LHB1-P1 4C 4sqmm XLPE/PVC 31 m 400 V MCCB TPN 20 A 8.29 kVA 0.75 6.22 kVA 8.98 A 41
LHB1-P1 to Final Point 2X1C 2.5sqmm PVC 30 m 230 V MCB SP 20 A 0.30 kVA 0.70 0.21 kVA 0.91 A 24
400 V
400 V
① LHB1-D1 P-H-B2-01 4C 16sqmm XLPE/PVC 73 m 400 V MCCB 3P 50 A 19.40 kVA 0.75 14.55 kVA 21.00 A 85
To Final Point (M Scope) 3C 6sqmm XLPE/PVC 30 m 400 V MCCB 3P 30 A 9.70 kVA 1.00 9.70 kVA 14.00 A 53
400 V
  LHB1-D1 P-H-B2-02 4C 16sqmm XLPE/PVC 114 m 400 V MCCB 3P 30 A 13.44 kVA 0.75 10.08 kVA 14.55 A 85
To Final Point (M Scope) 3C 4sqmm XLPE/PVC 30 m 400 V MCCB 3P 20 A 6.72 kVA 1.00 6.72 kVA 9.70 A 41
400 V
LHB1-D1 P-H-B2-27 4C 16sqmm XLPE/PVC 89 m 400 V MCCB 3P 30 A 13.44 kVA 0.75 10.08 kVA 14.55 A 85
To Final Point (M Scope) 3C 4sqmm XLPE/PVC 30 m 400 V MCCB 3P 20 A 6.72 kVA 1.00 6.72 kVA 9.70 A 41
400 V
LHB1-D1 Well pump-5 4C 25sqmm XLPE/PVC 22 m 400 V MCCB 3P 75 A 13.75 kVA 0.75 10.31 kVA 14.88 A 140
400 V Well P
0.00 0.00 0
CC ST-3 LHB1-D2 4C 95sqmm XLPE/PVC 147 m 400 V MCCB TPN 125 A 66.41 kVA 0.75 49.81 kVA 71.90 A 341
From Transformer to LHB1-D2 (FA+CC)
LHB1-D2 LHB2-P2 4C 4sqmm XLPE/PVC 19 m 400 V MCCB TPN 30 A 14.11 kVA 0.75 10.58 kVA 15.27 A 41
LHB2-P2 to Final Point 2X1C 2.5sqmm PVC 30 m 230 V MCB SP 20 A 1.50 kVA 0.70 1.05 kVA 4.57 A 24
400 V
400 V
LHB1-D2 LHB1-P2 4C 4sqmm XLPE/PVC 31 m 400 V MCCB TPN 20 A 9.65 kVA 0.75 7.24 kVA 10.45 A 41
LHB1-P2 to Final Point 2X1C 2.5sqmm PVC 30 m 230 V MCB SP 20 A 1.20 kVA 0.70 0.84 kVA 3.65 A 24
400 V
400 V
LHB1-D2 LHB1-C1 4C 4sqmm XLPE/PVC 6 m 400 V MCCB TPN 30 A 15.15 kVA 0.75 11.36 kVA 16.40 A 41
LHB1-C1 to Final Point 2X1C 2.5sqmm PVC 30 m 230 V MCB SP 20 A 3.00 kVA 0.50 1.50 kVA 6.52 A 24
400 V
400 V
LHB1-D2 Well pump-3 4C 25sqmm XLPE/PVC 46 m 400 V MCCB 3P 75 A 13.75 kVA 0.75 10.31 kVA 14.88 A 140
400 V Well P
LHB1-D2 Well pump-4 4C 25sqmm XLPE/PVC 45 m 400 V MCCB 3P 75 A 13.75 kVA 0.75 10.31 kVA 14.88 A 140
400 V Well P

Voltage Drop shall be less than 3%. - 118 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

0.00 0.00 0
CD ST-3 LHG-D1 4C 70sqmm XLPE/PVC 70 m 400 V MCCB TPN 200 A 95.44 kVA 0.75 71.58 kVA 103.32 A 279
From Transformer to LHG-D1 (FA+CD)
LHG-D1 LHG-C1 4C 16sqmm XLPE/PVC 20 m 400 V MCCB TPN 50 A 31.93 kVA 0.75 23.95 kVA 34.57 A 85
LHG-C1 to Final Point 2X1C 2.5sqmm PVC 30 m 230 V MCB SP 20 A 1.20 kVA 0.70 0.84 kVA 3.65 A 24
400 V
400 V
LHG-D1 P-H-G-01 4C 16sqmm XLPE/PVC 11 m 400 V MCCB 3P 60 A 21.63 kVA 0.75 16.22 kVA 23.41 A 85
To Final Point (M Scope) 3C 6sqmm XLPE/PVC 10 m 400 V MCCB 3P 40 A 12.47 kVA 1.00 12.47 kVA 18.00 A 53
400 V

Voltage Drop shall be less than 3%. - 119 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

LHG-D1 P-H-G-02 4C 16sqmm XLPE/PVC 11 m 400 V MCCB 3P 60 A 28.13 kVA 0.75 21.10 kVA 30.46 A 85
To Final Point (M Scope) 3C 16sqmm XLPE/PVC 10 m 400 V MCCB 3P 60 A 28.13 kVA 1.00 28.13 kVA 40.60 A 85
400 V
LHB1-D2 Well pump-2 4C 25sqmm XLPE/PVC 11 m 400 V MCCB 3P 75 A 13.75 kVA 0.75 10.31 kVA 14.88 A 140
400 V Well P
0.00 0.00 0
CE ST-3 LHG-C2 3C 150+1C 70sqmm XLPE/PVC 150 m 400 V MCCB TPN 175 A 104.33 kVA 0.75 78.25 kVA 112.95 A 461
LHG-C2 to Final Point 2X1C 2.5sqmm PVC 30 m 230 V MCB SP 20 A 0.99 kVA 0.70 0.69 kVA 3.00 A 24
400 V
400 V
0.00 0.00 0
CF ST-3 LHM-D2 4C 25sqmm XLPE/PVC 35 m 400 V MCCB TPN 100 A 46.05 kVA 0.75 34.54 kVA 49.86 A 140
From Transformer to LHG-D1 (FA+CF)
LHM-D2 LHM-C1 4C 6sqmm XLPE/PVC 7 m 400 V MCCB TPN 40 A 20.14 kVA 0.75 15.11 kVA 21.81 A 53
LHM-C1 to Final Point 2X1C 2.5sqmm PVC 30 m 230 V MCB SP 20 A 3.00 kVA 0.70 2.10 kVA 9.13 A 24
400 V
400 V
LHM-D2 P-H-M1-01 4C 10sqmm XLPE/PVC 42 m 400 V MCCB 3P 30 A 13.44 kVA 0.75 10.08 kVA 14.55 A 73
To Final Point (M Scope) 3C 4sqmm XLPE/PVC 15 m 400 V MCCB 3P 20 A 6.72 kVA 1.00 6.72 kVA 9.70 A 41
400 V
LHM-D2 P-H-GF-06 4C 16sqmm XLPE/PVC 86 m 400 V MCCB 3P 30 A 12.47 kVA 1.00 12.47 kVA 18.00 A 85
To Final Point (M Scope) 3C 6sqmm XLPE/PVC 15 m 400 V MCCB 3P 30 A 12.47 kVA 1.00 12.47 kVA 18.00 A 53
400 V
0.00 0.00 0
CG ST-3 LHM-D3 4C 70sqmm XLPE/PVC 146 m 400 V MCCB TPN 150 A 66.64 kVA 0.75 49.98 kVA 72.14 A 279
From Transformer to LHM-D3 (FA+CG)
LHM-D3 LHM-C2 4C 10sqmm XLPE/PVC 7 m 400 V MCCB TPN 60 A 34.01 kVA 1.00 34.01 kVA 49.09 A 73
LHM-C2 to Final Point 2X1C 2.5sqmm PVC 30 m 230 V MCB SP 20 A 1.50 kVA 0.70 1.05 kVA 4.57 A 24
400 V
400 V
LHM-D3 P-H-GF-03 4C 35sqmm XLPE/PVC 69 m 400 V MCCB 3P 75 A 25.91 kVA 1.00 25.91 kVA 37.40 A 176
To Final Point (M Scope) 3C 16sqmm XLPE/PVC 15 m 400 V MCCB 3P 60 A 18.71 kVA 1.00 18.71 kVA 27.01 A 85
400 V
LHM-D3 P-H-GF-04 4C 6sqmm XLPE/PVC 35 m 400 V MCCB 3P 30 A 6.72 kVA 1.00 6.72 kVA 9.70 A 53
To Final Point (M Scope) 3C 4sqmm XLPE/PVC 15 m 400 V MCCB 3P 20 A 6.72 kVA 1.00 6.72 kVA 9.70 A 41

Voltage Drop shall be less than 3%. - 120 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

400 V
0.00 0.00 0
CH ST-3 LH1-C2 4C 16sqmm XLPE/PVC 154 m 400 V MCCB TPN 40 A 18.92 kVA 0.75 14.19 kVA 20.48 A 85
LH1-C2 to Final Point 2X1C 2.5sqmm PVC 30 m 230 V MCB SP 20 A 1.50 kVA 0.70 1.05 kVA 4.57 A 24
400 V
400 V
0.00 0.00 0

Voltage Drop shall be less than 3%. - 121 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

CI ST-3 LH1-D1 4x1C 185sqmm XLPE/PVC 43 m 400 V MCCB TPN 400 A 207.01 kVA 0.75 155.26 kVA 224.11 A 530
From Transformer to LH1-D1 (FA+CI)
LH1-D1 LH1-C1 4C 25sqmm XLPE/PVC 9 m 400 V MCCB TPN 100 A 53.85 kVA 1.00 53.85 kVA 77.73 A 140
LH1-C1 to Final Point 4C 2.5sqmm XLPE/PVC 30 m 400 V MCCB TPN 20 A 6.80 kVA 1.00 6.80 kVA 9.82 A 31
400 V
LH1-D1 LH1-C3 4C 70sqmm XLPE/PVC 97 m 400 V MCCB TPN 125 A 73.16 kVA 1.00 73.16 kVA 105.60 A 279
LH1-C3 to Final Point 4C 2.5sqmm XLPE/PVC 30 m 400 V MCCB TPN 20 A 1.04 kVA 1.00 1.04 kVA 1.50 A 31
400 V
LH1-D1 Event panel 1 4C 16sqmm XLPE/PVC 43 m 400 V MCCB TPN 40 A 25.00 kVA 1.00 25.00 kVA 36.09 A 85
400 V Event
LH1-D1 Event panel 2 4C 16sqmm XLPE/PVC 70 m 400 V MCCB TPN 40 A 25.00 kVA 1.00 25.00 kVA 36.09 A 85
400 V Event
LH1-D1 Event panel 3 4C 10sqmm XLPE/PVC 71 m 400 V MCCB TPN 20 A 10.00 kVA 1.00 10.00 kVA 14.43 A 73
400 V Event
LH1-D1 Event panel 4 4C 10sqmm XLPE/PVC 78 m 400 V MCCB TPN 20 A 10.00 kVA 1.00 10.00 kVA 14.43 A 73
400 V Event
LH1-D1 Event panel 5 4C 10sqmm XLPE/PVC 87 m 400 V MCCB TPN 20 A 10.00 kVA 1.00 10.00 kVA 14.43 A 73
400 V Event

CJ ST-3 LH1-D1 4x1C 185sqmm XLPE/PVC 43 m 400 V MCCB TPN 400 A 217.52 kVA 0.75 163.14 kVA 235.48 A 530
From Transformer to LH1-D1 (FA+CJ)
LH1-D1 AV power panel G1 4C 50sqmm XLPE/PVC 43 m 400 V MCCB TPN 125 A 72.40 kVA 1.00 72.40 kVA 104.50 A 215
G1 to Final Point 4C 6sqmm XLPE/PVC 30 m 400 V MCCB TPN 20 A 6.00 kVA 1.00 6.00 kVA 8.66 A 53
400 V AV power p
LH1-D1 AV power panel G2 4C 50sqmm XLPE/PVC 70 m 400 V MCCB TPN 125 A 72.40 kVA 1.00 72.40 kVA 104.50 A 215
G2 to Final Point 4C 6sqmm XLPE/PVC 30 m 400 V MCCB TPN 20 A 6.00 kVA 1.00 6.00 kVA 8.66 A 53
400 V AV power p
LH1-D1 AV power panel F1 4C 16sqmm XLPE/PVC 71 m 400 V MCCB TPN 40 A 22.00 kVA 1.00 22.00 kVA 31.76 A 85
F1 to Final Point 4C 6sqmm XLPE/PVC 30 m 400 V MCCB TPN 20 A 6.00 kVA 1.00 6.00 kVA 8.66 A 53
400 V AV power p
LH1-D1 AV power panel F2 4C 16sqmm XLPE/PVC 78 m 400 V MCCB TPN 40 A 22.00 kVA 1.00 22.00 kVA 31.76 A 85
F2 to Final Point 4C 6sqmm XLPE/PVC 30 m 400 V MCCB TPN 20 A 6.00 kVA 1.00 6.00 kVA 8.66 A 53
400 V AV power p
LH1-D1 AV power panel F3 4C 16sqmm XLPE/PVC 87 m 400 V MCCB TPN 40 A 22.00 kVA 1.00 22.00 kVA 31.76 A 85
F3 to Final Point 4C 6sqmm XLPE/PVC 30 m 400 V MCCB TPN 20 A 6.00 kVA 1.00 6.00 kVA 8.66 A 53

Voltage Drop shall be less than 3%. - 122 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

400 V AV power p
LH1-D1 P-H-1-01 4C 4sqmm XLPE/PVC 40 m 400 V MCCB 3P 20 A 6.72 kVA 1.00 6.72 kVA 9.70 A 41
To Final Point (M Scope) 3C 4sqmm XLPE/PVC 15 m 400 V MCCB 3P 20 A 6.72 kVA 1.00 6.72 kVA 9.70 A 41
400 V
0.00 0.00 0

Voltage Drop shall be less than 3%. - 123 / 159 -


PROJECT : YCP
PROPOSED VOLTAGE DROP CALCULATION SHEET (UP TO FINAL POINT)

Demand
Cable Carry
S/N From To Type Of Cable Q'ty Voltage Breaker Size Capacity (KVA) Capacity (KVA) Ampere (A)
Cap (A)
Factor

38 ST-3 P-WT-B1-03 4C 95sqmm XLPE/PVC 165 m 400 V MCCB TPN 200 A 82.88 kVA 0.75 62.16 kVA 89.72 A 341
400 V P-WT
39 ST-3 P-WT-B1-05 4C 35sqmm XLPE/PVC 165 m 400 V MCCB TPN 125 A 33.25 kVA 0.75 24.94 kVA 36.00 A 176
400 V P-WT
40 ST-3 P-WT-B1-06 4C 6sqmm XLPE/PVC 165 m 400 V MCCB TPN 40 A 5.00 kVA 0.75 3.75 kVA 5.41 A 53
400 V P-WT
41 ST-3 P-WT-1F-04 4C 6sqmm XLPE/PVC 166 m 400 V MCCB TPN 30 A 2.75 kVA 0.75 2.06 kVA 2.97 A 53
400 V
42 ST-3 P-WT-2F-04 4C 16sqmm XLPE/PVC 200 m 400 V MCCB TPN 60 A 16.38 kVA 0.75 12.28 kVA 17.73 A 85
400 V
43 ST-3 Server UPS(MF) 4C 95sqmm XLPE/PVC 184 m 400 V MCCB TPN 150 A 100.00 kVA 0.75 75.00 kVA 108.26 A 341
400 V Server U
0.00 0.00 0
44 ST-3 P-H-1-02 4C 35sqmm XLPE/PVC 135 m 400 V MCCB TPN 125 A 40.65 kVA 1.00 40.65 kVA 58.67 A 176
To Final Point (M Scope) 3C 6sqmm XLPE/PVC 15 m 400 V MCCB 3P 30 A 14.00 kVA 1.00 14.00 kVA 20.21 A 53
400 V
0.00 0.00 0
0.00 0.00 0

Voltage Drop shall be less than 3%. - 124 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage Drop Total Voltage
Judge Factor Judge Voltage Drop (v) Judge
Cap (A) Cap (A) (v) Drop (%)
mV/A/m

0 0.00

A OK 1.00 4,000 A OK 0.02 2.73 V 2.73 V OK V%=0.68%


0 0.00
A OK 0.85 1,862 A OK 0.07 7.97 V 10.70 V OK V%=1.99%
A OK 1.00 1,250 A OK 0.07 0.18 V 10.88 V OK V%=0.05%
A OK 0.85 183 A OK 0.87 0.51 V 11.39 V OK V%=0.13%
Total Voltage Drop 11.39 V
A OK 0.85 35 A OK 10.00 1.50 V 12.38 V OK V%=0.38%
A OK 0.85 35 A OK 10.00 1.54 V 12.57 V OK V%=0.39%
P-H-GF-05 : Final Point Voltage Drop (Less than 4%) 14.43 V V%= 3.61%
A OK 0.85 35 A OK 10.00 1.82 V 1.82 V OK V%=0.46%
A OK 0.85 20 A OK 18.00 0.08 V 10.96 V ###
Convert to 3Phase 0.14 V
Standard : Final Point Voltage Drop (Less than 4%) 13.35 V V%= 3.34%
A OK 0.85 45 A OK 6.80 2.47 V 2.47 V OK V%=0.62%
A OK 0.85 20 A OK 18.00 0.08 V 10.96 V ###
Convert to 3Phase 0.14 V
Deluxe : Final Point Voltage Drop (Less than 4%) 14.00 V V%= 3.5%

A OK 1.00 1,250 A OK 0.07 0.15 V 11.03 V OK V%=0.04%


A OK 0.85 183 A OK 0.87 0.56 V 11.59 V OK V%=0.14%
Total Voltage Drop 11.59 V
A OK 0.85 45 A OK 6.80 0.73 V 11.76 V OK V%=0.18%
A OK 0.85 26 A OK 16.00 2.46 V 13.49 V OK V%=0.62%
P-H-3-01 : Final Point Voltage Drop (Less than 4%) 14.78 V V%= 3.7%
A OK 0.85 45 A OK 6.80 0.56 V 11.59 V OK V%=0.14%
A OK 0.85 26 A OK 16.00 0.22 V 11.25 V OK V%=0.06%
P-H-3-02 : Final Point Voltage Drop (Less than 4%) 12.37 V V%= 3.09%
A OK 0.85 35 A OK 10.00 1.82 V 1.82 V OK V%=0.46%
A OK 0.85 20 A OK 18.00 0.08 V 10.96 V ###
Convert to 3Phase 0.14 V
Standard : Final Point Voltage Drop (Less than 4%) 13.55 V V%= 3.39%
A OK 0.85 45 A OK 6.80 2.47 V 2.47 V OK V%=0.62%
A OK 0.85 20 A OK 18.00 0.08 V 10.96 V ###
Convert to 3Phase 0.14 V

Voltage Drop shall be less than 3%. - 125 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage Drop Total Voltage
Judge Factor Judge Voltage Drop (v) Judge
Cap (A) Cap (A) (v) Drop (%)
mV/A/m

Deluxe : Final Point Voltage Drop (Less than 4%) 14.20 V V%= 3.55%

Voltage Drop shall be less than 3%. - 126 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage Drop Total Voltage
Judge Factor Judge Voltage Drop (v) Judge
Cap (A) Cap (A) (v) Drop (%)
mV/A/m

A OK 1.00 1,250 A OK 0.07 0.13 V 11.16 V OK V%=0.03%


A OK 0.85 183 A OK 0.87 0.56 V 11.72 V OK V%=0.14%
Total Voltage Drop 11.72 V
A OK 0.85 45 A OK 6.80 0.73 V 11.89 V OK V%=0.18%
A OK 0.85 26 A OK 16.00 0.98 V 12.01 V OK V%=0.25%
P-H-4-01 : Final Point Voltage Drop (Less than 4%) 13.43 V V%= 3.36%
A OK 0.85 45 A OK 6.80 0.56 V 11.72 V OK V%=0.14%
A OK 0.85 26 A OK 16.00 0.98 V 12.01 V OK V%=0.25%
P-H-4-02 : Final Point Voltage Drop (Less than 4%) 13.26 V V%= 3.32%
A OK 0.85 35 A OK 10.00 1.82 V 1.82 V OK V%=0.46%
A OK 0.85 20 A OK 18.00 0.08 V 10.96 V ###
Convert to 3Phase 0.14 V
Standard : Final Point Voltage Drop (Less than 4%) 13.68 V V%= 3.42%
A OK 0.85 45 A OK 6.80 2.47 V 2.47 V OK V%=0.62%
A OK 0.85 20 A OK 18.00 0.08 V 10.96 V ###
Convert to 3Phase 0.14 V
Deluxe : Final Point Voltage Drop (Less than 4%) 14.33 V V%= 3.58%

A OK 1.00 1,250 A OK 0.07 0.10 V 11.26 V OK V%=0.03%


A OK 0.85 183 A OK 0.87 0.52 V 11.78 V OK V%=0.13%
Total Voltage Drop 11.78 V
A OK 0.85 45 A OK 6.80 0.73 V 11.99 V OK V%=0.18%
A OK 0.85 26 A OK 16.00 0.98 V 12.01 V OK V%=0.25%
P-H-5-01 : Final Point Voltage Drop (Less than 4%) 13.49 V V%= 3.37%
A OK 0.85 45 A OK 6.80 0.56 V 11.82 V OK V%=0.14%
A OK 0.85 26 A OK 16.00 0.98 V 12.01 V OK V%=0.25%
P-H-5-02 : Final Point Voltage Drop (Less than 4%) 13.32 V V%= 3.33%
A OK 0.85 35 A OK 10.00 1.82 V 1.82 V OK V%=0.46%
A OK 0.85 20 A OK 18.00 0.08 V 10.96 V ###
Convert to 3Phase 0.14 V
Standard : Final Point Voltage Drop (Less than 4%) 13.74 V V%= 3.43%
A OK 0.85 45 A OK 6.80 2.47 V 2.47 V OK V%=0.62%
A OK 0.85 20 A OK 18.00 0.08 V 10.96 V ###
Convert to 3Phase 0.14 V
Deluxe or Suit : Final Point Voltage Drop (Less than 4%) 14.39 V V%= 3.6%

Voltage Drop shall be less than 3%. - 127 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage Drop Total Voltage
Judge Factor Judge Voltage Drop (v) Judge
Cap (A) Cap (A) (v) Drop (%)
mV/A/m

Voltage Drop shall be less than 3%. - 128 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage Drop Total Voltage
Judge Factor Judge Voltage Drop (v) Judge
Cap (A) Cap (A) (v) Drop (%)
mV/A/m

A OK 1.00 1,250 A OK 0.07 0.37 V 11.63 V OK V%=0.09%


A OK 0.85 183 A OK 0.87 0.52 V 12.15 V OK V%=0.13%
Total Voltage Drop 12.15 V
A OK 0.85 45 A OK 6.80 0.73 V 12.36 V OK V%=0.18%
A OK 0.85 26 A OK 16.00 0.98 V 12.01 V OK V%=0.25%
P-H-6-01 : Final Point Voltage Drop (Less than 4%) 13.86 V V%= 3.47%
A OK 0.85 45 A OK 6.80 0.56 V 12.19 V OK V%=0.14%
A OK 0.85 26 A OK 16.00 0.98 V 12.01 V OK V%=0.25%
P-H-6-02 : Final Point Voltage Drop (Less than 4%) 13.69 V V%= 3.42%
A OK 0.85 35 A OK 10.00 1.82 V 1.82 V OK V%=0.46%
A OK 0.85 20 A OK 18.00 0.08 V 10.96 V ###
Convert to 3Phase 0.14 V
Standard : Final Point Voltage Drop (Less than 4%) 14.11 V V%= 3.53%
A OK 0.85 45 A OK 6.80 2.47 V 2.47 V OK V%=0.62%
A OK 0.85 20 A OK 18.00 0.08 V 10.96 V ###
Convert to 3Phase 0.14 V
Deluxe or Suit : Final Point Voltage Drop (Less than 4%) 14.76 V V%= 3.69%

A OK 1.00 1,250 A OK 0.07 0.05 V 11.68 V OK V%=0.01%


A OK 0.85 183 A OK 0.87 0.52 V 12.20 V OK V%=0.13%
Total Voltage Drop 12.20 V
A OK 0.85 45 A OK 6.80 0.73 V 12.41 V OK V%=0.18%
A OK 0.85 26 A OK 16.00 0.98 V 12.01 V OK V%=0.25%
P-H-7-01 : Final Point Voltage Drop (Less than 4%) 13.91 V V%= 3.48%
A OK 0.85 45 A OK 6.80 0.56 V 12.24 V OK V%=0.14%
A OK 0.85 26 A OK 16.00 0.98 V 12.01 V OK V%=0.25%
P-H-7-02 : Final Point Voltage Drop (Less than 4%) 13.74 V V%= 3.44%
A OK 0.85 35 A OK 10.00 1.82 V 1.82 V OK V%=0.46%
A OK 0.85 20 A OK 18.00 0.08 V 10.96 V ###
Convert to 3Phase 0.14 V
Standard : Final Point Voltage Drop (Less than 4%) 14.16 V V%= 3.54%
A OK 0.85 45 A OK 6.80 2.47 V 2.47 V OK V%=0.62%
A OK 0.85 20 A OK 18.00 0.08 V 10.96 V ###
Convert to 3Phase 0.14 V
Deluxe or Suit : Final Point Voltage Drop (Less than 4%) 14.81 V V%= 3.7%

Voltage Drop shall be less than 3%. - 129 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage Drop Total Voltage
Judge Factor Judge Voltage Drop (v) Judge
Cap (A) Cap (A) (v) Drop (%)
mV/A/m

Voltage Drop shall be less than 3%. - 130 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage Drop Total Voltage
Judge Factor Judge Voltage Drop (v) Judge
Cap (A) Cap (A) (v) Drop (%)
mV/A/m

A OK 1.00 1,250 A OK 0.07 0.02 V 11.70 V OK V%=0.01%


A OK 0.85 183 A OK 0.87 0.48 V 12.18 V OK V%=0.12%
Total Voltage Drop 12.18 V
A OK 0.85 45 A OK 6.80 1.33 V 13.03 V OK V%=0.33%
A OK 0.85 26 A OK 16.00 0.98 V 12.01 V OK V%=0.25%
P-H-8-01 : Final Point Voltage Drop (Less than 4%) 14.49 V V%= 3.62%
A OK 0.85 35 A OK 10.00 0.97 V 12.67 V OK V%=0.24%
A OK 0.85 26 A OK 16.00 1.55 V 12.58 V OK V%=0.39%
P-H-R-02 : Final Point Voltage Drop (Less than 4%) 14.70 V V%= 3.68%
A OK 0.85 35 A OK 10.00 1.82 V 1.82 V OK V%=0.46%
A OK 0.85 20 A OK 18.00 0.08 V 10.96 V ###
Convert to 3Phase 0.14 V
Standard : Final Point Voltage Drop (Less than 4%) 14.14 V V%= 3.53%
A OK 0.85 45 A OK 6.80 2.47 V 2.47 V OK V%=0.62%
A OK 0.85 20 A OK 18.00 0.08 V 10.96 V ###
Convert to 3Phase 0.14 V
Deluxe or Suit : Final Point Voltage Drop (Less than 4%) 14.79 V V%= 3.7%

0 0.00
A OK 0.85 1,443 A OK 0.10 7.75 V 10.48 V OK V%=1.94%
A OK 1.00 800 A OK 0.13 0.22 V 10.70 V OK V%=0.06%
A OK 0.85 150 A OK 1.15 0.49 V 11.19 V OK V%=0.12%
Total Voltage Drop 11.19 V
A OK 0.85 45 A OK 6.80 0.84 V 11.54 V OK V%=0.21%
A OK 0.85 20 A OK 18.00 1.41 V 12.29 V ###
Convert to 3Phase 2.44 V
LH2-C1 : Final Point Voltage Drop (Less than 4%) 14.47 V V%= 3.62%
A OK 0.85 35 A OK 10.00 1.82 V 1.82 V OK V%=0.46%
A OK 0.85 20 A OK 18.00 0.08 V 10.96 V ###
Convert to 3Phase 0.14 V
Standard : Final Point Voltage Drop (Less than 4%) 13.15 V V%= 3.29%

A OK 1.00 800 A OK 0.13 0.19 V 10.89 V OK V%=0.05%


A OK 0.85 150 A OK 1.15 0.50 V 11.39 V OK V%=0.13%
Total Voltage Drop 11.39 V

Voltage Drop shall be less than 3%. - 131 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage Drop Total Voltage
Judge Factor Judge Voltage Drop (v) Judge
Cap (A) Cap (A) (v) Drop (%)
mV/A/m

A OK 0.85 45 A OK 6.80 0.75 V 11.64 V OK V%=0.19%


A OK 0.85 20 A OK 18.00 1.41 V 12.29 V ###
Convert to 3Phase 2.44 V
LH3-C1 : Final Point Voltage Drop (Less than 4%) 14.58 V V%= 3.65%
A OK 0.85 35 A OK 10.00 1.82 V 1.82 V OK V%=0.46%
A OK 0.85 20 A OK 18.00 1.17 V 12.05 V ###
Convert to 3Phase 2.03 V
Standard : Final Point Voltage Drop (Less than 4%) 15.24 V V%= 3.81%

Voltage Drop shall be less than 3%. - 132 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage Drop Total Voltage
Judge Factor Judge Voltage Drop (v) Judge
Cap (A) Cap (A) (v) Drop (%)
mV/A/m

A OK 1.00 800 A OK 0.13 0.16 V 11.05 V OK V%=0.04%


A OK 0.85 150 A OK 1.15 0.50 V 11.55 V OK V%=0.13%
Total Voltage Drop 11.55 V
A OK 0.85 45 A OK 6.80 0.75 V 11.80 V OK V%=0.19%
A OK 0.85 20 A OK 18.00 1.41 V 12.29 V ###
Convert to 3Phase 2.44 V
LH4-C1 : Final Point Voltage Drop (Less than 4%) 14.74 V V%= 3.69%
A OK 0.85 35 A OK 10.00 1.82 V 1.82 V OK V%=0.46%
A OK 0.85 20 A OK 18.00 1.17 V 12.05 V ###
Convert to 3Phase 2.03 V
Standard : Final Point Voltage Drop (Less than 4%) 15.40 V V%= 3.85%

A OK 1.00 800 A OK 0.13 0.12 V 11.17 V OK V%=0.03%


A OK 0.85 150 A OK 1.15 0.49 V 11.66 V OK V%=0.12%
Total Voltage Drop 11.66 V
A OK 0.85 45 A OK 6.80 0.75 V 11.92 V OK V%=0.19%
A OK 0.85 20 A OK 18.00 1.41 V 12.29 V ###
Convert to 3Phase 2.44 V
LH5-C1 : Final Point Voltage Drop (Less than 4%) 14.85 V V%= 3.71%
A OK 0.85 35 A OK 10.00 1.82 V 1.82 V OK V%=0.46%
A OK 0.85 20 A OK 18.00 0.08 V 10.96 V ###
Convert to 3Phase 0.14 V
Standard : Final Point Voltage Drop (Less than 4%) 13.62 V V%= 3.4%
A OK 0.85 45 A OK 6.80 2.47 V 2.47 V OK V%=0.62%
A OK 0.85 20 A OK 18.00 0.08 V 10.96 V ###
Convert to 3Phase 0.14 V
Suit : Final Point Voltage Drop (Less than 4%) 14.27 V V%= 3.57%

A OK 1.00 800 A OK 0.13 0.09 V 11.26 V OK V%=0.02%


A OK 0.85 150 A OK 1.15 0.49 V 11.75 V OK V%=0.12%
Total Voltage Drop 11.75 V
A OK 0.85 45 A OK 6.80 0.75 V 12.01 V OK V%=0.19%
A OK 0.85 20 A OK 18.00 1.41 V 12.29 V ###
Convert to 3Phase 2.44 V
LH6-C1 : Final Point Voltage Drop (Less than 4%) 14.94 V V%= 3.74%

Voltage Drop shall be less than 3%. - 133 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage Drop Total Voltage
Judge Factor Judge Voltage Drop (v) Judge
Cap (A) Cap (A) (v) Drop (%)
mV/A/m

A OK 0.85 35 A OK 10.00 1.82 V 1.82 V OK V%=0.46%


A OK 0.85 20 A OK 18.00 0.08 V 10.96 V ###
Convert to 3Phase 0.14 V
Standard : Final Point Voltage Drop (Less than 4%) 13.71 V V%= 3.43%
A OK 0.85 45 A OK 6.80 2.47 V 2.47 V OK V%=0.62%
A OK 0.85 20 A OK 18.00 0.08 V 10.96 V ###
Convert to 3Phase 0.14 V
Suit : Final Point Voltage Drop (Less than 4%) 14.36 V V%= 3.59%

Voltage Drop shall be less than 3%. - 134 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage Drop Total Voltage
Judge Factor Judge Voltage Drop (v) Judge
Cap (A) Cap (A) (v) Drop (%)
mV/A/m

A OK 1.00 800 A OK 0.13 0.06 V 11.32 V OK V%=0.02%


A OK 0.85 150 A OK 1.15 0.47 V 11.79 V OK V%=0.12%
Total Voltage Drop 11.79 V
A OK 0.85 45 A OK 6.80 0.75 V 12.07 V OK V%=0.19%
A OK 0.85 20 A OK 18.00 1.41 V 12.29 V ###
Convert to 3Phase 2.44 V
LH7-C1 : Final Point Voltage Drop (Less than 4%) 14.98 V V%= 3.75%
A OK 0.85 35 A OK 10.00 1.82 V 1.82 V OK V%=0.46%
A OK 0.85 20 A OK 18.00 0.08 V 10.96 V ###
Convert to 3Phase 0.14 V
Standard : Final Point Voltage Drop (Less than 4%) 13.75 V V%= 3.44%
A OK 0.85 45 A OK 6.80 2.47 V 2.47 V OK V%=0.62%
A OK 0.85 20 A OK 18.00 0.08 V 10.96 V ###
Convert to 3Phase 0.14 V
Suit : Final Point Voltage Drop (Less than 4%) 14.40 V V%= 3.6%

A OK 1.00 800 A OK 0.13 0.03 V 11.35 V OK V%=0.01%


A OK 0.85 150 A OK 1.15 0.43 V 11.78 V OK V%=0.11%
Total Voltage Drop 11.78 V
A OK 0.85 45 A OK 6.80 0.81 V 12.16 V OK V%=0.20%
A OK 0.85 20 A OK 18.00 1.41 V 12.29 V ###
Convert to 3Phase 2.44 V
LH8-C1 : Final Point Voltage Drop (Less than 4%) 15.03 V V%= 3.76%
A OK 0.85 45 A OK 6.80 2.53 V 13.88 V OK V%=0.63%
A OK 0.85 59 A OK 2.80 0.49 V 0.49 V OK V%= 0.21%
Convert to 3Phase 0.85 V
LH8-C1 : Final Point Voltage Drop (Less than 4%) 15.16 V V%= 3.79%
A OK 0.85 35 A OK 10.00 1.82 V 1.82 V OK V%=0.46%
A OK 0.85 20 A OK 18.00 0.08 V 10.96 V ###
Convert to 3Phase 0.14 V
Standard : Final Point Voltage Drop (Less than 4%) 13.74 V V%= 3.43%
A OK 0.85 45 A OK 6.80 2.47 V 2.47 V OK V%=0.62%
A OK 0.85 20 A OK 18.00 0.08 V 10.96 V ###
Convert to 3Phase 0.14 V
Suit : Final Point Voltage Drop (Less than 4%) 14.39 V V%= 3.6%

Voltage Drop shall be less than 3%. - 135 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage Drop Total Voltage
Judge Factor Judge Voltage Drop (v) Judge
Cap (A) Cap (A) (v) Drop (%)
mV/A/m

A OK 0.85 1,607 A OK 0.08 4.01 V 6.74 V OK V%=1.00%


A OK 1.00 1,600 A OK 0.05 0.27 V 7.01 V OK V%=0.07%
A OK 0.85 237 A OK 0.62 0.64 V 7.65 V OK V%=0.16%
Total Voltage Drop 7.65 V
A OK 0.85 45 A OK 6.80 1.66 V 8.67 V OK V%=0.42%
A OK 0.85 20 A OK 18.00 0.58 V 11.46 V ###
Convert to 3Phase 1.00 V
LSG-C1 : Final Point Voltage Drop (Less than 4%) 10.31 V V%= 2.58%
A OK 0.85 35 A OK 10.00 2.16 V 9.17 V OK V%=0.54%
A OK 0.85 20 A OK 18.00 0.58 V 11.46 V ###
Convert to 3Phase 1.00 V
LS1-C1 : Final Point Voltage Drop (Less than 4%) 10.81 V V%= 2.7%
A OK 0.85 35 A OK 10.00 0.52 V 7.53 V OK V%=0.13%
A OK 0.85 20 A OK 18.00 0.58 V 11.46 V ###
Convert to 3Phase 1.00 V
LS2-C1 : Final Point Voltage Drop (Less than 4%) 9.17 V V%= 2.29%
A OK 0.85 35 A OK 10.00 5.05 V 12.06 V OK V%=1.26%
A OK 0.85 20 A OK 18.00 0.58 V 11.46 V ###
Convert to 3Phase 1.00 V
LS2-C1 : Final Point Voltage Drop (Less than 4%) 13.70 V V%= 3.43%

A OK 0.85 45 A OK 6.80 2.75 V 11.05 V OK V%=0.69%

A OK 0.85 20 A OK 18.00 0.08 V 10.96 V ###


Convert to 3Phase 0.14 V
1Bed or Stadio Type : Final Point Voltage Drop (Less than 4%) 10.54 V V%= 2.63%
A OK 0.85 45 A OK 6.80 3.37 V 11.67 V OK V%=0.84%
A OK 0.85 20 A OK 18.00 0.08 V 10.96 V ###
Convert to 3Phase 0.14 V
2Bed Type : Final Point Voltage Drop (Less than 4%) 11.16 V V%= 2.79%
A OK 0.85 45 A OK 6.80 1.86 V 10.16 V OK V%=0.47%
A OK 0.85 20 A OK 18.00 0.08 V 10.96 V ###
Convert to 3Phase 0.14 V
3Bed Type : Final Point Voltage Drop (Less than 4%) 9.65 V V%= 2.41%

A OK 1.00 1,600 A OK 0.05 0.15 V 7.16 V OK V%=0.04%

Voltage Drop shall be less than 3%. - 136 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage Drop Total Voltage
Judge Factor Judge Voltage Drop (v) Judge
Cap (A) Cap (A) (v) Drop (%)
mV/A/m

A OK 0.85 237 A OK 0.62 0.53 V 7.69 V OK V%=0.13%


Total Voltage Drop 7.69 V
A OK 0.85 35 A OK 10.00 0.50 V 7.66 V OK V%=0.13%
A OK 0.85 20 A OK 18.00 0.58 V 11.46 V ###
Convert to 3Phase 1.00 V
LS3-C1 : Final Point Voltage Drop (Less than 4%) 9.19 V V%= 2.3%

Voltage Drop shall be less than 3%. - 137 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage Drop Total Voltage
Judge Factor Judge Voltage Drop (v) Judge
Cap (A) Cap (A) (v) Drop (%)
mV/A/m

A OK 0.85 45 A OK 6.80 2.75 V 11.05 V OK V%=0.69%

A OK 0.85 20 A OK 18.00 0.08 V 10.96 V ###


Convert to 3Phase 0.14 V
1Bed or Stadio Type : Final Point Voltage Drop (Less than 4%) 10.58 V V%= 2.64%
A OK 0.85 45 A OK 6.80 3.37 V 11.67 V OK V%=0.84%
A OK 0.85 20 A OK 18.00 0.08 V 10.96 V ###
Convert to 3Phase 0.14 V
2Bed Type : Final Point Voltage Drop (Less than 4%) 11.20 V V%= 2.8%
A OK 0.85 45 A OK 6.80 1.86 V 10.16 V OK V%=0.47%
A OK 0.85 20 A OK 18.00 0.08 V 10.96 V ###
Convert to 3Phase 0.14 V
3Bed Type : Final Point Voltage Drop (Less than 4%) 9.69 V V%= 2.42%

A OK 1.00 1,600 A OK 0.05 0.13 V 7.29 V OK V%=0.03%


A OK 0.85 237 A OK 0.62 0.53 V 7.82 V OK V%=0.13%
Total Voltage Drop 7.82 V
A OK 0.85 35 A OK 10.00 0.50 V 7.79 V OK V%=0.13%
A OK 0.85 20 A OK 18.00 0.58 V 11.46 V ###
Convert to 3Phase 1.00 V
LS4-C1 : Final Point Voltage Drop (Less than 4%) 9.32 V V%= 2.33%

A OK 0.85 45 A OK 6.80 2.75 V 11.05 V OK V%=0.69%

A OK 0.85 20 A OK 18.00 0.08 V 10.96 V ###


Convert to 3Phase 0.14 V
1Bed or Stadio Type : Final Point Voltage Drop (Less than 4%) 10.71 V V%= 2.68%
A OK 0.85 45 A OK 6.80 3.37 V 11.67 V OK V%=0.84%
A OK 0.85 20 A OK 18.00 0.08 V 10.96 V ###
Convert to 3Phase 0.14 V
2Bed Type : Final Point Voltage Drop (Less than 4%) 11.33 V V%= 2.83%
A OK 0.85 45 A OK 6.80 1.86 V 10.16 V OK V%=0.47%
A OK 0.85 20 A OK 18.00 0.08 V 10.96 V ###
Convert to 3Phase 0.14 V
3Bed Type : Final Point Voltage Drop (Less than 4%) 9.82 V V%= 2.45%

A OK 1.00 1,600 A OK 0.05 0.10 V 7.39 V OK V%=0.03%

Voltage Drop shall be less than 3%. - 138 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage Drop Total Voltage
Judge Factor Judge Voltage Drop (v) Judge
Cap (A) Cap (A) (v) Drop (%)
mV/A/m

A OK 0.85 237 A OK 0.62 0.53 V 7.92 V OK V%=0.13%


Total Voltage Drop 7.92 V
A OK 0.85 35 A OK 10.00 0.50 V 7.89 V OK V%=0.13%
A OK 0.85 20 A OK 18.00 0.58 V 11.46 V ###
Convert to 3Phase 1.00 V
LS5-C1 : Final Point Voltage Drop (Less than 4%) 9.42 V V%= 2.36%

Voltage Drop shall be less than 3%. - 139 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage Drop Total Voltage
Judge Factor Judge Voltage Drop (v) Judge
Cap (A) Cap (A) (v) Drop (%)
mV/A/m

A OK 0.85 45 A OK 6.80 2.75 V 11.05 V OK V%=0.69%

A OK 0.85 20 A OK 18.00 0.08 V 10.96 V ###


Convert to 3Phase 0.14 V
1Bed or Stadio Type : Final Point Voltage Drop (Less than 4%) 10.81 V V%= 2.7%
A OK 0.85 45 A OK 6.80 3.37 V 11.67 V OK V%=0.84%
A OK 0.85 20 A OK 18.00 0.08 V 10.96 V ###
Convert to 3Phase 0.14 V
2Bed Type : Final Point Voltage Drop (Less than 4%) 11.43 V V%= 2.86%
A OK 0.85 45 A OK 6.80 1.86 V 10.16 V OK V%=0.47%
A OK 0.85 20 A OK 18.00 0.08 V 10.96 V ###
Convert to 3Phase 0.14 V
3Bed Type : Final Point Voltage Drop (Less than 4%) 9.92 V V%= 2.48%

A OK 1.00 1,600 A OK 0.05 0.41 V 7.80 V OK V%=0.10%


A OK 0.85 237 A OK 0.62 0.53 V 8.33 V OK V%=0.13%
Total Voltage Drop 8.33 V
A OK 0.85 35 A OK 10.00 0.50 V 8.30 V OK V%=0.13%
A OK 0.85 20 A OK 18.00 0.58 V 11.46 V ###
Convert to 3Phase 1.00 V
LS6-C1 : Final Point Voltage Drop (Less than 4%) 9.83 V V%= 2.46%

A OK 0.85 45 A OK 6.80 2.75 V 11.05 V OK V%=0.69%

A OK 0.85 20 A OK 18.00 0.08 V 10.96 V ###


Convert to 3Phase 0.14 V
1Bed or Stadio Type : Final Point Voltage Drop (Less than 4%) 11.22 V V%= 2.8%
A OK 0.85 45 A OK 6.80 3.37 V 11.67 V OK V%=0.84%
A OK 0.85 20 A OK 18.00 0.08 V 10.96 V ###
Convert to 3Phase 0.14 V
2Bed Type : Final Point Voltage Drop (Less than 4%) 11.84 V V%= 2.96%
A OK 0.85 45 A OK 6.80 1.86 V 10.16 V OK V%=0.47%
A OK 0.85 20 A OK 18.00 0.08 V 10.96 V ###
Convert to 3Phase 0.14 V
3Bed Type : Final Point Voltage Drop (Less than 4%) 10.33 V V%= 2.58%

A OK 1.00 1,600 A OK 0.05 0.05 V 7.85 V OK V%=0.01%

Voltage Drop shall be less than 3%. - 140 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage Drop Total Voltage
Judge Factor Judge Voltage Drop (v) Judge
Cap (A) Cap (A) (v) Drop (%)
mV/A/m

A OK 0.85 237 A OK 0.62 0.53 V 8.38 V OK V%=0.13%


Total Voltage Drop 8.38 V
A OK 0.85 35 A OK 10.00 0.50 V 8.35 V OK V%=0.13%
A OK 0.85 20 A OK 18.00 0.58 V 11.46 V ###
Convert to 3Phase 1.00 V
LS7-C1 : Final Point Voltage Drop (Less than 4%) 9.88 V V%= 2.47%

Voltage Drop shall be less than 3%. - 141 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage Drop Total Voltage
Judge Factor Judge Voltage Drop (v) Judge
Cap (A) Cap (A) (v) Drop (%)
mV/A/m

A OK 0.85 45 A OK 6.80 2.75 V 11.05 V OK V%=0.69%

A OK 0.85 20 A OK 18.00 0.08 V 10.96 V ###


Convert to 3Phase 0.14 V
1Bed or Stadio Type : Final Point Voltage Drop (Less than 4%) 11.27 V V%= 2.82%
A OK 0.85 45 A OK 6.80 3.37 V 11.67 V OK V%=0.84%
A OK 0.85 20 A OK 18.00 0.08 V 10.96 V ###
Convert to 3Phase 0.14 V
2Bed Type : Final Point Voltage Drop (Less than 4%) 11.89 V V%= 2.97%
A OK 0.85 45 A OK 6.80 1.86 V 10.16 V OK V%=0.47%
A OK 0.85 20 A OK 18.00 0.08 V 10.96 V ###
Convert to 3Phase 0.14 V
3Bed Type : Final Point Voltage Drop (Less than 4%) 10.38 V V%= 2.59%

A OK 1.00 1,600 A OK 0.05 0.02 V 7.87 V OK V%=0.01%


A OK 0.85 237 A OK 0.62 0.43 V 8.30 V OK V%=0.11%
Total Voltage Drop 8.30 V
A OK 0.85 35 A OK 10.00 0.47 V 8.34 V OK V%=0.12%
A OK 0.85 20 A OK 18.00 0.58 V 11.46 V ###
Convert to 3Phase 1.00 V
LS8-C1 : Final Point Voltage Drop (Less than 4%) 9.77 V V%= 2.44%

A OK 0.85 45 A OK 6.80 2.75 V 11.05 V OK V%=0.69%

A OK 0.85 20 A OK 18.00 0.08 V 10.96 V ###


Convert to 3Phase 0.14 V
1Bed or Stadio Type : Final Point Voltage Drop (Less than 4%) 11.19 V V%= 2.8%
A OK 0.85 45 A OK 6.80 3.37 V 11.67 V OK V%=0.84%
A OK 0.85 20 A OK 18.00 0.08 V 10.96 V ###
Convert to 3Phase 0.14 V
2Bed Type : Final Point Voltage Drop (Less than 4%) 11.81 V V%= 2.95%
A OK 0.85 45 A OK 6.80 1.86 V 10.16 V OK V%=0.47%
A OK 0.85 20 A OK 18.00 0.08 V 10.96 V ###
Convert to 3Phase 0.14 V
3Bed Type : Final Point Voltage Drop (Less than 4%) 10.30 V V%= 2.57%
0
0 0.00

Voltage Drop shall be less than 3%. - 142 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage Drop Total Voltage
Judge Factor Judge Voltage Drop (v) Judge
Cap (A) Cap (A) (v) Drop (%)
mV/A/m

A OK 0.85 150 A OK 1.15 6.59 V 9.32 V OK V%=1.65%


Total Voltage Drop 9.32 V
A OK 0.85 45 A OK 6.80 0.49 V 3.22 V OK V%=0.12%
A OK 0.85 35 A OK 10.00 2.91 V 2.91 V OK V%= 0.73%
P-H-B2-03 : Final Point Voltage Drop (Less than 4%) 12.72 V V%= 3.18%
A OK 0.85 45 A OK 6.80 0.49 V 3.22 V OK V%=0.12%
A OK 0.85 35 A OK 10.00 2.91 V 2.91 V OK V%= 0.73%
P-H-B2-05 : Final Point Voltage Drop (Less than 4%) 12.72 V V%= 3.18%

Voltage Drop shall be less than 3%. - 143 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage Drop Total Voltage
Judge Factor Judge Voltage Drop (v) Judge
Cap (A) Cap (A) (v) Drop (%)
mV/A/m

A OK 0.85 183 A OK 0.87 9.43 V 12.16 V OK V%=2.36%


Total Voltage Drop 12.16 V
A OK 0.85 45 A OK 6.80 0.49 V 3.22 V OK V%=0.12%
A OK 0.85 35 A OK 10.00 2.91 V 2.91 V OK V%= 0.73%
P-H-B2-06 : Final Point Voltage Drop (Less than 4%) 15.56 V V%= 3.89%
A OK 0.85 150 A OK 1.15 0.23 V 2.96 V OK V%=0.06%
A OK 0.85 72 A OK 2.50 2.02 V 2.02 V OK V%= 0.51%
P-H-B2-08 : Final Point Voltage Drop (Less than 4%) 14.41 V V%= 3.6%
A OK 0.85 45 A OK 6.80 0.31 V 3.04 V OK V%=0.08%
A OK 0.85 26 A OK 16.00 2.92 V 2.92 V OK V%= 0.73%
P-H-B2-09 : Final Point Voltage Drop (Less than 4%) 15.39 V V%= 3.85%

A OK 0.85 150 A OK 1.15 9.16 V 11.89 V OK V%=2.29%


Total Voltage Drop 11.89 V
A OK 0.85 45 A OK 6.80 0.49 V 3.22 V OK V%=0.12%
A OK 0.85 35 A OK 10.00 2.91 V 2.91 V OK V%= 0.73%
P-H-B2-10 : Final Point Voltage Drop (Less than 4%) 15.29 V V%= 3.82%
A OK 0.85 45 A OK 6.80 0.49 V 3.22 V OK V%=0.12%
A OK 0.85 35 A OK 10.00 2.91 V 2.91 V OK V%= 0.73%
P-H-B2-12 : Final Point Voltage Drop (Less than 4%) 15.29 V V%= 3.82%
A OK 0.85 45 A OK 6.80 0.66 V 3.39 V OK V%=0.17%
A OK 0.85 35 A OK 10.00 2.91 V 2.91 V OK V%= 0.73%
P-H-B2-13 : Final Point Voltage Drop (Less than 4%) 15.46 V V%= 3.87%

A OK 0.85 237 A OK 0.62 8.04 V 10.77 V OK V%=2.01%


Total Voltage Drop 10.77 V
A OK 0.85 45 A OK 6.80 0.19 V 2.92 V OK V%=0.05%
A OK 0.85 26 A OK 16.00 0.31 V 0.31 V OK V%= 0.08%
P-H-B2-15 : Final Point Voltage Drop (Less than 4%) 11.27 V V%= 2.82%
A OK 0.85 45 A OK 6.80 0.49 V 3.22 V OK V%=0.12%
A OK 0.85 35 A OK 10.00 2.91 V 2.91 V OK V%= 0.73%
P-H-B2-16 : Final Point Voltage Drop (Less than 4%) 14.17 V V%= 3.54%
A OK 0.85 150 A OK 1.15 0.31 V 3.04 V OK V%=0.08%
A OK 0.85 72 A OK 2.50 2.03 V 2.03 V OK V%= 0.51%
P-H-B2-17 : Final Point Voltage Drop (Less than 4%) 13.11 V V%= 3.28%

Voltage Drop shall be less than 3%. - 144 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage Drop Total Voltage
Judge Factor Judge Voltage Drop (v) Judge
Cap (A) Cap (A) (v) Drop (%)
mV/A/m

A OK 0.85 150 A OK 1.15 0.31 V 3.04 V OK V%=0.08%


A OK 0.85 72 A OK 2.50 2.03 V 2.03 V OK V%= 0.51%
P-H-B2-19 : Final Point Voltage Drop (Less than 4%) 13.11 V V%= 3.28%

Voltage Drop shall be less than 3%. - 145 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage Drop Total Voltage
Judge Factor Judge Voltage Drop (v) Judge
Cap (A) Cap (A) (v) Drop (%)
mV/A/m

A OK 0.85 183 A OK 0.87 7.76 V 10.49 V OK V%=1.94%


Total Voltage Drop 10.49 V
A OK 0.85 183 A OK 0.87 0.26 V 2.99 V OK V%=0.07%
A OK 0.85 72 A OK 2.50 1.01 V 1.01 V OK V%= 0.25%
P-H-B2-20 : Final Point Voltage Drop (Less than 4%) 11.76 V V%= 2.94%
A OK 0.85 183 A OK 0.87 0.26 V 2.99 V OK V%=0.07%
A OK 0.85 72 A OK 2.50 2.03 V 2.03 V OK V%= 0.51%
P-H-B2-21 : Final Point Voltage Drop (Less than 4%) 12.78 V V%= 3.2%
A OK 0.85 72 A OK 2.50 0.45 V 3.18 V OK V%=0.11%
A OK 0.85 62 A OK 4.00 2.16 V 2.16 V OK V%= 0.54%
P-H-B2-22 : Final Point Voltage Drop (Less than 4%) 13.10 V V%= 3.28%

A OK 0.85 72 A OK 2.50 6.42 V 9.15 V OK V%=1.61%


Total Voltage Drop 9.15 V
A OK 0.85 45 A OK 6.80 0.49 V 3.22 V OK V%=0.12%
A OK 0.85 35 A OK 10.00 1.45 V 1.45 V OK V%= 0.36%
P-H-B2-24 : Final Point Voltage Drop (Less than 4%) 11.09 V V%= 2.77%
A OK 0.85 45 A OK 6.80 0.49 V 3.22 V OK V%=0.12%
A OK 0.85 35 A OK 10.00 2.91 V 2.91 V OK V%= 0.73%
P-H-B2-25 : Final Point Voltage Drop (Less than 4%) 12.55 V V%= 3.14%

A OK 0.85 392 A OK 0.32 3.57 V 6.3 V OK V%=0.89%


A OK 0.85 290 A OK 0.46 1.16 V 1.16 V OK V%= 0.29%
P-H-2-1 : Final Point Voltage Drop (Less than 4%) 7.46 V V%= 1.87%
A OK 0.85 35 A OK 10.00 6.17 V 8.9 V OK V%=1.54%
A OK 0.85 26 A OK 16.00 0.69 V 0.69 V OK V%= 0.17%
P-H-2-2 : Final Point Voltage Drop (Less than 4%) 9.59 V V%= 2.4%
A OK 0.85 183 A OK 0.87 9.49 V 12.22 V OK V%=2.37%
A OK 0.85 62 A OK 4.00 1.44 V 1.44 V OK V%= 0.36%
P-H-2-3 : Final Point Voltage Drop (Less than 4%) 13.66 V V%= 3.42%
A OK 0.85 183 A OK 0.87 6.12 V 8.85 V OK V%=1.53%
A OK 0.85 45 A OK 6.80 1.90 V 1.90 V OK V%= 0.48%
P-H-3-1 : Final Point Voltage Drop (Less than 4%) 10.75 V V%= 2.69%

0 0.00

Voltage Drop shall be less than 3%. - 146 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage Drop Total Voltage
Judge Factor Judge Voltage Drop (v) Judge
Cap (A) Cap (A) (v) Drop (%)
mV/A/m

A OK 0.85 237 A OK 0.62 12.41 V 15.14 V OK V%=3.10%


A OK 0.85 72 A OK 2.50 0.16 V 5.59 V OK V%=0.07%
Convert to 3Phase 0.28 V
LHG-K1 : Final Point Voltage Drop (Less than 4%) 15.42 V V%= 3.85%

A OK 0.85 290 A OK 0.46 11.60 V 14.33 V OK V%=2.90%

A OK 0.85 72 A OK 2.50 0.65 V 6.08 V OK V%=0.28%


Convert to 3Phase 1.13 V
LHG-K2 : Final Point Voltage Drop (Less than 4%) 15.46 V V%= 3.86%

Voltage Drop shall be less than 3%. - 147 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage Drop Total Voltage
Judge Factor Judge Voltage Drop (v) Judge
Cap (A) Cap (A) (v) Drop (%)
mV/A/m
A OK 0.85 237 A OK 0.62 7.32 V 10.05 V OK V%=1.83%
A OK 0.85 45 A OK 6.80 2.25 V 7.68 V OK V%=0.98%
Convert to 3Phase 3.90 V
LHG-K31 : Final Point Voltage Drop (Less than 4%) 13.95 V V%= 3.49%
A OK 0.85 338 A OK 0.38 6.65 V 9.38 V OK V%=1.66%
A OK 0.85 119 A OK 1.60 1.57 V 7.00 V OK V%=0.39%
LHG-K31 : Final Point Voltage Drop (Less than 4%) 10.95 V V%= 2.74%
A OK 0.85 72 A OK 2.50 5.86 V 8.59 V OK V%=1.47%
A OK 0.85 20 A OK 18.00 1.41 V 12.29 V ###
Convert to 3Phase 2.44 V
LHG-K32 : Final Point Voltage Drop (Less than 4%) 11.03 V V%= 2.76%
A OK 0.85 183 A OK 0.87 9.49 V 12.22 V OK V%=2.37%
A OK 0.85 26 A OK 16.00 3.14 V 8.57 V OK V%=0.79%
LHG-K4 : Final Point Voltage Drop (Less than 4%) 15.36 V V%= 3.84%
A OK 0.85 119 A OK 1.60 6.95 V 9.68 V OK V%=1.74%
A OK 0.85 35 A OK 10.00 2.92 V 8.35 V OK V%=0.73%
LHG-K1 : Final Point Voltage Drop (Less than 4%) 12.60 V V%= 3.15%
A OK 0.85 451 A OK 0.28 9.95 V 12.68 V OK V%=2.49%
A OK 0.85 62 A OK 4.00 1.18 V 6.61 V OK V%=0.51%
Convert to 3Phase 2.04 V
LH1-K1 : Final Point Voltage Drop (Less than 4%) 14.72 V V%= 3.68%
A OK 0.85 183 A OK 0.87 10.09 V 12.82 V OK V%=2.52%
A OK 0.85 119 A OK 1.60 1.57 V 7.00 V OK V%=0.39%
LHG-K1 : Final Point Voltage Drop (Less than 4%) 14.39 V V%= 3.6%
A OK 0.85 150 A OK 1.15 9.90 V 12.63 V OK V%=2.48%
A OK 0.85 72 A OK 2.50 1.22 V 6.65 V OK V%=0.53%
Convert to 3Phase 2.11 V
LH1-K2 : Final Point Voltage Drop (Less than 4%) 14.74 V V%= 3.69%
A OK 0.85 392 A OK 0.32 10.54 V 13.27 V OK V%=2.64%
A OK 0.85 119 A OK 1.60 1.69 V 7.12 V OK V%=0.42%
LHG-K2 : Final Point Voltage Drop (Less than 4%) 14.96 V V%= 3.74%
A OK 0.85 290 A OK 0.46 6.55 V 9.28 V OK V%=1.64%
A OK 0.85 20 A OK 18.00 2.35 V 13.23 V ###
Convert to 3Phase 4.07 V
LH2-K1 : Final Point Voltage Drop (Less than 4%) 13.35 V V%= 3.34%
A OK 0.85 237 A OK 0.62 11.29 V 14.02 V OK V%=2.82%

Voltage Drop shall be less than 3%. - 148 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage Drop Total Voltage
Judge Factor Judge Voltage Drop (v) Judge
Cap (A) Cap (A) (v) Drop (%)
mV/A/m

A OK 0.85 62 A OK 4.00 1.50 V 6.93 V OK V%=0.38%


LH8-K1 : Final Point Voltage Drop (Less than 4%) 15.52 V V%= 3.88%
A OK 0.85 237 A OK 0.62 11.35 V 14.08 V OK V%=2.84%
A OK 0.85 119 A OK 1.60 0.56 V 5.99 V OK V%=0.14%
LHB1-L1 : Final Point Voltage Drop (Less than 4%) 14.64 V V%= 3.66%

Voltage Drop shall be less than 3%. - 149 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage Drop Total Voltage
Judge Factor Judge Voltage Drop (v) Judge
Cap (A) Cap (A) (v) Drop (%)
mV/A/m

A OK 0.85 621 A OK 0.21 3.11 V 5.84 V OK V%=0.78%


Total Voltage Drop 5.84 V
A OK 0.85 150 A OK 1.15 2.20 V 8.04 V OK V%=0.55%
A OK 0.85 20 A OK 18.00 0.47 V 11.35 V ###
Convert to 3Phase 0.81 V
LHG-T2 : Final Point Voltage Drop (Less than 4%) 8.85 V V%= 2.21%
A OK 0.85 35 A OK 10.00 5.96 V 11.80 V OK V%=1.49%
A OK 0.85 20 A OK 18.00 0.47 V 11.35 V ###
Convert to 3Phase 0.81 V
LHG-T3 : Final Point Voltage Drop (Less than 4%) 12.61 V V%= 3.15%
A OK 0.85 45 A OK 6.80 4.97 V 10.81 V OK V%=1.24%
A OK 0.85 20 A OK 18.00 0.47 V 11.35 V ###
Convert to 3Phase 0.81 V
LHG-T4 : Final Point Voltage Drop (Less than 4%) 11.62 V V%= 2.91%
A OK 0.85 150 A OK 1.15 3.70 V 9.54 V OK V%=0.93%
A OK 0.85 20 A OK 18.00 0.47 V 11.35 V ###
Convert to 3Phase 0.81 V
LHG-T5 : Final Point Voltage Drop (Less than 4%) 10.35 V V%= 2.59%
A OK 0.85 183 A OK 0.87 4.16 V 10.00 V OK V%=1.04%
A OK 0.85 20 A OK 18.00 0.47 V 11.35 V ###
Convert to 3Phase 0.81 V
LHG-T6 : Final Point Voltage Drop (Less than 4%) 10.81 V V%= 2.7%
A OK 0.85 62 A OK 4.00 5.06 V 10.90 V OK V%=1.27%
A OK 0.85 20 A OK 18.00 0.47 V 11.35 V ###
Convert to 3Phase 0.81 V
LHG-T6 : Final Point Voltage Drop (Less than 4%) 11.71 V V%= 2.93%
A OK 0.85 62 A OK 4.00 5.02 V 10.86 V OK V%=1.26%
A OK 0.85 20 A OK 18.00 0.47 V 11.35 V ###
Convert to 3Phase 0.81 V
LHG-T8 : Final Point Voltage Drop (Less than 4%) 11.67 V V%= 2.92%
A OK 0.85 62 A OK 4.00 4.06 V 9.90 V OK V%=1.02%
A OK 0.85 20 A OK 18.00 2.82 V 13.70 V ###
Convert to 3Phase 4.88 V
LHG-T9 : Final Point Voltage Drop (Less than 4%) 14.78 V V%= 3.7%
0 0.00

Voltage Drop shall be less than 3%. - 150 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage Drop Total Voltage
Judge Factor Judge Voltage Drop (v) Judge
Cap (A) Cap (A) (v) Drop (%)
mV/A/m

A OK 0.85 290 A OK 0.46 2.81 V 5.54 V OK V%=0.70%


Total Voltage Drop 5.54 V
A OK 0.85 35 A OK 10.00 5.20 V 10.74 V OK V%=1.30%
A OK 0.85 20 A OK 18.00 0.49 V 11.37 V ###
Convert to 3Phase 0.85 V

Voltage Drop shall be less than 3%. - 151 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage Drop Total Voltage
Judge Factor Judge Voltage Drop (v) Judge
Cap (A) Cap (A) (v) Drop (%)
mV/A/m

LHB2-P1: Final Point Voltage Drop (Less than 4%) 11.59 V V%= 2.9%
A OK 0.85 35 A OK 10.00 2.78 V 8.32 V OK V%=0.70%
A OK 0.85 20 A OK 18.00 0.49 V 11.37 V ###
Convert to 3Phase 0.85 V
LHB1-P1: Final Point Voltage Drop (Less than 4%) 9.17 V V%= 2.29%
A OK 0.85 72 A OK 2.50 3.83 V 9.37 V OK V%=0.96%
A OK 0.85 45 A OK 6.80 2.86 V 2.86 V OK V%= 0.72%
P-H-B2-01: Final Point Voltage Drop (Less than 4%) 12.23 V V%= 3.06%
A OK 0.85 72 A OK 2.50 4.15 V 9.69 V OK V%=1.04%
A OK 0.85 35 A OK 10.00 2.91 V 2.91 V OK V%= 0.73%
P-H-B2-02: Final Point Voltage Drop (Less than 4%) 12.60 V V%= 3.15%
A OK 0.85 72 A OK 2.50 3.25 V 8.79 V OK V%=0.81%
A OK 0.85 35 A OK 10.00 2.91 V 2.91 V OK V%= 0.73%
P-H-B2-02: Final Point Voltage Drop (Less than 4%) 11.70 V V%= 2.93%
A OK 0.85 119 A OK 1.60 0.53 V 6.07 V OK V%=0.13%
Well Pump-5: Final Point Voltage Drop (Less than 4%) 6.07 V V%= 1.52%
0 0.00
A OK 0.85 290 A OK 0.46 4.86 V 7.59 V OK V%=1.22%
Total Voltage Drop 7.59 V
A OK 0.85 35 A OK 10.00 2.90 V 10.49 V OK V%=0.73%
A OK 0.85 20 A OK 18.00 2.47 V 13.35 V ###
Convert to 3Phase 4.28 V
LHB2-P2: Final Point Voltage Drop (Less than 4%) 14.77 V V%= 3.69%
A OK 0.85 35 A OK 10.00 3.24 V 10.83 V OK V%=0.81%
A OK 0.85 20 A OK 18.00 1.97 V 12.85 V ###
Convert to 3Phase 3.41 V
LHB1-P2: Final Point Voltage Drop (Less than 4%) 14.24 V V%= 3.56%
A OK 0.85 35 A OK 10.00 0.98 V 8.57 V OK V%=0.25%
A OK 0.85 20 A OK 18.00 3.52 V 14.40 V ###
Convert to 3Phase 6.10 V
LHB1-C1: Final Point Voltage Drop (Less than 4%) 14.67 V V%= 3.67%
A OK 0.85 119 A OK 1.60 1.09 V 8.68 V OK V%=0.27%
Well Pump-3: Final Point Voltage Drop (Less than 4%) 8.68 V V%= 2.17%
A OK 0.85 119 A OK 1.60 1.08 V 8.67 V OK V%=0.27%
Well Pump-4: Final Point Voltage Drop (Less than 4%) 8.67 V V%= 2.17%

Voltage Drop shall be less than 3%. - 152 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage Drop Total Voltage
Judge Factor Judge Voltage Drop (v) Judge
Cap (A) Cap (A) (v) Drop (%)
mV/A/m

0 0.00
A OK 0.85 237 A OK 0.62 4.48 V 7.21 V OK V%=1.12%
Total Voltage Drop 7.21 V
A OK 0.85 72 A OK 2.50 1.73 V 8.94 V OK V%=0.43%
A OK 0.85 20 A OK 18.00 1.97 V 12.85 V ###
Convert to 3Phase 3.41 V
LHG-C1: Final Point Voltage Drop (Less than 4%) 12.35 V V%= 3.09%
A OK 0.85 72 A OK 2.50 0.64 V 7.85 V OK V%=0.16%
A OK 0.85 45 A OK 6.80 1.22 V 1.22 V OK V%= 0.31%
P-H-G-01: Final Point Voltage Drop (Less than 4%) 9.07 V V%= 2.27%

Voltage Drop shall be less than 3%. - 153 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage Drop Total Voltage
Judge Factor Judge Voltage Drop (v) Judge
Cap (A) Cap (A) (v) Drop (%)
mV/A/m

A OK 0.85 72 A OK 2.50 0.84 V 8.05 V OK V%=0.21%


A OK 0.85 72 A OK 2.50 1.02 V 1.02 V OK V%= 0.26%
P-H-G-02: Final Point Voltage Drop (Less than 4%) 9.07 V V%= 2.27%
A OK 0.85 119 A OK 1.60 0.26 V 7.47 V OK V%=0.07%
Well Pump-2: Final Point Voltage Drop (Less than 4%) 7.47 V V%= 1.87%
0 0.00
A OK 0.85 392 A OK 0.32 5.42 V 8.15 V OK V%=1.36%
A OK 0.85 20 A OK 18.00 1.62 V 12.50 V ###
Convert to 3Phase 2.81 V
LHG-C2: Final Point Voltage Drop (Less than 4%) 15.44 V V%= 3.86%
0 0.00
A OK 0.85 119 A OK 1.60 2.79 V 5.52 V OK V%=0.70%
Total Voltage Drop 5.52 V
A OK 0.85 45 A OK 6.80 1.04 V 6.56 V OK V%=0.26%
A OK 0.85 20 A OK 18.00 4.93 V 15.81 V ###
Convert to 3Phase 8.54 V
LHM-C1: Final Point Voltage Drop (Less than 4%) 15.10 V V%= 3.77%
A OK 0.85 62 A OK 4.00 2.44 V 7.96 V OK V%=0.61%
A OK 0.85 35 A OK 10.00 1.45 V 1.45 V OK V%= 0.36%
P-H-M1-01: Final Point Voltage Drop (Less than 4%) 9.41 V V%= 2.35%
A OK 0.85 72 A OK 2.50 3.85 V 9.37 V OK V%=0.96%
A OK 0.85 45 A OK 6.80 1.84 V 1.84 V OK V%= 0.46%
P-H-GF-06: Final Point Voltage Drop (Less than 4%) 11.21 V V%= 2.8%
0 0.00
A OK 0.85 237 A OK 0.62 6.53 V 9.26 V OK V%=1.63%
Total Voltage Drop 6.67 V
A OK 0.85 62 A OK 4.00 1.37 V 10.63 V OK V%=0.34%
A OK 0.85 20 A OK 18.00 2.47 V 13.35 V ###
Convert to 3Phase 4.28 V
LHM-C2: Final Point Voltage Drop (Less than 4%) 12.32 V V%= 3.08%
A OK 0.85 150 A OK 1.15 2.98 V 12.24 V OK V%=0.75%
A OK 0.85 72 A OK 2.50 1.01 V 1.01 V OK V%= 0.25%
P-H-GF-03: Final Point Voltage Drop (Less than 4%) 10.66 V V%= 2.66%
A OK 0.85 45 A OK 6.80 2.28 V 11.54 V OK V%=0.57%
A OK 0.85 35 A OK 10.00 1.45 V 1.45 V OK V%= 0.36%

Voltage Drop shall be less than 3%. - 154 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage Drop Total Voltage
Judge Factor Judge Voltage Drop (v) Judge
Cap (A) Cap (A) (v) Drop (%)
mV/A/m

P-H-GF-04: Final Point Voltage Drop (Less than 4%) 10.40 V V%= 2.6%
0 0.00
A OK 0.85 72 A OK 2.50 7.89 V 10.62 V OK V%=1.97%
A OK 0.85 20 A OK 18.00 2.47 V 13.35 V ###
Convert to 3Phase 4.28 V
LHM-C2: Final Point Voltage Drop (Less than 4%) 14.90 V V%= 3.72%
0 0.00

Voltage Drop shall be less than 3%. - 155 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage Drop Total Voltage
Judge Factor Judge Voltage Drop (v) Judge
Cap (A) Cap (A) (v) Drop (%)
mV/A/m

A OK 0.85 451 A OK 0.28 2.70 V 5.43 V OK V%=0.68%


Total Voltage Drop 5.43 V
A OK 0.85 119 A OK 1.60 1.12 V 6.55 V OK V%=0.28%
A OK 0.85 26 A OK 16.00 4.71 V 10.14 V OK V%=1.18%
LH1-C1: Final Point Voltage Drop (Less than 4%) 11.26 V V%= 2.82%
A OK 0.85 237 A OK 0.62 6.35 V 11.78 V OK V%=1.59%
A OK 0.85 26 A OK 16.00 0.72 V 6.15 V OK V%=0.18%
LH1-C3: Final Point Voltage Drop (Less than 4%) 12.50 V V%= 3.13%
A OK 0.85 72 A OK 2.50 3.88 V 9.31 V OK V%=0.97%
Event panel 1: Final Point Voltage Drop (Less than 4%) 9.31 V V%= 2.33%
A OK 0.85 72 A OK 2.50 6.31 V 11.74 V OK V%=1.58%
Event panel 2: Final Point Voltage Drop (Less than 4%) 11.74 V V%= 2.94%
A OK 0.85 62 A OK 4.00 4.10 V 9.53 V OK V%=1.03%
Event panel 3: Final Point Voltage Drop (Less than 4%) 9.53 V V%= 2.38%
A OK 0.85 62 A OK 4.00 4.50 V 9.93 V OK V%=1.13%
Event panel 4: Final Point Voltage Drop (Less than 4%) 9.93 V V%= 2.48%
A OK 0.85 62 A OK 4.00 5.02 V 10.45 V OK V%=1.26%
Event panel 5: Final Point Voltage Drop (Less than 4%) 10.45 V V%= 2.61%

A OK 0.85 451 A OK 0.28 2.84 V 5.57 V OK V%=0.71%


Total Voltage Drop 5.57 V
A OK 0.85 183 A OK 0.87 3.91 V 9.48 V OK V%=0.98%
A OK 0.85 45 A OK 6.80 1.77 V 7.20 V OK V%=0.44%
AV power panel G1: Final Point Voltage Drop (Less than 4%) 11.25 V V%= 2.81%
A OK 0.85 183 A OK 0.87 6.36 V 11.93 V OK V%=1.59%
A OK 0.85 45 A OK 6.80 1.77 V 7.20 V OK V%=0.44%
AV power panel G2: Final Point Voltage Drop (Less than 4%) 13.70 V V%= 3.43%
A OK 0.85 72 A OK 2.50 5.64 V 11.21 V OK V%=1.41%
A OK 0.85 45 A OK 6.80 1.77 V 7.20 V OK V%=0.44%
AV power panel F1: Final Point Voltage Drop (Less than 4%) 12.98 V V%= 3.25%
A OK 0.85 72 A OK 2.50 6.19 V 11.76 V OK V%=1.55%
A OK 0.85 45 A OK 6.80 1.77 V 7.20 V OK V%=0.44%
AV power panel F2: Final Point Voltage Drop (Less than 4%) 13.53 V V%= 3.38%
A OK 0.85 72 A OK 2.50 6.91 V 12.48 V OK V%=1.73%
A OK 0.85 45 A OK 6.80 1.77 V 7.20 V OK V%=0.44%

Voltage Drop shall be less than 3%. - 156 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage Drop Total Voltage
Judge Factor Judge Voltage Drop (v) Judge
Cap (A) Cap (A) (v) Drop (%)
mV/A/m

AV power panel F3: Final Point Voltage Drop (Less than 4%) 14.25 V V%= 3.56%
A OK 0.85 35 A OK 10.00 3.86 V 9.43 V OK V%=0.97%
A OK 0.85 35 A OK 10.00 1.45 V 1.45 V OK V%= 0.36%
P-H-1-01: Final Point Voltage Drop (Less than 4%) 10.88 V V%= 2.72%
0 0.00

Voltage Drop shall be less than 3%. - 157 / 159 -


DATE:
08-Nov-17

Factor
Cable Carry Actual Cable Carry Total Voltage Drop Total Voltage
Judge Factor Judge Voltage Drop (v) Judge
Cap (A) Cap (A) (v) Drop (%)
mV/A/m

A OK 0.85 290 A OK 0.46 6.82 V 9.55 V OK V%=1.71%


P-WT-B1-03 : Final Point Voltage Drop (Less than 4%) 9.55 V V%= 2.39%
A OK 0.85 150 A OK 1.15 6.84 V 9.57 V OK V%=1.71%
P-WT-B1-05 : Final Point Voltage Drop (Less than 4%) 9.57 V V%= 2.39%
A OK 0.85 45 A OK 6.80 6.08 V 8.81 V OK V%=1.52%
P-WT-B1-06 : Final Point Voltage Drop (Less than 4%) 8.81 V V%= 2.2%
A OK 0.85 45 A OK 6.80 3.35 V 6.08 V OK V%=0.84%
P-WT-1F-04: Final Point Voltage Drop (Less than 4%) 6.08 V V%= 1.52%
A OK 0.85 72 A OK 2.50 8.85 V 11.58 V OK V%=2.21%
P-WT-2F-04 : Final Point Voltage Drop (Less than 4%) 11.58 V V%= 2.9%
A OK 0.85 290 A OK 0.46 9.16 V 11.89 V OK V%=2.29%
Server UPS(MF): Final Point Voltage Drop (Less than 4%) 11.89 V V%= 2.97%
0 0.00
A OK 0.85 150 A OK 1.15 9.11 V 14.68 V OK V%=2.28%
A OK 0.85 45 A OK 6.80 2.06 V 2.06 V OK V%= 0.52%
P-H-1-02: Final Point Voltage Drop (Less than 4%) 13.90 V V%= 3.48%
0 0.00
0 0.00

Voltage Drop shall be less than 3%. - 158 / 159 -


2 Core 3 Core 2 Core 3 Core
Method Method Method Method Method Method
2cable, DC Method 3 Method 12 Method 3 Method 12 2cable, DC Method 3 Method 12 Method 3 Method 12
1,11 1,11 1,11 1,11 1,11 1,11
(Trefoil) (Touch) (Trefoil) (Touch)
Group Cables A A A A A A A A mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m
*1 *2 *3 *4 *5 *6 *7 *8 *1 *2 *3 *4 *5 *6 *7 *8

3c 2.5xp 3C 2.5sqmm XLPE/PVC 23 31 31 31 18 16 16 16 16 15


3c 4xp 3C 4sqmm XLPE/PVC 30 41 41 41 11 10 10 10 10 20
3c 6xp 3C 6sqmm XLPE/PVC 38 53 56 53 7.3 6.8 6.8 6.8 6.8 30
3c 10xp 3C 10sqmm XLPE/PVC 52 78 78 73 4.4 4 4 4 4 40
3c 16xp 3C 16sqmm XLPE/PVC 69 85 85 85 85 2.8 2.5 2.5 2.5 2.5 50
3c 25xp 3C 25sqmm XLPE/PVC 111 140 140 138 1.65 1.6 1.6 1.65 60
3c 35xp 3C 35sqmm XLPE/PVC 146 185 138 176 176 171 1.35 1.35 1.35 1.35 1.15 1.15 1.15 1.2 75
3c 50xp 3C 50sqmm XLPE/PVC 175 225 168 215 215 209 1 1 1 1 0.9 0.87 0.87 0.89 100
3c 70xp 3C 70sqmm XLPE/PVC 221 289 214 279 279 270 0.69 0.69 0.69 0.69 0.65 0.61 0.62 0.65 125
3c 95xp 3C 95sqmm XLPE/PVC 290 375 259 341 341 330 0.49 0.58 0.52 0.56 0.5 0.45 0.46 0.49 150
3c 120xp 3C 120sqmm XLPE/PVC 263 336 436 453 299 398 398 385 0.39 0.48 0.43 0.47 0.42 0.37 0.38 0.42 175
3c 150xp 3C 150sqmm XLPE/PVC 300 375 505 524 328 461 461 445 0.32 0.43 0.36 0.41 0.37 0.31 0.32 0.37 200
3c 185xp 3C 185sqmm XLPE/PVC 341 426 530 600 370 530 530 511 0.25 0.37 0.3 0.36 0.32 0.26 0.28 0.33 225
3c 240xp 3C 240sqmm XLPE/PVC 400 500 686 711 433 630 630 606 0.19 0.33 0.25 0.31 0.29 0.22 0.24 0.29 250
3c 300xp 3C 300sqmm XLPE/PVC 459 573 794 824 493 730 730 701 0.155 0.31 0.22 0.29 0.27 0.195 0.21 0.27 300
3c 400xp 3C 400sqmm XLPE/PVC 683 915 994 584 849 849 994 0.12 0.29 0.2 0.27 0.25 0.175 0.195 0.26 350
4c 2.5xp 4C 2.5sqmm XLPE/PVC 31 31 31 16 16 16 16 400
4c 4xp 4C 4sqmm XLPE/PVC 41 41 41 10 10 10 10 500
4c 6xp 4C 6sqmm XLPE/PVC 53 56 53 6.8 6.8 6.8 6.8 600
4c 10xp 4C 10sqmm XLPE/PVC 78 78 73 4 4 4 4 700
4c 16xp 4C 16sqmm XLPE/PVC 85 85 85 85 2.5 2.5 2.5 2.5 800
4c 25xp 4C 25sqmm XLPE/PVC 111 140 140 138 1.65 1.6 1.6 1.65 1000
4c 35xp 4C 35sqmm XLPE/PVC 146 185 138 176 176 171 1.35 1.35 1.35 1.35 1.15 1.15 1.15 1.2 1250
4c 50xp 4C 50sqmm XLPE/PVC 175 225 168 215 215 209 1 1 1 1 0.9 0.87 0.87 0.89 1600
4c 70xp 4C 70sqmm XLPE/PVC 221 289 214 279 279 270 0.69 0.69 0.69 0.69 0.65 0.61 0.62 0.65 2000
4c 95xp 4C 95sqmm XLPE/PVC 290 375 259 341 341 330 0.49 0.58 0.52 0.56 0.5 0.45 0.46 0.49 2500
3c 120xp+N 3C 120+1C 70sqmm XLPE/PVC 263 336 436 453 299 398 398 385 0.39 0.48 0.43 0.47 0.42 0.37 0.38 0.42 3200
3c 150xp+N 3C 150+1C 70sqmm XLPE/PVC 300 375 505 524 328 461 461 445 0.32 0.43 0.36 0.41 0.37 0.31 0.32 0.37 4000
3c 185xp+N 3C 185+1C 95sqmm XLPE/PVC 341 426 530 600 370 530 530 511 0.25 0.37 0.3 0.36 0.32 0.26 0.28 0.33 5000
3c 240xp+N 3C 240+1C 120sqmm XLPE/PVC 400 500 686 711 433 630 630 606 0.19 0.33 0.25 0.31 0.29 0.22 0.24 0.29 6300
3c 300xp+N 3C 300+1C 150sqmm XLPE/PVC 459 573 794 824 493 730 730 701 0.155 0.31 0.22 0.29 0.27 0.195 0.21 0.27
3c 400xp+N 3C 400+1C 185sqmm XLPE/PVC 683 915 994 584 849 849 994 0.12 0.29 0.2 0.27 0.25 0.175 0.195 0.26
4x1 95xp 4x1C 95sqmm XLPE/PVC 228 290 375 389 259 341 341 330 0.49 0.58 0.52 0.56 0.5 0.45 0.46 0.49
4x1 120xp 4x1C 120sqmm XLPE/PVC 263 336 436 453 299 398 398 385 0.39 0.48 0.43 0.47 0.42 0.37 0.38 0.42
4x1 150xp 4x1C 150sqmm XLPE/PVC 300 375 505 524 328 461 461 445 0.32 0.43 0.36 0.41 0.37 0.31 0.32 0.37
4x1 185xp 4x1C 185sqmm XLPE/PVC 341 426 530 600 370 530 530 511 0.25 0.37 0.3 0.36 0.32 0.26 0.28 0.33
4x1 240xp 4x1C 240sqmm XLPE/PVC 400 500 686 711 433 630 630 606 0.19 0.33 0.25 0.31 0.29 0.22 0.24 0.29
4x1 300xp 4x1C 300sqmm XLPE/PVC 459 573 794 824 493 730 730 701 0.155 0.31 0.22 0.29 0.27 0.195 0.21 0.27
4x1 400xp 4x1C 400sqmm XLPE/PVC 683 915 994 584 849 849 994 0.12 0.29 0.2 0.27 0.25 0.175 0.195 0.26
4x1 500xp 4x1C 500sqmm XLPE/PVC 786 1044 1150 666 973 973 936 0.093 0.28 0.185 0.26 0.24 0.16 0.18 0.25
4x1 630xp 4x1C 630sqmm XLPE/PVC 900 1191 1338 764 1115 1115 1069 0.072 0.27 0.175 0.25 0.23 0.15 0.17 0.24
6x1 120xp 6x1C 120sqmm XLPE/PVC 526 672 872 906 598 796 796 770 0.195 0.24 0.215 0.235 0.21 0.185 0.19 0.21
6x1 150xp 6x1C 150sqmm XLPE/PVC 600 750 1010 1048 656 922 922 890 0.16 0.215 0.18 0.205 0.185 0.155 0.16 0.185
6x1 185xp 6x1C 185sqmm XLPE/PVC 682 852 1060 1200 740 1060 1060 1022 0.125 0.185 0.15 0.18 0.16 0.13 0.14 0.165
6x1 240xp 6x1C 240sqmm XLPE/PVC 800 1000 1372 1422 866 1260 1260 1212 0.095 0.165 0.125 0.155 0.145 0.11 0.12 0.145
6x1 300xp 6x1C 300sqmm XLPE/PVC 918 1146 1588 1648 986 1460 1460 1402 0.078 0.155 0.11 0.145 0.135 0.098 0.105 0.135
6x1 400xp 6x1C 400sqmm XLPE/PVC 0 1366 1830 1988 1168 1698 1698 1988 0.06 0.145 0.1 0.135 0.125 0.088 0.098 0.13
6x1 500xp 6x1C 500sqmm XLPE/PVC 0 1572 2088 2300 1332 1946 1946 1872 0.047 0.14 0.093 0.13 0.12 0.08 0.09 0.125
6x1 630xp 6x1C 630sqmm XLPE/PVC 0 1800 2382 2676 1528 2230 2230 2138 0.036 0.135 0.088 0.125 0.115 0.075 0.085 0.12
8x1 120xp 8x1C 120sqmm XLPE/PVC 526 672 872 906 598 796 796 770 0.195 0.24 0.215 0.235 0.21 0.185 0.19 0.21
8x1 150xp 8x1C 150sqmm XLPE/PVC 600 750 1010 1048 656 922 922 890 0.16 0.215 0.18 0.205 0.185 0.155 0.16 0.185
8x1 185xp 8x1C 185sqmm XLPE/PVC 682 852 1060 1200 740 1060 1060 1022 0.125 0.185 0.15 0.18 0.16 0.13 0.14 0.165
8x1 240xp 8x1C 240sqmm XLPE/PVC 800 1000 1372 1422 866 1260 1260 1212 0.095 0.165 0.125 0.155 0.145 0.11 0.12 0.145
8x1 300xp 8x1C 300sqmm XLPE/PVC 918 1146 1588 1648 986 1460 1460 1402 0.078 0.155 0.11 0.145 0.135 0.098 0.105 0.135
8x1 400xp 8x1C 400sqmm XLPE/PVC 0 1366 1830 1988 1168 1698 1698 1988 0.06 0.145 0.1 0.135 0.125 0.088 0.098 0.13
8x1 500xp 8x1C 500sqmm XLPE/PVC 0 1572 2088 2300 1332 1946 1946 1872 0.047 0.14 0.093 0.13 0.12 0.08 0.09 0.125
8x1 630xp 8x1C 630sqmm XLPE/PVC 0 1800 2382 2676 1528 2230 2230 2138 0.036 0.135 0.088 0.125 0.115 0.075 0.085 0.12
12x1 150xp 12x1C 150sqmm XLPE/PVC 900 1125 1515 1572 984 1383 1383 1335 0.107 0.143 0.12 0.137 0.123 0.103 0.107 0.123
12x1 185xp 12x1C 185sqmm XLPE/PVC 1023 1278 1590 1800 1110 1590 1590 1533 0.083 0.123 0.1 0.12 0.107 0.087 0.093 0.11
12x1 240xp 12x1C 240sqmm XLPE/PVC 1200 1500 2058 2133 1299 1890 1890 1818 0.063 0.11 0.083 0.103 0.097 0.073 0.08 0.097
12x1 300xp 12x1C 300sqmm XLPE/PVC 1377 1719 2382 2472 1479 2190 2190 2103 0.052 0.103 0.073 0.097 0.09 0.065 0.07 0.09
12x1 400xp 12x1C 400sqmm XLPE/PVC 0 2049 2745 2982 1752 2547 2547 2982 0.04 0.097 0.067 0.09 0.083 0.058 0.065 0.087
12x1 500xp 12x1C 500sqmm XLPE/PVC 0 2358 3132 3450 1998 2919 2919 2808 0.031 0.093 0.062 0.087 0.08 0.053 0.06 0.083
12x1 630xp 12x1C 630sqmm XLPE/PVC 0 2700 3573 4014 2292 3345 3345 3207 0.024 0.09 0.058 0.083 0.077 0.05 0.057 0.08
16x1 185xp 16x1C 185sqmm XLPE/PVC 1364 1704 2120 2400 1480 2120 2120 2044 0.063 0.093 0.075 0.09 0.08 0.065 0.07 0.083
16x1 240xp 16x1C 240sqmm XLPE/PVC 1600 2000 2744 2844 1732 2520 2520 2424 0.048 0.083 0.063 0.078 0.073 0.055 0.06 0.073
16x1 300xp 16x1C 300sqmm XLPE/PVC 1836 2292 3176 3296 1972 2920 2920 2804 0.039 0.078 0.055 0.073 0.068 0.049 0.053 0.068
16x1 400xp 16x1C 400sqmm XLPE/PVC 0 2732 3660 3976 2336 3396 3396 3976 0.03 0.073 0.05 0.068 0.063 0.044 0.049 0.065
16x1 500xp 16x1C 500sqmm XLPE/PVC 0 3144 4176 4600 2664 3892 3892 3744 0.023 0.07 0.046 0.065 0.06 0.04 0.045 0.063
16x1 630xp 16x1C 630sqmm XLPE/PVC 0 3600 4764 5352 3056 4460 4460 4276 0.018 0.068 0.044 0.063 0.058 0.038 0.043 0.06
20x1 240xp 20x1C 240sqmm XLPE/PVC 2000 2500 3430 3555 2165 3150 3150 3030 0.038 0.066 0.05 0.062 0.058 0.044 0.048 0.058
20x1 300xp 20x1C 300sqmm XLPE/PVC 2295 2865 3970 4120 2465 3650 3650 3505 0.031 0.062 0.044 0.058 0.054 0.039 0.042 0.054
20x1 400xp 20x1C 400sqmm XLPE/PVC 0 3415 4575 4970 2920 4245 4245 4970 0.024 0.058 0.04 0.054 0.05 0.035 0.039 0.052
20x1 500xp 20x1C 500sqmm XLPE/PVC 0 3930 5220 5750 3330 4865 4865 4680 0.019 0.056 0.037 0.052 0.048 0.032 0.036 0.05
20x1 630xp 20x1C 630sqmm XLPE/PVC 0 4500 5955 6690 3820 5575 5575 5345 0.014 0.054 0.035 0.05 0.046 0.03 0.034 0.048
24x1 240xp 24x1C 240sqmm XLPE/PVC 2400 3000 4116 4266 2598 3780 3780 3636 0.032 0.055 0.042 0.052 0.048 0.037 0.04 0.048
24x1 300xp 24x1C 300sqmm XLPE/PVC 2754 3438 4764 4944 2958 4380 4380 4206 0.026 0.052 0.037 0.048 0.045 0.033 0.035 0.045
28x1 240xp 28x1C 240sqmm XLPE/PVC 2800 5502 7308 8050 4662 6811 6811 6552 0.027 0.047 0.036 0.044 0.041 0.031 0.034 0.041
28x1 300xp 28x1C 300sqmm XLPE/PVC 0 6300 8337 9366 5348 7805 7805 7483 0.022 0.044 0.031 0.041 0.039 0.028 0.03 0.039
32x1 240xp 32x1C 240sqmm XLPE/PVC 0 6288 8352 9200 5328 7784 7784 7488 0.01163 0.035 0.02313 0.0325 0.03 0.02 0.0225 0.03125
32x1 300xp 32x1C 300sqmm XLPE/PVC 0 7200 9528 10704 6112 8920 8920 8552 0.009 0.03375 0.02188 0.03125 0.02875 0.01875 0.02125 0.03 0.85
40x1 240xp 10x3C 240+1C 120sqmm XLPE/PVC 4000 5000 6860 7110 4330 6300 6300 6060 0.02 0.03 0.03 0.03 0.03 0.02 0.02 0.03
BD 400 4W BD 400 4W Cu-Fe 400 0.2383 9.53
BD 630 4W BD 630 4W Cu-Fe 630 0.1452 9.15
BD 800 4W BD 800 4W Cu-Fe 800 0.1304 10.43
BD 1000 4W BD 1000 4W Cu-Fe 1000 0.0982 9.82
BD 1250 4W BD 1250 4W Cu-Fe 1250 0.0729 9.11
BD 1500 4W BD 1500 4W Cu-Fe 1500 0.0624 9.36
BD 1600 4W BD 1600 4W Cu-Fe 1600 0.0532 8.51
BD 2000 4W BD 2000 4W Cu-Fe 2000 0.0443 8.85
BD 2500 4W BD 2500 4W Cu-Fe 2500 0.0366 9.15
BD 3200 4W BD 3200 4W Cu-Fe 3200 0.0268 8.56
BD 3500 4W BD 3500 4W Cu-Fe 3500 0.0233 8.17
BD 4000 4W BD 4000 4W Cu-Fe 4000 0.0223 8.9
BD 4500 4W BD 4500 4W Cu-Fe 4500 0.0191 8.59
BD 5000 4W BD 5000 4W Cu-Fe 5000 0.0185 9.24

FR3C 2.5 3C-2.5sqmm FR Cable 34 31 19 16


FR3C 4 3C-4.0sqmm FR Cable 46 41 12 10
FR3C 6 3C-6.0sqmm FR Cable 59 54 7.9 6.8
FR3C 10 3C-10sqmm FR Cable 81 74 4.7 4
FR3C 16 3C-16sqmm FR Cable 109 99 2.9 2.5
FR3C 25 3C-25sqmm FR Cable 141 135 1.9 1.65
FR3C 35 3C-35sqmm FR Cable 176 169 1.35 1.16
FR3C 50 3C-50sqmm FR Cable 216 207 1 0.87
FR3C 70 3C-70sqmm FR Cable 279 268 0.69 0.6
FR3C 95 3C-95sqmm FR Cable 342 328 0.52 0.45
FR3C 120 3C-120sqmm FR Cable 400 383 0.42 0.37
FR3C 150 3C-150sqmm FR Cable 464 444 0.35 0.3
FR3C 185 3C-185sqmm FR Cable 533 510 0.29 0.26
FR3C 240 3C-240sqmm FR Cable 634 607 0.24 0.21
FR3C 300 3C-300sqmm FR Cable 736 703 0.21 0.185
FR3C 400 3C-400sqmm FR Cable 868 823 0.19 0.165

FR4C 2.5 4C-2.5sqmm FR Cable 34 31 19 16


FR4C 4 4C-4.0sqmm FR Cable 46 41 12 10
FR4C 6 4C-6.0sqmm FR Cable 59 54 7.9 6.8
FR4C 10 4C-10sqmm FR Cable 81 74 4.7 4
FR4C 16 4C-16sqmm FR Cable 109 99 2.9 2.5
FR4C 25 4C-25sqmm FR Cable 141 135 1.9 1.65
FR4C 35 4C-35sqmm FR Cable 176 169 1.35 1.16
FR4C 50 4C-50sqmm FR Cable 216 207 1 0.87
FR4C 70 4C-70sqmm FR Cable 279 268 0.69 0.6
FR4C 95 4C-95sqmm FR Cable 342 328 0.52 0.45
FR4C 120 4C-120sqmm FR Cable 400 383 0.42 0.37
FR4C 150 4C-150sqmm FR Cable 464 444 0.35 0.3
FR4C 185 4C-185sqmm FR Cable 533 510 0.29 0.26
FR4C 240 4C-240sqmm FR Cable 634 607 0.24 0.21
FR4C 300 4C-300sqmm FR Cable 736 703 0.21 0.185
FR4C 400 4C-400sqmm FR Cable 868 823 0.19 0.165