RED PLANET HOTELS

6-12mmØ VERT. BARS


NORTH AVENUE

170mm
A A'

LOT-05, BLK N-22, NORTH AVENUE, QUEZON CITY

300mm
SECTION A-A'

DETAIL A CAT LADDER DETAIL


200mm

COUNTER BOX DETAIL ARCHITECTURE + INTERIORS + PLANNING


2865 Finlandia St. Makati City 1234 Philippines

LIGHTNING CONTROL Fax: 02 893 5975

TERMINAL
Tel: 02 844 2848 . 844 2701 . 369 9353 to 54
Email: rmda.architects@gmail.com
FINISHED GRADE Web: www.rmdaarchitects.com

CONCRETE COVER ROLANDO B. MERCADO


ARCHITECT
F.F.L. CONCRETE TILES, FIBER
PRC No.: 5298 PTR No.: 4748687
OR CAST IRON PIPE VALIDITY: 12/07/2017 DATE: 01 / 05 / 2015
30Sqmm BARE COPPER WIRE IAPOA No.: 01361 127615 093014 PLACE: MAKATI CITY
STRANDED, SOFT DRAWN O.R. No. / DATE: 127615/ 09-30-2014 TIN: 113-398-644

PAVED AREAS (or AS SPECIFIED)


GROUND ROD
20mmØ x 3.00 M. LONG
EXOTHERMIC WELD
TYPE "GT" CONNECTION
MACEC
M.A.CORONEL Engineering Consultancy
Engineers*Designers*Construction Managers
BACKFILL-SPRAY W/ MAGNESIUM Rm. 404, 4th Flr., R.&G.Tirol Bldg., 831 EDSA cor .E. Lopez Drive
Diliman, Quezon City Tel. No. 332-9119

SULFATE SOLUTION-1KG/20LTRS
WATER
MANLO A. CORONEL
STRUCTURAL ENGINEER
UNPAVED AREAS
PRC No.: DATE:
VALIDITY: PLACE:
O.R. No. / DATE: TIN:

BASE PLATE DETAIL CLAMP DETAIL GROUND ROD INSTALLATION PTR No.:

CONCRETE PEDESTAL DETAIL F.A. VELASCO DESIGN & CONSTRUCTION


GROUND ROD DETAILS LIGHTNING ARRESTER DETAIL
FV
FERDINAND A. VELASCO
ELECTRICAL ENGINEER

PRC No.: 2684 DATE: JAN. 4, 2016


VALIDITY: DEC. 3, 2017 PLACE: MAKATI CITY
O.R. No. / DATE: TIN: 117-684-563
PTR No.: 5324266

LP (TYP.)

SMOKE DETECTOR INSTALLATION DET.


JOSELITO S. ROSAS

PANELBOARD DETAIL PINLIGHT DETAIL SANITARY ENGINEER

PRC No.: DATE:


VALIDITY: PLACE:
O.R. No. / DATE: TIN:
4,000
1500 2500 PTR No.:
BE

GR
1100

GL

FPA and ASSOCIATES, Engineers


SECONDARY TRENCH

CONSULTANTS DESIGNERS
PRIMARY TRENCH

45 General Malvar Street, Brgy. San Antonio, Pasig City


1400

BE

℃ Tel./Fax No. 584-1941 Email: fpa_a@yahoo.com


CONCRETE LEDGE
REINFORCED
5,000
1400

BE FROILAN P. AZOR
MECHANICAL ENGINEER

FD PRC No.: DATE:


1100

CP

ED
VALIDITY: PLACE:

GW EF
EXIT LIGHT DETAIL EMERGENCY LIGHT DETAIL CONDUIT HANGER DETAIL MANUAL PULL STATION & FIRE ALARM BELL ELEVATION
O.R. No. / DATE:
PTR No.:
TIN:

CUSTOMER'S SECONDARY BE

MAIN CIRCUIT BREAKER

PLAN TYPICAL TRANSFORMER VAULT LAYOUT


(CYLINDRICAL TYPE) AT THE SECOND FLOOR
4,000 LEGEND: NOTES: BILL OF MATERIALS
DOOR HANDLE WELDED EF - EXHAUST FAN: FOR FORCED AIR VENTILATION; TEMPERATURE-CONTROLLED; 1. THE TRANSFORMER VAULT SHALL MEET THE REQUIREMENTS OF PEC PART 1. THE WALLS, ITEM DESCRIPTION STOCK NO. UNIT QTY.
DIRECT DRIVEN BY TOTALLY ENCLOSED MOTOR WITH GRAVITY TYPE DAMPERS. THE ROOF AND FLOOR SHALL BE CONSTRUCTED OF 150mm THICK (MINIMUM) REINFORCED
TO STEEL DOOR
ED EF
FAN SHALL BE RATED 3 4 HP, 71 CU.M/MIN (2500 CFM) @ 3.2mm (18") STATIC PRESSURE. CONCRETE EXCEPT WHERE THE VAULT IS DIRECTLY ABOVE EARTH, THE FLOOR CAN BE 1 CONCRETE CU. M. 5.50
CONSTRUCTED USING 100mm THICK REINFORCED CONCRETE. 2 REINFORCING BARS, 12mm Ø x 6000mm LONG 500 - 070 - 0011 - 01 EA 37.00
ED - EXHAUST DUCT: MADE OF G.I. SHEET, GAGE 20. 3 REINFORCING BARS, 16mm Ø x 6000mm LONG 500 - 070 - 0013 -09 EA 24.00
2. THE TRANSFORMER VAULT SHALL HAVE DIRECT ACCESS FROM THE OUTSIDE OF THE BUILDING.
800 to
1000

4 REINFORCING BARS, 20mm Ø x 6000mm LONG EA 5.00


3,000

JANUARY 10, 2017


HAPS WELDED TO DW - DOORWAY: FOR PERSONNEL ACCESS FROM THE OUTSIDE OF THE BUILDING, 0.8M
BE BE TRANSFORMER 3. THE FLOOR SHALL BE ABLE TO SUPPORT THE WEIGHT OF THE LARGEST TRANSFORMER AND 5 FORM LUMBER, 25 x 300 x 3660 ( 1" x 12" x 12' ) BD. FT. 504.00
DOOR ACCESS
STEEL DOORS WIDE X 2.0M HIGH X 3.2mm THICK STEEL DOOR, OUTWARD SWING WITH 150mm HIGH
DOOR SILL. THE DOOR SHALL BE FITTED WITH A LATCH DEVICE FOR VECO PADLOCK CONCRETE PAD IN CONSIDERATION FOR FUTURE LOAD UPGRADE. THE APPROXIMATE WEIGHT 6 FORM LUMBER, 50 x 150 x 4270 ( 2" x 6" x 14' ) BD. FT. 210.00
1,000

300 GW (SEE DETAIL 'A'). IT SHALL BE PROVIDED WITH A PANIC BAR DESIGNED TO OPEN OF THE LARGEST PADMOUNTED TRANSFORMER IS 8,000 KG. 7 COMMON NAIL, 75mm LONG 500 - 060 - 0021 - 01 KG 3.50
REINFORCED
CONCRETE LEDGE OUTWARD UNDER SIMPLE PRESSURE DURING EMERGENCY. 8 COMMON NAIL, 40mm LONG 500 - 060 - 0023 - 01 KG 3.00
4. THE PADMOUNTED TRANSFORMER SHALL BE PROVIDED WITH A CONCRETE PAD 75mm IN
400

9 THE WIRE, GA. NO. 16 G.I. KG 3.00


600

HEIGHT AND AN INTEGRAL PULL BOX. THE CONCRETE PAD SHALL SLOPE GRADUALLY
800

TA - TRANSFORMER ACCESS DOOR: 3.0M WIDE X 2.5M HIGH X 3.2mm THICK STEEL DOOR;
10 MACHINE BOLT, 16mm Ø x 150mm LONG 002 - 008 - 0290 - 07 EA 4.00

DATE ISSUED:
DOUBLE OUTWARD SWING WITH 150mm HIGH DOOR SILL FOR EQUIPMENT IN AND OUT DOWNWARDS TOWARDS THE TRANSFORMER ACCESS DOORWAY TO FACILITATE ROLLING OF
700 700 1,300 VECO PADLOCK ACCESS. THE DOORS SHALL BE LOUVERED AT THE LOWER HALF (SEE DETAIL 'B') AND THE EQUIPMENT. 11 PULLING-IN IRON EA 3.00
32MMØ (1-1/4") W.I. BAR 12 MANHOLE FRAME & COVER, DWG. EA 1.00
SHALL BE FITTED WITH A LATCH DEVICE FOR VECO PADLOCK (SEE DETAIL 'A').
WITH 16MMØ HOLE 5. PRIMARY AND SECONDARY CABLE DUCTS SHALL BE 100mm Ø THICK WALLED, RED ORANGE
13 WATER STOP SEALER, POLYVINYL PLASTIC, 100 WIDE 500 - 061 - 0020 - 01 M 30.00
CONCRETE ENCASED CONCRETE ENCASED FOR MERALCO PADLOCK COLOR, MADE OF UNPLASTICIZED PVC PER PNS 14 AND SHALL BE ENCASED IN CONCRETE.
SECONDARY DUCTS PRIMARY DUCTS DETAIL "A" DS - DANGER SIGN: TO BE PAINTED AND/OR POSTED AT THE STEEL DOOR (SEE DETAIL 'C').
THE DIMENSION OF THE CONCRETE ENVELOPE FOR THE SECONDARY DUCTS SHALL DEPEND
14 DRAIN PIT COVER GRATING, DWG. NO. E - 620 - 1
GROUND ROD, 16mm Ø x 2400mm LONG
500 - 061 - 0023 - 08 EA 1.00
(SEE NOTES) (SEE NOTES) 15 002 - 022 - 0170 - 04 EA 3.00
T - TRANSFORMER: PADMOUNTED, COMPARTMENTAL TYPE, DEAD FRONT, 3-PH., 60HZ., ON THE NUMBER OF DUCTS INSTALLED, REFER TO UNDERGROUND CONSTRUCTIVE UNIT
16 ANCHOR BOLT, 19mm Ø x 200mm LONG EA 4.00

SIDE VIEW A. PADLOCKING POSITION LESS-FLAMABLE LIQUID-FILLED; EQUIPPED WITH PRESSURE-RELIEF DEVICE,
EXPULSION FUSES AND CURRENT LIMITING FUSES; BUILT-IN ACCORDANCE WITH ANSI
DRAWING CODES P-FP02, P-FP03, P-FP04, P-FP05, P-FP06 AND P-FP07. AS A RULE, SEPARATION
BETWEEN DUCTS (SURFACE TO SURFACE) SHALL BE 50mm. THE THICKNESS OF CONCRETE
17 MACHINE BOLT, 12mm Ø x 175mm LONG 002 - 008 - 0610 - 00 EA 24.00
C57 12.26, LATEST REVISION. APPLICATION NOTES
100 ENVELOPE FROM THE SURFACE OF THE DUCTS SHALL BE 75mm. SPECIFY CONSTRUCTIVE UNIT
GR - GROUND ROD: GALVANIZED STEEL ROD, SIZE 25mm Ø X 3M LONG OR EQUIVALENT. 1. PRIMARY BOX SHALL BE USED PRIMARILY ALONG ROADWAYS.
WITH MORE THAN THE REQUIRED DUCTS TO CONSIDER FUTURE LOAD UPGRADE.
5,000
50

2. ULTIMATE COMPRESSIVE STRENGTH OF CONCRETE F'c SHALL BE 17.2 Mpa ( 2500 psi ).
1,100 1,400 1,400 1,100 ° 6. THE FOLLOWING EQUIPMENT AND MATERIALS IN THE TRANSFORMER VAULT SHALL BE
25

.00 INSIDE OF GL - GROUND LEAD: SIZE 100mm² (AEG #4 / 0) BAR, STRANDED, SOFT-DRAWN COPPER,
OUTSIDE OF 135 3. REINFORCING BARS SHALL CONFORM TO PS GRADE 275, F'Y = 275 Mpa ( 40000 psi ).
TYP

PROVIDED BY CUSTOMER AND INSTALLED BY MERALCO, i.e., TRANSFORMER, PRIMARY CABLES,


100

FROM GROUND ROD TO GROUNDING SYSTEM INSIDE THE TRANSFORMER VAULT.

FOR BIDDING
VAULT VAULT 4. THE MINIMUM SOIL BEARING CAPACITY SHALL BE 96 KN/sq.m. ( 2000 psf ).
SECONDARY CABLES FROM THE TRANSFORMER TO THE COSTUMERS MAIN CIRCUIT BREAKER
EF ED
GW - GROUND WIRE: SIZE 100mm² (AEG #4 / 0) BAR, STRANDED, SOFT-ANNEALED AND METERING FACILITIES. ALL OTHERS SHALL BE SUPPLIED AND INSTALLED BY THE COSTUMER. 5. ALL LAP SPLICES IN REINFORCING BARS SHALL BE TO A MINIMUM OF 300mm.
GA. NO 14 6. SEAL WITH WATER STOP SEALER ALL CONSTRUCTION JOINTS PRIOR TO NEXT POURING.
(OR THICKER) COPPER, CONNECTING THE TRANSFORMER NEUTRAL TO THE GROUND LEAD
7. TOTAL GROUND RESISTANCE SHALL BE NOT MORE THAN 5 OHMS. ALL GROUNDING
CUSTOMER'S SECONDARY
MAIN CIRCUIT BREAKER 600 STEEL PLATE DETAIL "B" INSIDE THE TRANSFORMER VAULT.
CONNECTIONS/TAPS SHALL BE THROUGH THE USE OF GROUND CLAMPS OR SHALL BE BRAZED.
7. FLOOR SLAB SHALL SLOPE GRADUALLY TOWARDS DRAIN PIT TO PROVIDE POSITIVE DRAIN, CONNECT DRAIN PIPE TO DRAINAGE SYSTEM.
3,000

8. PULLING-IN IRON SHALL BE INSTALLED ON THE WALL OPPOSITE THE CONDUIT ENTRANCE AND IN LINE WITH THE DUCTS AND INSTALLED NOT CONCRETE PEDESTAL DETAIL
BE BE FD - FLOOR DRAIN: FOR DRAINAGE SYSTEM OF ANY ACCUMULATION OF WATER IN THE
HIGHER THAN THE CENTERLINES OF THE LOWER MOST DUCTS AT THE OPPOSITE CONDUIT ENTRANCE.
COMPANY LOGO TRANSFORMER VAULT; 200 SQUARE X 100mm DEEP TRAPPED DRAIN WITH 8. DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE SPECIFIED. GROUNDING DETAIL,
200

STRAINER AND 50mm Ø DRAIN PIPE CONNECTED TO A POSITIVE DRAINAGE SYSTEM 9. ALL EDGES OF SLAB OPENING SHALL BE REINFORFED ACCORDINGLY.
MERALCO LIGHTNING ARRESTER DETAILS,
1,000

RED BACKGROUND OR SUMP FACILITIES. THE FLOOR DRAIN SHALL BE LOCATED WHERE IT SHALL BE 10. CLEAR CONDUIT ENTRANCE FROM REINFORCED BARS. BEND OR LOOP AROUND GROUP OF DUCTS AS FIELD CONDITIONS MAY REQUIRE.
DANGER
GR GR
TRANSFORMER DETAIL,
150

WHITE LETTERS WITH BLACK OUTLINE VISIBLE AND SAFELY ACCESSIBLE FROM THE DOORWAY. THE FLOOR SHALL BE 11. FOR DETAILS OF PULLING-IN IRON AND CONDUIT ENTRANCE SEE - DWGS. E - 788 AND UGH - MH - AC.
600

HIGH VOLTAGE 34,500V


RED LETTERS PITCHED TOWARD THE DRAIN. STANDARD DETAILS
600

CKT NO._____________________ 12. PVC ELECTRICAL DUCTS USED IN THE CONSTRUCTION OF PRIMARY CONDUIT SYSTEM MAY BE USED AS DRAIN PIPE.
250

TLN NO._____________________
SECONDARY TRENCH UNAUTHORIZED PERSONS KEEP
OUT BLACK LETTERS 13. WHERE DRAIN PIPE LEADS DIRECTLY INTO SEWERS. TRAP SHOULD BE USED TO KEEP SEWER GAS OUT OF THE PULLING BOX.
KEEP DOORS ALWAYS LOCKED
BE - BOLT-EYE: GALVANIZED STEEL, AT LEAST 10,000 KG STRENGTH; ANCHORED ON
EMERGENCY TEL NO. 16220
WHITE BACKGROUND 14. ALL BACKFILL UNDER FLOOR SLAB SHALL BE FIRMLY TAMPED BEFORE POURING.
THE WALL 1000mm HIGH.
DETAIL "C" 15. LABOR COSTS INCLUDE EXCAVATION AND BACKFILL. DESIGNED BY: FAVDC

ISSUED AS:
CP - CONCRETE PAD: 75mm HIGH, (SEE DETAIL 'D').
VOLUME OF EXCAVATION = 18m3

ELEVATION B. STEEL LOUVER C. DANGER SIGN CONSTRUCTIVE UNIT CODE


DM03W
APPLICATION
TO INSTALL PRIMARY MANHOLE, 3-WAY
VOLUME OF BACKFILL = 1.8m3
16. DIMENSIONS ARE IN MILLIMETERS.
CAD BY: FBA

E-04
DATE: 23 DEC. 2016