21. Soft starter symbol shall be removed.

18.This shall be Multi function Meter ( MFM)


Key Plan
Duplicated What type of Over load
19.This text shall be 23.As per MEW distribution
TYPE & SIZE OF WIRE / CABLE & METHOD OF INSTALLATION
deleted specification, DC Control Voltage
WIRES IN PVC CONDUIT NOTES shall be 50V.
1 2 2
4x1.5mm + 1x1.0mm Cu/PVC WIRE IN 20mm Ø PVC CONDUIT PROTECTION RELAYS DISTRIBUTION SYSTEM 1. 11 KV SWITCHBOARDS SHALL COMPLY WITH RELATED CONTRACT SPECIFICATION.
2 2 2
4x2.5mm + 1x1.0mm Cu/PVC WIRE IN 20mm Ø PVC CONDUIT
2 2
27/59 : UNDER VOLTAGE AND OVER VOLTAGE SYMBOL 2. OPEN/CLOSED / TRIPPED STATUS OF 11KV CIRCUIT BREAKERS & 110V DC SUPPLY FAILURE DIGITAL
3 4x4.0mm + 1x2.5mm Cu/PVC WIRE IN 25mm Ø PVC CONDUIT
37 : UNDER CURRENT DESCRIPTION SIGNALS SHALL BE PROVIDED FOR MONITORING.
2 2
3A 2x4.0mm + 1x2.5mm Cu/PVC WIRE IN 25mm Ø PVC CONDUIT 3. 11 KV CB LOCAL CONTROL PANEL. SHALL HAVE THE FOLLOWING:
4 2 2 38 : BEARING OVER TEMPERATURE
4x6.0mm + 1x2.5mm Cu/PVC WIRE IN 38mm Ø PVC CONDUIT
2 2
a. 11 KV CB STATUS INDICATION (OPEN/CLOSED/TRIP/CIRCUIT EARTHED/SPACE HEATER
4A 2x6.0mm + 1x2.5mm Cu/PVC WIRE IN 38mm Ø PVC CONDUIT 46 : CURRENT UNBALANCE
2 2
“ON” & CONTROL C IRCUIT S BLOWN FUSE INDICATION.
5 4x10mm + 1x6.0mm Cu/PVC WIRE IN 38mm Ø PVC CONDUIT 47 : UNDER VOLTAGE / REVERSE PHASE SEQUENCE A
3P MOTORIZED VACUUM CIRCUIT BREAKER (VCB) b. 11 KV SELECTOR SWITCH (LOCAL/OFF/REMOTE).
2 2 M
5A 2x10mm + 1x6.0mm Cu/PVC WIRE IN 38mm Ø PVC CONDUIT
48 : INCOMPLETE SEQUENCE VCB CT rating with class & Burden?
2 2 c. 11 KV CB CONTROL (OPEN/CL OSE).
6 4x16mm + 1x6.0mm Cu/PVC WIRE IN 38mm Ø PVC CONDUIT
2 2 49 : OVER LOAD 24. 50V DC d. 11 KV BUS EARTHING CUBICLES. INDICATION OF BUS EARTHED.
6A 2x16mm + 1x6.0mm Cu/PVC WIRE IN 38mm Ø PVC CONDUIT
2 2 4. PROTECTION CT OUTPUT ACCURACY AND ACCURACY LIMIT FACTOR (ALF) SHALL BE Please clarify this
7 4x25mm + 1x16mm Cu/PVC WIRE IN 50mm Ø PVC CONDUIT 49R : WINDING OVER TEMPERATURE MDM MULTI DIGITAL METER (MDM)
2 2 DETERMINED BY SWITCHBOARD MANUFACTURER note and its purpose?
7A 2x25mm + 1x16mm Cu/PVC WIRE IN 50mm Ø PVC CONDUIT 50/51 : INSTANTANEOUS AND TIME OVER CURRENT
2 2 5. 11KV FEEDER CB IN EARTH POSITION SHALL INTERTRIP TO RELEVANT 415V CB.
8 4x35mm + 1x16mm Cu/PVC WIRE IN 50mm Ø PVC CONDUIT
2 2
50GS/51GS : INSTANTANEOUS AND TIME OVER CURRENT 6. CLOSE/OPEN/TRI PPED STATUS OF ALL 11KV CIRCUIT BREAKERS SHALL BE TRANSMITTED BY
9 4x50mm + 1x16mm Cu/PVC WIRE IN 50mm Ø PVC CONDUIT SOFT STARTER WITH EARTH LEAKAGE RELAY
GROUND SENSOR. MEANS OF THEIR AUXILIARY CONTACT AND THROUGH INTERPOSING RELAY TO SCADA
CABLE ON CABLE TRAY / IN PVC DUCT
50N/51N : INSTANTANEOUS OVER CURRENT RELAYS 7. THE STATUS OF 110V DC SUPPLY SHALL BE TRANSMITTED TO SCADA THROUGH INTERPOSING
11 4C-1.5mm2 Cu/XLPE/SWA/PVC CABLE ON CABLE TRAY / IN PVC DUCT
12 2 66 : SUCCESSIVE STARTS RELAY.
4C-2.5mm Cu/XLPE/SWA/PVC CABLE ON CABLE TRAY / IN PVC DUCT PT
13 2
4C-4.0mm Cu/XLPE/SWA/PVC CABLE ON CABLE TRAY / IN PVC DUCT 86M : LOCKOUT AUXILIARY RELAY POTENTIAL TRANSFORMER 8. CTS FOR METERING : CT - 1 Is this accuracy adequate for PR? Notes
2 9. CTS FOR O/C & E / F PROTECTION: CT - 10P10
14 4C-6.0mm Cu/XLPE/SWA/PVC CABLE ON CABLE TRAY / IN PVC DUCT 87M : DIFFERENTIAL RELAY
15 2 10. THE VCB RATING INDICATED ON THE SCHEMATIC DIAGRAM IS IEC RATING.
4C-10mm Cu/XLPE/SWA/PVC CABLE ON CABLE TRAY / IN PVC DUCT 81L/H: LOW/HIGH FREQUENCY 20. Current transformer symbol shall be
2
16 4C-16mm Cu/XLPE/SWA/PVC CABLE ON CABLE TRAY / IN PVC DUCT added. 11. PROVIDE INTERLOCKS TO PREVENT PARRALLELING BETWEEN INCOMING SUPPLIES FROM PSS-C & PSS-D 1. ALL MEASUREMENTS ARE IN MILLIMETERS UNLESS OTHER WISE
2 26 : CHECK SYNCHRONIZING RELAY . NOTED.
17 4C-25mm Cu/XLPE/SWA/PVC CABLE ON CABLE TRAY / IN PVC DUCT 12. PROVIDE BUS BAR EARTHING TRUCK WITH NECESSARY INTERLOCK
18 2 22.Protection Relays
4C-35mm Cu/XLPE/SWA/PVC CABLE ON CABLE TRAY / IN PVC DUCT 67 : AC DIRECTIONAL OVER CURRENT RELAY .
19 2
4C-50mm Cu/XLPE/SWA/PVC CABLE ON CABLE TRAY / IN PVC DUCT
67N : NEUTRAL DIRECTIONAL OVER CURRENT
20 4C-70mm2 Cu/XLPE/SWA/PVC CABLE ON CABLE TRAY / IN PVC DUCT 87L- Pilot Cable differential Protection
21 4C-95mm2 Cu/XLPE/SWA/PVC CABLE ON CABLE TRAY / IN PVC DUCT 50/51- Instantaneous and Time over current protection
22 4C-120mm2 Cu/XLPE/SWA/PVC CABLE ON CABLE TRAY / IN PVC DUCT 27/59- Under voltage and Over voltage protection Where this device been used?
23 4C-150mm2 Cu/XLPE/SWA/PVC CABLE ON CABLE TRAY / IN PVC DUCT What is the purpose oh showing LV cables in MV SLD?
2
24 4C-185mm Cu/XLPE/SWA/PVC CABLE ON CABLE TRAY / IN PVC DUCT Other protections shall be removed.
2 Reference drawings
25 4C-240mm Cu/XLPE/SWA/PVC CABLE ON CABLE TRAY / IN PVC DUCT
26 4C-300mm2 Cu/XLPE/SWA/PVC CABLE ON CABLE TRAY / IN PVC DUCT FOR SYMBOLS, ABBREVIATIONS & NOTES REFER DWG.NO.
2 MKP_P1_3BC-MMD-TST-000-XX-DR-EE-0001,0002 & 0003.
27 4C-400mm Cu/XLPE/SWA/PVC CABLE ON CABLE TRAY / IN PVC DUCT
SINGLE CORE CABLE ON CABLE TRAY / IN PVC DUCT MKP_P1_3BC_MMD-UEL-000-XX-DR-EE-0500
2 2 All devices/ equipments proposed shall be incorporated with intended rating. MKP_P1_3BC_MMD-UEL-000-XX-DR-EE-0700
31 8x1C-630mm+1x70mm Cu/XLPE/PVC CABLE ON CABLE TRAY / IN PVC DUCT
2 2 All symbols shown are not covered in the legend sheet. MKP_P1_3BC_B3A-MMD-SST-001-XX-DR-EE-5001
32 8x1C-800mm+1x70mm Cu/XLPE/PVC CABLE ON CABLE TRAY / IN PVC DUCT
33 2 1. All this relay elements been used in this SLD? MKP_P1_3BC_B3A-MMD-SST-001-ZZ-DR-EE-2100
8x1C-630mm Cu/XLPE/PVC CABLE ON CABLE TRAY / IN PVC DUCT
2 2. Many of the relay elements shown are not applicable for this project/ purpose. MKP_P1_3BC_B3A-MMD-SST-001-ZZ-DR-EE-2400
34 8x1C-800mm Cu/XLPE/PVC CABLE ON CABLE TRAY / IN PVC DUCT MKP_P1_3BC_B3A-MMD-SST-001-GF-DR-EE-2700
2 3. A thorough review on the list of relays required shall be assessed and implemented
35 12x1C-800mm Cu/XLPE/PVC CABLE ON CABLE TRAY / IN PVC DUCT LV cables shall be for safe and satisfactory functional operation of the MV switchgear system.
THREE CORE CABLE ON CABLE TRAY / IN PVC DUCT removed.
2 4. Propose only applicable relays for the intended protection.
36 3C-185mm Cu/SC/XLPE/SC/CUT/PVC/SWA/PVC MV CABLE ON CABLE TRAY / IN PVC DUCT
2 5. Details/ function of each relay shall be mentioned clearly.
37 3C-300mm Cu/SC/XLPE/SC/CUT/PVC/SWA/PVC MV CABLE ON CABLE TRAY / IN PVC DUCT
2 2 e.g.
38 6C-2.5mm + 10C-0.635mm Cu/PE/SWA/PVC SCREENED PILOT CABLE
50 - Instantaneous over-current relay
X 3x25mm Cu TAPE
51 - Inverse time over-current relay
EMDP-SST-001-1

MDP-SST-001-1
TXSST001.1

TXSST001.2
T5.3 27-09-2018 S.K. Issued For Tender P.R. A.M.

T5.2 14-06-2018 S.K. Issued For Tender P.R. A.M.

T5.1 29-03-2018 S.K. Issued For Tender P.R. A.M.

Rev Date Drawn Description Ch’k’d App’d


Client
11kV CABLE

11kV CABLE
14.Add one more CT core for Pilot cable differential protection.
15. CT details for 87L Protection,
36 36 Ratio: 400/300/1A
Class: X
16. CT details for Backup protections ( 50/51/50N/51N) Control voltage?
Ratio: 400/1A
Class: 5P20 Program Management & Proxy Operators Consultant
Burden: 15VA
17. CT details for Metering
Ratio: 400/1A
Class: 1
Burden: 15VA

SPARE
Consultant
Al Ghunaim Complex
Qiblah Area 1, Street No.1
ES ES ES
Building No.1, 2nd Floor
PO Box 3788 Safat, 13038
CT-10P10 CT-10P10 CT-10P10 Kuwait City, Kuwait
TO SCADA

TO SCADA

TO SCADA
What is the rating +965 (0) 22479468
50/51/50N/51N 50/51/50N/51N 50/51/50N/51N
+965 (0) 22479467
CT-1 CT-1 CT-1
www.mottmac.com
888 888 888
888 MDM 888 MDM 888 MDM
VCB MFM VCB VCB
M M MFM M
630A 630A 630A
13.Busbar rating: 31.5kA for 3 sec 3P 3P 3P Consultant
CONNECT TO BUS PT CONNECT TO BUS PT CONNECT TO BUS PT

11kV,800A TP + E
BUSBAR CH. (31.5kA) 1. All CT symbol shall be changed as
CT CT
BUS PT
11.Ratio: 11kV/√3/110/√3 VCB
87L 87L
VCB Project
50/27/59
81L/81H

630A 630A
Burden: 100VA 3P
M
PT
86L 86L
3P
M
PT
2. CT position for 87L shall be changed to after CB. Mubarak Al Kabeer Port Project
Class: 1/3P 8. 86L lockout relay 3. CT details for 87L Protection,
shall be removed. Ratio: 400/300/1A
Phase 1 Stage 3B and 3C
50/50N/67 50/50N/67
CT-10P10 51/51N/67N

888
CT-10P10 51/51N/67N

888
Class: X Contract No. A/10/2012
CT-1 CT-1
888 MDM 888 MDM
Title
ES 9. MDM shall be
replaced by MFM
ES
4. Backup protection -67,67N shall be deleted.
MV-SST-001-1
2 Transformers
12.Protection functions
5. CT details for Backup protections ( 50/51/50N/51N)
Substation SST-001
81L/81H, 50 shall be deleted.
Ratio: 400/1A
T.C.L = 1803.700 KVA (S) Electrical Schematic Diagram - MV
37 38 38 37
10.Automatic transfer Class: 5P20 = 1878.700 KVA (W)
equipment shall be provided Burden: 15VA M.D.L = 1444.400 KVA (S)
in the MEW incomer feeder. = 1473.700 KVA (W)
MEW SUBSTATION

MEW SUBSTATION

Designed A.Khalid AK Eng check P.Raj PR


PSS-C 132/11kV

PSS-D 132/11kV

6. CT details for Metering


7.PT details: Drawn S.Khan SK Coordination C. Gay CG
Ratio: 400/1A
Ratio: 11kV/√3/110/√3 Class: 1 Dwg check A.Khalid AK Approved A.Madhoun AM
Burden: 15VA Scale at A1 Status Rev
Burden: 100VA
Class: 1/3P N.T.S TEN T5.3
Drawing Number