Calculation for level

D/ P Transmitter with Wet Leg


AABBBBBABAAUSTYRENE II CLIENT : SADAF Al-Jubail

DATE : 4/2/2000 CAL. BY : DABOY REVISION : 0

TAG No. : 11LT3020 VESSEL : 27V63 Flange C to C : 973 mm

CALIBRATION DATA
h1 700 mm
h3 973 mm 100%
h0 0 mm
h1 b C to C
h2 273 mm
Sp.G. vapour : d3 0 0% h3
h0
Sp.G. wet leg : d2 1.067
h2
Sp.G. tank liquid : d1 0.824
Sp.G. tank leg h2: d0 1.067 L H
H L
H
CALCULATED RANGE

LRV 0% 4 mA -746.9 mmH2O -7.32 kPa


URV 100% 20 mA -170.1 mmH2O -1.67 kPa

SPAN 576.8 mmH2O 5.66 kPa

Note 1 : Minus sign indicates that the bench calibration pressure is to be


applied to the low-pressure side of the transmitter.

Note 2 : Check that the C to C value = or < transmitter Upper Range Limit / seal oil Sp. Gr.
Transmitter by Honeywell Model STD924
URL of transmitter 10198 mmH2O 1000.0 mBar
C to C max 9557 mmH2O 937 mBar Zero Elevation is -7.3%
LRL of transmitter 204 mmH2O 20 mBar

Chosen Transmitter is OK for the vertical C to C between the Seals.


Calculated Span is > LRL? Yes OK If "No", select another capsule range.
Is LRV < URL ? Yes, OK If "No", check h2 value (location of transmitter).

File:405953305.xls 11LT3020 VRN Issue 1 10:22:09 01/04/2019


Level Calculation for Closed Vessel
Differential Pressure Transmitter with Liquid Purge
PROJECT: CLIENT :

DATE : BY : REVISION :

TAG No. : VESSEL : Flange C to C : 1854 mm

CALIBRATION DATA
h1 1778 mm
h3 2031.8 mm 100%
h0 76.2 mm
h1 b C to C
h2 177.8 mm
Sp.G. vapour : d3 0 0% h3
h0 Purge
Sp.G. purge : d2 1.2
h2 Liquid
Sp.G. tank liquid : d1 1.1
Sp.G. tank leg h2 : d0 1.2
H L

CALCULATED RANGE

LRV 0% 4 mA -2141.0 mmH2O -209.9 mBar


URV 100% 20 mA -185.2 mmH2O -18.2 mBar

SPAN 1955.8 mmH2O 191.8 mBar

Note 1 : Minus sign indicates that the bench calibration pressure is to be


applied to the low-pressure side of the transmitter.

Note 2 : Check that the C to C value = or < transmitter Upper Range Limit / seal oil Sp. Gr.
Transmitter by Rosemount Model 1151DP-4
URL of transmitter 3803 mmH2O 372.9 mBar
C to C max 3169 mmH2O 311 mBar Zero Elevation is -56%
LRL of transmitter 634 mmH2O 62.2 mBar

Chosen Transmitter is OK for the vertical C to C between the Seals.


Calculated Span is > LRL? Yes OK If "No", select another capsule range.
Is LRV < URL ? Yes, OK If "No", check h2 value (location of transmitter).

File:405953305.xls Liquid Purge VRN Isuue 1 01/04/2019


Level Calculation for Open Vessel
Differential Pressure Transmitter

PROJECT: CLIENT :

DATE : CAL. BY : REVISION :

TAG No. : VESSEL : Flange C to C : 2500 mm

CALIBRATION DATA
h1 2000 mm
100%
h0 100 mm
h1 b
h2 0 mm
0%
h0
h2
Sp.G. tank liquid : d1 0.8
Sp.G. tank leg h2: d0 0.9
H L

CALCULATED RANGE

LRV 0% 4 mA 80.0 mmH2O 7.8 mBar Elevation


URV 100% 20 mA 1680.0 mmH2O 164.7 mBar

SPAN 1600.0 mmH2O 156.9 mBar

Note 1 : Minus sign indicates that the bench calibration pressure is to be


applied to the low-pressure side of the transmitter.

File: 405953305.xls Open Tank VRN Issue 1 01/04/2019


Liquid Interface Level Calculation for Open or Closed Tank
Differential Pressure Transmitter with Wet Leg
PROJECT: CLIENT :

DATE : 20/03/02 BY : Hareth KM REVISION :

TAG No. : 82LT7012 VESSEL : 82V05 Flange C to C : 1385 mm

CALIBRATION DATA
h4 263 mm
h1 812 mm
Zero elevation h3 1695 mm
h0 0 mm 100%
b C to C
h2 310 mm h1 h4
Sp.G. vapour : d3 0 0% h3
h0
Sp.G. wet leg : d2 1
du 0.56 h2
Sp.G. tank upper :
Sp.G. tank leg h2: d0 1
Sp.G. tank lower: dl 1 H L

CALCULATED RANGE

LRV 0% 4 mA -783.0 mmH2O -76.8 mBar


URV 100% 20 mA -425.7 mmH2O -41.7 mBar

SPAN 357.3 mmH2O 35.0 mBar

Note 1 : Minus sign indicates that the bench calibration pressure is to be


applied to the low-pressure side of the transmitter.

Note 2 : Check that the C to C value = or < transmitter Upper Range Limit / seal oil Sp. Gr.
Transmitter by Foxboro Model 863DP-M
URL of transmitter 2549 mmH2O 250.0 mBar
C to C max 2549 mmH2O 250 mBar Zero Elevation is -31%
LRL of transmitter 133 mmH2O 13 mBar

Chosen Transmitter is OK for the vertical C to C between the Seals.


Calculated Span is > LRL? Yes OK If "No", select another capsule range.
Is LRV < URL ? Yes, OK If "No", check h2 value (location of transmitter).

File: 405953305.xls Interface Wet L. VRN Issue 1 10:22:09 01/04/2019


Level Calculation for Closed Vessel
Differential Pressure Transmitter with External Gas Purge
PROJECT: CLIENT :

DATE : BY : REVISION :

TAG No. : VESSEL : Flange C to C : 2500 mm


L H
CALIBRATION DATA Gas
Purge
h1 2300 mm
100%
h0 100 mm
h1 b
0%
Sp.G. purge gas : d2 0
Sp.G. tank liquid : d1 0.8 h0

CALCULATED RANGE

LRV 0% 4 mA 80.0 mmH2O 7.8 mBar Suppression


URV 100% 20 mA 1920.0 mmH2O 188.3 mBar

SPAN 1840.0 mmH2O 180.4 mBar

Note 1 : Minus sign indicates that the bench calibration pressure is to be


applied to the low-pressure side of the transmitter.

File: 405953305.xls Gas Purge VRN Issue 1 10:22:0901/04/2019


Level Calculation for Closed Vessel.
Differential Pressure Transmitter with Two Seals
PROJECT: CLIENT :

DATE : CAL. BY : REVISION :

TAG No. : VESSEL : Flange C to C : 2540 mm

CALIBRATION DATA
h1 1778 mm
100%
h0 508 mm
h1 b C to C
Sp.Gr. vapour : d3 0 0%
h0
Sp.Gr. sealing oil : d2 0.9
Sp.Gr. tank liquid : d1 0.8

H L
CALCULATED RANGE

LRV 0% 4 mA -1879.6 mmH2O -184.3 mBar


URV 100% 20 mA -457.2 mmH2O -44.8 mBar

SPAN 1422.4 mmH2O 139.5 mBar

Note 1 : Minus sign indicates that the zero is elevated, and that the bench calibration pressure is to be
applied to the low-pressure side of the transmitter.
Note 2 :
Sealing Oil BSO-02 BSO-19 BSO-21 BSO-22 BSO-25 Syltherm DC200 Fluorocarbon
Specific Gravity 0.93 1.11 1.068 0.949 1.87 0.934 0.934 1.85
BSO = Badotherm Sealing Oil at 25 C.
Syltherm and DC200 are trademarks of Dow Corning Corp.
Note 3 : To obtain optimum performance, position the transmitter at or below the midpoint of dimension "C to C".
Note 4 : For vacuum service, position the transmitter at or lower than the lower process connection.
Pressure at H capsule of transmitter shall not be lower than 30 mbara.
Note 5 : Check that the C to C value = or < transmitter Upper Range Limit / seal oil Sp. Gr.
Transmitter by Rosemount Model 1151DP-4
URL of transmitter 3803 mmH2O 372.9 mBar
C to C max 4225 mmH2O 414 mBar Zero Elevation is -49%
LRL of transmitter 634 mmH2O 62.2 mBar

Chosen Transmitter is OK for the vertical C to C between the Seals.


Calculated Span is > LRL? Yes OK If "No"select another capsule range.
Is LRV < URL? Yes, OK If "No"select another capsule range.
Note 6 : Capillary length greater than the C to C value is for installation convenience only.
For low response time and minimizing temperature effects keep the length as short as possible.

File: 405953305.xls Two Seals VRN Issue 1 10:22:09 01/04/2019


Level Calculation for Open Vessel
Differential Pressure Transmitter with one Seal
PROJECT: CLIENT :

DATE : CAL. BY : REVISION :

TAG No. : VESSEL :

CALIBRATION DATA
h1 3048 mm
100%
h0 500 mm
h1 b
h2 2500 mm
0% h0
Sp.Gr. sealing oil : d2 0.934
Sp.Gr. tank liquid : d1 1.2 h2

H L
CALCULATED RANGE

LRV 0% 4 mA 2935.0 mmH2O 287.8 mBar Zero Suppression See Note 4


URV 100% 20 mA 6592.6 mmH2O 646.5 mBar

SPAN 3657.6 mmH2O 358.7 mBar

Note 1 : Minus sign indicates that the bench calibration pressure is to be


applied to the low-pressure side of the transmitter.

Note 2 :
Sealing Oil BSO-02 BSO-19 BSO-21 BSO-22 BSO-25 Syltherm800 DC200 Fluorocarbon
Specific Gravity 0.93 1.11 1.068 0.949 1.87 0.934 0.934 1.85
BSO = Badotherm Sealing Oil at 25 C.
Syltherm and DC200 are trademarks of Dow Corning Corp.

Note 3 : For vacuum service, position the transmitter at or lower than the lower process connection.
Pressure at H capsule of transmitter shall not be lower than 30 mbara.
Note 4 : Check that h2, the zero suppression of the transmitter = or < transmitter Upper Range Limit / seal oil Sp. Gr.
Transmitter by Rosemount Model 1151DP-5
URL of transmitter 19009 mmH2O 1864.0 mBar
h2 max 20352 mmH2O 1996 mBar Zero Suppression is 15.4%
LRL of transmitter 3172 mmH2O 311 mBar

Chosen Transmitter is OK for the calculated zero suppression.


Calculated Span is > LRL? Yes OK If "No", select another capsule range.
Is LRV < URL ? Yes, OK If "No", check h2 value (location of transmitter).
Is URV < URL ? Yes, OK If "No", check h2 value (location of transmitter).
Note 5 : Capillary length greater than the suppression value is for installation convenience only.
For low response time and minimizing temperature effects keep the length as short as possible.

File : 405953305.xls One Seal Below VRN Issue 1 01/04/2019


Level Calculation for Open Vessel
Differential Pressure Transmitter with One Seal above Process Connection
PROJECT: CLIENT :

DATE : CAL. BY : REVISION :

TAG No. : VESSEL :

CALIBRATION DATA
h1 3048 mm
100%
h2
h0 500 mm H L
h1 b
Zero elevation h2 762 mm
0%
Sp.Gr. sealing oil : d2 1.9
Sp.Gr. tank liquid : d1 1.1 h0

CALCULATED RANGE
LRV 0% 4 mA -897.8 mmH2O -88.0 mBar Zero Elevation See Note 4
URV 100% 20 mA 2455.0 mmH2O 240.7 mBar

SPAN 3352.8 mmH2O 328.8 mBar

Note 1 : Minus sign indicates that the bench calibration pressure is to be


applied to the low-pressure side of the transmitter.

Note 2 :
Sealing Oil BSO-02 BSO-19 BSO-21 BSO-22 BSO-25 Syltherm800 DC200 Fluorocarbon
Specific Gravity 0.93 1.11 1.068 0.949 1.87 0.934 0.934 1.85
BSO = Badotherm Sealing Oil at 25 C.
Syltherm and DC200 are trademarks of Dow Corning Corp.

Note 3 : For vacuum service, preferred position of the transmitter is at or below process connection.
Pressure at H capsule of transmitter shall not be lower than 30 mbara.
Note 4 : Check that h2, the zero elevation of the transmitter = or < transmitter Upper Range Limit / seal oil Sp. Gr.
Transmitter by Rosemount Model 1151DP-4
URL of transmitter 3803 mm 372.9 mbar
h2 max 2001 mm 196 mbar Zero Elevation is -23.6%
LRL of transmitter 3172 mmH2O 311 mBar
Chosen Transmitter is OK for the calculated zero elevation.
Calculated Span is > LRL? Yes OK If "No", select another capsule range.
Is LRV < URL ? Yes, OK If "No", check h2 value (location of transmitter).
Is URV < URL ? Yes, OK If "No", check h2 value (location of transmitter).

Note 5 : Capillary length greater than the elevation value is for installation convenience only.
For low response time and minimizing temperature effects keep the length as short as possible.

File : 405953305.xls One Seal Above Vrn Issue 1 01/04/2019


Level Calculation for Open Tank
Bubble Type Installation
PROJECT: CLIENT :

DATE : BY : REVISION :

TAG No. : VESSEL :


air supply H L
CALIBRATION DATA
h1 2000 mm
100%
h0 200 mm
h1 b
0%

Sp.G. tank liquid : d1 0.8


h0

CALCULATED RANGE

LRV 0% 4 mA 160 mmH2O 15.7 mBar Suppression


URV 100% 20 mA 1760 mmH2O 172.6 mBar

SPAN 1600 mmH2O 156.9 mBar

File ; 405953305.xls Bubble Level VRN Issue 1 10:22:09 01/04/2019


Interface Level Calculation for Open Tank
Bubble Type Differential Pressure Transmitter

PROJECT: CLIENT :

DATE : BY : REVISION :

TAG No. : VESSEL :


air supply H L
CALIBRATION DATA
h1 1016 mm

100%

h1
0%
Sp.G. tank upper : du 1
Sp.G. tank lower : dl 1.7

CALCULATED RANGE

LRV 0% 4 mA 1016 mmH2O 99.6 mBar Suppression


URV 100% 20 mA 1727 mmH2O 169.4 mBar

SPAN 711 mmH2O 69.7 mBar

File : 405953305.xls Bubble Interface VRN Issue 1 10:22:09 01/04/2019


Liquid Interface Level Calculation for Closed Vessel
Differential Pressure Transmitter with Two Seals
PROJECT: CLIENT :

DATE : BY : REVISION :

TAG No. : VESSEL : Flange C to C : 2960 mm


CALIBRATION DATA
h4 127 mm
h1 1270 mm

h0 254 mm 100%
b C to C
h1 h4
Sp.G. vapour : d3 0 0%
h0
Sp.G. sealing oil : d2 1.2
Sp.G. tank upper : du 0.8

Sp.G. tank lower: dl 1.1 H L

CALCULATED RANGE

LRV 0% 4 mA -2155.0 mmH2O -211.3 mBar


URV 100% 20 mA -1774.0 mmH2O -174.0 mBar

SPAN 381.0 mmH2O 37.4 mBar

Note 1 : Minus sign indicates that the zero is elevated, and that the bench calibration pressure is to be
applied to the low-pressure side of the transmitter.

Note 2 :
Sealing Oil Description BSO-02 BSO-19 BSO-21 BSO-22 BSO-25 Syltherm DC200 Fluorocarbon
Specific Gravity 0.93 1.11 1.068 0.949 1.87 0.934 0.934 1.85
BSO = Badotherm Sealing Oil at 25 C.
Syltherm and DC200 are trademarks of Dow Corning Corp.
Note 3 : To obtain optimum performance, position the transmitter at or below the midpoint of dimension "C to C".
Note 4 : For vacuum service, position the transmitter at or lower than the lower process connection.
Pressure at H capsule of transmitter shall not be lower than 30 mbara.
Note 5 : Check that the C to C value = or < transmitter Upper Range Limit / seal oil Sp. Gr.
Transmitter by Foxboro Model 863DP-M
URL of transmitter 2549 mmH2O 250.0 mBar
C to C max 2125 mmH2O 208 mBar Zero Elevation is -85%
LRL of transmitter 133 mmH2O 13 mBar
Chosen Transmitter is Not OK for the vertical C to C between the Seals.
Calculated Span is > LRL? Yes OK If "No" select another another capsule range.
Is LRV < URL? Yes, OK If "No" select another another capsule range.
Note 6 : Capillary length greater than the C to C max value is for installation convenience only.
For low response time and minimizing temperature effects keep the length as short as possible.

File : 405953305.xls Two Seal Interface VRN Issue 1 10:22:09 01/04/2019