Sei sulla pagina 1di 2

180 Chapter 4 Digital Output Termination Panels

Field Wiring Diagrams


This figure illustrates how to connect a 16-point digital output module and a 9670-110F to the
field (1 of 16 points shown).

Figure 133 Field Wiring for 9670-110F with a 3601E DO Module

Field Terminations Guide for Tricon v9–v10 Systems


Non-Commoned Interposing Relay Term Panels 181

Simplified Schematics
This is a simplified schematic of a typical 16-point AC digital output module with a non-
commoned interposing relay panel (1 of 16 points shown).

32-POINT DUAL DIGITAL OUTPUT MODULE BACKPLANE CABLE RELAY OUTPUT PANEL

A
LED
*
Output POWER1 +
Switch
CONTACT
Drive
(1C)
Circuitry A B
CONTACT
(1NO)
A "B
Output
Switch
Drive
Circuitry

B
Output
Switch
Drive
Circuitry
C A B
C POWER1 –
Output
Switch
Drive PW1 +
A Voltage
Circuitry
B Loopback to
hot PW1 –
C Detector spare

PW2 +
TYPICAL DIGITAL INPUT POINT (OPTIONAL)

PW2 –
Bridge Current-
rectifier limiting
Optical isolation
AC
Smoothing
Threshold Detect
Opto-Isolator

to
spare
module

* LEDs are blown-fuse indicators

Figure 134 Simplified Schematic of a 3601E DO Module with a Non-Commoned Interposing Relay
Panel

Field Terminations Guide for Tricon v9–v10 Systems