Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
SPECIFICATION
SR-150
FOR
161/13.8/13.8 kV,
56/28/28 MVA
POWER TRANSFORMER
1. Fill in all the required data in the intended fields. M. Cheausu 11/9/17
2. After filling completion, save the Excel document using the format name Checked
"SR-150_Your Company’s name_version num" (for example “SR150_IECo_ver1”)
Dr. H. Ben-Haim 12/9/17
3. For additional instructions/support, refer to sub-clause 9.1 of this
Specification or contact: kristi.burdhima@iec.co.il .
Approved B. Reshef 24/10/17
Copyright ©. All Rights Reserved. No part of this Specification may be reproduced, stored in retrieval system,
or transmitted , in any form or by any means, electronic, mechanical, photocopying, recording, or otherwise
or used for purposes other than participation in this tender, without the prior written permission of
RELIABILITY & H.V. EQUIPMENT DEPARTMENT, The Israel Electric Corporation Ltd. .
SEPTEMBER 2017
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
Table of Contents:
CHAPTER 1 PURCHASER
CHAPTER 4 SCOPE
CHAPTER 15 NOTES
B-1
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
1 PURCHASER
2 NAME OF ITEM
3 LOCATION OF ITEM
4 SCOPE
Design, develop, manufacture, test, preserve, pack for overseas shipment and transport to an agreed-upon destination a 3-phase,
4.1.1
161/13.8/13.8kV, 56/28/28MVA, step-down, oil-immersed Power Transformer, in accordance with this Specification as detailed hereunder.
4.2.1 ITEM 1: 3-PHASE, 161/13.8/13.8 kV, 56/28/28 MVA, OIL-IMMERSED POWER TRANSFORMER
The transformer shall be delivered tested in the factory according to the requirements in paragraph Tests (clause 11) and equipped with all
4.2.6
accessories, as specified under paragraph "Design and Construction" (clause 10.5.1.1).
The 56 MVA Transformer HV line terminals shall be connected to 161kV Transmission Grid and LV line terminals to 13.8 kV Distribution
5.1
Grid.
6.1
The supplier's structure, policy and procedures shall be according to APPENDIX 9 (Subclauses 2.1 and 2.2 in APPENDIX 9 are
compulsory requirements) .s
Any equipment provided for Israel Electric Corporation Ltd. or use for software/hardware maintenance actions shall be according to
6.2
APPENDIX 9
B-2
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
Certification Body (CB) – An independent external body authorized to confirm that tended/supplier's Management System conforms with the
7.1.1
requirements specified in the standard, by issuing a certificate. The Certification Body should be qualified to certify by an Accreditation Body.
Accreditation Body (AB) – An independent body, being a member of the International Accreditation Forum Multilateral Arrangement – IAF
7.1.2
MLA, having authority to formally approve the competence of a CB providing certification services.
7.1.4 The selection of Contractor's subcontractors (for the contract) shall be subjected to Purchaser's approval.
The Purchaser shall have the right to audit and comment on Contractor’s Quality Assurance System regardless of whether it was previously
7.1.5
audited by a certifying agency or any other body.
The tender/supplier shall have a Quality Management System (QMS) having a certificate evidencing compliance with the requirements of
7.1.6 the valid revision of ISO 9001 or any other Management System standard specifically indicating that it implements the requirements of ISO
9001 Which are valid on the date that specified for submission of the proposal.
Approval of conformance with the ISO 9001 requirements, as indicated in clause 7.2.3 above, shall be in a form of a certificate issued by a
7.1.7
Certification Body (CB) which is a qualified by an Accreditation Body [(AB), see 7.1.2 )].
7.1.8 The certificate should bare the logo of the CB and of its Accreditation Body and/or the logo of the IAF MLA.
7.1.9 The certificate shall be valid on the date set for submission of the proposal.
7.1.10 The certificate shall be valid for the scope of activities requested in the request for proposal.
The scope of activities indicated in the certificate of the QMS, shall specifically cover the scope of work required by the tender/spec. (i.e.
7.1.11
power transformer design, testing and manufacturing).
Further to the Contractor's QMS certification by any certification body, the Purchaser shall have the right to audit and comment about its
7.1.12
QMS.
It is the Contractor's responsibility to assure that its subcontractors and supplier's QMS and scope of supply meet Purchaser's quality
7.1.13
requirements as imposed by the Purchaser in the Specification.
List of all subcontractors or subsuppliers, including name, address and status of their QMS (Quality
7.2.1
Management System) certification.(e.g. ISO 9001:2008, AS 9100,TL 90001, ISO/TS 16949, etc.)
The offered type of power transformer shall be a proven design (not a prototype) with high experience in
7.2.2
work.(Manufacturer declaration)
A mutually agreed Inspection Plan, including witness and hold points, shall be agreed between Purchaser
7.2.3 and Contractor. Any subsequent alternation to his program shall require the Purchaser’s agreement, prior to
start to any work affected by these alternations.
Test and Inspection certificates as required in this Specification and the applicable Standards, shall be
7.2.4 submitted immediately following their generation. The certificates shall be original, signed by Contractor and
contain actual measured values.
The generation of certificates, including those generated by Subcontractors and Sub-suppliers, shall bear
7.2.4.1
no extra cost to Purchaser.
Any equipment non-conformance to drawings, Specification or other purchase order requirements shall be
7.2.5
solved according to the terms and requirement included in APPENDIX 12
All materials used in the manufacture of the equipment shall conform to the Specification, approved
7.2.6
drawings and accepted Standards
The Contractor shall be responsible for assuring that his subcontractor’s Quality Assurance/Quality Control Programs, including their
7.2.7 organizations, procedures, personnel qualification etc., are approved and are consistent with the specific requirements imposed by the
Purchaser in the Specification.
B-3
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
7.3 INTERCHANGEABILITY
All transformer components of the same functional type and rating shall be respectively interchangeable both electrically and mechanically
and when so interchanged shall perform their function equally well in every respect. All dismountable parts, of the same functional type and
7.3.1
rating, shall be also interchangeable for all transformer components and, when so interchanged, shall perform their function equally well in
every respect.
Unless otherwise specified, all equipment shall be designed, constructed and tested in accordance with the requirements of the latest
relevant published Recommendations of the International Electrotechnical Commission (IEC), as amended up to date. All aspects, tests,
etc. not covered by IEC Recommendations shall be executed according to the latest published issue of official or otherwise approved
8.1
standards of Manufacturer's country. All relevant standards shall be stated by Contractor. In case the requirements in this Specification
differ from those in IEC Publications in any respect, the equipment shall conform to requirements in this Specification concerning that Item.
The following standards are applicable in the relevant parts to the individual components of the transformer:
8.1.2 IEC 60076-2/2011: Power Transformer Part-2: Temperature rise for liquid immersed oil transformers.
8.1.3 IEC 60076-3/2013: Insulation levels, dielectric tests and external clearances in air.
8.1.4 IEC 60076-4/2002: Guide to the lightning impulse and switching impulse testing - Power transformers and reactors.
8.1.8 IEC 60815-1/2008: High-voltage insulators intended for use in polluted conditions :Definitions, information and general principles.
8.1.9 IEC 60815-2/2008: High-voltage insulators intended for use in polluted conditions :Ceramic and glass insulators for a.c. systems.
8.1.10 IEC 60815-3/2008: High-voltage insulators intended for use in polluted conditions :Polymer insulators for a.c. systems.
8.1.11 IEC 61083-1/2001: Instruments and software used for measurement in high-voltage impulse tests : Requirements for instruments.
IEC 61083-2/2013: Instruments and software used for measurement in high-voltage impulse tests : Requirements for software for tests with
8.1.12
impulse voltages and currents.
8.1.13 IEC 61869-2/2012: Instrument transformers: Additional requirements for Current transformers.
8.1.15 IEC 60137/2008: Insulating bushings for alternating voltages above 1000 V.
8.1.17 IEC 60255-26/2013: Electrical disturbance tests for measuring relays and protection equipment.
8.1.18 IEC 60296/2012: Specification for unused mineral insulating oils for transformers and switchgear.
8.1.19 IEC 60317/2013: Specifications for particular types of winding wires - Enameled round and rectangular copper wire.
IEC 60404-8-7/2008: Specifications for individual materials - Cold-rolled grain-oriented electrical steel strip and sheet delivered in the fully-
8.1.20
processed state.
8.1.22 IEC 60554/2001: Specification for cellulosic papers for electrical purposes.
8.1.23 IEC 60567/2011: Oil-filled electrical equipment – Sampling of gases and analysis of free and dissolved gases - Guidance.
B-4
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
8.1.30 IEC 61000-5-7: Electromagnetic compatibility (EMC) - Degrees of protection provided by enclosures against electromagnetic disturb.
8.1.31 IEC 62155/2003: Tests on hollow insulators for use in electrical equipment.
8.1.33 IEEE Std. C57.109-2008: Guide for Liquid-Immersed Transformer Through-Fault-Current Duration.
8.1.34 IEEE Std C57.12.90-2015: Test Code for Liquid-Immersed Distribution, Power, and Regulating Transformers.
8.1.35 IEEE Std C57.93-2007: Guide for Installation and Maintenance of Liquid-Immersed Power Transformers.
8.1.36 IEEE Std 693-2005: Recommended Practice for Seismic Design for Substations.
8.1.37 ANSI/IEEE C57.12.00-2010: General Requirements for Liquid-Immersed Distribution, Power, and Regulating Transformers.
8.1.38 ISO/IEC 17025/2006: General requirements for the competence of testing and calibration laboratories.
ISO 9001 Quality Management Systems Requirements or any other Management System standard specifically indicating that it implements
8.1.39
the requirements of ISO 9001, valid on the date specified for submission of the proposal
8.1.40 ISO 14001 Environmental Management Systems (valid on the date specified for submission of the proposal).
8.1.41 ISO 14025:2006: Environmental labels and declarations - Type III environmental declarations - Principles and procedures.
8.1.42 ISO 4871:2009: Acoustics - Declaration and verification of noise emission values of machinery and equipment
8.1.44 API STD 650-2011: Welded Steel Tanks for Oil Storage.
8.1.45 ASTM A 153M-2009: Standard specification for Zinc Coating (Hot-Dip) on Iron and Steel Hardware.
8.1.47 ASTM B 579-73/2009: Standard specification for Electrodeposited Coatings of Tin-Lead Alloy. (Solder Plate)
8.1.48 ASTM B 580-79/2009: Standard specification for Anodic Oxide Coatings on Aluminum.
8.1.49 ASTM A876/2012: Standard specification for Flat-Rolled, Grain-Oriented, Silicon-Iron, Electrical Steel, Fully Processed Types.
8.1.50 ASTM D 3455/2011: Standard Test Methods for Compatibility of Construction Material with Electrical Insulating Oil of Petroleum Origin.
8.1.51 ASTM F 1135-99/2004: Standard specification for Cadmium or Zinc Chromate Organic Corrosion Protective Coating for Fasteners.
DIN EN 50216-4:2015 Power transformer and reactor fittings. Basic accessories (earthing terminal, drain and filling devices, thermometer
8.1.55
pocket, wheel assembly)
If after issuing of the current Specification some of the mentioned standards are updated, amended, withdrawn or superseded with other
8.2 ones, the impact of these changes on the Specification and on the final product will be subjected to discussion between the Manufacturer
and the Purchaser.
8.3 For the purpose of this Specification, the definitions listed in IEC 60050 (IEV) and other IEC standards have been used.
B-5
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
9 TECHNICAL DOCUMENTATION
9.1 GENERAL
This document contains proprietary information of Israel Electric Corporation (I.E.Co.) and is to be used for the Project and for the sole
purpose for which it is furnished. The recipient or anyone on its behalf shall not be entitled to use the document, or any part thereof, for any
9.1.1 other purpose without the prior written approval of I.E.Co. The recipient shall keep this document in strict confidence and shall not transfer,
disclose or divulge it to any other person without the prior written approval of I.E.Co.
I.E.Co. is the sole owner of all intellectual property rights associated with this document and any future work product thereof.
The Bidder is requested to fill-in the offered data in the Specification (".xls") format file and in the attached (".pdf") Form published by I.E.Co.
Procurement Division. Answers shall be inserted in the questionnaire tables in the free columns of the right hand side. A definite answer
9.1.3
(data, yes or no, or appropriate comments) shall be given to all the requirements. Any supplementary data relevant to the evaluation shall be
well referenced to be taken into account.
Bidder's Proposal containing the filled-in Specification (".xls") format file, as well as all documents intended to complete the Bid, shall be
9.1.4
submitted as required in Tender documents, at Proposal submission term, in two different formats:
9.1.4.2 One (1) hard-copy, the printed files (of the documentation) sent according to subclause 9.1.4.1
I.E.Co. keeps the right to demand any clarification and/or technical documentation to demonstrate any answer. In case of unclear or missing
9.1.5
answer/information, I.E.Co. will complete the information according to its understanding / worst case.
The Bidder's proposal will be disqualified, whether his answer on any clause marked by the symbol ©, will not comply with the I.E.Co.
9.1.6 Specification requirement.
Furthermore I.E.Co. keeps the right to disqualify the Bidder's proposal which will not meet other technical requirements of this specification.
In case that Bidder has to comment/ to clarify/ to adapt any of the clauses of this Specification, he has to do it either on the right free
9.1.7
"OFFERED" columns or chapters 15 and 16 of this Specification.
Bidder’s offered data and parameters as well as definite answers or comments will be evaluated from technical point of view according to
9.1.9
their conformance level. Every evaluated answer will be multiplied by its technical weight by using an expert evaluation computer program.
9.1.10 Missing of answer/information/comment in Bidder's Proposal will affect negatively its total score.
The technical weight of relevant subclauses is stated in the Evaluation Criteria document, which is attached to Tender documents and is
9.1.11
identical for every Bidder.
9.1.12.1 Microsoft Office – Excel file type: This is a protected file that allows data input only in designated areas.
9.1.12.2 Adobe Reader – PDF file type: These are protected files; some of them allow data input only in designated areas.
9.1.12.2.1 Files sent by the Bidder shall comply with cyber security requirements.
The Specification is sent without any automated process / MACRO's and shall be returned in the same format without any automated
9.1.12.3
process / MACRO's.
9.1.12.4 Filled-in files shall be in the same format as they were sent
B-6
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
Cross-section of core window with windings, indicating clearances between windings of the same phase,
9.2.5 Attach document
between windings of different phases to core etc.
Cross-section drawing of transformer core, showing the selector switch and manholes with approximate
9.2.6 Attach document
dimensions.
External view, on transformer side on which manholes are located, showing all external accessories near
9.2.7 Attach document
the manholes.
9.2.8 Description, technical data and catalogue of On-Load Tap-Changer. Attach document
9.2.11 Description, technical data and catalogue of transformer monitoring system. Attach document
9.2.13 Technical data of oil and oil test report. Attach document
General information and drawings of the cooling equipment. Description of temperature actuating relays.
9.2.14 Temperature at which cooling equipment starts and range of adjustment, power and control voltage supply Attach document
9.2.15 Complete description of coolers and fans including metal coating, painting and test reports. Attach document
9.2.16 Drawing and description of transformer tank air-drain system. Attach document
9.2.17.1 Environmental conditions (humidity / temperature etc.), during coating application. Attach document
9.2.17.2 Coating application system selected for the different parts/areas of the transformer, as follows: Attach document
9.2.17.2.6 Transformer control box coating application system (according to table 2.1, APPENDIX 7) : Attach document
B-7
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
Description and drawing of transformer control box and list of all measuring, control and protection relaying
9.2.18 Attach document
equipment included.
9.2.19 Description of protection devices and their connection diagram. Attach document
9.2.20 Drawings and technical data for each type of transformer bushing. Attach document
9.2.21 Description, cross-section, wiring diagram and drawings of bushing CT’s. Attach document
9.2.22 List of accessories and fittings with short description, technical data and catalogues. Attach document
9.2.26 Example of routine test report for the offered transformer type. Attach document
9.2.27 Type test report (authority, number and date) for the offered transformer type. Attach document
The type tests shall be performed by a neutral certified laboratory accredited to ISO/IEC 17025-2006 by an
9.2.27.1 Attach document
Accreditation Body.
9.2.28 Short-circuit test reports for similar supplied transformers. Attach document
9.2.29 Main accessories (OLTC, bushings, radiators, CT’s) type test reports Attach document
Manufacturer is requested to fill in the enclosed APPENDIX 2 "Reliability, Maintainability, Safety (RMS)”
9.2.31 based on relevant information from users. Manufacturer shall describe the system of relevant data Attach document
Prolonged storage (2-3 years) before installation, taking into account the specific conditions under clause
9.2.32.1 Attach document
10.1.2 .
9.2.33 Reference list for the last five (5) years Attach document
B-8
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
List of recommended special tools and instruments necessary for assembling and disassembling of the
9.2.35 Attach document
transformer.
9.2.37 A list of recommended spare parts with details as follows: Attach document
9.2.37.1 Manufacturer
9.2.37.3 Type
9.2.38 A list of all parts which could wear out after 5, 10, and 20 years of Transformer operation. Attach document
9.2.39 A valid certification to ISO 9001:2008 granted by a CB as indicated in clause 7.1 . Attach document
A certificate attesting to the fact that the Manufacturer maintains and environmental management system
9.2.40 Attach document
that fully complies with ISO 14001 international standard,.
9.2.41 An environmental product declaration (EPD) approved and certified by an accredited certification body (CB). Attach document
9.2.42 A copy of Contractor's Quality Manual and specific QMS (Quality Management System) Procedures. Attach document
9.2.44 A preliminary Inspection and Test Plan. (I&T Plan) Attach document
9.2.45 Acceptance test procedures for materials and subsystems. Attach document
9.2.49 List of qualified suppliers of Transformer main parts and components. Attach document
B-9
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
Not later than one (1) month after notification of award, Contractor shall submit to Purchaser for approval
9.3.1 one (1) electronic (*.pdf format) and three (3) complete sets of prints of drawings and transformer technical
documentation.
Purchaser reserves the right to require additional necessary data, descriptions, drawings, etc. that may
9.3.2
contribute in completing information supplied about the transformer.
9.3.4 The submitted technical documentation shall cover the following information:
Drawings of Transformer complete with all accessories, including all necessary details for mounting,: fixing
9.3.4.1
holes, weight, major dimensions, permissible static and dynamic forces.
Detailed information of transformer tank. Including material, welding procedures, water and oil tightness,
9.3.4.3
probe pockets etc.
Details of skid base and wheels, provisions for anchoring the transformer after it’s installation, coolers,
9.3.4.4
bushing terminals, anti-seismic provisions etc.
Details of anchorage forces acting on the concrete beams during an earthquake regime acording to
9.3.4.5
Drawing No. 7 .
Wiring diagrams of all accessory equipment supplied with the transformer, including connections to OLTC
9.3.4.14
and software specifications.
9.3.4.15 Size and location of earthing connectors for transformer and control box.
9.3.4.16 Nameplate.
A list of all gaskets and sealing rings including location, dimensions, number of catalogue, resilience
9.3.4.18
properties and duration of conservation in storage without loss of qualities.
Painting procedures including: surface preparation procedures, application procedures, materials (paints
9.3.4.19 and metal coating), technical data sheets, details about protecting of problematic places (special thickness,
strip coats), quality control procedures.
Final list of all subcontractors and subsuppliers including name, address and a copy of their Quality
9.3.4.20
Assurance certificates.
B - 10
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
Instruction manuals, technical directives, drawings and any other relevant descriptive materials containing
9.3.4.21 all information required for the mounting, commissioning, operation, maintenance, periodic checking,
testing and repairing of the transformer.
Any additional information considered necessary for clarifying various aspects of Transformer performance,
9.3.4.22
operation, maintenance, etc.
For transformer models development purposes used in transient overvoltages and overcurrents calculation
9.3.4.23
of switching operations, the following data shall be provided:
9.3.4.23.1 Transformer capacitive scheme (computed for earthed core case), including:
9.3.4.23.2 Flux density at rated voltage and the saturation flux density
Magnetizing curve of the assembled magnetic core (for the closest winding to the core) in the following
9.3.4.23.3
conditions:
9.3.4.23.3.1 Represented as the peak values of the voltage (or magnetic flux) vs no-load peak current.
9.3.4.23.3.3 The air-core inductance for 2 pu to 2.5 pu. (computed from HV side and LV side)
9.3.4.23.4 Core power losses dependence on peak value of the voltage.(in uniform scale representation)
Complete instruction books as may be required for Transformer installation, operation and maintainance,
9.3.4.25
one (1) electronic and one (1) printed copy.
9.3.4.26 Instruction books shall include necessary technical information and drawings for:
9.3.4.26.7 Dismantling.
B - 11
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
A list of all bolts used, including dimensions, number of catalogue, material, type of thread, maximum
9.3.4.29
fastening.torque.
Instructions for the disassembly and end of life procedures for different components of the equipment
9.3.4.30
(composition, weight, toxicity etc.)
Not later than two (2) months after the approval of documents is completed, Contractor shall submit to
9.3.5 Purchaser one (1) electronic (*.pdf format) and three (3) printed copies of transformer drawings and
instruction books.
All descriptive materials (lists, instruction books, etc.) shall be numbered and dated for easy identification
9.3.6
and reference purposes.
All data and descriptive material in the above drawings and instruction books shall be in English or Hebrew.
9.3.7
All dimensions shall be shown in metric units.
B - 12
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
10 TECHNICAL REQUIREMENTS
10.1.1.4 System neutral grounding method Solid Grounding Solid / Resistor Grounding
10.1.1.9 Transmission / distribution system line autoreclosing policy Single-phase one shot Three-phase two shots
Dry period of nearly 8-9 months and more than 100 dangerous wetting events a
10.1.2.1.1
year.
10.1.2.1.3 Humidity:
10.1.2.2.2 Severe atmospheric and industrial air pollution, dust, salt spray, sand storms
Water from sources other than rain: Spraying water and water jets with water
10.1.2.2.4 15
velocity (m/sec)
B - 13
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
IEC 60721-3
10.1.2.2.5 Chemically active substances according to IEC specifications
Table 4 3C4
IEC 60721-3
10.1.2.2.6 Mechanically active substances according to IEC specifications
Table 5 3S4
10.1.2.2.6.1 Sand (mg/m^3) 1000
The seismic design of the transformer installed on its foundation shall be based
10.1.2.3.1 IEEE Std. 693-2005
on the seismic qualification requirements stated in
10.1.2.3.2 The required seismic qualification level for transformer shall be Moderate
10.1.2.4.1.3 Severity level for electrical 1 MHz burst disturbance (kV) 2.5
Indicate the time duration, the power transformer is able to withstand the
temperature rise caused by a 50 Amps DC current passing through its neutral
10.1.2.5.1
point, as a result of Geomagnetic Disturbance (GMD) or Electromagnetic pulse
(EMP). (min)
B - 14
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
10.2.1 Contractor/Manufacturer shall submit with the proposal failure statistics for installed power transformers
The Contractor/Manufacturer shall state the minimum guarantee MTBF including confidence level.
10.2.2 Contractor shall indicate the methods by which the MTBF values were determined and shall submit
supporting data
Service life expectancy of the equipment and possible performance degradation with time, defined in
10.2.3
quantitative terms
10.2.4 The Contractor/Manufacturer shall furnish suggested actions to prevent recurrence of component failure
The Manufacturer shall notify the Purchaser, without any undue delay, of any defect failure, malfunction or
incompatibility in the equipment, or in similar types of equipment, which shall have appeared, or discovered
10.2.7 in the course of the period, extending from the execution of the Contract of supply until three years after the
expiration of the warranty period, in as much as it affects or may affect the use, performance, qualities,
lifetime, or safety of the equipment.
The notification shall be in written form and shall specify the nature of the defect, failure, malfunction, or
10.2.7.1 incompatibility, any ramifications, stemming therefrom and any relevant corrective measures, adopted or
recommended by the Manufacturer.
©
10.3.2 Connection symbol
YN yn6 yn6 dd
©
10.3.3 Rated frequency (Hz)
50
10.3.4 Rated voltages: ©
B - 15
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
Transformer HV neutral shall be brought out through proper neutral bushing and
10.3.8
shall be suitable for operation with:
©
Ratings of the transformer shall be based on the ambient air temperature stated
10.3.10
on subclause 10.1.2.1.2 and on the following temperature conditions:
©
IEC 60076-7
10.3.10.4 Design ambient temperature (C), according to:
subcl. 3.16
Thermal time constant (estimated values shall be indicated ,exact values will be
10.3.14 IEC 60076-2 & 7
submitted after performing the temperature rise test ) for :
B - 16
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
10.3.15.1.3 LV (13.8 kV) line and neutral terminal (kV peak) 110
B - 17
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
Single-phase voltage applied to short-circuited XV winding line terminals and its Xo±10
10.3.17.3
neutral with HV ,YV and TV windings open-circuited (Ω/phase ± tolerance%)
The difference of the same impedance between any of the supplied transformers
10.3.18
acc. to this Specification, shall not exceed:
B - 18
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
rd
10.3.21.1 3 (%)
th
10.3.21.2 5 (%)
th
10.3.21.3 7 (%)
Permissible time the transformer can withstand the following power frequency
10.3.23
overvoltages at no-load:
10.3.25 Each transformer shall have at least overload capability in accordance with:
©
IEC 60076-7
B - 19
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
10.3.25.2 Previous continuous loading, related to 56 MVA (K1) 0.5 0.7 0.8 0.9 1
10.3.25.3 Permissible overload, related to 56 MVA (K2), for following overloading time:
10.3.25.3.1 0.5 h
10.3.25.3.2 1h
10.3.25.3.3 4h
10.3.25.3.4 8h
10.3.25.3.5 24 h
All components of the transformer including bushings, bushing CT’s and OLTC
10.3.25.4
shall shall withstand overload according to subcl. 10.3.25.3 .
©
Load loss evaluation will take in consideration the maximum between three
10.3.26.5 guaranteed load loss values (three OLTC step positions), as will be submitted in
the following subclause 10.3.27.4
10.3.27.1 The tolerances for losses are according to IEEE Std C57.12.00
Maximum
Calculated losses values shall be introduced. Final measured values shall be Calculated tolerance
10.3.27.2
within tolerances. loss (kW)
(%) ©
10.3.27.3 No load loss (excitation loss) at:
B - 20
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
The average tolerance of all supplied transformers in the same order, according
10.3.27.5
to this specification, shall not exceed:
10.3.27.5.1 For no-load losses (%) 0 (zero)
In addition, for 2 or more units belonging to the same order, the average
10.3.27.7 tolerances for no-load and short-circuit losses of all ordered units on maximum, 0 (zero)
minimum and principal taps shall not exceed (%)
Maximum
Auxiliary power (total power requirements for cooling) required by the Aux. power
10.3.27.8 tolerance
transformer, with loading as follows: (kW)
(%)
Voltage applied to HV winding with XV winding short-circuited and YV winding
10.3.27.8.1 10
unloaded, based on 28 MVA:
In case that transformer losses exceed the declared values, I.E.Co reserves the
10.3.27.9 right to reject the transformer or to accept it with compensation, according to
APPENDIX 11
B - 21
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
Maximum guaranteed sound power level of the transformer under no-load and
10.3.29.5 excited at rated voltage and rated frequency, with the OLTC in the principal
tapping and cooling equipment out of service. [dB(A)]
Maximum guaranteed total sound power level at rated voltage, rated current and
rated frequency, with cooling equipment in operation and the OLTC in the
10.3.29.6 IEC 60076-10
principal tapping calculated by summarizing the guaranteed values under
subclause 10.3.29.3 and 10.3.29.5, according to:
10.4.2.1.10 Transportation dimensions and weight according to sub-clauses 12.4 and 12.5
B - 22
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
The core shall be manufactured of high quality cold-rolled, grain oriented, low- ASTM A876 and/or IEC
10.5.1.1
loss, steel lamination, non-aging sheet, according to: 60404-8-7
10.5.1.2 Type
10.5.1.3 Manufacturer
10.5.1.10 Sheets shall be pressed by means of glass tapes and suitable tension screw
All the sections of the magnetic core separated by oil channels or electrically
insulated shall be brought outside the transformer tank, each one through a
separate transition bushing.
The transition bushings shall be located in a weatherproof box, protected IP55
and mounted on the tank cover.
Inside this box, all these bushings shall be linked together and the connection
between this link and the earthing point in the lower part of transformer tank shall
10.5.1.13.1
be carried out by an insulated copper cable 1×16 mm², rated 1 kV and passed
through an insulated flexible metallic conduit.
The upper end of the flexible metallic conduit shall be grounded to the
weatherproof box.
The earthing connection point located in the lower part of transformer tank shall
be marked by a nameplate located close to the grounding pad.
On the nameplate shall be written “Magnetic Core Grounding Point".
Indicate the number of transition bushings for the magnetic core sections as stated in
10.5.1.13.2
subclause 10.5.1.13.1
The metallic transformer active parts insulated from the tank and insulated
between them, such as core frame, beams, tie plates, braces etc. shall be linked
together by an insulated wire and brought outside the transformer tank through a
separate transition bushing. This bushing shall be located in the same
weatherproof box on the tank cover (see subclause 10.5.1.13.1). The link
between the different part shall be performed in such a manner to avoid loop
10.5.1.13.3 forming. The connection between this bushing and the earthing point in the lower
part of transformer tank shall be carried out by an insulated copper cable 1×95
mm², rated 1 kV and passed through the insulated flexible metallic conduit
mentioned in subclause 10.5.1.13.1 . The earthing connection point located in
the lower part of transformer tank shall be marked by a nameplate located close
to the grounding pad. On the nameplate shall be written “Core Clamp Grounding
Point”.
B - 23
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
10.5.2 WINDINGS
10.5.2.1.4 TV winding(s)
In order to protect the coil copper wire against sulfur corrosion phenomena, the copper
10.5.2.2.1 IEC 60317
wire used for windings production shall be enameled acc. to
All materials used in transformer construction (insulation materials, glues etc.) shall be
10.5.2.2.2
corrosive sulfur free
10.5.2.4.2 Thermal class of winding insulation according to IEC 60085 (°C): 120 (E)
Winding hot-spot temperature and metallic parts in contact with cellulosic insulation
10.5.2.4.3 110
material shall not exceed (°C)
10.5.2.4.5.1 HV winding
10.5.2.4.5.2 LV winding
B - 24
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
10.5.2.9.1 HV winding:
B - 25
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
The flexible connections inside the tank shall be performed with thin copper
10.5.2.14
tapes.
B - 26
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
10.5.3.10 Oil of diverter switch shall be completely separated from transformer oil.
10.5.3.11.3 Transformer ratio at principal tap ("0" tap position) (kV/kV/kV): 161/13.8/13.8
10.5.3.16 OLTC maximum rated through current (A), according to: IEC 60214.
OLTC shall be capable to carry and switch the maximum permissible overload
10.5.3.18.4
current of the transformer
B - 27
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
Between the first and last contacts of the tap selector or selector switch and,
10.5.3.21.3.3
where fitted, of the change-over selector (kV peak)
Between any two adjacent contacts of the tap selector or selector switch or any
10.5.3.21.3.4
other contacts relevant to OLTC contact configuration (kV peak)
10.5.3.21.3.5 Between diverter switch contacts in their final open position (kV peak)
Between the first and last contacts of the tap selector or selector switch and,
10.5.3.21.4.3
where fitted, of the change-over selector (kV rms)
Between any two adjacent contacts of the tap selector or selector switch or any
10.5.3.21.4.4
other contacts relevant to OLTC contact configuration (kV rms)
10.5.3.21.4.5 Between diverter switch contacts in their final open position (kV rms)
10.5.3.24 Gas oil flow relay for protection of diverter switch compartment:
RS-2001 or equivalent
10.5.3.24.1 Manufacturer designation (according to subclause
9.1.8)
10.5.3.24.2 Type oil flow speed
10.5.3.24.3 Variant
10.5.3.24.5 Critical oil flow tripping the flap valve at 20°C (m/s ±%)
Make/break current of the trip contact for 250 V DC and time constant 40 ms
10.5.3.24.7
(A/A)
AC: 5A 250V cos φ= 1
10.5.3.24.8 Switching capacity DC: 0.4A 250V (non-
inductive)
10.5.3.24.9 Test voltage to ground 50 Hz, 1 min (kV) 2.5
10.5.3.25 The OLTC shall be complete with all necessary devices for:
B - 28
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
“Incomplete tap changer operation” (indicates that a preset time for the tap
10.5.3.26.2
operation had elapsed without completing a tap change)
“Extreme tap position” (indicates the two extreme positions, maximum and
10.5.3.26.3
minimum positions)
“Motor protective switch open” (indicates that the motor protective switch of the
10.5.3.26.4
tap-changer is open
Moving of tap selector to the selected tap shall be performed by the motor drive
10.5.3.27
unit
10.5.3.27.4 Phase 3
All mechanical and electrical parts necessary for operating of OLTC shall be
10.5.3.28 housed in weatherproof hot-dip galvanized metal or aluminum control box with IP 55
locked gasket door. Degree of protection, acc. to IEC 60529:
10.5.3.28.1 Control box shall be provided with thermostat controlled heaters (kW)
B - 29
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
Bushings shall be designed for the service conditions stated in clause 10.1.2 of
10.5.4.2 IEC 60137
this Specification and tested according to
10.5.4.6 Technical requirements - Type 1 and Type 2: Type 1 Type 2 Type 1 - Type 2
Micafil or
10.5.4.6.1 Manufacturer: HSP
preferred.
10.5.4.6.3 Type
10.5.4.6.6.2.1 Manufacturer
Silicone Rubber-
10.5.4.6.6.3 Envelope Hydrophobicity Transfer
Material (SiR-HTM)
10.5.4.6.6.3.1 Manufacturer
B - 30
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
10.5.4.6.8.1 Lightning impulse withstand voltage 1.2/50µsec (dry) (kV peak) 750 125
10.5.4.6.8.2 Power frequency withstand voltage 1min., 50Hz (dry) (kV) 355 55
10.5.4.6.8.3 Power frequency withstand voltage 1min., 50Hz (wet) (kV) 325 55
IEC 60137
10.5.4.6.9 Rated currents according to
clause 4.2 to 4.4
10.5.4.6.9.1 Rated current (Ir) (A) 400 2000
10.5.4.6.9.2 Rated thermal short-time current (Ith) at 2 sec (kA) 17.7Ir 17.7Ir
HV capacitance graded bushings shall be provided with a test tap for partial
10.5.4.6.12 N.A
discharge and dielectric dissipation factor (tan δ) measurements
10.5.4.6.12.1 Value of capacitance to earth of the test tap shall not exceed (pF) 10000 N.A
Value of dielectric dissipation factor (tan δ) of the test tap, measured at power
10.5.4.6.12.2 0.4 N.A
frequency, shall not exceed:(%)
A measurement of tan δ and capacitance at a voltage between 2 kV and
10.5.4.6.12.3 20 kV shall be performed as a reference value for measurements carried out
later when the bushing is in operation
10.5.4.6.13 Partial discharge level at 1.5Un/√3 shall not exceed (pC) 10 10 -
Bushings shall be capable to carry the maximum permissible overload current of IEC
10.5.4.6.19
Transformer, according to : 60137—table 2
B - 31
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
Thickness of bushing SiR envelope in its connection zones with bushing upper
10.5.4.7 metal part (top flange) and with bushing bottom metal part (Bottom flange) shall 6 N.A
be at least (mm)
Bushings shall be provided with condenser layers for controlling the distribution
10.5.4.7.2 N.A
of electro-magnetic field
The gap between bushing active part and insulator shall be filled with solid
10.5.4.7.3 N.A
insulated material
10.5.4.7.4 Oil-filled bushings, if any, shall be provided with oil level indicators N.A
10.5.4.7.5 Type 2 LV bushings shall be of simple design such as hollow insulator N.A.
The connection between the windings and the Type 2 LV bushing terminals shall
10.5.4.7.6 be performed in a such manner to avoid the current passing through any N.A.
screwed connection
10.5.4.7.8 Applied special treatments for bushing metallic parts corrosion protection
10.5.4.8.1 Manufacturer
10.5.4.8.2 Type
10.5.4.8.3 Standard
10.5.4.8.11 Power frequency withstand voltage, dry and wet (kV rms)
10.5.4.9 All transformer bushings shall be provided with nameplates, according to: IEC 60137 cl. 6.2
10.5.5.2 Bushing CT's shall be designed, marked and tested according to : IEC 61869-2
CT's secondary windings shall be wired to barrier type terminals in a terminal box
10.5.5.2.1
mounted on Transformer tank
10.5.5.2.2 Provisions shall be made for secondary windings earthing inside the terminal box
B - 32
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
10.5.5.3.1 Type 1 - HV (161 kV) one-phase bushing CT’s for thermal image Measuring
10.5.5.3.2 Type 2 - HV neutral bushing CT’s for zero-sequence overcurrent protection. Protection
Type 3 - LV (13.8 kV, XV and YV winding) neutral bushings CT’s for restricted
10.5.5.3.3 Protection
EF protection and zero-sequence overcurrent protection.
Type 5 - LV (XV and YV winding) three-phase bushings CT’s for thermal image
10.5.5.3.5 Measuring
and voltage regulator..
10.5.5.4.1 Manufacturer
10.5.5.4.16 Class of insulation, according to IEC 61869-2 and IEC 60085 (°C) 105 (A)
10.5.5.5.1 Manufacturer
B - 33
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
10.5.5.5.15 Class of insulation, according to IEC 61869-2 and IEC 60085 (°C) 105 (A)
10.5.5.6.1 Manufacturer
10.5.5.6.12 Composite error at rated accuracy limit primary current not exceeding (%) 10
10.5.5.6.16 Class of insulation, according to IEC 61869-2 and IEC 60085 (°C) 105 (A)
B - 34
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
10.5.5.7.1 Manufacturer
10.5.5.7.15 Class of insulation, according to IEC 61869-2 and IEC 60085 (°C) 105 (A)
10.5.5.8.1 Manufacturer
10.5.5.8.16 Class of insulation, according to IEC 61869-2 and IEC 60085 (°C) 105 (A)
B - 35
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
Transformer oil, as well as its manufacturer and type, shall meet the
10.5.6.1 requirements indicated in I.E.Co Specification for inhibited mineral insulating oil ©
No. 50/2009 (APPENDIX 3)
Oil preservation system shall contain main conservator and conservator for the
10.5.6.8
OLTC.
10.5.6.9.1 Type
10.5.6.9.2 Manufacturer
10.5.6.9.3 Number
Main conservator shall be provided with synthetic membrane and all necessary
10.5.6.10
drain cocks, plugs for oil filling, connection to tank, etc.
10.5.6.10.1 Type
10.5.6.10.2 Material
10.5.6.10.3 Manufacturer
The synthetic membrane shall keep its quality and properties over the entire
10.5.6.10.5
service period of the transformer.
If bushing center tube is oil-filled by transformer oil, then conservator lower oil
10.5.6.11
level shall be higher than the oil level of the bushing center tube top-end.
Each oil conservator shall be provided with a cobalt-free Silica Gel air-drier,
10.5.6.12 `
according to APPENDIX 4.
10.5.6.12.1 Type
10.5.6.12.2 Manufacturer
Silica Gel shall be clearly visible through a glass and shall be mounted for each
10.5.6.13
conservator at 1.5 m approximately above ground level
B - 36
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
All welding shall be according to the standard for “Welded steel tanks for oil API 650 or European
10.5.7.5
storage” equivalent standard
Details of welding: Tank and its structural attachments shall be welded by the
SMAW with basic E70 covered electrodes conform to AWS A5.1, GTAW, SAW,
FCAW with E71T-5 electrode conform to AWS A5.20. Use of any other process
10.5.7.5.1
shall be by agreement between the Contractor and the Purchaser. Welding shall
be performed in a manner that ensure full penetration and complete fusion in the
vertical and horizontal butt welds
10.5.7.5.2 Inspection of welds:
Butt welds: Inspection for the quality of the welds shall be made using the
10.5.7.5.2.1
radiographic method and the visual method
Fillet welds: Inspection for the quality of the welds shall be made using the visual
10.5.7.5.2.2
method
Radiographic inspection is required for shell butt welds. For butt welded joints in
which the thinner shell plate is less than or equal to 9.6 mm thick, one (1) spot
10.5.7.5.3.1
radiograph shall be taken in the first 2 m of complete vertical joints of each type
and thickness welded by each welder or welding operator
One (1) spot radiograph shall be taken in the first 2 m of complete horizontal butt
10.5.7.5.3.2
joint
Contractor shall conduct tests for all welders assigned to manual and semi-
10.5.7.6 automatic welding and all operators assigned to automatic welding to
demonstrate their ability to make acceptable welds
Contractor shall submit for approval, six (6) months prior to the delivery of the
10.5.7.7 first transformer, the authorization documents of welding procedures, as well as
welders qualification documents.
Transformer tank shall be absolutely water and hot-oil tight and provided with an
10.5.7.8
oil tight cover
The mechanical design of the tank shall prevent water accumulation on the
10.5.7.9
transformer cover in order to avoid corrosion appearance
The tank, oil-filled components and pipe works shall withstand the maximum
10.5.7.11 0.5
static weight of oil in service plus an additional over pressure of minimum (barg)
Joints between the tank and the cover and between various sections shall be
10.5.7.13 provided with suitable flanges and properly spaced bolts and gaskets to make
joints oil-tight
Five (5) pockets (two oil temperature sensor, two winding temperature sensor
10.5.7.14
and one spare) shall be provided on transformer tank cover
Two (2) pockets for oil temperature sensors, shall be provided on the bottom of
10.5.7.15
the transformer
Four (4) jacking points shall be provided at height not less than 350 mm to
10.5.7.17 transformer base and shall be sufficient wide to permit a tolerance from the
center line of 150 mm.
B - 37
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
10.5.7.19.2.2 Type:
10.5.7.19.3.2 Type:
Opposite to Oil drain
10.5.7.19.3.3 Location:
valve
10.5.7.19.4 Tank-emptying flanged valve
10.5.7.19.4.2 Type:
10.5.7.19.4.3 Location:
10.5.7.19.4.3.
In the tank bottom as illustrated in Drawing No.5
1
10.5.7.19.4.3.
Under oil filling valve.
2
10.5.7.19.4.3.
The distance between empting valve and drain valve shall be maximum.
3
10.5.7.19.4.3.
Minimum gap between end of the bottom drain to ground (mm). 100
4
10.5.7.19.5 Sampling valve
The pipes connecting between the sampling points and the valves shall be linked
10.5.7.19.5.8
to the external transformer tank surface
10.5.7.19.6.2 Size:
10.5.7.19.6.3 Type:
B - 38
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
Between the valve located on conservator side and the Buchholz relay, a shutter
10.5.7.19.7.1 valve with electrical driver and limiting switches ("close" and "open") shall be
mounted.
Shutter valves wiring shall be connected in control box to free terminals for
10.5.7.19.7.2
Purchaser use.
10.5.7.19.8 All additional valves required by the Manufacturer technology shall be provided.
The connection between the gas collecting pipes and the collection points
10.5.7.20 (turrets, cover etc.) on the upper side of the cover shall be metal to metal flanged
connections. The flanges shall be of rotating type.
Transformer tank shall be provided with a round manhole and space all around
10.5.7.21
OLTC in order to permit easy inspection and repair.
10.5.7.21.2 Minimum all-around space between OLTC and tank, on vertical axis (mm) 400
10.5.7.21.3 Manhole cover shall be provided with two door knobs for an easy grip.
Transformer shall be provided with safety support for ladder (see Drawing No.3).
10.5.7.23 Location of support shall be determined by Manufacturer and shall ensure the
safety going up of the worker on the cover
Transformer shall be provided with the safety fencing to ensure the safety works
10.5.7.24
on the cover
10.5.7.24.1 The fencing shall be folded down during operation of the transformer.
The installing and folding of safety fencing shall be carried out from ground level
10.5.7.24.2
by a mechanical operating mechanism (see Drawing No.4).
The fencing shall be blocked in the folded up (or raised) position to ensure the
10.5.7.24.3
safety work on the cover.
Transformer tank shall be provided with provisions for mounting metal supports
10.5.7.25 for surge arresters on HV, LV and LV neutral side. Location and relevant
dimensions shall be according to Drawing No.2
Transformer cover shall be provided with provisions for protect all the
10.5.7.27
accessories mounted on the cover against mechanical damage.
Radiators shall be equipped with top and bottom valves to permit the removal of
10.5.8.1.3
any radiator without oil draining.
Vent holes with plugs shall be provided in the top and drain holes with plugs in
10.5.8.1.4
the bottom of each radiator.
10.5.8.2 Fans
B - 39
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
10.5.8.2.1 Forced air cooling of the transformer shall be achieved by silent fans
10.5.8.2.2 Manufacturer
10.5.8.2.4 Type
10.5.8.2.8.1 Manufacturer:
10.5.8.2.8.4 Phase 3
10.5.8.2.9.1 Type
10.5.8.2.9.2 Manufacturer
10.5.8.2.9.3 Number
10.5.8.2.11 Fan motors shall be provided with thermal overload and overcurrent protection
B - 40
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
A complete control system for the automatic operation of the cooling system
10.5.8.3.2
shall be provided
A transfer switch for automatic or manual control of the cooling system shall be
10.5.8.3.3
provided
Cooling system control shall be fully automatic and shall include relays or
10.5.8.3.4 auxiliary contacts for remote indications of the number of fans in operation and
remote alarm for failure
Cooling system control shall start fans immediately upon sudden increase of
10.5.8.3.6
load above a threshold value, agreed between the Purchaser and Contractor
10.5.8.3.8 All control equipment shall be housed in the transformer control box.
Estimated time that the transformer can carry full load (56 MVA) without damage
10.5.8.5 at 30°C ambient temperature, with all fans out of service in the following initial
conditions:
B - 41
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
10.5.9 ACCESSORIES
Oil temperature indicator shall have contacts for alarm and tripping of the
10.5.9.1.8
transformer:
10.5.9.1.8.6 Shock and vibration proof up to (m/sec2, frequency range (Hz) ) 2g, 5-15
10.5.9.2.5.4 Thermometer case welded into transformer according to: DS/EN 50216-4
B - 42
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
Winding temperature indicator shall have contacts for alarms and tripping of the
10.5.9.2.8
transformer
2
10.5.9.2.14 Shock and vibration proof up to (m/sec , frequency range (Hz) ) 2g, 5-15
Make/break current of the trip contacts, for 60V DC and time constant 40 msec
10.5.9.3.7
(A/A)
AC: 5A 250V cos φ= 1
10.5.9.3.8 Switching capacity of the trip contacts DC: 0.4A 250V (non-
inductive)
10.5.9.3.9 Test voltage to ground 50 Hz, 1min. (kV rms) 2
B - 43
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
10.5.9.4.4.2 Make/break current for 220V DC and time constant 40 msec (A/A) 2/2
AC: 5A 250V cos φ= 1
10.5.9.4.4.3 Switching capacity of the contacts DC: 0.4A 250V (non-
inductive)
10.5.9.4.4.4 Switching contact type: Magnet contact tube
Vent valve shall be provided for emptying the gas which accumulates in the
10.5.9.4.6
Buchholz relay and for taking gas sample.
10.5.9.4.7 The vent valve shall be linked by an appropriate pipe to a gas sampler.
The gas sampler and its connection pipe will be joined to the external surface of
10.5.9.4.8.6
the transformer tank
3
10.5.9.4.12.2 Gas accumulation or oil loss (cm ±) -
B - 44
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
10.5.10.6.1 Eight (8) configurable internal output relays for control, trip and alarm signals.
10.5.10.6.2 One (1) system state relay for internal and circuit diagnostics.
At least four (4) fully programmable 4-20 mA DC output current loops, for use
10.5.10.6.3
with SCADA .
RS-232, USB 2.0, RJ45 /
10.5.10.6.4 Communication ports with optical interface
Ethernet / FO
Red color LED set point indicator, coupled to each output relay , for set point
10.5.10.6.7
exceeding indication .
10.5.10.7 Digital Transformer Monitor required input modules (quantity and type)
Contact closure input module (dry contact) for fan control contactor state
10.5.10.7.2
monitoring (energized / not energized)
10.5.10.7.3 CT input module for winding temperature monitoring . 3
B - 45
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
10.5.10.9.2 Oil level sensor with local indication for OLTC conservator
10.5.10.9.2.2 Dry contact for both minimum and maximum oil level indication. 1 NO + 1 NC
10.5.10.9.3 Oil level sensor with local indication for main conservator
10.5.10.9.3.2 Dry contact for minimum and maximum oil level indication. 1 NO + 1 NC
Local indicator scale shall be related to different oil temperature values, in order
10.5.10.9.3.3
to allow a appropriate oil filling procedure.
The distance from the transformer to the Digital Transformer Monitor location
10.5.10.13 100
(control room) shall be approx. (m) :
10.5.10.14 Shock and vibration proof up to (m/sec2, frequency range (Hz) ) 10g
Maschinenfabrik
10.5.11.2 Manufacturer Reinhausen GmbH
(preferred)
TAPCON BU (preferred)
10.5.11.3 Type or equivalent (according
to subclause 9.1.8)
" Automatic" or "Manual" control may be selected from a selector switch or push
10.5.11.5.1.1
buttons located on Voltage Regulator, when it is set to “Local” mode
B - 46
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
In "Remote" control mode, voltage level shall be provided from the following
10.5.11.5.2.1
sources:
10.5.11.5.2.1. Station Control System (SCS) via a TCP/IP ETHERNET LAN according to IEC
1 61850
10.5.11.5.2.1.
Dispatch Center via 60V DC inputs
2
10.5.11.5.2.1. Also, " Automatic" or "Manual" control of the VR may be selected from the SCS
3 (by communication) or from the Dispatch Center (60V DC inputs)
Three pre-defined levels of "Voltage desired value" may be selected from the
10.5.11.5.3
SCS (by communication) or from the dispatch center (60V DC inputs)
Desired value may be changed from SCS (by communication) or from the
10.5.11.5.4
dispatch center (60VDC DV Lower/Raise inputs) in 0.1V steps
10.5.11.5.5.2. using inputs from SCS (by communication) or from Dispatch Center (60V DC
2 inputs)
The VR will send back indications, to the SCS (by communication) and to the
10.5.11.5.6.1
dispatch center (Relay contacts in BCD code), regarding the OLTC tap position
The VR will send back indications to SCS (by communication) and to Dispatch
10.5.11.5.6.2
Center (relay contacts) regarding the VR mode and status
The VR will send back indications, to the SCS (by communication) and to the
10.5.11.5.6.3
dispatch center (4-20mA analoge output), regarding the "Desired Value" reading.
Voltage regulator shall include the hardware and software required for a TCP/IP
10.5.11.6
ETHERNET LAN communication with the SCS.
10.5.11.8 Voltage regulator shall comply with the requirements of IEC standard: IEC 61850, Edition 2
Voltage regulator and all other static equipment shall be protected against
10.5.11.10
shocks, vibrations, electromagnetic influence etc.
10.5.11.12 Power frequency withstand voltage 50 Hz (1 min) at least (kV rms) 2.5
10.5.11.13 Lightning impulse withstand voltage 1.2/50 µsec at least (kV peak) 5
B - 47
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
One (1) incoming power supply circuit breaker with overcurrent protection relay
10.5.12.2.1 15
shall be provided with switching capacity (kA):
Door for front access, handles, locking facilities (key locks) and all equipment
10.5.12.2.6
required for local operation
10.5.12.2.7 An alarm signal shall be provided for opened control box door.
10.5.12.8 The control box shall be supported by suitable vibration damping device
The control box shall be accessible from ground level for operation by a
10.5.12.9 2300
workman. Maximum height above ground (mm):
10.5.13 WIRING
All the wiring for power supply, control and alarm circuits shall be done through
10.5.13.3
metallic conduit or shielded cables, earthed on both sides.
B - 48
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
2
10.5.13.4.1 Control and alarm circuits (mm ) 1.5
2
10.5.13.4.2 Secondary circuits of bushing current transformers (mm ) 4
Terminal blocks shall be spaced to allow 1½” (inch) clearance on all sides. Free
10.5.13.8
space shall be provided for Purchaser’s incoming leads
10% of the terminals shall be left free at Purchaser’s disposal, in each terminal
10.5.13.10
block
10.5.13.11.1 Wiring for aux. power and control circuits at (kV AC) 2
10.5.14 GASKETS
The necessary gaskets shall be tight under all conditions. Means shall be
10.5.14.1
provided to prevent overpressure of the gaskets.
10.5.14.2 Material of gaskets shall not deteriorate under the action of hot oil. synthetic rubber
10.5.14.3 The materials used in gaskets production shall be corrosive sulfur free
Gaskets between metal surfaces shall be set in grooves so that all parts are
10.5.14.4
bolted metal to metal.
The coating repairs after test shall be according to APPENDIX 8 and collected in
10.5.15.3
a summary report attached to transformer test reports.
Transformer oil, coating layers, insulating materials and all other components
10.5.15.4 must not chemically react and must not interfere with each other under normal
operating conditions.
Transformer earthing shall include all metallic parts which are normally not
10.5.16.1
energized (tank, radiators, conservator, pipes, control box, etc.)
Four (4) earthing pads with tapped holes shall be welded, one on each side of
10.5.16.2
transformer tank.
Earthing pads shall be copper coated and marked. with appropriate graphical
10.5.16.3
symbols.
Maximum potential difference between any point of the equipment and the
10.5.16.6 nearest earthing pad or between any two points of adjacent equipment shall not 50
exceed, for the maximum internal or external fault current (V)
10.5.16.8 All parts on transformer cover shall be connected to it's earthing terminals
B - 49
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
The OLTC cover shall be earthed by two (2) opposite points parallel with the long
10.5.16.10
transformer axis
In order to assure earthing path continuity, grounding straps between cover and
10.5.16.12
tank shall be provided
The bottom of power transformer shall be provided with a steel skid base,
10.5.17.1
suitable for pulling in directions parallel to both center lines of the tank.
10.5.17.2 The skid base of transformer shall be prepared for installing wheels assembly
Pulling eyes at base of transformer for moving the transformer parallel to either
10.5.17.3
center line of transformer shall be provided
Transformer wheels shall be able to turn in both directions, parallel to the center
10.5.17.4
lines of transformer tank.
S49 DIN5902 or
10.5.17.5 Transformer wheels shall be suitable for rails of type:
FRANCE-U50
Transformer wheels and their mounting details shall be according to Drawing
10.5.17.6
No.1
Adequate equipment for blocking the wheels after transformer installation shall
10.5.17.7
be provided.
Location, size and length of field welds shall be indicated on the equipment
10.5.17.8
outline drawing
10.5.18 FOUNDATION
Two concrete beams running at right angles to a line through the high voltage
10.5.18.2 Drawing No. 7
bushings will be used to support the transformer.
10.5.18.2.1 A drawing for Transformer anchoring to the concrete beams shall be provided.
The anchorage welds of the transformer to the support shall fulfill the IEEE 693
10.5.18.2.2
requirements of : APPENDIX D.6
Two rails running at right angles to a line through the HV bushings will be used to
10.5.18.3 support the transformer (Drawing No. 7). The required distance between rail 2350 ©
center lines (mm):
Two rails running parallel to a line through the HV bushings will be used to
10.5.18.4 transport the transformer through the handling corridor (Drawing No. 7). The 1505 ©
required distance between rail center lines (mm):
B - 50
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
Due to the severe environmental conditions to which the equipment may be subjected during its service life,
the following requirements for its protection form an integral part of the Specification and are in addition to
10.5.19.1
the standard design and protective measures which Manufacturer would normally invoke for these
conditions:
All transformer components shall successfully withstand for the entire service life
10.5.19.2 duration the climatic and environmental conditions as defined in subclause
10.1.2 .
10.5.19.3 Bolts, nuts and washers greater than 1/2" shall be:
Electrolytically or
10.5.19.3.1 Zinc coated by the method
Thermo diffusion
ASTM F 1135-99 Grade
10.5.19.3.2 Passivated according to 3 Olive Drab color finish,
or equivalent standard
Components such as springs, pins and those for which a tight maintained
dimensional tolerance is required shall be made of stainless steel. The preferred
stainless steel is an austenitic grade; however, if physical requirements are
10.5.19.4
overriding, other stainless steel grades will be acceptable. Austenitic grades will
be subject to a solution quench. Prior to being placed into service all stainless
steel components will be cleaned and passivated.
All aluminum components shall be fabricated from grades of aluminum that show
resistance to salt spray and moist conditions; e.g., Al-Mg base alloys. Al-Cu
10.5.19.5
alloys are not acceptable. After fabrication, all aluminum components shall be
anodized to ASTM B 580-79 Type A, or equivalent (indicate the standard).
Components such as sleeves or bushings having an inner face of one metal and
a supporting outer face of another, or conductors which are used with connectors
10.5.19.7
of a different metal, shall have their exposed interfaces protected against
moisture.
All bearings shall be sealed type. The seal shall be guaranteed to be protective
10.5.19.8
against sand, salt spray and moisture for a minimum period of 10 years.
B - 51
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
Contractor/Manufacturer shall submit a Commissioning Program for approval by Purchaser, three (3)
10.6.2 months prior to scheduled commissioning date. Changes or modifications to Commissioning Program shall
also be approved by Purchaser
Inspection to detect faults which have occurred during transportation, storage or during transformer
10.6.3.1
assembly on-site.
Preparation for use and procedures to describe the activities required to prepare systems for testing and
10.6.3.2
operation
Checking of rated data, connection, loading, etc. of the new equipment and necessary interface with the
10.6.3.3
existing equipment supplied by others
Checking of indicating meters, relays, control and communications equipment and similar functions
10.6.3.4
associated with the existing equipment
Checking of station auxiliaries associated with the new equipment as A.C. supply, batteries and chargers
10.6.3.5
etc.
Commissioning results shall be witnessed by the Purchaser technical staff and documented on forms to be
10.6.4 agreed upon by the Contractor. The record shall include other issues such as omissions or unsatisfactory
test results
Contractor/Manufacturer shall maintain an up-to-date record of all inspections and tests, which shall be
10.6.5
handed over to the Purchaser at the completion of the site testing and commissioning
Purchaser shall be responsible for connection and disconnection of the new equipment to and from power
10.6.7 grid, including first energization of new equipment, with the advice and technical assistance of the
Contractor/Manufacturer.
Contractor shall be responsible for safety of commissioning.personnel and shall take all possible
10.6.9
precautions and be fully aware of the dangers involved in commissioning process.
Major failure or damage to equipment will require either its return to the factory or assignment of a special
10.6.10
crew to carry out repairs
Minor failure as failures in metering, relaying control and communications equipment shall be repaired by
10.6.11
commissioning personnel
All expenses (including transport to factory and return) in connection with damages and repairs as
10.6.12
described above shall be paid by Contractor
B - 52
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
10.7.1 GENERAL
10.7.1.1 All mechanical couplings, contacts and other mechanisms shall be preadjusted and tested at the factory.
10.7.1.2 Specify which individual part shall be adjusted, regulated or tested on-site before and during assembling
10.7.1.4 Time period of Transformer operation under normal service conditions between successive checking of:
10.7.1.6.3 Acidity
10.7.1.15 Number of months between successive cleaning, painting and rust proofing of metal parts
10.7.1.16 Number of months between successive lubrication of fan bearing and drives
10.7.1.17 Expected man-hours required for periodical inspection and maintenance (hours)
10.7.1.18 Manufacturer shall ensure spare parts for transformer for a period of life duration
The transformer shall be designed for live-washing (automatic and manual) taking into account service
10.7.1.19
conditions described under clause 10.1.2 in this Specification.
B - 53
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
A full spare set of gaskets for the transformer, OLTC, bushings, radiators and all valves shall be provided,
10.7.2.1.6
with instructions and drawings for identification, location and storage.
Manufacturer shall conduct a Follow-On Support Program after the expiration of the warranty period. Terms
10.7.3.1
and conditions for its performance shall be included.
10.7.3.2 The Program shall be defined under this paragraph and shall consist of:
Participation in all the meetings required by the Purchaser in Israel, during the technical clarifications as
10.7.3.2.3
well as during the transformer entire life duration
Repair of systematic failures, design defects and latent defects, performing retrofits and updating of
10.7.3.2.5
relevant documentation
10.7.3.2.6 Repair services for the equipment, its subassemblies, modules and cards
Automatic submissions of updates and corrections to software. Update modules shall be field tested and
10.7.3.2.7
validated by Manufacturer
Notifications of new functions, applications or other software were becoming available for incorporation in
10.7.3.2.8 Purchaser’s System. The Manufacturer shall propose such software and its integration upon Purchaser’s
request
10.7.3.2.9 Follow-on supports services shall be provided for the lifetime period duration of the equipment
10.8 SAFETY
B - 54
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
Contractor shall ensure the training course for The Israel Electric Corporation Ltd. operating and installation
10.9.1
workmen.
10.10.1 N.A.
10.11.1 N.A.
10.12 METHODS
10.12.1 N.A.
11.1 GENERAL
Contractor shall notify Purchaser the exact date of performing the tests eight (8)
11.1.2
weeks in advance.
The tests shall be performed in a Test Laboratory which is accredited to ISO/IEC
17025/2005 by an Accreditation Body which has agreement signed with ILAC to
11.1.3
use the ILAC-MRA symbol in combination with the accreditation symbol or use
only the accreditation symbol.
11.1.4 The tests shall be carried out in the presence of the Purchaser representatives
IEC 60076-3
11.1.5 The dielectric test sequence shall be according to
sub-clause 7.2.3
During dielectric tests the transformer shall be equipped with the bushings that
11.1.6
will be in permanent operation
All external components and fittings that are likely to affect the performance of
11.1.7
the transformer during the tests shall be mounted
11.1.8 The permissible tolerance for each test result shall be indicated.
Contractor shall submit test data to prove that the design has the capability to
11.1.9
meet all the specified ratings as well as relevant test reports .
Routine, type and special test reports as well as the tests for main components
(bushings, OLTC, CT’s, etc.) of each transformer shall be submitted to I.E.Co.
11.1.10
for approval, not later than one (1) month from the date of performing the test,
in electronic (*.pdf format).
Contractor shall submit with test reports a list of all measuring instruments
11.1.11 including their accuracy class and type, test equipment, test circuits and
calibration certificates
Transformer can be delivered only after approval of the relevant routine, type
11.1.13
and special test reports by Purchaser.
B - 55
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
Routine tests for all accessories (bushing, grounding bushing, CT’s, etc.)
11.2.2
according to the relevant standards, shall be submitted
11.2.3.1.2 HV windings, on first, principal and last tap position, phase to phase
11.2.3.1.5 TV windings
Measuring of voltage ratio and check of phase displacement on each tap IEC 60076-1
11.2.3.2
position. subcl.11.3
Chopped wave Lightning impulse (LIC) on HV maximum, minimum and IEC 60076-3
11.2.3.5.1
principal tap subclause 13.3
11.2.3.5.1.1.2 Full level full impulse, one application (kV peak) 650
11.2.3.5.1.1.3 Reduced level chopped impulse, one or more applications (kV peak)
11.2.3.5.1.1.4 Full level chopped impulse, two applications (kV peak) 750
11.2.3.5.1.1.6 Full level full impulse, two applications (kV peak) 650
11.2.3.5.1.2.2 Full level full impulse, one application (kV peak) 110
11.2.3.5.1.2.3 Reduced level chopped impulse, one or more applications (kV peak)
11.2.3.5.1.2.4 Full level chopped impulse, two applications (kV peak) 130
11.2.3.5.1.2.6 Full level full impulse, two applications (kV peak) 110
B - 56
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
11.2.3.5.1.3.3 Reduced level chopped impulse, one or more applications (kV peak)
11.2.3.5.2 Lightning impulse neutral terminals by direct application (LIN) IEC 60076-3 subcl. 13.4
11.2.3.5.2.1.2 Full level full impulse, three applications (kV peak) 450
11.2.3.5.2.2.2 Full level full impulse, three applications (kV peak) 110
11.2.3.5.4 Induced voltage test with partial discharge measurements (IVPD) IEC 60076-3 subcl.11.3
Measurement of the dielectric dissipation factor (tan δ) and winding IEEE Std C.57.12.90,
11.2.3.5.6
capacitance subcl.10.10
11.2.3.5.6.1 A detailed list of winding pairs and guarded circuits shall be submitted
B - 57
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
The test shall be performed with guarded circuits, for three-winding transformer,
IEEE Std C.57.12.90,
11.2.3.5.6.3.4 in the same zones the insulation resistance is measured (the following 11.2.3.5.7
Table 4
subclause) and according to:
In the test report, both measured test temperature and reference temperature
11.2.3.5.6.3.5
shall be indicated
A table with the temperature correction factor in steps of 5°C up to the maximum
11.2.3.5.6.3.7
temperature rise of the transformer shall be provided.
For the first transformer, exact measurements of temperature correction factor
11.2.3.5.6.3.8 shall be performed during its cooling, after that temperature rise test is
completed.
11.2.3.5.7 Measurement of insulation resistance and polarization index
Measurement of the windings insulation resistance and of the polarization index
(the ratio of apparent insulation resistance after 10 min. to that after 1 min. after
11.2.3.5.7.1 5
the application of testing voltage) shall be performed, on each transformer, at
(kV DC)
11.2.3.5.7.2 Measurement shall be made between:
11.2.3.5.7.2.1
TV winding(s) and Tank
0
Test Report for the polarization index measurement as well as variation of
11.2.3.5.7.3
apparent winding insulation resistance with time shall be provided
11.2.3.5.7.3.1 The minimum value will be agreed between Purchaser and Manufacturer
B - 58
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
Permanent tank deflection after oil leak test and vacuum withstand test shall be
11.2.3.9
recorded in the test reports
Mechanical test of transformer tank, oil level gauges and valves to prove proper
11.2.3.10
operation
Routine and Sample tests for the hollow insulators performed by insulators
11.2.3.16 IEC 62155
Manufacturer, according to
Oil tests for each oil quantity existing in the different transformer compartments,
11.2.3.18 or delivered in separate containers (if any), according to APPENDIX 3 and IEC IEC 60296
Standard:
The report shall contain a table with the temperature correction factor in steps of
11.3.2.1.2.3
5°C up to the maximum temperature rise of the transformer
A chromatographic analysis of dissolved gases in Transformer oil shall be IEC 60076-2 Annex C.4,
11.3.2.1.3
performed before and after temperature-rise test according to IEC 61181 & IEC 60567
B - 59
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
11.3.2.2.2 The test, performed with the OLTC on principal tap, shall include:
Type tests reports for main Transformer parts (OLTC, CT's, VR, bushings etc),
11.3.3
according to the relevant standards, shall be submitted
If the transformer will be shipped without oil, the Dew Point test shall be provided
11.4.1.2 IEEE Std C57.93
for each delivered transformer unit, according to
Moisture content of dry weight on each transformer insulation shall not exceed
11.4.1.2.1 1
(%)
When tests are performed in principal tap position, the previous tap position
11.4.1.6.2 must also be recorded. It is recommended that principal tap position
measurements be made after arriving from lower tap positions.
B - 60
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
11.4.1.7.6 During the measurements, the neutral terminal 1N shall not be earthed.
Magnetization curves based on the test values, for voltages up to 110% (or
11.4.1.8 120% if possible) of nominal and on calculated values for voltage above 110%
(120%) up to 140% on each transformer.
In case the Contractor has the ability to perform a short-circuit test for the
11.4.1.9.2 specified transformer, a price proposal for this test shall be included in Annexure
"C"
Winding capacitance and tan δ shall be recorded for each voltage step on both
11.4.1.12.1
increasing and reducung voltage.
11.4.1.13.1 HV (kV)
11.4.1.13.2 LV (kV)
B - 61
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
11.5.2 The transformer shall be qualified taking into account the service configuration
11.5.6 Required qualification method for different kind of equipment: IEEE Std 693
After shake-table testing, bushings shall be subjected to and pass all routine
11.5.6.4 IEEE C57.19.00
tests, as specified in the latest revision of:
11.5.6.5.1 Seismic analysis qualification report according to: IEEE Std 693/ Annex S
11.5.6.5.2 Seismic test qualification report according to: IEEE Std 693/ Annex T
Contractor shall submit a list of all tests to be performed on-site, after mounting
11.6.1
of the transformer and during operation
11.6.2 Final on-site test program shall be agreed between Purchaser and Contractor
11.6.2.1.4 Prerequisites
On-site tests will be performed by the Purchaser in the presence and under
11.6.3 responsibility of Contractor’s delegate according to the approved commissioning
program, required tests list in APPENDIX 6 and subclauses 11.6.1 and 11.6.2 .
On-site tests shall include also a SFRA test to compare its results with the
11.6.4
"fingerprint" test, carried out according to subclause 11.4.1.6
B - 62
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
All components or accessories not included in the main shipment may need to
be shipped by Air Mail by Air Express or by Air Freight at Contractor’s expense, if
12.3
required by Purchaser..In which case such shipment shall be handled according
to conditions stated in relevant Tender's commercial annexures.
12.6 If transformer oil will be shipped separately, indicate oil weight (t)
If transformer shall be shipped oil-filled, it shall be fitted with oil level shipping
12.7
gauges.
12.8 Transformer shipped partly oil-filled shall be completed with gas under pressure nitrogen or dry air
12.8.2 Gas pressure at 15°C, that shall be ensured until oil completion (Psi) 5 (0.34 atm)
12.8.3 Gas pressure shall be monitored continuously until the refilling with oil.
Manufacturer shall take all necessary steps to prevent any oil leakage, both
during transport to site and during operation. Such steps shall include, for
example: instructions for loading transformer on trailer, instructions for ensuring
protection of transformer against inertial forces in all directions during transport,
12.10
instructions for unloading, etc. as well as instructions for prevention of damage
during installation, instructions for prevention of damage in operation with
permanent vibrations caused by working conditions and with wind loading under
dynamic conditions etc. according to IEC 60076-1 and subclause 10.1.2.6 .
All items shall have their lifting, jacking and haulage points and safe working
12.11
loads clearly marked at all stage of transport and installation period process.
The package shall be provided with means for moisture control and supervision
12.12
and shall be appropriate for long term storage
The main shipping piece (transformer) shall be provided with shock detectors in
12.13 3g
all directions, having a minimum acceleration recorded level of:
The spare parts can be delivered only after approval of the relevant
12.14
documentation (part number etc.)
Spare parts and special tools shall be packed separately and a detailed packing
12.14.1
list shall be sent
All components or accessories shipped dismantled for field mounting or field
assembly shall be suitably tagged to show identification and service. Tags shall
12.15
be exceptionally durable and securely tied to items by wire or other approved
methods
Contractor shall supply three (3) months before shipment of the equipment five
12.16 (5) sets of complete Bill of Materials, to enable checking and identifying of
equipment upon receipt.
Contractor shall mail before shipment of the equipment the relevant test reports
12.17
and shop inspection report
B - 63
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
Contractor shall include with the shipment a Bill of Materials to enable the
12.18
Purchaser to determine if all dissemble items have been received
The Contractor will be required to undertake to arrange on behalf of the
Purchaser and in consultation with and at the expense of the Purchaser for the
shipment in due time of the transformers to be supplied hereunder, on a vessel
12.19 suitably equipped for loading the said equipment at the port of origin, for carrying
the same and for unloading same at port of destination in Israel, and the
Contractor shall further be required to undertake to have the transformers
properly stowed on the said vessel, at Contractor's expense
Taking into account the specific climatic conditions described under clause
13.1
10.1.2 , Manufacturer shall indicate:
B - 64
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
The reduced temperature rise limits indicated in subcl. 10.3.10 shall be specified IEC 60076-2,
14.3
according to: clause 6.3.2
B - 65
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
15 NOTES
15.1.1
B - 66
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
16 SPECIAL REQUIREMENTS
16.1.1 Manufacturer is requested to describe or indicate deviations of the equipment and accessories from Specification requirements:
16.1.1.1
In case no deviations are mentioned it will be understood that Manufacturer’s offer entirely complies with all
16.1.2
requirements in this Specification.
B - 67
ANNEXURE "B" AND SUMMARY OF DATA SPECIFICATION SR-150
17.1 APPENDICES
17.1.3 APPENDIX 3 - MINERAL INSULATING OIL SUPPLIED FOR/WITHIN NEW ELECTRICAL EQUIPMENT OIL
APPENDIX 4 - SELF INDICATING ORANGE-WHITE SILICA GEL COBALT FREE FOR USE AS
17.1.4 silica gel
DESICCANT IN TRANSFORMER AIR DEHYDRATORS
17.1.8 APPENDIX 8 - SPECIFICATION FOR COATING REQUIREMENTS OF POWER TRANSFORMERS COATING FOR
POWER
TRANSFORMER
17.2 DRAWINGS
17.2.1 DRAWING No.1 : Transformer wheels assembly proposal - EVK-8501 dwg1 - WHEELS
17.2.3 DRAWING No.3 : Power transformer support for ladder- EVK-8496 DWG3 - SUPPORT
FOR LADDER
17.2.4 DRAWING No.4 : Safety fencing on transformer tank proposal- EVK-8497 DWG4 - SAFETY
FENCING
17.2.7 DRAWING No.7 - Foundations and anchoring. General dimensions - EVK-8498 DWG7 -
FOUNDATIONS
B - 68
APPENDICES
1-14
B - 69
APPENDICES:
B - 70
BUSHINGS
Requirements for Alternating sheds type, Composite Insulator designed for Type 1-
1.2
H.V. and Type 2- L.V. bushings:
1.2.1 REQUIRED OFFERED
composite (polymer)
1.2.2 parameters composite (polymer) parameters
Type 1-H.V. Type 2-L.V.
1.2.3 p1-p2 15 mm p1-p2 =
1.2.5 c > 45 mm c =
1.2.6 α = 10˚-15 ˚ α =
1.2.10 ka = 1 ka =
1.2.17 tc ≥ 6 tc ≥ N.A.
B - 71
2.1 Non-Alternating (Uniform) sheds
Figure 2
2.2.4 c > 45 mm c =
2.2.5 α = 10˚-15 ˚ α =
2.2.9 ka = 1 ka =
2.2.15 tc ≥ 6 tc ≥ N.A.
B - 72
2.3 Terms, definitions and abbreviations
2.3.1 Parameter Description
2.3.2 p1-p2 Shed overhang distance.
Spacing versus shed overhang is ratio of the vertical distance between two
2.3.3 s/p
similar points.
2.3.4 c The minimum distance between adjacent sheds of the same diameter.
Diameter factor
2.3.10 Kad Kad = 1, for Da < 300 mm
Kad = 0.0005 Da + 0.85, for Da ≥ 300 mm
Corrected reference unified specific creepage distance
2.3.11 Corrected USCD
corrected USCD=RUSCD∙Ka∙Kad
2.3.12 L Total nominal creepage distance - L_total=(u_max/√3)∙corrected USCD
2.3.13 CF=L/A Creepage factor is a global check of the overall density of creepage distance.
The highest ratio found on any section, for example on the underside of a cap
and pin insulator.
2.3.14 l/d l - The part of the creepage distance measured between the above two points.
d - The straight air distance between two points on the insulating part or between
a point on the insulating part and another on a metal part.
B - 73
3 Thickness of the SIR (silicone rubber)
Figure 3
B - 74
THE ISRAEL ELECTRIC CORPORATION LTD.
PLANNING DEVELOPMENT AND TECHNOLOGY DIVISION
RELIABILITY AND H.V. EQUIPMENT DEPARTMENT
SR-150
___________________________________________________
VERSION A VERSION B
B - 75
RMS SR-150
1. Reliability
The Contractor shall present the reliability tasks and methods which he used to improve
the design for reliability, and to evaluate the MTTF/MTBF of the Power Transformer and its
main components.
The Contractor shall provide expected values for the relevant parameters of the power
transformer (see Table 1).
Bidder Reaction:
3. Maintainability
Contractor shall present his maintainability tasks and methods used to improve the design
for maintainability according to IEC-60706-2 (2006). Contractor shall determine the
following parameters for the main maintenance activities (see Table 2):
(1) List of maintenance activities.
(2) Duration time needed for maintenance activities [men*hours].
Bidder Reaction:
4. Failure Analysis
The Contractor will implement an effective Failure Reporting Analysis and
Corrective Action System. In case of a failure the Contractor will register the failure in
a Logbook, with the following details:
- Date of occurrence.
- Failure description.
2
B - 76
RMS SR-150
6. Safety
The Contractor shall design and manufacture his power transformer for I.E.Co. in such
manner that it shall not endanger in any way any human being, neither property, nor it
causes any environmental damage. For achieving this requirement, the Contractor is
required to use the most advanced engineering, and Safety Standards according to IEC-
60529
Bidder Reaction:
B - 77
RMS SR-150
7. RAM Data
7.1 Contractor Declaration
Contractor shall declare the following RAM parameters for his power transformers as per
Table 1:
Table 1: RAM DATA FOR POWER TRANSFORMERS
Where:
B - 78
RMS SR-150
Mean Time To
Repair/Replace
B - 79
RMS SR-150
B - 80
RMS SR-150
Where:
r - Number of relevant failures.
- Contractor’s risk.
U - Upper limit for the MTBF
CL - Confidence level
8.4 Rational
If the number of occurring failures in t years is X, and the maximum failures allowed in that
period is k, then the probability of not passing the demonstration is, when there will be
more than k failures in t years. The probability is actually identical to Contractor’s risk ().
This risk is given by the following Poisson distribution formula:
-t/
k ( t/ ) i e
P{X k} 1 - (1)
i 0 i!
As is the required MTBF,
The upper limit for the MTBF, U, may be calculated by using the chi-square distribution:
2t
U (2)
2 ( CL 2,2r)
B - 81
RMS SR-150
relevant ones will be considered and counted for Accept/Reject criterion. The FRF will
include all failure information.
(3) In case of Systematic Failure the manufacturer will repair all the Power Transformers,
and perform a Corrective Action (preventive measures) to all the Power Transformers
including Power Transformers which already installed, to I.E.Co satisfaction. In this
case, the Failure Review Board (as detailed in paragraph 8.5) may decide, depends
upon the failure severity, to reset the accumulated test time, and to restart the RFD
from the beginning,
(4) In all other failures (Minor or Major failures) the time test measurement will be
resumed after the repair.
(5) Parts replacement due to and during preventive maintenance action will not be
considered as a failure.
8.7 Penalties
(1) After and only after expiration of the Warranty Period even in the course of the UPD,
I.E.Co. will assume full responsibility for all repair/replace costs. Anyway, during
Warranty Period the Contractor will assume full responsibility for all repair/replace
costs.
(2) If the UDP is terminated in “Accept” decision, responsibility remains as stated in the
previous paragraph (para. 1).
(3) If the UDP is terminated in “Reject” decision due to Major Failures, The Contractor will
retroactively assume responsibility for all repair/replace cost and will extend his
Warranty for Major Failures only to additional period of ten (10) years.
(4) If the UDP is terminated in “Reject” decision due to Minor Failures, The Contractor will
retroactively assume responsibility for all repair/replace cost and will extend his
Warranty for Minor Failures only to additional period of ten (10) years.
B - 82
RMS SR-150
B - 83
RMS SR-150
10
B - 84
RMS SR-150
(17)MTTR
MTTR is the mean time required to perform a repair (including checks) or replace of a
Power Transformer.
(18)Maintainability
Maintainability is a design characteristic defining the ability of a Power Transformer to
be restored quickly to its operable condition after a failure. Therefore, a Power
Transformer maintainability is the probability that a failed Power Transformer is restored
to its functioning condition, within specified period of time, under stated condition, using
stated procedures (defined by the Contractor), and resources (defined by the I.E.Co.).
MTTR is a maintainability parameter.
(19)I.E.Co.
Israel Electric Corporation Ltd.
(20)IEC
International Electrotechnical Commission.
11
B - 85
Israel Electric Corp. Ltd. חברת החשמל לישראל בע"מ
Power and Energy Group חטיבת הייצור והאנרגיה
Generation Division אגף הייצור
Chief Chemist Department מחלקת י הכימאי הראש
מפרט מס50 :
בתוקף מתאריך24/01/2016 : מפרט טכני לכימיקלים וחומרים
דף מס' 1מתוך 7 הנושא INSULATING OIL :
שם המפרט:
MINERAL INSULATING OIL
SUPPLIED FOR/WITHIN ELECTRICAL
EQUIPMENT
04/02/2016
ד"ר ויקטור מרקו אושר ע"י
B - 86
1. Scope
This specification covers new (unused) mineral insulating inhibited oil of petroleum origin, as
delivered, for use in Israel Electric Corporation as an insulating and cooling medium in new
and existing power and distribution electrical apparatus, such as transformers, regulators, circuit
breakers, switchgear and similar equipment. It also applies to oil delivered to Israel Electric
Corporation in new electric equipment and along with new electric equipment.
2. Reference Documents
IEC 60296:2012, Unused mineral insulating oils for transformers and switchgear
IEC 60156, Insulating liquids-Determination of the breakdown voltage at power frequency-Test method
IEC 60247, Measurement of relative permittivity, dielectric dissipation factor and d.c. resistivity of
insulating fluids
IEC 60422, Supervision and maintenance guide for mineral insulating oils in electrical equipment
IEC 60475, Method of sampling liquid dielectrics
IEC 60628, Gassing of insulating liquids under electrical stress and ionization
IEC 60666, Detection and determination of specified anti-oxidant additives in insulating oils
IEC 60814, Insulating liquids – Oil-impregnated paper and pressboard – Determination of water by
automatic coulometric Karl Fischer titration
IEC 61125, Unused hydrocarbon based insulating liquids – Test methods for evaluating the oxidation
stability
IEC 61198, Mineral insulating oils – Methods for the determination of 2-furfural and related
compounds
IEC 61619, Insulating liquids – Contamination by polychlorinated biphenyls (PCBs) – Method of
determination by capillary column gas chromatography
IEC 61620, Insulating liquids-Determination of the dielectric dissipation factor by measurement of the
conductance and capacitance – Test method
IEC 61868, Mineral insulating oils – Determination of kinematic viscosity at very low temperatures
IEC 62021-1, Insulating liquids-Determination of acidity – Part 1: Automatic potentiometric titration
ISO 2719, Determination of flash point – Pensky-Martens closed cup method
ISO 3016, Petroleum products – Determination of pour point
ISO 3104, Petroleum products – Transparent and opaque liquids – Determination of kinematic viscosity
and calculation of dynamic viscosity
ISO 3675, Crude petroleum and liquid petroleum products – Laboratory determination of density –
Hydrometer method
ISO 6295, Petroleum products – Mineral oils – Determination of interfacial tension of oil against water
– Ring method
ISO 12185, Crude petroleum and petroleum products – Determination of density – Oscillating U-tube
method
ISO 14596, Petroleum products – Determination of sulfur content – Wavelength-dispersive X-ray
fluorescence spectrometry
DIN 51353, Detection of corrosive sulfur – Silver strip
BS 2000, Part 346, Determination of polycyclic aromatics in lubricant base oil and asphaltene free
petroleum fractions – Dimethylsulfoxide refractive method
ISO/IEC 17025:2005, General requirements for the competence of testing and calibration laboratories
B - 87
3. Property Requirements for Insulating Oil (information shall be provided by the oil supplier)
3.1 M i n e r a l insulating oil as delivered by the supplier shall meet all the requirements of
IEC60296:2012 Unused mineral insulating oils for transformers and switchgear f o r inhibited oils.
3.2 Use of re-refined oil is allowed if it complies with all the properties listed in that standard.
TABLE A
Name of oil manufacturer:
Type of oil:
Property Test method Limits Supplier data
Unused Inhibited Mineral Insulating Oil Property Requirements
Test Function
No.
1 Viscosity at 40 °C ISO 3104 Max. 12 mm²/s
2 Viscosity at -30 °C ISO 3104 Max. 1 800 mm²/s
3 Pour point ISO 3016 Max. -40 °C
Refining/stability
B - 88
Test Property Test method Limits Supplier data
No.
Health, safety and
environment
27 Flash point ISO 2719 Min. 135 °C
28 PCA content IP 346 Max. 3%
29 PCB content (mg/kg) IEC 61619 Not detectable (< 2 total)
Requirements for Mineral Insulating Oils after Filling in New Electrical Equipment
Highest voltage for equipment kV
Property
<72.5 72.5 to 170 >170
30 Appearance Clear, free from sediment and suspended matter
31 Colour (on scale given in Max. 2.0 Max. 2.0 Max. 2.0
ISO 2049)
32 Breakdown voltage (kV) >55 >60 >60
g h
33 Water content (mg/kg) 20 <10 <10
34 Acidity (mg KOH/g) Max. 0.03 Max. 0.03 Max. 0.03
35 Dielectric dissipation Max.0.015 Max.0.015 Max.0.015
factor at 90°C and 40 Hz
to 60 Hz
36 Resistivity at 90°C Min.60 Min.60 Min.60
(GΩm)
37 Oxidation stability i As specified in IEC 60296
38 Interfacial tension Min.35 Min.35 Min.35
(mN/m)
39 Total PCB content Not detectable (< 2 total)
(mg/kg) i
40 Particles (counting, - Should be made as a baseline for future comparison
sizing)
41 Inhibitor content i -
42 Total gas content – - <1% <0.5%
according IEC 61181 j
43 DGA according to IEC -
61181 j
44 FTIR - fingerprint i -
a
For bulk supply.
b
For delivery in drums.
c
After laboratory treatment.
d
Results must be provided.
e
The supplier shall declare the generic type of all additives, and their concentrations in the case of antioxidant additives.
f
To be performed at the end of oxidation stability test.
g
The values should be without temperature correction.
h
A different value could be agreed between supplier and user depending upon local circumstances.
i
Shall be similar to the value before first filling (Unused Inhibited Mineral Insulating Oil Property Requirements).
j
By vacuum extraction.
B - 89
3.3 Tests required at various stages in complete process for power transformers commissioning (>72.5KV):
TABLE B
Stage description TEST No. Test certificate by
1i Bidder acceptance 1-29 Pre-approved laboratories (see
clause 7.2)
2 C.O.T. from oil supplier after order 3-5,8,9,11,14-17,21,29 Pre-approved laboratories (see
confirmationa. clause 7.2)
3 Incoming inspection. 4,11,21 Accredited/approved Lab h
f
4 After first filling, before electrical 30-36,38-41,43,44 Accredited/approved Lab h
testing at manufacturer site.
5 Afterf electrical testing at 43,19 Accredited/approved Lab h
manufacturer site.
6 Testing of oil before transformer delivery to purchaser, according to one of the following scenarios:
6.1 Filled with dry gasb and Partially 1-19,21,22d Pre-approved laboratories (see
assembled. clause 7.2)
f
6.2 After transformer was filled with oil 17,30-44 (for test No. 37 Pre-approved laboratories (see
and fully assembledc. seed) clause 7.2)
6.3 After transformer was partially filled with oil and Partially assembledc:
f
6.3.1 Tests for main Transformer. 17,30-41 (for test No. 37 Pre-approved laboratories (see
seed), 44 clause 7.2)
6.3.2 Tests for separated oil. 44 (same as 6.3.1 oil) Pre-approved laboratories (see
clause 7.2)
7i Testing of oil according to the destination of the transformer according to one of the following
scenariose:
7.1 Storage:
7.1.1 With option 6.1 afterf D.P. test, full 32-35,38,40,43,44 Accredited/approved Lab h
assembly and full with oil according
to manufacturer instructions.
7.1.2 With option 6.2 4,5,8,11,43 – After one Accredited/approved Lab h
year
7.1.3 With option 6.3 and after f full 32,33,35,38,41-44 Accredited/approved Lab h
assembly and full with oil according
to manufacturer instructions
7.2 Purchaser station:
g
7.2.1 Before energizing and after f full 30-36,38,40,41,43,44 Pre-approved laboratories (see
assembly and full with oil according clause 7.2)
to manufacturer instructions.
7.2.2 Storage:
7.2.2.1 With option 6.1 afterf D.P. test, full 32-35,38,40,43,44 Accredited/approved Lab h
assembly and full with oil according
to manufacturer instructions.
7.2.2.2 With option 6.2 4,5,8,11,43 – After one Accredited/approved Lab h
year
7.2.2.3 With option 6.3 and after f fully 32,33,35,38,41-44 – Accredited/approved Lab h
assembled according to
manufacturer instructions
a
For 20 ton batch for each order or as agreed between supplier and purchaser.
b
Dew point < -60˚C
c
The oil will not be treated and/or circulated before energizing at purchaser site
d
The result should not postpone delivery.
e
According to commercial annexures (if it's include in manufacturer warranty/responsibility).
f
Sample shall be taken between 24 – 48 hours.
g
Each transformer have to perform 7.2.1 tests before energizing at purchaser station.
h
Labs that shall be agreed between purchaser and supplier.
i
The oil tests reports provided for current stage shall include also the reports of the oil tests performed between the
previous stage and the current stage.
B - 90
Note: The oil will be tested in storage up to 5 years according to paragraph 6.2 and limits therein. The
transformer oil will be tested also during operation within the warranty period once every 3 months
according to routine tests specified by IEC60422. Any excess of trends and limits will be a clause to contact
the transformer supplier and find out the cause for it.
3.4 Test at stages in complete process for distribution and small transformers (<72.5KV), one certificate is
enough for a group of 20 supplied transformers.
TABLE C
Stage description TEST No. Test certificate by
1d Bidder acceptance 1-29 Pre-approved laboratories
(see clause 7.2)
2 C.O.T. from oil 3-5,8,9,11,14-17,21,29 Pre-approved laboratories
supplier after order (see clause 7.2)
confirmationa.
3 Incoming inspection. 4,11,21 Accredited/approved Lab c
4d Afterb electrical 30-36,38-41,43,44 Pre-approved laboratories
testing at (see clause 7.2)
manufacturer site.
a
For 20 ton for each order or as agreed between supplier and purchaser.
b
Sample shall be taken between 24 – 48 hours.
c
Labs that shall be agreed between purchaser and supplier.
d
The oil tests reports provided for current stage shall include also the reports of the oil tests performed between the
previous stage and the current stage.
For transformers with higher operating temperatures or designed for extended service life, Israel
Electric Corporation may require the oil (catalog Nº 5236327) to comply with restricted limits after
oxidation test according to IEC 61125:1992 (Method C). Specific requirements oils are in generally
more robust to aging and can prolong the transformer life.
5.1 Oil shall be delivered in bulk, tank containers or packed in steel drums. These shall
be clean and suitable for this purpose to avoid any contamination. Israel Electric
Corporation catalog numbers (for the oils that comply with General Specification):
847103 (drums), 3177771 (bulk).
5.2 Oil drums shall be new and free of any internal coating.
5.3 Oil drums and sample containers shall carry at least the following markings:
• manufacturer's designation;
• classification;
• oil quantity.
5.4 Marking shall be accomplished by labeling or stenciling.
5.5 Paint type and/or sticker shall be water and oil proof.
B - 91
5.6 Each oil delivery shall be accompanied by a document from the supplier specifying at
least: manufacturer's designation, oil classification and compliance certificate.
5.7 Israel Electric Corporation is free to send at any time an oil sample to any of the pre-
approved laboratories of 7.2, to check if the oil values of a specific delivery meet the initial
specification. If any contradiction is found between the actual measurements and the certificate
values, the oil can be returned to the supplier after further clarification.
6. Sampling
Sampling for any purpose, shall be carried out only in accordance with the procedure described in
IEC 60475.
7.2 Pre-approved laboratories for transformer oil testing shall include the following independent
laboratories:
B - 92
Appendix A- Approved Insulating Oil Sources and Types
This document lists the insulating oil sources and types approved for Israel
Electric use, as of 24.01.2016.
B - 93
Israel Electric Corp. Ltd. חברת החשמל לישראל בע"מ
Generation & Transmission Group חטיבת ייצור והולכה
Generation Division אגף הייצור
Chief Chemist Dpt.
מחלקת הכימאי הראשי
שם המפרט:
SELF INDICATING ORANGE SILICA GEL
FOR USE AS DESICCANT IN TRANSFORMER
AIR DEHYDRATORS
נבדק ע"י
B - 94
1. Scope
The products shall not contain any material that has been regenerated.
2. Technical requirements
2.1 The material shall consist of silica gel in beaded form and free from
extraneous matter. The bead size of 90% of it should be 2-6 mm.
2.2 The product shall conform to the technical requirements given in Table 1.
2.4 The regeneration conditions of silica gel shall be specified by the supplier in
Table 2.
3 . Packaging
3.1 The desiccant shall be filled into strong, sound clean, dry and transparent
packages (to determine the color of the product). Each package shall contain 1.2 kg
of desiccant, and it shall be hermeticaly sealed after filling. The packages shall be air
tight and capable of being easily opened (e.g. transparent plastic bags, which cannot
be torn).
3.2 The bagged desiccant shall be packaged in leakproof and air tight containers.
The containers shall be approximately full and shall hold an agreed quantity of bags
per container.
3.3 Each package and each container (both internal and external) shall be legibly
and durably marked with at least the following details:
B - 95
Table 1. Property Requirements for Silica Gel
B - 96
THE ISRAEL ELECTRIC CORPORATION LTD.
ORGANIZATION, QUALITY AND SAFETY DIVISION
QUALITY CONTROL UNIT
TITLE APPENDICES FOR CONTRACTS / ORDERS Spec. No. Q - APP - 02
SUB Rev. 4
QUALITY REQUIREMENTS Status 03/ 2011
TITLE
Volume PAGE 1 FROM 6
1. GENERAL
1.1 In addition to the provisions of the General Conditions – Annexure "A" and
without derogating from the generality there, the Quality Requirements as
specified in this document constitute an integral part of the Contract between
the Purchaser and the Contractor. Implementing these requirements shall not
constitute any base/reason, for the Contractor to change the Contract schedule
and/or price.
1.2 The Contractor shall make all the necessary arrangements and prepare all the
required and necessary means to enable IEC's Quality Control Unit
Representative (see clause 2) to review, observe, audit, inspect, test and survey
the Work - at any facilities where Work or any part thereof is performed,
including those of Contractor and Sub- Contractors, without any additional cost
to the Purchaser or any change in the Contract schedule.
1.3 The Contractor shall nominate, as part of the execution of the Contract a
quality engineer or a quality specialist to control and manage the quality
requirements of the Contract. This person shall have the authority and
responsibility with respect to all quality requirements of the Contract (including
notifying the Purchaser about inspections, tests, etc.) and shall serve as
Purchaser's liaison for quality matters.
1.4 The Contractor shall be responsible that all of the Contract’s quality
requirements are known, accepted and performed by its Sub- Contractors.
Special attention should be given to Contractor's procurement control and its
Sub- Contractor's design control, process and manufacturing control, purchasing
control, nonconforming material/events control and inspection notification.
Upon Purchaser's request Contractor shall submit un-priced copies of purchase
orders pertaining to the Work/Contact.
B - 97
THE ISRAEL ELECTRIC CORPORATION LTD.
ORGANIZATION, QUALITY AND SAFETY DIVISION
QUALITY CONTROL UNIT
TITLE APPENDICES FOR CONTRACTS / ORDERS Spec. No. Q - APP - 02
SUB Rev. 4
QUALITY REQUIREMENTS Status 03/ 2011
TITLE
Volume PAGE 2 FROM 6
2.2. QUALITY PLAN (QP) - Plan, prepared by the Contractor especially for the
Contract, in accordance with ISO 10005 which covers all Contract stages.
2.3. INSPECTION AND TEST PLAN (ITP) – a plan, specifying all the
inspections and tests for the Work throughout all Contract stages (from its
initialing through design, in process inspection, type tests, product
qualification, first article inspection, final inspection/s and test/s, packing,
transportation and supply to the Purchaser, erection - including Site Acceptance
Test and commissioning). ITP shall also specify Witness and Hold Points.
2.4. WITNESS POINT (WP) - a planned visit of the QCUR for purposes indicated
in clause 1.2 for specific point of the ITP or Quality Plan.
2.5. HOLD POINT (HP) – the same as WP but with the distinction that the
Contractor is not permitted to proceed with its planned activities without having
received Purchaser’s written approval.
2.9. WORK - Scope of the Contract and the means to execute it.
2.10. QCUR - the Purchaser's Quality Control Unit Representative and/or any
authorized representative of it.
B - 98
THE ISRAEL ELECTRIC CORPORATION LTD.
ORGANIZATION, QUALITY AND SAFETY DIVISION
QUALITY CONTROL UNIT
TITLE APPENDICES FOR CONTRACTS / ORDERS Spec. No. Q - APP - 02
SUB Rev. 4
QUALITY REQUIREMENTS Status 03/ 2011
TITLE
Volume PAGE 3 FROM 6
3.2 Contractor shall not commence work prior to receiving Purchaser’s written
approval to the QP and ITP.
4. DOCUMENTATION
4.1 The Contractor shall submit to the Purchaser for review, along with the QP and
ITP, its quality and manufacturing/operations procedures that pertain to the
Work execution. The Purchaser has the right to receive explanations with respect
thereto. Contractor shall provide Purchaser with all amendments and/or updates
of documentation.
4.3 The Contractor shall submit to the Purchaser, for review, comment and approval
(as required by the Contract) all the process qualifications and the employees
certifications for special processes which pertain to the Work and are relevant to
the Contract execution.
4.4 Supplying Work which is not manufactured by the Contractor (under Contract
terms) and which he has no control over the manufacturing process, shall not
derogate from Contractors responsibility to supply the Purchaser with the
documentation and quality records as indicated in Articles 4 and 7.
B - 99
THE ISRAEL ELECTRIC CORPORATION LTD.
ORGANIZATION, QUALITY AND SAFETY DIVISION
QUALITY CONTROL UNIT
TITLE APPENDICES FOR CONTRACTS / ORDERS Spec. No. Q - APP - 02
SUB Rev. 4
QUALITY REQUIREMENTS Status 03/ 2011
TITLE
Volume PAGE 4 FROM 6
5.2 If Contractor uses the services of a Sub - Contractor to carry out any
test/inspection required by the Work, only inspection companies certified to EN
45004 (level A or C) are acceptable.
5.2.1 Type test, Routine Test and Sample test shall be carried out according to
Contract requirements.
5.3 Any other qualification test (for mechanical equipment) shall be carried out in the
presence of the QCUR, followed by all quality records. The serial manufacturing
shall commence only after 1st Article/piece test have successfully carried out
witnessed by the Purchaser's QCUR.
6. INSPECTION NOTIFICATION
6.1. The Contractor shall indicate each inspection/test and notify the Purchaser of it
in advance. An ITP schedule (on a GANT form) shall be prepared by the
Contractor, within six (6) weeks after initialing of the Contract.
Indications of inspection/test dates may in any event not be less than six (6)
weeks in advance. Both inspection/test notification and ITP schedule shall be
reported to the Purchaser's Project Management. In addition to the above ITP
schedule, Contractor shall submit to Purchaser a final notice of planned
tests/inspections not less than twenty-two (22) Israeli working days in advance.
7. QUALITY RECORDS
7.1. The Quality Records stipulated in this clause shall be, either in Hebrew, in
dual/multi-language form with English, in English only, or if not available
translated to English by Contractor.
7.2. Contractor shall submit to the Purchaser copy of the quality records
documenting the inspections, tests or other quality operations of the Work, as
indicated in the ITP, QP and the Contract. All quality records of skipped or
missed WP and/or HP shall be submitted to Purchaser immediately after their
generation.
7.3. All Test and Inspection Certificates/ Reports of materials, operations and or
inspection/test, purchased or carried out for the Work and/or required by the
B - 100
THE ISRAEL ELECTRIC CORPORATION LTD.
ORGANIZATION, QUALITY AND SAFETY DIVISION
QUALITY CONTROL UNIT
TITLE APPENDICES FOR CONTRACTS / ORDERS Spec. No. Q - APP - 02
SUB Rev. 4
QUALITY REQUIREMENTS Status 03/ 2011
TITLE
Volume PAGE 5 FROM 6
7.4. Contractor shall make available to Purchaser upon its request, for review and
comment, at Purchaser’s premises or other mutually agreed place (in Israel), the
quality records of any - Type test, Routine test, Qualification test, First Article
Inspection/Test, Process qualification, Special process and/or any other
inspection/test/examination required by Purchaser, after initialing of the
Contract, to evaluate the Work (at all stages) regardless of the QP and the ITP.
7.5. Submission of the documents and quality records, regarding the Equipment to
which the documents relate, to Purchaser, as specified in Articles 4 and 7, shall
be a condition, precedent to shipment by Contractor and payment by Purchaser.
8.1. It is Purchaser's policy to reject Work and/or Goods that do not conform to all
contractual requirements, unless acceptance is in the best interests of
Purchaser. Acceptance of nonconforming Work or Goods is the sole
prerogative of Purchaser.
8.3. If the Contractor fails to report about a non conformance on time, Purchaser
may request Contractor to dismantle the nonconforming Work (to witness the
NC) with no additional cost. The documentation and quality records concerning
this NC shall be immediately submitted to the Purchaser.
8.5. Deviating from 8.4 can cause stoppage of the Work and its rejection till the
proper CA is taken by the Contractor.
B - 101
THE ISRAEL ELECTRIC CORPORATION LTD.
ORGANIZATION, QUALITY AND SAFETY DIVISION
QUALITY CONTROL UNIT
TITLE APPENDICES FOR CONTRACTS / ORDERS Spec. No. Q - APP - 02
SUB Rev. 4
QUALITY REQUIREMENTS Status 03/ 2011
TITLE
Volume PAGE 6 FROM 6
EXHIBIT A
CONTRACTOR'S: NAME, I&T PLAN TITLE, THE PRODUCT INSPECTED/TESTED, and DOCUMENT IDENTITY &
APPROVAL.
THE
INSPECTED / TESTED BY REPORT /
No.THE APPLICABLE WP/HP CERTIFICATE REMARKS
SUB-
INSPECTION OR DCUMENTS OR AND
CONT./ CONTR- PURCH- OTHER
TEST OTHER ITS REF. STD/
SUPP ACTOR ASER
PROCEDURE
B - 102
TESTS ON SITE
B - 103
Israel Electric Corp. Ltd. חברת החשמל לישראל בע"מ
Generation & Transmission Group חטיבת ייצור והולכה
Generation Division - Chief Chemist Dpt. מחלקת הכימאי הראשי- אגף הייצור
elmalem@iec.co.il 04-8183362 - אלמלם דוד צבע וציפויים
shay@iec.co.il 04-8183158 - ליטני שי 04-8185706 :פקס
27.4.2017 10.2.2016
217-000260-2015
General
The specification deals with painting cabinets, Steel Structure or equipment.
The surfaces for coating can be one of the following: Hot Deep Galvanized, Electrolytic
Galvanized surface or Aluminium.
The coating application will be "wet" or powder coating (electrostatic Application).
Painting over galvanized surface requires an early experiment to ensure adherence to
substrate.
All the coating materials shall be of a single manufacturer.
Each layer shall be in different shade.
Manufacturer is required to supply his recommendation for painting procedure of all
interiors parts.
The coating application shall be engineering quality as outlined in SSPC standard PA-1,
and in accordance with the manufacturer's instructions on the product pages. The finished
product shall have a uniform appearance and lacks liquidity, wrinkles or other defects,
has a uniform thickness in proportion to demand. The coating layers will firmly glue to
the substrate. The final color determined by the customer.
B - 104
contents
B - 105
1. Surface preparation for painting on Zinc
1.1. On Hot Deep Galvanized surface
B. Chemical treatment
Phosphate washing (BS-3189).
B - 106
2. Coating application
All materials shall be made by the same manufacturer.
Each layer shall be in different color (shade).
Approved Products for liquid coating – see table 3.1
Approved Products for powder coating – see table 3.2
B - 107
3. Approved Coating Products
3.1. Approved Liquid Coating
B - 108
Israel Electric Corp. Ltd. חברת החשמל לישראל בע"מ
Generation & Transmission Group חטיבת ייצור והולכה
Generation Division - Chief Chemist Dpt. מחלקת הכימאי הראשי- אגף הייצור
elmalem@iec.co.il 04-8183362 - אלמלם דוד Paints and coatings
shay@iec.co.il 04-8183158 - ליטני שי 04-8185706 :Fax
2009-217-141707
24.11.2015 20.9.2015
B - 109
File: APP8-COATING FOR POWER TRANSFORMER Page 2 of 5
B - 110
The coating technical information shall be coordinated with the paints manufacturer and shall include at
least:
Coating procedure description
Surface preparation procedures
Description of application procedures
Required surface roughness
Special treatment of problematic areas (cover, thin edges, radiators, strip coats etc.)
Materials
Manufacturer name and address.
Generic classification of coating system.
The full commercial paints name, technical datasheets of the paints and materials.
Quality control
Quality reports and environmental conditions during application shall be given to the tank,
radiators and other elements separately.
List of Parameters to be measured and measuring standards (thickness, adhesion and their
scattering are mandatory).
Tests required:
Dry Film Thickness (DFT) shall be measured according to SSPC PA-2 or ISO 19840 (the
supplier has to declare which standard he uses as a routine).
Adhesion test shall be according to ISO 16276 "Paints and varnishes – Cross cut test"
(or ASTM D-3359), Level 1 required.
Previous experience:
Names and addresses of two (2) customers. Dates of application, project description.
Maintenance repairing instructions: for damages during shipment or erection or operation of all
painting systems.
B - 111
Principal Options for Protective Coating
The supplier shall suggest a coating system for the approval of Israel Electric Corp. Ltd.
Such approval will include checking the suggested coating system to its purpose as well as
compliance with all requirements of the current document.
The supplier shall declare which option he uses for protection (see options A-D):
Option A
A Duplex system- Hot deep galvanized and painted (Information to be delivered by the
manufacturer):
Galvanizing transformers is routine at the manufacturer's (indicate two customers)
Galvanizing shall be according to "ASTM-A 153/2003 Std spec. for Zinc coating (Hot-Dip)
on iron and steel" or by an international or regional accepted standard.
The metal shall be suitable for galvanizing
Surface preparation according to galvanizer's procedures
Zinc thickness: 75 microns (minimum)
Surface preparation for painting (without passivation).
Paint system with 2 layers of 120 micron minimum thicknesses, except cover having 220
microns (minimum) and antiskid requirements.
Option B
Painted fused sprayed Zinc (equal to IEC's Spec. CL-100):
(Information to be delivered by the manufacturer)
Submission of method and workers audition certificates
Two customers' addresses with 5 years experience
Surface preparation for Zinc spraying
Zinc thickness of 100 microns (minimum) + coating: primer 70 micron and topcoat 50
microns, except cover having 220 microns of paint (minimum) and an antiskid requirement.
Option C
A 3 layer system Zinc-rich/ Epoxy/ Polyurethane
Zinc-rich base is the routine for the manufacturer (indicate two customers)
Zinc-rich shall be stated according to ASTM-D 520
Description of Surface preparation.
Total Thickness of 250 micron (minimum, with base layer thickness of 70 microns) , except
cover having 350 microns(minimum) and an antiskid requirements.
B - 112
Option D
A 3 layer system Epoxy/ Epoxy/ Polyurethane
Epoxy/Epoxy/Polyurethane is the routine for the manufacturer (indicate two customers)
Description of Surface preparation.
Total Thickness of 350 micron (minimum, with base layer thickness of 70 microns), except
cover having 450 microns (minimum) and an antiskid requirements.
Internal
Transformer manufacturer declaration that internal coating is a routine process
(indicate two satisfied customers).
Paint manufacturer declaration for compliance with mineral transformer oil.
B - 113
Senior Vice President for
Planning, Development and Technology File num. 95
Transmission Planning, Reliability and Equipment
System Reliability & H.V. Equipment Dept. Date: 04/5/17
CYBER REQUIREMENTS
2. The supplier shall agree1 to three documents attached to his proposal as follows :
2.1 NDA - ©2
1
In case of requirements that cannot be fulfilled, it shall be explicitly indicated by supplier.
2
© - Compulsory requirements.
3. Network and security safeguards:
The supplier that will stand the requirements of tender first stage (threshold conditions and compulsory
requirements),
would be requested to answer to additional cyber security questions at the secondary stage.
Y. Cohen 25/4/17
Prepared
D. Visan 4/5/17
A.Aspurtas 4/517
B - 114
Senior Vice President for
Planning, Development and Technology File num. 96
Transmission Planning, Reliability and Equipment
System Reliability & H.V. Equipment Dept. Date: 04/5/17
NON-DISCLOSURE AGREEMENT
AND PRELIMINARY CYBER REQUIREMENTS
1. NDA :
No parts of all the technological and management information in the specification may be reproduced, stored
in retrieval system or transmitted in any form or by any means electronic, mechanical, photocopying recording
or otherwise, without the prior written permission of the RELIABILITY & H.V. EQUIPMENT
DEPARTMENT Israel Electric Corporation (I.E.Co.)
3. SIGNATURE:
B - 115
Customers Division
Cyber Security Department
VERSION: 20-04-2017
STATUS: FINAL
B - 116
Customers Division
Cyber Security Department
Table of Contents
1. General 3
2. Topology & Secured Network Architecture 3
3. Hardening & Configuration Management 5
4. Additional Security Measures 6
4.1 Hardware Configuration & Device control 6
4.2 Detection of Unauthorized Software and Unauthorized Modifications to Software 6
4.3 Database Protection 6
4.4 Anti-Malware Detection & Prevention System 7
4.5 Software Updates, Security Patches & Signature Updates 7
5. Identification, Authentication & Authorization 7
5.1 General 7
5.2 Default generic accounts 7
5.3 User Authentication 7
5.4 Access Security Management 8
5.5 Appropriate Use Banner 8
5.6 Password Policy 8
5.7 Authorization & Separation of Privileges 8
6. Contractor’s Maintenance 8
7. Monitoring, Indication & Control 8
8. Application Security 9
8.1 General 9
8.2 Free of “Electronic Self-Help” Enabled Software 9
8.3 Obligation for Notification of Security Vulnerabilities in Contractor-Provided
Software 9
9. System Test 10
Page 2 of 10
B - 117
Customers Division
Cyber Security Department
1. General
1) All system plans based on the principles in this document is subject to the approval of the IEC’S
Regulator. The contractor shall undertake to comply with any provisions of any annex which will be
added to this document. Deviations shall be permitted only with the approval of the regulator.
2) The Contractor must base its security considerations and requirements on the requirements of the
standards declared by IEC.
3) The Contractor must comply with IEC’s Information Security policies and procedures.
4) All security functions required by this Specification must be implemented in a non-interfering manner,
such that authorized and legitimate use of the system is not hampered, nor is the ability to perform
required functions impeded by the security features.
5) All equipment, servers, workstations, software and systems proposed and ultimately supplied with
these component systems shall be considered Critical Cyber Assets for the purposes of the system
and this contract.
6) All systems, networks, and equipment, as well as the equipment that defines the security perimeter
shall be treated and configured as Critical Cyber Assets.
7) All systems and equipment should follow international cyber security standards like “NERC CIP
standards”, “IEEE Standard Cyber Security Requirements for Substation Automation, Protection, and
Control Systems” etc.
8) All network and security equipment\ software designed for the purchased system, must be approved
by IEC.
2) Each of the systems/equipment supplied, by the selected Contractor, shall include clearly defined
electronic security perimeters within which all associated system devices reside.
3) The primary access points through this perimeter shall be IEC-provided Firewalls.
4) Where technically feasible, communications shall be designed so that the most privileged application
shall initiate communications.
5) The Contractor shall provide documents and drawings depicting the electronic security perimeters, all
interconnected system components within the electronic security perimeter(s), all access points
through the electronic security perimeter(s), and all assets deployed or configured for controlling and
monitoring access to the defined access points.
Page 3 of 10
B - 118
Customers Division
Cyber Security Department
6) The Contractor shall limit required port access to a minimum and provide a list of all required ports,
services and addresses requiring access through any and all Firewalls that support normal, emergency
and ongoing maintenance functions.
7) This will include ports and services required for basic operating system functions.
8) As directed by IEC, the Contractor shall provide assistance to IEC in helping to determine the minimum
required access permissions for the firewalls that allow a functional, yet secure, operation of the
system, including normal, emergency and required ongoing maintenance actions.
9) The Corporate network shall not have direct query or access capability to any data stores or processes
within the system.
10) The system network shall be divided into segments. The location of the various components will be
determined by criteria such as their functionality, use, geographic location, belonging to a particular
system, Belonging to a particular environment (Production/test/developments etc...), the protocols
needed for their operation etc. It should be emphasized that any function/criteria, as mentioned
above, must be placed in a separate segment.
11) No communication shall be allowed between different segments, except for operational needs
(such as synchronization between components).
12) There shall be a dedicated management segment for managing components out of band.
13) Shutting down management workstations at the end of a working day will not have adverse effect
on the operation of the systems.
14) A local management will be allowed only in a case of an operational malfunction, in which remotely
management is not possible.
15) Management connection shall be through a separation of communication (physical or logical) from
the production communication, such as a different NIC, a different port, a different protocol etc. The
management communication shall be encrypted for any component in the critical Infrastructure.
16) A communication control, in white list format, shall be implemented between the different segments,
including the management segment.
17) The control level shall be at least by the ‘Stateful inspection’ method.
18) Hubs shall not be used for communication purposes.
19) For permanent communication monitoring, a TAP shall be used. For temporary communication
monitoring, Span Port shall be used.
20) Only wired communication is allowed and wireless communication to the system components shall be
blocked (Such as WIFI, Bluetooth etc.).
21) In components which support time synchronization, the synchronization shall be from a centralized
Time source within the critical Infrastructure.
22) File & Print sharing services, within the critical Infrastructure, will be operated only from a dedicated
& centralized server.
23) Shares shall not be created on the end users workstations.
24) Network Connectivity:
Page 4 of 10
B - 119
Customers Division
Cyber Security Department
Page 5 of 10
B - 120
Customers Division
Cyber Security Department
7) All components shall be hardened in a way that will minimize cyber-attacks or surface cyber-attacks
and will expose the minimum ports and functionality needed for them to run. Hardening procedures
shall follow well-known hardening standards, such as NIST, the vendor’s best practices etc.
8) Any optional back-door shall be removed (Such as hard coded passwords etc).
9) The Contractor shall also perform hardening according IEC policy.
10) The Contractor shall document and submit documentation that the foregoing has been completed.
11) Error/Informative messages, displayed to the user, should not expose sensitive information, such as
versions, manufacturers, identifications of devices in the critical infrastructure etc.
12) Unsecured channels (for remote access or file transfer) shall be disabled, like TELNET, unsecured
RDP, FTP etc.
13) All security mechanisms within the controllers shall be operated and running.
14) Access for controller configuration will be made from a dedicated permitted workstation within the
critical infrastructure.
15) Source code deletion – The logical functionality, source code, shall not reside in the controller itself.
Only the final executable files shall reside on the controller.
2) This mechanism shall be installed and running throughout the development, test, commissioning and
acceptance of the system to ensure that their performance impact is known and tested.
Page 6 of 10
B - 121
Customers Division
Cyber Security Department
Page 7 of 10
B - 122
Customers Division
Cyber Security Department
6. Contractor’s Maintenance
1) Remote maintenance connectivity, for the contractor, shall be approved first by the IEC’s regulator.
2) The maintenance connectivity mechanism shall be implemented by IEC.
Page 8 of 10
B - 123
Customers Division
Cyber Security Department
8. Application Security
8.1 General
1) The system code development shall be according IEC policy and international standards.
Page 9 of 10
B - 124
Customers Division
Cyber Security Department
13) The contractor shall protect problem reports of a security nature from public disclosure and when
notifying other customers shall not release any information to indicate that IEC identified the
problem.
14) The contractor shall verify and provide documentation that all services are patched to current status.
9. System Test
1) Cyber vulnerability assessment and penetration test shall be performed on FAT and SAT according to
IEC policy.
Page 10 of 10
B - 125
SECURITY OF PROJECT PERFORMED BY VENDOR ABROAD
This document sets security requirements the purpose of which is to ensure the proper management of security in development or upgrade of a
1.1.1 project for I.E.Co. (henceforth: the requirements). The body performing this development/upgrade will be called henceforth: the supplier.
Compliance of supplier to the requirements set forth in this document will be accomplished when:
Information' - This document regards information as any data and/or technical material and/or personal and/or technological and/or commercial
of I.E.Co. and/or its affiliates; including that handed to I.E.Co. by third party, as long as it hasn't become public according to I.E.Co. permission;
1.1.2 and any data pertaining I.E.Co. business or its customers' business, given to the supplier and/or to supplier employees and/or became their
possession during their work, by heart, in writing, in electronic media or any other way, including any product, idea, plan or document. Any
technological and managerial information in the project are included in the above 'information' definition.
B - 126
2 SUPPLIER STRUCTURE, POLICY AND PROCEDURES REQUIRED OFFERED
The supplier shall present security policy or alternatively shall refer specifically, in
2.1 its quality control policy, that refer to the paragraph requirements. Please attaché Attach file
here a security policy or quality control policy.
2.1.1 Managing the protection of I.E.Co. hardware and software assets, Yes/No
2.1.1.1 Supplier organizational structure which supports the security issue; Yes/No
2.2 The supplier is required to nominate a manager to the project security. Yes/No
Supplier shall prepare a security plan for the project. The plan shall include
implementation of the requirements in this document and detailed reference
regarding the following subjects: risk management and vulnerability scans and
their remedies/treatment; prohibiting access to the project information including
industrial espionage; and possible advanced security measures exercised by
2.5 supplier in the project. Attach file
All the requirements included in this document apply to any place in which the
project or part of it is performed, including third parties.
The security plan shall be handed to I.E.Co. for approval prior to project design
and shall be a pre-requisite to project development.Please attaché here a
security plan for the project.
3 PROJECT SECURITY IMPLEMENTATION REQUIRED OFFERED
I.E.Co. representative will install and operate logical security tools on the project
system, in collaboration with the supplier, including hardening. As an extra
3.2 Yes/No
security measure, I.E.Co. representative may be granted full control on the
security tools in the project system.
The supplier agrees to accept the directives of I.E.Co. representative per par. 3.2
3.3 Yes/No
above throughout the project period.
The secured area walls shall be rigid construction. The secured area shall have
4.2 Attach file
four walls, ceiling and floor. Please attaché here the secured area drawing.
The entrance doors to the secured area shall be metal made and equipped with
electromagnetic locks. The locks shall be approved beforehand in writing by
4.3 Yes/No
I.E.Co.. The entrance to the secured area shall be controlled according to the
following conditions:
Identification via biometric or encrypted proximity card, in a reputed standard
4.3.1 approved by I.E.Co. beforehand. Please attaché here a general description of Attach file
your access control system.
The entrance control shall be in the supplier internal network and shall not be
4.3.2 connected to any external network or Internet. Please attaché here a general Attach file
description/ drawing of your internal network.
Entitlement to give entrance permits shall be granted only to a supplier employee,
whom I.E.Co. will approve beforehand. The supplier shall prepare a procedure
for entrance permits, which will include a process for granting reasonable permits
4.3.3 Attach file
to authorized personnel. Please attaché here a general description for your
entrance permits procedures including new permits and the termination of void
permits.
B - 127
The entrance control system shall enable entry of authorized personnel only. It
shall alarm on unauthorized access attempts, on attempts to neutralize the
4.3.4 Yes/No
control system, and any illegal attempt to enter the secured area through its
doors.
The entrance control system shall alarm on 'bothered' door whenever the
4.3.5 Yes/No
secured area door is left open for a period longer than one minute.
The entrance control system shall provide reports and facilitate forensic features
4.3.6 Yes/No
namely. full interrogation of events at least ninety days back.
4.4 The secured area shall not be identified as an I.E.Co. project. Yes/No
CCTV cameras shall be installed in the secured area to cover the whole area.
The cameras shall photo and record 24 hours. The records shall be stored and
available for at least 90 days back. The recording computer and records shall
4.5 Attach file
reside in a place which may be accessed by security personnel only Please
attaché here a general description for your CCTV permits procedures and a
drawing of your CCTV location regarding the secured area .
Physical intrusion detection system shall be installed in the secured area. It shall
cover the whole area and all apertures. The intrusion detection system shall
adhere to reputed standards; include local horn; and connection to security
center as per par.4.7. The intrusion detection system shall include at least two
communication channels (cellular and wire) which enable messaging
4.6 Attach file
alarms/faults. The intrusion detection system center/concentrator shall reside in
a place which may be accessed by security personnel only. Please attaché here
a general description for your physical intrusion detection system permits
procedures and a drawing of your physical intrusion detection system location
regarding the secured area
The entrance control system, the intrusion detection system and the CCTV shall
be connected to security center which is active around the clock. The security
4.7 Yes/No
center shall be able to send a force which will reach the secured area within
maximum period of 10 minutes from receipt of alarm or other security message.
I.E.Co. will be authorized to watch, under prior coordination with supplier, the
4.8 information depicted above, on the security systems - in order to examine Yes/No
security events.
The supplier undertakes to inform I.E.Co. of any intrusion to its premises even
though nothing has been stolen, immediately upon occurrence. The supplier
shall be responsible to inform I.E.Co. security entities via I.E.Co. central security;
4.9 Yes/No
available 24 hours including weekends and holydays, on phone number
97235678045 (multi-line). Example events are: theft of data/information,
intrusion, lost of laptop/external memory etc.
Supplier shall manage records on employees who are involved in any stage of an
5.1 Yes/No
I.E.Co. project.
The supplier undertakes to inform I.E.Co. promptly of any change in the status of
any employee (including third party/subcontractor) who is working on any stage of
5.3 Yes/No
an I.E.Co. project. Examples are: criminal conduct, termination of employment,
prolonged private staying abroad without reasonable cause etc.
The supplier shall submit a copy of the records to I.E.Co. prior to employment of
5.4 the person on I.E.Co. project. It is emphasized that a person shall not be allowed Yes/No
to work or enter the secured area unless prior written consent from I.E.Co..
The supplier undertakes to monitor the permits and privileges of its employees in
a manner which grants access to the secured area and/or to I.E.Co. information
5.5 and/or to handling I.E.Co. project items – only to authorized personnel. In this Yes/No
context the supplier undertakes to promptly remove the permits and privileges of
any person who ceased for any reason to work on any stage of I.E.Co. project.
The supplier undertakes to sign up each and every authorized worker on the Non
5.6 Yes/No
Disclosure Agreement (NDA), appendix 2 of this document.
B - 128
Identification to access the data shall be done via complex password with at least
six characters comprising special character and alphanumeric. Password
6.1.2 Yes/No
change shall be enforced once every ninety days. Last six passwords shall not
be allowed. Access shall be locked upon three erroneous trials.
The supplier shall monitor for authorized access to I.E.Co. data, and proper audit
6.1.3 Yes/No
trail and logging of this activity.
6.1.4 The supplier shall record and audit all data retrievals. Yes/No
The supplier shall backup I.E.Co. data and verify that the backup files are
separated from the general premises backup system – namely, I.E.Co. backup
6.1.5 Attach file
shall be done in a secured network. Please attaché here a general description/
drawing of your backup system network segmentation
6.2 Access to I.E.Co. data shall be granted only to security authorized persons. Yes/No
Access rights to I.E.Co. data shall be periodically verified (at least once a month).
6.3 Yes/No
This activity shall be recorded.
The supplier shall manage, and present upon request, records of all I.E.Co. data
owned at its premises – including data/information developed by supplier for
6.4 Yes/No
I.E.Co.; including physical and electronic/computerized.The records shall also
include dates of receipt and dates of handling.
Security of records – The supplier shall centrally manage I.E.Co. data, which is
stored on I.E.Co. physical items/entities, at the secured area or at other secured
area conforming to the above security requirements. Regarding this clause, data
is any material pertaining I.E.Co. and the services given by supplier to I.E.Co.
6.5 Attach file
critical systems, which is stored at supplier premises or at subcontractors / third
parties. The supplier shall store the data in locked metal cabinets or vaults.
Access to the stored data physical location shall be granted only to I.E.Co. and
supplier authorized personnel.Please attaché here a general description.
Cleaning of the secured area shall be done only in the presence of authorized
personnel. The entry and/or work of visitors, maintenance personnel, cleaners
6.6 Yes/No
etc. to the secured area shall be personally accompanied by supplier
employee(s) throughout their presence in the secured area.
The door of the office/place in which the cabinet/vault is located shall be locked
6.7 Yes/No
upon leaving of the last authorized person.
Duplication and coping of the material shall be done only by authorized person.
6.8 Yes/No
Surplus copies shall be promptly discarded via shredding.
The supplier shall not forward I.E.Co. information to third party unless given in
6.9 advance written consent from I.E.Co.. The information shall be transferred in Yes/No
encrypted manner.
The laptop shall be connected only to the secured network of the supplier per
6.10.1 Yes/No
par. 6.1
The laptop shall not be connected to any other network, including wireless. This
6.10.2 directive shall be enforced by physical and logical disconnection of the Yes/No
connection capability.
Supplier shall enforce its security policy, including antivirus updates, on these
6.10.3 Yes/No
laptops.
The hard disc of the laptop and any other device which storing I.E.Co. classified
6.10.4 material, shall be encrypted. The encryption tool shall be approved in advance Yes/No
by I.E.Co. security bodies.
Laptops shall not be left unattended in a parking car or other vehicle, including
6.10.5 Yes/No
trunk /luggage compartment.
I.E.Co. data shall not be allowed to be taken to workers residence via laptop or
6.10.6 Yes/No
any other mean.
B - 129
The secured network configuration shall be preserved throughout the project.
7.3 Yes/No
Any configuration change shall have prior written I.E.Co. approval.
The supplier shall monitor and control the secured network and its configuration
continuously. As a minimum the supplier shall control the users, password policy
7.4 – change, complexity, configuration of security devices, updated antivirus, Yes/No
communication security and prevention of attempt to connect unauthorized
devices. The supplier shall own documented procedures for this activity.
The test equipment used during all phases of the project shall conform to the
7.5 following requirements: Please attaché here a general description/ drawing of
your network
The test equipment shall be connected to the secured network only, and comply
7.5.1 Yes/No
the secured network requirements.
In case the test equipment had been used in other projects, the supplier shall fully
reset the equipment, uninstall and erase all tools and files which where used by
7.5.2 the previous projects, perform antivirus check, neutralize all access from external Yes/No
devices, perform hardening according to joint I.E.Co.-supplier procedures; and
prevent execution of any files which are not legal part of I.E.Co. project.
Upon termination of the project at supplier premises the following actions shall be
8.1 Yes/No
performed, in the presence and with supervision of I.E.Co. representative:
I.E.Co. representative shall put a unique sticker on each case (namely items
which unite to a case such as PC, controller etc.). The sticker will be supplied by
8.3 Yes/No
I.E.Co. security department. The sticker shall be placed in a manner which
disables the opening of the case from any side unless damaging the sticker.
8.4 The delivery list shall indicate every device which had been marked with a sticker. Yes/No
During the entire packing and delivery phases the project equipment shall be
8.5 Yes/No
placed in the secured area.
Upon receipt of delivery in Israel, the cases shall be opened in the presence of
I.E.Co. representative, and all listed stickers shall be checked for integrity. In
8.6 Yes/No
case any of the above requirements is violated, an immediate notification to
I.E.Co. security center shall be made.
Supplier shall return to I.E.Co. all the information stored at its premises regarding
I.E.Co. project, except for technical documentation which has been decided by
8.7 I.E.Co. and supplier to remain in the hands of the supplier for maintenance. All Yes/No
security requirements shall apply regarding this information as long as it is being
held at supplier premises, even though the project period is over.
All correspondence between I.E.Co. and the supplier regarding the critical
system, such as operation, maintenance, configuration, reports etc; and
particularly configurations of security measures – shall be done via encrypted
media. The encryption of the media shall be done by reputed standard and
9.1 proven technology which conforms to the networking/communication and security Attach file
infrastructure at I.E.Co.. General guidelines for this issue are: data encryption,
authentication of data source, integrity of data, ratification upon receipt and
sending of data Please attaché here a general description/ drawing of your
solution.
Validity – these requirements shall be valid for all phases of the contract,
9.2 Yes/No
beginning with kickoff, through installations and operation.
Supplier personnel shall coordinate all site visits with the power plant personnel
10.2 Yes/No
and will be escorted during their visits.
Supplier support personnel shall comply with I.E.Co. site's general policy and
10.3.1 Yes/No
rules of data security.
Any requirement for the connection of an external computer to the system shall
10.3.2 be previously coordinated with the I.E.Co. site data security manager and the Yes/No
system manager.
B - 130
The external computer shall have an updated version of security safeguard
10.3.3 programs for online protection, detection, cleaning and logging of executed Yes/No
actions to protect from viruses, vandals, worms etc.
Prior to the connection of the external computer to the system, supplier personnel
shall hand-in the computer to the data security manager in the power plant for
10.3.4 Yes/No
thorough checkup of the computer. Only after this checkup is completed, may
the external computer be connected to the system.
If after the checkup, the external computer has been exposed to external data
(other than the System's network, internet, external data transfer such as via Disk
10.3.5 Yes/No
On-Key etc.), the computer shall be handed-in again to the data security
manager in The power plant for checkup of the newly added files.
B - 131
Report of Sound Pressure Level Measurement and Sound Power Calculation
Table No. 1: The Spatially Averaged Sound Pressure Level measured at a distance of
2.0 meter
Frequency range 16÷10,000Hz
The cooling system operated
Energized at : Energized at :
Equipment
Operation
Tap position
16
25
Spatially averaged sound pressure levels at 1/3 octave band frequency (dB)
31.5
40
50
63
80
100
125
160
200
250
316
400
500
630
800
1000
1250
1600
2000
2500
3150
4000
5000
6300
8000
10000
Overall spatially averaged A
weighted sound pressure Level,
dBA
B - 132
Table No. 2: The Spatially Averaged Sound Pressure Level measured at a distance of 1.0
meter
Frequency range 16÷10,000Hz
The cooling system not operated
Energized at : Energized at :
Equipment
Operation
Tap position
16
25
Spatially averaged sound pressure levels at 1/3 octave band frequency (dB)
31.5
40
50
63
80
100
125
160
200
250
316
400
500
630
800
1000
1250
1600
2000
2500
3150
4000
5000
6300
8000
10000
Overall spatially averaged A weighted
sound pressure Level, dBA
B - 133
Table No. 3: The Calculated Sound Power Level:
- Frequency range 16÷10,000Hz
- The cooling system operated/not operated
Equipment Operation
63
80
100
125
160
200
250
316
400
500
630
800
1000
1250
1600
2000
2500
3150
4000
5000
6300
8000
10000
Overall A weighted
Sound Power
Level, dBA
B - 134
CONTRACTOR’S TECHNICAL PERFORMANCE GUARANTEES
When during testing it is shown that the losses exceed the guaranteed level plus
tolerances on the principal, minimum and maximum taps as stated in this
Specification, the Contractor shall pay the I.E.Co. liquidated damages as follows:
1. For each transformer unit that the losses exceed the guaranteed level plus
tolerances on the principal, minimum and maximum taps, the Contractor shall
pay for each kW of losses in excess of the declared values (subcl. 10.3.27) ,
without tolerances, liquidated damages as prescribed hereunder:
The liquidated damages are a genuine estimate of the direct damages foreseen
and are not to be regarded as penalty. They shall be calculated separately for
each type of losses indicated above and shall be cumulative.
The reference temperature for the losses considered in the calculation of the
above indicated damages shall be the standard reference temperature.
The calculation of exceeded losses will be performed separately for each type of
transformer and separately for no-load and short-circuit losses as well as for the
losses on the principal, minimum and maximum transformer taps.
1/1
B - 135
The Israel Electric Corporation Ltd.
PROCEDURE
FOR
HANDLING OF NON-CONFORMANCES
B - 136
It is the obligation of the Contactor to inform Israel Electric Corp. Ltd. (I.E.Co.)
about any deviation from the contract technical specifications, which occurs on
any action/item of the contract realization, such as design, raw materials,
manufacturing testing and inspection and so on. The deviations will be classified
into the following three (3) non conformance levels:
1.3.1. Any other NC which is not included in the previous levels (For
instance such a NC which can affect even uncertainly mandatory
requirement or contract value).
B - 137
2. HANDLING OF NON CONFORMANCE
B - 138
B - 139
DESIGN REVIEW FOR TRANSFORMER ENGINEERING
1. Winding Design
Arrangement of Windings
Type of Winding (layered , continuous Disc, etc.)
Conductor configuration in each winding including conductor size and
insulation thickness
Regulating Winding location, design construction and tap lead exits
Leakage flux considerations
Fiber optics Temperature Probe location and calculations
2. Insulation design
Shielding in Winding
Clearances
Dielectric strength versus design margins
3. Short Circuit Design
Calculated stresses in windings compared to maximum design allowed
stresses
Calculated forces on members
Winding processing and compression during drying operations and final
clamping
4. Transient Voltage Distribution
Impulse
Switching
5. Core Design
Geometry, step lap, etc.
Induction level
Cooling ducts
Material
Core grounding
Leakage flux heating
6. Load Tap Changer
Voltage per step
Current per step
BIL
B - 140
Contact life and maintenance requirements
Lead clearances And routing outside of winding
Tap changer must be operated at less than 80% of its current rating to
extend maintenance interval requirements
7. Cooling
Calculated winding and oil rises
Hot spot rises in each winding
Oil flow
Tap leads
Overload calculations
8. Tank Design and Oil Preservation System
Welding procedure
Gasket design
Radiator bank supports
Shielding
Core & Coil support
Access to equipment for maintenance, i.e. Bushings, core ground , cts
Valves
9. Test Program
functional test of all control circuits in factory to verify wiring
10. Preparation for Shipment, Field Installation and Field Processing
11. General Arrangement Drawing and Wiring Schematics Drawings
B - 141
B - 142
The Israel Electric LTD SPECIFICATION SR-98
Engineering Project Group
Engineering Division
Electrical Sector APPENDIX NO. 9
B - 143
The Israel Electric LTD SPECIFICATION SR-98
Engineering Project Group
Engineering Division
Electrical Sector APPENDIX NO. 9
פרויקט:
סוג מסמך:
עקרון תכנון
חישובים תזכיר תכנוני
רשימת מחשב מפרט
תקן /נוהל נייר עמדה
02 01 - הוצאה מס'
??? לא נשלח 09/2004 תאריך:
חתימה שם חתימה שם חתימה שם
ר .ושלר הכין
א .רוזנברג בדק
ג .סנטו תואם
תואם
מ .זיידמן תואם
א .פינץ תואם
ד"ר ל .אלצ'ה אישר
אישרר
הפצה אל ה"ה:
B - 144
The Israel Electric LTD SPECIFICATION SR-98
Engineering Project Group
Engineering Division
Electrical Sector APPENDIX NO. 9
CONTENT: PAGE
1. GENERAL 4
3. TERMINAL BLOCKS 6
4. ARRANGEMENT OF WIRING 8
5. TERMINATIONS 10
6. MISCELLANEOUS 11
7. WIRING TESTS 12
EPD-A.03 4 13
Electrical Wiring Requirements.
1. GENERAL.
2.1.3 Connections between fixed and hinged panels shall be made with stranded
( extra-flexible) switchboard wire , having the same insulation as specified
above .
2.2.2 For control and supervisory circuits in which the current is less than
0.2 A , wires sized 1.0 sq.mm ( No. 18 AWG ), shall be used .
B - 146
The Israel Electric LTD SPECIFICATION SR-98
Engineering Project Group
Engineering Division
Electrical Sector APPENDIX NO. 9
2.3.2 The wiring of the above devices shall be made with similar wires
as defined in paragraph 2.1 .
The size of the wire shall be correlated with the control transformer
primary and secondary currents , with the incoming power circuits
currents and with the circuit protection .
B - 147
The Israel Electric LTD SPECIFICATION SR-98
Engineering Project Group
Engineering Division
Electrical Sector APPENDIX NO. 9
3. TERMINAL BLOCKS .
3.1.1 The terminals shall comply with IEC 60947-7-1 , July 2002
Standard .
3.1.4 The metal parts ( clamping parts and current carrying parts ) shall
be made of copper alloy to eliminate corrosion .
The screw clamping method shall be vibration resistant .
B - 148
The Israel Electric LTD SPECIFICATION SR-98
Engineering Project Group
Engineering Division
Electrical Sector APPENDIX NO. 9
3.2.1 The terminals shall comply with the NEMA Standard Publication
No. ICS 4 /2000 and shall be UL approved .
3.2.5 The metal parts ( clamping parts and current carrying parts ) shall
be made of copper alloy to eliminate corrosion .
B - 149
The Israel Electric LTD SPECIFICATION SR-98
Engineering Project Group
Engineering Division
Electrical Sector APPENDIX NO. 9
4.1 Wire and wire groups extending from terminal blocks to instruments or
devices on cubicles , or from one cubicle to another , shall be installed
in halogen free ducts or troughs and packed in neatly formed bundles
securely clamped or tied together and supported from the cubicle
framework.
Plastic cable ties ( Halogen free or EPR ) shall be used to bundle wires
outside of ducts or troughs .
No more than 30 wires shall be bundled together in wire hinge loops.
4.2 When wiring is installed in wire ducts or troughs , the edges of the
cut-outs troughs which the wires pass shall be provided with suitable
protection of the insulation from cuts or nicks .
4.4 Drain wires and shield tapes shall be fully insulated and terminated at
terminal blocks .
Grounding of shielded wires shall be as defined in the Project
Specification or drawings .
B - 150
The Israel Electric LTD SPECIFICATION SR-98
Engineering Project Group
Engineering Division
Electrical Sector APPENDIX NO. 9
EPD-A.03 9 13
Electrical Wiring Requirements.
4.6 All wiring shall be installed exactly as shown on the wiring diagrams .
4.8 Spare contacts from each device ( circuit breaker , auxiliary relay ,
control switch, etc ) shall be wired to terminal blocks , as per specific
Project Specification requirements .
4.9 Both ends of each wire shall be tagged with appropriate plastic
markers.
Mylar wire markers such as Brady Type SLFW or similar as agreed
upon , should be used .
4.13 All the alarm circuits should be connected to adjacent terminal block
points , to facilitate Purchaser's field wiring .
4.15 Wiring shall be routed in such a manner that it will not prevent blank
cubicle ( spare ( from being used for the addition of future
equipment.
EPD-A.03 10 13
Electrical Wiring Requirements.
5. TERMINATIONS .
5.2 The wire insulation shall be removed for the lug application without
nicking the conductor .
The wire shall be firmly inserted into the lug and crimped with the
specified tool , recommended by the lug manufacturer .
Devices having compression clamps, push-on, etc type terminals will
be wired accordingly .
5.3 All solder and push-on type connections shall have snug fittings
insulated sleeves which cover the entire lug and extend 1/4 inch
( 6mm ) over the insulation .
5.4 Terminal blocks shall be provided for terminating all wiring entering
and leaving the cubicles , except the leads from thermocouples and
other temperature detecting devices , and devices connected with
prefabricated cables , that may be field run directly to the terminals in
the instrument cases .
5.5 Thermocouple extension wire and other solid wire terminations shall
be made without the use of lugs .
B - 152
The Israel Electric LTD SPECIFICATION SR-98
Engineering Project Group
Engineering Division
Electrical Sector APPENDIX NO. 9
One side of the terminal blocks shall be left free for Purchaser's
connections.
All jumpers between terminals shall be made on the internal wiring
side .
Terminals associated with individual items of equipment shall be
grouped together for convenient cable connections .
5.8 The terminal blocks shall not be mounted closer than 7 inches
( 180 mm ) from the control cubicle walls and at least 10 inches
( 250 mm ) from the cable entrance .
Central line distance between terminal blocks shall be a minimum
of 8 inches ( 200 mm ) .
Where terminal blocks for Purchaser's connections are mounted on
vertical wire-ways , the inside area of said wire-ways shall be reserved
exclusively for Purchaser's incoming cables .
5.9.1 Power
5.9.2 Control AC / DC ( 120 V/ 220 V)
5.9.3 Control DC circuits 24 VDC , 48 VDC , 60 VDC
5.9.4 Instrumentation
5.10 Where bottom cable entry is used , the vertical wire-ways shall be
located over floor openings , to allow Purchaser's cable to have a clear
run directly to the terminal blocks .
6. MISCELLANEOUS .
7. WIRING TESTS .
7.2 The factory tests shall demonstrate freedom from grounds and
accuracy of the wiring .
7.4 Megger or other high voltage tests shall not be applied to any coaxial
shielded or solid-state components .
B - 154
The Israel Electric LTD SPECIFICATION SR-98
Engineering Project Group
Engineering Division
Electrical Sector APPENDIX NO. 9
The following color coding is required for the internal wiring of control
cubicles :
8.1 AC CIRCUITS .
- FINAL -
B - 155
DRAWINGS
B - 156
DRAWINGS:
B - 157
B - 158
B - 159
B - 160
B - 161
B - 162
VIEW B-B
Transformer tank
A A
DN 80
Ø=200 mm
B
`
VIEW A-A
B - 163
THE ELECTRIC CORPORATION LTD.
Planning, Development and Technology
Transmission Planning, Reliability and Equipment
System Reliability & H.V. Equipment Dept.