12/6/2018 Substation Maintenance: Protection

Process of commissioning of the batteries of different make and capacities;

Sl. Particulars Standard Emco Ub-mek Electro flo N


.No. 80AH 200AH 80AH 200AH 80AH 200AH 80AH 200AH o
t
A Initial filling of the
e
batteries
1 Electrolyte sp.Gravity 1.19 0 @27oC 1.19 0 @27oC 1.19 0 @27oC 1.19 0 @27oC
2 Soakingtime 12to16hrs. 12to16hrs. 12to16hrs. 12to16hrs.
B First charge But not >24Hrs. But not >24Hrs. But not >24Hrs. But not >24Hrs.
1 Initialchargingduration 100Hrs. 80Hrs. 50Hrs. 100Hrs.
2 Rating of charging 4A for 60hrs. 10A for 60hrs. 3.2A for 8.0A for 6.0A for 15.0A for 4A for 60hrs. 10A for
10hrs. 80hrs. 50hrs. 50hrs. 60hrs.
Restfor 4Hrs. -- Restfor 4Hrs.
3. 4A for 40hrs. 10A for 40hrs. 4A for 40hrs. 10A for
40hrs.
4. Maximum permissible 50oC 50oC 50oC 50oC 50oC 50oC 50oC 50oC
temperatures
5. During charging readings 2.55V 2.55 2.40 2.40 2.40 2.40 2.5 2.6
[Voltage]
6. At the end of the charging 1200+0.05 1200+0.05 1200+0.05 1200+0.05 1200+0.05 1200+0.05 1200+0.05 1200+0.0
[Sp.Gravity @27oC ] 5
C] Capacity /discharge test
1 Discharge current 8A 20A 8A 20A 8A 20A 8A 20A
2 Test procedure : After completion of the 1st charge, allow the battery to stand on open circuit for not less than 12hrs. butnot more than 24Hrs.
discharge the battery through a variable resistor or acetated water load at constant current equal to I=0.1C, the discharge shall be
stopped when the closed circuit voltage of each battery falls to 1.85V, and specific gravity falls to 1.130 obtained in the duration of
10Hrs, maximum.
D] Recharging
1. Normal recharge
2. Current and end voltage of 8A up to 20A up to 11.2A up to 28A up to 8A up to 20A up to 8A up to 20A up to
the cell 2.35V to 2.35V to 2.4V 2.4V 2.4V 2.4V 2.4V 2.4V