Sei sulla pagina 1di 1

CONCRETE RAISED FOUNDATION * 45 , 50 NOS FOUNDATION

FOR PLINTH MTG. OF TRANSFOMER M24 FOR PAD OF PIPE


HEIGHT FROM RAIL LEVEL TO TOP SUPPORT 300 X 595
OF CONCRETE 380 mm. SEE DETAIL "X" & "A"
7250

"N" PAD "N" PAD


2 JACK POINT & JACK POINT & DRAIN FOR OIL
1400 1400 75 X 50 DEEP

1
L 65X65X6
4440 PLATE SIZE STD RAIL WELDED TO CLEAT
700 1950 700
(400X595) 500
ANGLE
150
(TYP)

600
PEDESTAL 450
FOR CEAT ANGLE 50X50X6

~
24400 PLATE

500
TRANSFORMER 70 LONG WELDED TO
350X300X10 THK

270
500 c/c RAIL AT 500c/c
P.C.C. LINE

2900 JACK POINT & PIPE SUPPORT

FOR BS-90R RAILS.


1743 RAILS CENTER
1676 RAIL GAUGE

1726 ROLLER CRS

400
2000

4000

75
450 THK RAIL 2 NOS-25x6THK

=
TB

(T
TB

TB

TB

TB

TB

TB

TB

TB

TB
450

Y
CUM SUPPORT LUGS WELDED TO

P)
=
R.C.C. WALL 'D' THE PLATE.

2606
THE HOOK IN CLOSED TIES THE HOOK IN OPEN TIES
TYPICAL DETAIL OF HOOKS
100 mm

FOR BS-90R RAILS.


VIEW LOOKING
1743

FROM HV SIDE
1743 RAILS CENTER
663 663 400

RAIL LEVEL
TANK BASE
RAIL GAUGE FOR

1350
TB
400 INSERT PLATE DETAILS
ROLLER SET. 450 THK RAIL
9250

6700
TB

TB

TB

TB

TB

TB

TB

TB

TB
450
CL CUM SUPPORT
THE TRANSFORMER ON RAISED UP

500
CONCRETE FOUNDATION (PLINTH)

R.C.C. WALL 'C'


MOUNTING LUGS FOR MOUNTING

1550
TB

1743
ON TANK BASE PLATE (40TK)

8 X 1 NO FOUNDATION BOLT

FOR BS-90R RAILS.


1743 RAILS CENTER
1676 RAIL GAUGE

3100 JACK POINT

1726 ROLLER CRS


2606
1068

3050
450 THK RAIL

=
TB

TB

TB

TB

TB

TB

TB

TB

TB
450
CUM SUPPORT

TB
M24 MARKED "N".

=
4000
R.C.C. WALL 'B'

2000
1068

1743 RAILS CENTER 1743 RAILS CENTER 1743 RAILS CENTER


FOR BS-90R RAILS FOR BS-90R RAILS FOR BS-90R RAILS
R.C.C. RAFT
875

FOUNDATION 425 1676 RAIL GAUGE 1676 RAIL GAUGE

500
450

450
PL SIZE 450 THK RAIL
JACKING PAD (490X435) PLATE SIZE
CUM SUPPORT PLINTH FOR 75MM THK. P.C.C(1:4:8)

1
6 NOS MARKED "J" 1400 1400 (400X850)
2500

R.C.C. WALL 'A' TRANSFORMER


P.C.C. LINE.
150 MM ALLAROUND.

AS PER SITE
CONDITION
2 JACK POINT & JACK POINT &
"N" PAD 75 THK

650
6000
"N" PAD BRICKWORK. TIE BEAM TIE BEAM TIE BEAM
10600
475

1150 1150 (300 X 450)


(300 X 450) (300 X 450)
FILLING. FILLING.
DIRECTION OF
650

WITHDRAWL OF

500

500
1020 730 730
TRANSFORMER
650

1070
FILLING. FILLING.
WELL COMPACTED WELL COMPACTED WELL COMPACTED
EARTH EARTH EARTH
360

AS PER SITE CONDITION


970

P P
1322 1263 1322
4500 (M. KIOSK)
BOLTS FOR MARSHALING KIOSK
2 X 2 NOS M16 FOUNDATION

1650
800 330 330 800 7800
8 X 4 NOS FOUNDATION BOLT
M24 FOR PAD OF COOLER # 10 @ 140 c/c # 10 @ 140 c/c
1743 RAILS CENTER
1000 2100 2600
SUPPORT 25 TK X 300 X 300
1743 RAILS CENTER 1743 RAILS CENTER # 12 @ 125 c/c # 12 @ 125 c/c # 12 @ 125 c/c
2400

2400

N.G.L. N.G.L.
CL OF 2606 2606
PEDESTAL
935

1726 ROLLER CRS 1726 ROLLER CRS


5NOS.

AS PER SITE CONDITION


CL OF 1743 1743
DRAIN FOR OIL
885 COOLING BANK 75 X 50 DEEP
DRAIN FOR OIL
935

1 st COOLING BANK 2 nd COOLING BANK

1500(MIN)
75 X 50 DEEP #10@150c/c #10@150c/c
SLOPE IN SLOPE IN SLOPE IN
CL OF GR OUT GROUT GROUT GROUT BOTHWAYS BOTHWAYS
PEDESTAL SLOPE IN SLOPE IN
GROUT
3950 750 2000 4700

635 230 1770

500
= = = = 300

300 (TYP)
CLOF RAIL GROUND (TYP)

650
TANK 300 (TYP)
CL OF COOLER BANK

150
7 X 2 NOS FOUNDATION MIN . 3 NOS BAR
BOLTS M20 FOR PAD OF PIPE PROVIDED BELOW # 12 @200c/c
SUPPORT 170 X 220 ( FOR P+B+I) FOUNDATION PLAN FOR 315 MVA , 400 / 220 / 33 Kv EACH BERAING M:10 P.C.C.
#10@250c/c #16@125c/c
AUTO TRANSFORMER . PLATE. # 10 SECTION:-1-1
TYPICAL SECTION SHOWING RAIL ROAD RENFORCEMENT.

AS PER SITE CONDITION


#12@200c/c #12@200c/c
300

HEX. SET SCREW


SPRING WASHER
10650
45

M:25 N.G.L.
GRADE CONCRETE. PLAIN WASHER
DIMN. ' M ' QTY. FOUNDATION
BRACKET RAIL LEVEL
# 10 @ 125 c/c
210

300

LINKS

AS PER SITE CONDITION


M 24 100 SETS # 8 @ 200 c/c # 12 @ 125 c/c

M 16 4 SETS

260 FOR M24


200 FOR M12
250 FOR M20
1500(MIN)
CONCRET
M 20 14 SETS 1500 1500 FOUNDATION
210 45
SEE DETAIL-A

DETAIL:- 'X'

500
PART SECTION:-P-P

150
BOTHWAYS T. / B.
#20@125c/c M:10 P.C.C.
FOUNDATION
100 SQ FOR M24 & M20
SECTION:-2-2 BOLT ROD
0.25L1 Ld 0.3L1 0.3L1 1.5 X L3 80 SQ FOR M12
DETAIL-`A'
EMBEDMENT DETAIL
OF FOUNDATION BOLT THIS DRAWING SHALL WITH REF. DRAWING :-
PEDESTAL DETAILS (COLUMN RINGS # 8 @ 250 c/c) ( U.N.O. )
1) DRG. NO.:-- 2 / 14 / 0855 / R1
2) DRG. NO.:-- 1 / 14 / 0639 / R2 SHEET 2 OF 2 & SHEET NO 1 OF 2.
QTY. LOAD ON PEDESTAL PEDESTAL REINFORCEMENT
0.1L1 0.1L1 REF DESCRPTION
EACH PAD NO. SIZE ( B X D )
STP1 STP2 STP1 STP1 STP2 STP1 STP1 NOTES:-
J JACKING PAD 6 NOS. 60 TONNES 28,29,38,39,46,49. REFER DETAIL
L2 L3 1) DO NOT SCALE THIS DRAWING , FOLLOW ONLY WRITTEN DIMENSION.
R ROLLER LOCKING PAD 31,32,35,36,41, 2) IN CASE OF DISCREPANCY REVERT BACK TO OFFICE BEFORE EXECUTION OF WORK.
8 SETS 45 TONNES 42,47,48. REFER DETAIL
( WITH ROLLER )
TYPICAL BEAM DETAIL 3) ALL DIMENSIONS ARE IN MM AND LEVELS ARE IN METERS UNLESS NOTED OTHERWISE.
C PAD FOR COOLER SUPPORT 8 SETS 12 TONNES 1,2,3,4,5,6,7,8. ( 450 X 450 ) 4 - # 20 + 4 - # 16 450
400 750
4) USE CONCRETE GRADE M:25 R.C.C. WORK & GRAD M:10 FOR P.C.C. WORK.
P PAD FOR PUMP SUPPORT 4 SETS 1 TONNES 14,15,16,17. ( 400 X 400 ) 8 - # 16 5) USE HIGH STRENGTH DEFORMED BARS ( TOR STEEL) OF GRADE Fe 415 CONFORMING TO I.S-1786 AS
1000
SCHEDULE OF TIE BEAMS B
PAD FOR REVERSE FLOW
2 SETS 1.5 TONNES 18,19. ( 400 X 400 ) 8 - # 16
REINFORCEMENT STEEL BARS ARE DENOTED AS #.

400
400

BLOCKING DEVICE
450

6) CLEAR CONCRETE COVER TO REINFORCEMENT SHALL BE AS FOLLOWS


REINFORCEMENT I PAD FOR PIPE SUPPORT 1 SETS 1.5 TONNES 23. ( 400 X 400 ) 8 - # 16 i) FOOTING 50MM,

300
SIZE BOTTOM BARS TOP EXTRA BARS STIRRUPS M PAD FOR M. KIOSK 2 SETS 0.5 TONNES 20,21. ( 1000 X 300 ) 12 - # 16
ii) COLUMN 40MM,
BEAM NOS. TOP REMARKS iii) BEAMS 25MM,
BXD BARS OVER OVER PAD FOR ADDITION PIPE 9,10,11,22,24,27,
STRAIGHT CURTAILED MIDDLE END * 11 SETS 1.5 TONNES ( 450 X 450 ) 4 - # 20 + 4 - # 16 8 - # 16 iv) WALL 25MM,
(Tst) STIRRUPS1 STIRRUPS2 SUPPORT 30,37,40,45,50. 4-#20+4-#16
(Bst) (Bcurt) SUPPORT SUPPORT
N PAD FOR PLINTH MTG. 8 SETS
25,26,27,33,34,43,
REFER DETAIL 12 - # 16 7) MINIMUM LAP LENGTH SHALL BE 50 TIMS THE BAR DIANETER, LAPS SHALL BE STAGGERED.
(Ted) (Tes) 44,51,52. 12 - # 16
FIRE EXTINGUISHING 8) FOUNDATION BOLTS SHALL BE KEPT IN POSITION BEFORE CONCRITING.
F 2 SETS 0.5 TONNES 12,13. ( 750 X 400 ) 12 - # 16
SUPPORT 9) TOP OF CONCRETE FOR TB IS 150MM BELOW F.G.L.
COLUMN LINKS ARRANGEMENTS
LA 216 Kv LA 3 SETS ( 550 X 550 ) 10) CONSIDERED S.B.C. 10 T / SQ.MTS AT 1.5 MTS BELOW N.G.L.
FOR COLUMN PEDESTALS
BPI 216 Kv BPI 3 SETS ( 550 X 550 ) 11) ALL DIMENSIONS SHALL BE CORRECTED WITH RELEVENT EQUIPMENTS / ELECTRICAL DRAWING
& SPECIFICATIONS.

AJAY MAHALE
CONSULTING CIVIL & STRUCTURAL ENGINEERS.
203, IRANI BUILDING OPP.
NEW TMC. SANT DNYANESHWAR
MARG, PANCHPAKHADI, THANE.
TELE PH, NO:-25435628.
TELE FAX NO. :- 022-25435628
EMAIL :- dss_consultants@yahoo.co.in

Potrebbero piacerti anche