Sei sulla pagina 1di 1

TEMPERATURE CONTROL FOR NEW EQUIPMENT: GENERAL NOTES:

EXISTING PIPING
SUPPORTS (TYP.)
1. ALL DUCTWORK AND PIPES SHALL BE COORDINATED WITH (OTHER NEW AND EXISTING PIPES AND DUCTWORK ) LIGHTS, STRUCTURAL
MECHANICAL LEGEND
THE CHILLER SHALL BE ENERGIZED AND DE-ENERGIZED BY THE OWNER'S EXISTING BUILDING AUTOMATION SYSTEM (BAS) BASED ON THE
OWNER'S CURRENT OCCUPANCY AND SCHEDULE CONTROL. PRIMARY CHILLED WATER PUMPS (CWP-1 & 2) AND CONDENSER WATER PUMPS SYSTEM, CEILING SUPPORTS AND FRAMING BEFORE INSTALLATION. MINOR DUCT AND PIPE OFFSETS AND MINOR TRANSITIONS SHALL BE AIR SEPARATOR AS
TO COOLING (CDP) SHALL BE CONFIGURED TO OPERATE THROUGH THE BAS IN CONJUNCTION WITH THE NEW CHILLER CONTROLLER. PROVIDED AS REQUIRED. MEASUREMENTS FOR VERTICAL CLEARANCES OF DUCTWORK AND PIPING SHALL BE TAKEN AT THE JOB SITE ANCHOR
TOWER BEFORE INSTALLATION. ANGLE VALVE
WATER COOLED CHILLER: BALANCING VALVE
CWR CDR 2. ALL EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S PUBLISHED INSTRUCTIONS. CAPACITY CAP
GENERAL: THE CHILLER SHALL BE CONTROLLED THROUGH THE UNIT-MOUNTED STAND-ALONE MICROPROCESSOR CONTROLLER AND CEILING CLG
FACTORY-INSTALLED BAS COMMUNICATION MODULES. THE BAS COMMUNICATION MODULES SHALL BE COORDINATED TO INTEROPERATE VIA 3. MATERIALS AND INSTALLATION SHALL COMPLY WITH LOCAL CODES, APPLICABLE PROVISIONS OF LATEST EDITION OF NATIONAL FIRE CHECK VALVE
CWS CDS
THE APPROPRIATE PROTOCOL WITH THE EXISTING NOVAR BAS. PROTECTION ASSOCIATION, LOCAL UTILITY REGULATIONS AND GOVERNMENTAL DEPARTMENTS HAVING JURISDICTION. CIRCUIT SETTER
CS(GPM)
TO SYSTEM 4. CONTRACTOR SHALL SEAL AND FLASH ALL PENETRATIONS IN EXISTING WALLS. CLEANOUT CO CO
THE CHILLER AND ITS PRIMARY CHILLED WATER PUMP (CWP-P1 AND CWP-P2) AND CONDENSER WATER PUMPS (CDP) SHALL BE SEQUENCED IN
EXISTING PIPING ACCORDANCE TO CONTROL SOFTWARE WITHIN THE CHILLER MICROPROCESSORS AND THE BAS. THE CHILLER MICROPROCESSORS SHALL BE COMMON C
ENABLED THROUGH THE BAS SCHEDULE AND AMBIENT TEMPERATURE. AN INPUT SHALL ALLOW FOR OPERATION OVERRIDE. 5. VERIFY WALL OPENINGS WITH STRUCTURE. CONTROL SWITCH S
PRESSURE DEGREES FAHRENHEIT °F
GAUGE (TYP.) CHILLER OPERATION: THE CONTROLS SHALL START AND STOP THE CHILLER BASED UPON THE SYSTEM CHILLED WATER SUPPLY 6. VERIFY THE LOCATION OF ALL THERMOSTATS, TEMPERATURE SENSORS, PANELS AND CONTROL INSTRUMENTS WITH THE OWNER PRIOR TO DIAMETER DIA
TEMPERATURE AND SYSTEM CHILLED WATER RETURN TEMPERATURE. THE CHILLED WATER SUPPLY TEMPERATURE SETPOINT SHALL BE 44°F ROUGH-IN. DIRECTION OF FLOW
(ADJUSTABLE THROUGH THE BAS). UPON A CALL FOR CHILLER STARTUP, THE FOLLOWING SHALL OCCUR:
NEW SCHEDULE 80 CPVC 7. VERIFY LOCATIONS OF NEW AND EXISTING EQUIPMENT AND ROUTE OF PIPING AND DUCTWORK WITH EXISTING CONDITIONS. DIRECTION OF SLOPE DOWN
PIPING (CONDENSER a. START THE CHILLED WATER PUMP. DOMESTIC COLD WATER PIPE CW
WATER PIPING ONLY) b. PROVE THAT CHILLED WATER IS FLOWING THROUGH THE EVAPORATOR. 8. ALL CUTTING AND PATCHING FOR THE INSTALLATION OF NEW WORK IN EXISTING BUILDING SHALL BE DONE BY THE CONTRACTOR. DOWN DN
c. IF CHILLER FLOW IS NOT PROVEN WITHIN A TIME DELAY, A SIGNAL SHALL ALARM THE BAS. THE BAS SHALL DISABLE THE DRY BULB DB
CHILLED WATER FLEXIBLE PIPE 9. COORDINATE THE EXACT LOCATIONS OF CHILLERS, PUMPS, PIPING, DUCTWORK AND OTHER MECHANICAL EQUIPMENT WITH LIGHTS, BEAMS EACH EA
CHILLER.
FLOW SWITCH CONNECTORS AND OTHER BUILDING COMPONENTS. ENTERING WATER TEMPERATURE EWT
d. START THE CONDENSER WATER PUMP.
(TYP.) EXISTING EX
e. PROVE THAT CONDENSER WATER IS FLOWING THROUGH THE CONDENSER.
f. IF CONDENSER FLOW IS NOT PROVEN WITHIN A TIME DELAY, A SIGNAL SHALL ALARM THE BAS. 10. CONTRACTOR SHALL PROVIDE ALL SUPPORTS REQUIRED TO MOUNT MECHANICAL EQUIPMENT, DUCTWORK, PIPING AND ACCESSORIES.
EXISTING, REMOVE FROM THIS POINT
g. OPERATE THE CONDENSER WATER BYPASS/MIXING VALVE TO MAINTAIN REFRIGERANT HEAD PRESSURE REQUIREMENTS
STRAINER (TYP) IN ACCORDANCE WITH THE CHILLER MANUFACTURER'S RECOMMENDATIONS. 11. WHERE PIPE CONNECTIONS ARE SHOWN CONNECTING TO EXISTING, CONTRACTOR SHALL DETERMINE EXACT LOCATIONS AND CONNECTION
EXPANSION JOINT EJ
h. SOFT START THE CHILLER AFTER BOTH CHILLED WATER AND CONDENSER WATER FLOW IS PROVEN. THE CHILLER SHALL SIZES PRIOR TO INSTALLATION.
CONDENSER WATER EXPANSION TANK ET
FLOW SWITCH START UNLOADED AND AFTER AN ADJUSTABLE TIME BECOMES LOADED THROUGH CURRENT LIMITING. CONTROLS
12. NEW PIPING AND PIPE INSULATION SHALL BE AS SPECIFIED. INSULATION THAT IS DAMAGED OR REMOVED FOR NEW WORK SHALL BE FEET FT
SHALL MONITOR THE SYSTEM TEMPERATURES AND ANTICIPATE CHANGES TO ACCOMPLISH SOFT START.
REPLACED, REPAIRED AND SEALED AS REQUIRED. FEET PER MINUTE FPM
R i. THE CHILLER SHALL LOAD AND UNLOAD TO MEET CHILLED WATER SUPPLY SETPOINT. THE CALCULATED SETPOINT FOR
FLEXIBLE PIPE CONNECTION
THE CHILLER SHALL DEPEND UPON:
TO FLOOR DRAIN 13. ALL CHILLED WATER PIPING SHALL BE INSULATED. FLOAT & THERMOSTATIC TRAP
CHILLER (1) SYSTEM SUPPLY WATER TEMPERATURE SETPOINT,
FLOOR FL E ALT H O F V
(2) SYSTEM FLOW SWITCH,
14. EXPOSED PIPING RUNOUTS SHALL BE INSTALLED IN PRACTICAL ALIGNMENT WITH THE BUILDING AND SHALL BE ADEQUATELY SECURED TO FLOW SWITCH FSW FSW NW

IR
O
(3) SYSTEM RETURN WATER TEMPERATURE,
FROM FRM 09 /12/ 17

M
THE BUILDING STRUCTURE.

GI
EXISTING CONCRETE (4) CAPACITY OF THE CHILLER PLANT,

CO M
FUEL OIL SUPPLY PIPE FOS FOS

NI A
HOUSEKEEPING PAD (5) OPERATOR DEFINED MINIMUM CHILLED WATER SETPOINT FOR THE CHILLER
15. PROVIDE ACCESS DOORS OF SUFFICIENT SIZE FOR ALL CONCEALED CONTROLS, DAMPERS OR ANY ITEMS REQUIRING ACCESS. GALLONS PER MINUTE GPM
j. THE CONTROLS SHALL ALLOW ADJUSTABLE TIME DELAYS FOR CHILLER START/STOP TO PREVENT EXCESSIVE CHILLER GAS COCK
CYCLING. GLOBE VALVE GBV
16. ALL REMOTE MOUNTED TEMPERATURE CONTROL DEVICES AND TEMPERATURE CONTROL WIRING SHALL BE FURNISHED AND INSTALLED BY
HEATING WATER PUMP HWP

R
THE CONTRACTOR.

PR
CHILLER MALFUNCTION SHALL BE COMMUNICATED TO THE BAS FOR ALARM.

EE
FLOOR HEATING WATER RETURN PIPE HWR HWR

O
FE
17. ALL EQUIPMENT SHALL BE SECURED TO CONCRETE HOUSEKEEPING PADS WITH HOLD-DOWN BOLTS TO PREVENT MOVEMENT. HEATING WATER SUPPLY PIPE HWS HWS SS IN
HOSE END DRAIN VALVES (TYP.) CHILLER CONTROL PANEL SHALL BACNET INTERFACE WITH THE BAS AND PROVIDE THE FOLLOWING FEATURES AT THE CENTRAL BUILDING HORSEPOWER HP IO NA L ENG
NEOPRENE VIBRATION CONTROL STATION.
18. CONDUIT, WIRING, PIPING AND SUPPORTS SHALL NOT IMPEDE MECHANICAL EQUIPMENT ACCESS. HOUR HR
ISOLATION PADS (TYP.)
INCH IN
THE FOLLOWING POINTS SHALL BE MONITORED BY THE CHILLER CONTROL SYSTEM AND SHALL BE REPORTED TO THE BUILDING AUTOMATION
CHILLER CONNECTION DETAIL SYSTEM (BAS) TO AUTOMATICALLY MAKE A DAILY LOG: CHILLED WATER INLET TEMPERATURE, CHILLED WATER OUTLET TEMPERATURE,
EVAPORATOR REFRIGERANT PRESSURE, EVAPORATOR REFRIGERANT TEMPERATURE, CONDENSER WATER INLET TEMPERATURE,
19. PIPING AND DUCTWORK SHALL NOT BE INSTALLED ABOVE ELECTRICAL PANELS. COORDINATE INSTALLATION OF PIPING AND DUCTWORK
WITH ELECTRICAL PANELS WHEN SHOWN NEAR PANELS OR OVER ELECTRICAL ROOMS.
KILOWATT
LEAVING WATER TEMPERATURE
KW
LWT
SCHEMATIC CONDENSER WATER OUTLET TEMPERATURE, CONDENSER REFRIGERANT PRESSURE, CONDENSER REFRIGERANT TEMPERATURE, MAV
MANUAL AIR VENT REVISION DATE
20. INSTRUCT THE OWNER IN THE PROPER OPERATION AND MAINTENANCE OF THE MECHANICAL SYSTEMS UNTIL THE OWNER IS FULLY
CONDENSER APPROACH TEMPERATURE, COMPRESSOR REFRIGERANT DISCHARGE TEMPERATURE, COMPRESSOR REFRIGERANT SUCTION NATURAL GAS PIPE, NEW G G
PREPARED TO OPERATE AND MAINTAIN THE MECHANICAL SYSTEM. HOWEVER, LENGTH OF INSTRUCTION TIME SHALL BE LIMITED TO ONE
SUCTION DISCHARGE TEMPERATURE, PURGE EXHAUST TIME OR DISCHARGE RATE. EXISTING TO REMAIN G EX G
DAY.
WALL EXISTING TO BE REMOVED G G
GALVANIZED STEEL AT A MINIMUM THE FOLLOWING POINTS/INFORMATION SHALL BE COMMUNICATED FROM THE CHILLER CONTROL TO/FROM THE BAS: CHILLER
21. SYSTEMS SHALL OPERATE UNDER CONDITIONS OF LOAD WITHOUT UNUSUAL OR EXCESSIVE NOISE OR VIBRATION. UNUSUAL OR EXCESSIVE
PIPE SLEEVE CONTROL PANEL DIAGNOSTICS, COMPRESSOR MOTOR TEMPERATURE AND HIGH TEMPERATURE ALARM, CHILLER STARTER DIAGNOSTICS,
NOISE OR VIBRATION SHALL BE CORRECTED.
CHILLED WATER PUMP ENABLE, CHILLED WATER FLOW STATUS, CONDENSER WATER PUMP ENABLE, CONDENSER WATER FLOW STATUS, NEW CONNECTED TO EXISTING
LEAVING CHILLED WATER TEMPERATURE, ENTERING CHILLED WATER TEMPERATURE, LEAVING CONDENSER WATER TEMPERATURE,
22. EQUIPMENT, MATERIALS AND LABOR REQUIRED BY THESE CONTRACT DRAWINGS SHALL BE GUARANTEED TO BE FREE FROM DEFECTIVE
ENTERING CONDENSER WATER TEMPERATURE, SYSTEM CHILLED WATER SUPPLY TEMPERATURE, SYSTEM CHILLED WATER RETURN NORMALLY CLOSED NC
PIPE MATERIALS OR WORKMANSHIP FOR ONE YEAR AFTER FINAL ACCEPTANCE OF THE PROJECT UNLESS SPECIFIED OTHERWISE. DEFECTIVE
TEMPERATURE, EVAPORATOR REFRIGERANT TEMPERATURE AND PRESSURE, CONDENSER REFRIGERANT TEMPERATURE AND PRESSURE, NORMALLY OPEN NO
MATERIALS OR WORKMANSHIP OCCURRING DURING THIS PERIOD SHALL BE CORRECTED AT NO ADDITIONAL COST.
COOLING TOWER ENABLE. OUTDOOR AIR OA
1/4" COCK
CS 23. EQUIPMENT LISTED IN THE EQUIPMENT NOTES IS THE BASIS OF DESIGN. IF THE AWARDED BID RESULTS IN AN EQUIPMENT SUBSTITUTION, PIPING INDICATION WITH RESPECT
CHILLED WATER PUMPS (CWP-1 AND CWP-2): EACH PUMP SHALL OPERATE IN CONJUNCTION WITH THE OWNER'S EXISTING BAS SEQUENCE TO FLOW
ANY CHANGES REQUIRED TO ALL TRADES DUE TO EQUIPMENT SUBSTITUTION ARE THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR
AND IN CONJUNCTION WITH THE CHILLER SYSTEM AS A PRIMARY CONSTANT VOLUME PUMP. THE CHILLER SHALL ENERGIZE CWP-1 OR CWP-2 BOTTOM TAKEOFF
AND SHALL BE PERFORMED WITHOUT ADDITIONAL COST TO THE OWNER.
HANG THIS PIPE (BASED ON RUN HOURS) AND PROVE FLOW PRIOR TO INITIATING THE CHILLER COMPRESSORS. ON THE FAILURE OF THE CHILLED WATER SIDE CONNECTION
FROM ABOVE SO
NO WEIGHT RESTS
1/4" COCK
1/4" SPACE BETWEEN
PUMP TO OPERATE, AN ALARM MESSAGE SHALL BE TRANSMITTED TO THE BAS. PUMP FLOW SHALL BE PROVEN PRIOR TO INITIATING CHILLER
OPERATION. UPON A PRIMARY PUMP FAILURE, THE BAS SHALL BE ALARMED AND THE STANDBY PUMP SHALL BE ENERGIZED.
SPECIAL PROJECT NOTES: TOP TAKEOFF
TURN DOWN OR FROM BELOW
FLEXIBLE PIPE
ON PUMP CASING SLEEVE & INSULATION TURN UP OR DOWN
(TYPICAL) PIPE INSULATION EXISTING CONDENSER WATER PUMP ( CDP REVISE EXISTING SEQUENCE): THE EXISTING CONDENSER WATER PUMP SHALL OPERATE IN IN ADDITION TO ALL OF THE REQUIREMENTS SHOWN ON THE DRAWINGS AND IN THE SPECIFICATIONS, THE CONTRACTOR SHALL BE RESPONSIBLE
TURN UP OR FROM ABOVE
PUMP (WHERE REQUIRED) CONJUNCTION WITH THE CHILLER SYSTEM AND CONTROLS TO PROVIDE COOLING TOWER WATER TO THE CHILLER CONDENSER. BEFORE THE FOR ALL OF THE FOLLOWING:
SUCTION DIFFUSER POUNDS LBS
CHILLER IS ENABLED, THE CHILLER SHALL ENERGIZE THE EXISTING CONDENSER WATER PUMP. PUMP FLOW SHALL BE PROVEN PRIOR TO POUNDS PER SQUARE INCH GAGE PSIG
WALL 1. THIS PROJECT CONSISTS OF REMOVING ONE (1) EXISTING WATER COOLED CHILLER AND REPLACING IT WITH ONE (1) NEW WATER COOLED
INITIATING CHILLER COMPRESSORS. UPON PUMP FAILURE, THE BAS SHALL BE ALARMED. PRESSURE DROP PD
MOTOR CHILLER AND ASSOCIATED ELECTRICAL AND CONTROLS WORK REQUIRED; ALSO INCLUDED ARE THE REMOVAL AND REPLACEMENT OF THE
3/4" HOSE-END LEVEL GROUT NOTE: COOLING TOWER (EXISTING SEQUENCE): WHENEVER THE EXISTING CONDENSER WATER PUMP CDP IS ENERGIZED, THE COOLING TOWER FAN CHILLED WATER PUMP WITH TWO NEW CHILLED WATER PUMPS AND THE ADDITION OF A NEW REFRIGERANT EVACUATION SYSTEM.
PRESSURE GAUGE
DRAIN VALVE WHERE PIPES PENETRATE FIRE-RATED WALLS, FILL SHALL BE ALLOWED TO OPERATE. WITH WATER FLOW TO THE COOLING TOWER, THE BAS CONTROLLER SHALL CONTROL THE COOLING ADDITIONAL WORK INCLUDES CONTROL SYSTEM UPGRADES/MODIFICATIONS FOR THE ADDITION OF THE CONDENSER WATER BYPASS/MIXING
SPACE BETWEEN PIPE AND SLEEVE WITH A TOWER FAN THROUGH ITS EXISTING VFD TO MAINTAIN A MAXIMUM 85 DEG. F. SUPPLY CONDENSER WATER. IF THE CONDENSER SUPPLY VALVE AND THE REFRIGERANT EVACUATION SYSTEM. THE REPLACEMENT CHILLER SHALL BE MAGNETIC BEARING, OIL-FREE, SEMI-HERMETIC PRESSURE REDUCING VALVE (FILL VALVE) PRV
FLOOR LINE EXISTING CONCRETE BASE FIRE-RESISTANT MATERIAL WITH SUFFICIENT RATING TO WATER APPROACHES 85 DEG. F., THEN THE COOLING TOWER AIR FLOW SHALL BE AUTOMATICALLY INCREASED. ON A FALL IN THE CENTRIFUGAL TYPE, MODEL AS INDICATED ON SHEET M-1, AS SPECIFIED SHEET M-4.
MAINTAIN THE FIRE RATING OF THE WALL. WHERE PIPE TEMPERATURE OF THE CONDENSER SUPPLY WATER, THE REVERSE SHALL OCCUR. THE COOLING TOWER FAN IS VARIABLE SPEED TYPE WITH PRESSURE RELIEF VALVE
PIPE SUPPORT WITH PENETRATE EXTERIOR WALLS, FILL SPACE BETWEEN 2. FOR THE CHILLER AND THE CWP THE CONTRACTOR SHALL REMOVE EXISTING CONTROLS, CHILLED WATER PIPING, AND CONDENSER WATER
VARIABLE FREQUENCY DRIVE (VFD) CONTROLLER. REVOLUTIONS PER MINUTE RPM
VIBRATION ELIMINATOR PIPE AND SLEEVE WITH FIBERGLASS INSULATION. PIPING AND INSTALL ALL NEW ITEMS TO REPLACE THE EXISTING ITEMS. THE EXISTING SUPPORTS AND INDOOR PIPE HANGERS FOR THE SERVICE VALVE
PAD SAME AS BASE EXISTING CHILLED AND CONDENSER WATER PIPING SHALL BE REUSED FOR SUPPORT OF THE NEW PIPING. ADJUST THE LOCATIONS OF
COOLING TOWER BYPASS VALVE: COOLING TOWER BYPASS VALVE SHALL BE CONTROLLED BY THE STAND-ALONE CHILLER STATIC PRESSURE SP
MICROPROCESSOR CONTROLLER TO MODULATE AND MAINTAIN REFRIGERANT HEAD PRESSURE AT THE CHILLER. EXISTING PIPE SUPPORTS AND PROVIDE ADDITIONAL PIPE SUPPORTS AS REQUIRED FOR THE NEW CHILLED WATER AND CONDENSER PIPING. STRAINER
BASE MOUNTED PUMP DETAIL WALL PIPE SLEEVE DETAIL

HVAC LEGENDS, NOTES, EQUIPMENT NOTES


REFRIGERANT MONITOR ALARM: THE REFRIGERANT MONITOR ALARM SHALL BE MONITORED THROUGH THE BAS. THE REFRIGERANT 3. NEW CONTROLS FOR CHILLER, CWP-1, CWP-2, AND REF SHALL BE PROVIDED FOR CONNECTION TO THE OWNER'S EXISTING BUILDING THERMOMETER
NO SCALE NO SCALE MONITOR ALARM SYSTEM SHALL MONITOR MECHANICAL ROOM REFRIGERANT LEVEL IN PPM AND SHALL ALARM WHEN REFRIGERANT LEVELS AUTOMATION SYSTEM (BAS). ALERTON IS THE PREFERRED CONTROLS CONTRACTOR FOR THIS PROJECT. THE CONTRACTOR SHALL PROVIDE THERMOSTAT OR TEMPERATURE SENSOR T'STAT
HANGER ROD, SUPPORT EXCEED THE SET-POINT (ADJUSTABLE). UPON DETECTION OF A REFRIGERANT LEAK, THE BAS SHALL DE-ENERGIZE THE BOILERS, THE ALL HARDWARE AND SOFTWARE REQUIRED FOR CONTROL FROM AND FULL COMMUNICATIONS WITH THE OWNER'S EXISTING BAS SYSTEM. THOUSAND BTU PER HOUR MBH
FROM BUILDING STRUCTURE REFRIGERANT MONITOR ALARM SHALL OPEN THE ASSOCIATED MOTORIZED DAMPERS AND ENERGIZE THE EXHAUST FAN REF TO RUN AT ITS THE CONTRACTOR WILL DISCONNECT THE EXISTING BAS COMMUNICATION WIRING FROM EXISTING CHILLER AND CWP AND RECONNECT TO
MAXIMUM CFM SETTING. THE NEW TERMINALS. THE CONTRACTOR SHALL PROVIDE NEW CONTROL WIRING AND NEW CONDUIT FOR ALL NEW CONTROLS AS REQUIRED. THREE-WAY CONTROL VALVE
THE CONTRACTOR WILL MAKE FINAL BAS COMMUNICATION WIRING CONNECTIONS.
EXHAUST FAN REF: UPON BOILER ROOM OCCUPANCY AS DETECTED BY THE OCCUPANCY SENSOR (REFER TO ELECTRICAL PLANS), THE THE TWO-WAY CONTROL VALVE

JACKSON VIA ELEMENTARY SCHOOL


BAS SHALL OPEN THE ASSOCIATED MOTORIZED DAMPER AND ENERGIZE THE EXHAUST FAN REF TO RUN AT ITS MINIMUM CFM SETTING. 4. THE CONTRACTOR SHALL COORDINATE WITH THE OWNER TO ENSURE A PROPER AND TIMELY INSTALLATION OF THE NEW EQUIPMENT. ALL UNION
HEAVY DUTY
PIPING, LOUVERS, DOORS AND WALL PANELS REQUIRED TO BE REMOVED FOR UNIT INSTALLATION SHALL BE STORED BY THE CONTRACTOR WET BULB WB
CLEVIS HANGER
FOR RE-INSTALLATION FOLLOWING INSTALLATION OF NEW CHILLER, CWP-1, CWP-2 & REF.

CHILLER (QTY 1): DAIKIN 5. EXISTING INSULATION DAMAGED AS A RESULT OF THE WORK SHALL BE REPAIRED OR REPLACED AS SPECIFIED FOR NEW INSULATION.
LID
MODEL WMC048DDSN15 MAGNETIC BEARING, CENTRIFUGAL WATER COOLED
6. DAMAGED INSULATION ON REMAINING PIPING SHALL BE REPAIRED OR REPLACED AS SPECIFIED FOR NEW PIPING.
CHILLER, R134a; TOTAL COOLING CAPACITY 175 TONS; MINIMUM TWO (2) VARIABLE
GLOBE VALVE SPEED COMPRESSORS; 610 GPM EVAPORATOR WATER FLOW, 55°F EWT, 44°F LWT,
PIPE 7. CONTRACTOR SHALL ENSURE THAT THE OWNER SHALL WITNESS ALL PIPING PRESSURE TESTS, WATER SYSTEM DRAIN DOWN AND REFILL.
19.0 FT H2O MAXIMUM PRESSURE DROP IN EVAPORATOR; 525 GPM CONDENSER
INSULATION WATER FLOW, 85°F EWT, 95°F LWT, 6.0 FT H2O MAXIMUM PRESSURE DROP IN 8. THE CONTRACTOR SHALL VISIT THE SITE AND CONSULT THE OWNER TO DETERMINE THE EXTENT OF THE WORK FOR THIS PROJECT BEFORE
VAPOR BARRIER CONDENSER. 460V/3PH; 171 MCA; 84 LRA (PER COMPRESSOR) - 99.5 kW (UNIT INPUT SUBMITTING BIDS. CONTRACTOR SHALL BE EXPERIENCED IN THIS TYPE OF CONSTRUCTION AND CAPABLE OF PROVIDING COMPLETE

CHILLER REPLACEMENT
WHERE REQUIRED POWER); .336 KW/TON NPLV; .5685 KW/TON EFFICIENCY. INCLUDES SINGLE POINT
FROM 3/4" PUMP FUNCTIONING SYSTEMS AT THE COMPLETION OF THIS PROJECT.
POWER CONNECTION, BACnet COMMUNICATIONS, ISOLATION PADS, INSULATION KIT,
DISCHARGE LOW AMBIENT KIT, REFRIGERANT SPECIALTY KIT,AND STRAINER KIT. MAX
16 GAGE ZINC COATED OPERATING WEIGHT 10,000 LBS.
SHEET STEEL SADDLE 12" LONG, HALF-SECTION
OF HYDROUS CALCIUM
GENERAL DEMOLITION NOTES:

CHARLOTTESVILLE, VIRGINIA
AT LEAST 12" LONG
SILICATE AT EACH HANGER FEEDER BODY
PUMPS: BELL & GOSSETT
SUPPORT
1. THE EXISTING CHILLER IN THE EXISTING MECHANICAL ROOM, INCLUDING THE CHILLED WATER PUMP, CHILLED WATER AND CONDENSER
REMOVABLE BASKET CAPACITY MAX / MIN VOLTAGE & WATER SUPPLY AND RETURN PIPING AS INDICATED ON THE DRAWINGS, RELIEF CONNECTIONS, DRAIN CONNECTIONS, AND CONTROLS
NOTE: MARK HEAD (FT. H ₂O) MOTOR (HP) RPM SERIES MODEL NO.

AND DETAILS
AND FILTER (GPM) PHASE SHALL BE REMOVED. INSULATION ON THE REMAINING EXISTING PIPING THAT IS DAMAGED OR REMOVED DUE TO THE DEMOLITION WORK
SADDLE AND HALF-SECTION OF HYDROUS CALCIUM
SHALL BE REPLACED AND SEALED AS REQUIRED.
SILICATE SHALL BE INSTALLED AT THE SAME TIME TO 3/4" PUMP CWP-1 610 90 20 1750 460V/3PH 1510 4EB
THAT THE PIPE AND PIPE HANGERS ARE INSTALLED. INTAKE 2. THE CONTRACTOR SHALL REMOVE OR ALTER AS NECESSARY ALL EXISTING PIPING, EQUIPMENT, EQUIPMENT FOUNDATIONS, CONTROLS,
CWP-2 610 90 20 1750 460V/3PH 1510 4EB
ELECTRICAL COMPONENTS, DUCTWORK, AND APPURTENANCES THAT ARE NOT REQUIRED FOR THE EXISTING SYSTEMS OR TO REMAIN.
SEE SPECIFICATIONS FOR LOCATIONS WHERE 3/4"
HOSE END CONTRACTOR SHALL VISIT THE SITE TO DETERMINE THE SCOPE OF THIS WORK AND VERIFY EXISTING CONDITIONS PRIOR TO PRICING.
HYDROUS CALCIUM SILICATE SHALL BE REQUIRED.
DRAIN VALVE
PIPE SUPPORT DETAIL NOTE:
3. THE CONTRACTOR SHALL REMOVE ALL HVAC CONTROLS, CONTROL PANELS, EXPOSED TUBING AND ACTUATORS NOT REQUIRED FOR THE
NEW SYSTEMS TO OPERATE. VERIFY WITH THE OWNER WHICH ITEMS MAY NEED TO BE RETAINED BY THE OWNER AND PROTECTED DURING
NO SCALE REMOVAL.
CS FLOW SIZE FILTER FEEDER AS RECOMMENDED BY UNIT MANUFACTURER. FANS: GREENHECK
BYPASS CHEMICAL FEEDER AREA MAXIMUM MINIMUM
2. EXISTING EQUIPMENT SHALL BE TURNED OVER TO THE OWNER, UNLESS DIRECTED OTHERWISE AND LOCATED ON SITE AS DIRECTED BY
THE OWNER. ALL OTHER ITEMS TO BE REMOVED SHALL BECOME THE PROPERTY OF THE CONTRACTOR AND REMOVED FROM THE
NO SCALE MARK ESP RPM MOTOR HP VOLTS/PH MODEL NOTES PREMISES.
SERVED CFM CFM
5 DIA'S 5 DIA'S 3. PROTECT ALL EXISTING ITEMS TO REMAIN FROM DAMAGE DURING DEMOLITION. EXISTING ITEMS THAT ARE DAMAGED OR MISTAKENLY
BOILER DESIGNED DRAWN
REF 2530 525 0.750 1605 1 115/60/1 SQ-140-VG 1 REMOVED DURING DEMOLITION SHALL BE REPAIRED OR REPLACED.
ROOM
NOTE: MEH MEH
1. THERE SHALL BE UNINTERRUPTED STRAIGHT PIPE 5 DIAMETERS 4. BUILDING SURFACES WHICH ARE AFFECTED BY HVAC DEMOLITION SHALL BE PATCHED AND REPAIRED TO MATCH THE EXISTING ADJACENT
NOTES: SURFACES.
OF PIPE DOWNSTREAM AND 5 DIAMETERS OF PIPE UPSTREAM CHECKED APPROVED
FROM EACH CIRCUIT SENSOR. BALANCE VALVE SHALL BE
1. PROVIDE MOTOR OPERATED DAMPERS (MOD) UNLESS OTHERWISE NOTED. 5. THE EXISTING SYSTEMS INDICATED ARE FROM CONSTRUCTION DOCUMENTS DATED JULY 12, 1968. ADDITIONAL INFORMATION IS FROM SITE JAP/MEH LPA
ADJUSTED TO PROVIDE GPM REQUIRED AT EACH C.S.
VISITS. THE CONTRACTOR IS CAUTIONED THAT THE EXISTING HVAC SYSTEM LAYOUTS ARE INDICATED AS ONLY AN APPROXIMATION OF
2. THE ENTIRE CIRCUIT SETTER SHALL BE INSULATED WITH EXISTING CONDITIONS. NOT ALL EXISTING SYSTEMS ARE SHOWN AND SELECTIVE DEMOLITION IS REQUIRED. THE CONTRACTOR SHALL COMM. NO. DATE
REMOVABLE SECTIONS OF PIPE INSULATION SIZED TO OVERLAP VERIFY ACTUAL SYSTEM CONFIGURATIONS, PIPING, DUCTWORK, AND EQUIPMENT LOCATIONS AND ELEVATIONS IN THE FIELD AND SHALL
17119.01 09-12-17
THE CONNECTED PIPE INSULATION. INSULATION SHALL COORDINATE ACCORDINGLY.
OVERLAP 3 INCHES.
6. WHERE EXISTING PIPING OR DUCTWORK IS SHOWN TERMINATED, PROVIDE CAPPED OUTLET. SHEET

CIRCUIT SETTER DETAIL


SCHEMATIC
7. DEMOLITION ACTIVITIES SHALL BE CLOSELY COORDINATED WITH THE OWNER TO MAINTAIN ACTIVE STATUS OF EXISTING SYSTEMS UNTIL
SUCH TIME THE PLANNED DEMOLITION CAN BE EXECUTED. M-1

Potrebbero piacerti anche