Sei sulla pagina 1di 12

Outdoor Air Conditioner

Installation Instructions
Variable Speed Ultra-High SEER Split System
These units have been designed and tested The iQ Drive System consists of an outdoor
for capacity and efficiency in accordance with unit, indoor unit, controller Thermostat and
ARI standards. These outdoor air conditioning connecting lines.
units are designed for use exclusively with
select NORDYNE G6 gas furnaces and select 1. The Outdoor Unit:
NORDYNE B5 air handlers equipped with The outdoor section consists of large heat
dedicated matched indoor coils. exchanger surface, Inverter motor Drive,
Brushless motor type rotary compressor
These instructions are primarily intended to
and an integrated drive brushless fan
assist qualified individuals experienced in the
motor coupled with a specially designed
proper installation of Heating and Air Condition-
fan blade, in addition to refrigerant valves
ing equipment including the iQ DriveTM System.
housed in sturdy attractive chassis.
Local codes may require licensed installation/
service personnel for this type of equipment.
2. The Indoor Unit:
Read all instructions carefully before starting
The matched indoor coil may be a stand
the installation.
alone cased coil intended to be installed
in NORDYNE G6 Model Gas Furnaces or
may be part of a dedicated NORDYNE B5
IMPORTANT NOTE Model Air Handler.

This equipment is one part of a total system The indoor coil is equipped with Electronic
designed for maximum efficiency, adequate Expansion Valve to precisely control
capacity and total comfort. The system must refrigerant flow over the wide range of
function as intended. Under no circumstances system capacity modulation.
any part of the system may be substituted with
other components. For the stand alone dedicated cased
coil in gas furnace, a Furnace Blower
Conversion Kit is required to allow the
THE iQ DRIVETM SYSTEM addition of required system components
such as the Integrated Drive Brushless
The iQ Drive Air Conditioning System features Indoor Blower Assembly, Interface Board,
fully variable speed compressor technology upgraded transformer and The Coil Kelvin
and variable speed indoor and outdoor motors. Controller.
The system provides variable cooling capacity
as needed modulating over a five degree F Consult Installation Instructions provided
temperature range. It operates near the nominal with the Indoor Coil and the Furnace Blower
rated capacity at the thermostat set point and Conversion Kit for details.
modulates as temperature difference between
set point and room temperature changes. The For the dedicated Air Handler, the matched
system may run at additional 18% capacity coil and all required components are
to provide rapid cooling and modulates down included. Consult Installation Instructions
to minimum capacity if the room temperature provided with the Air Handler Unit for
reaches 2 degree F below set point, then it turns details.
off if room temperature drops more than 2 degree
F below set point. The system has a built-in 3. System Controller Thermostat:
humidity control that will activate a humidifier The system controller is the master
equipment (if supplied), and reduces blower component that communicates with
speed if indoor relative humidity is greater than and controls the inverter driven system
set point (default set at 60%). components.
The Inverter in the outdoor unit receives NFPA 70) and electrical conductors and circuit
signals from compressor, heat exchanger, protection must be in compliance with information
fan motor and outdoor ambient which listed on the outdoor unit data label.
are communicated to the controller
via connections to the Indoor Interface
Board. The controller responds back with
appropriate messages for each device 2. SAFETY CONSIDERATIONS
operation command. If no message is
received for 10 seconds, the device will Pressures within the System — Split System
stop. The controller communicates with Air Conditioning equipment contains liquid and
the indoor section via the Indoor Interface gaseous refrigerant under pressure. Installation
Board which is powered by 24 VAC from and servicing of this equipment should be per-
transformer in the furnace or air handler. formed by qualified, trained personnel thoroughly
Transformer in the gas furnace MUST be familiar with this type of equipment. Under no
replaced with the one supplied in the gas circumstances should the homeowner attempt
furnace blower conversion kit. to install and/or service the equipment.

Labels, Tags, Precautions — When working


with this equipment, follow all precautions in the
1. GENERAL INFORMATION literature, on tags, and on labels provided with
Read the following instructions completely the equipment. Read and thoroughly understand
before performing the installation. the instructions provided with the equipment prior
to performing the installation and operational
checkout of the equipment.
CAUTION: Brazing Operations — Installation of equipment
This unit is charged with R-410A requires brazing operations. Safety codes must
be complied with. Safety equipment (e.g. safety
refrigerant. DO NOT under any
glasses, work gloves, fire extinguisher, etc.) must
circumstances use any other be used when performing brazing operations.
refrigerant besides R-410A in this
unit. Use of another refrigerant will
damage this unit.
WARNING:
Condensing Unit Section — Unit is factory Ensure all electrical power to the unit
charged with refrigerant charge adequate to
is OFF prior to installing or servicing
operate the outdoor section with the indoor
matched coil or air handler, and 15 feet of the equipment. Failure to do so may
refrigeration line. cause personal injury or death.

NOTE: DO NOT USE ANY PORTION OF THE


REFRIGERANT CHARGE FOR PURGING OR
LEAK TESTING. 3. SITE PREPARATION
Unpacking Equipment — Remove the
Matching coils and Air Handlers are shipped
cardboard carton and user’s manual from the
with a small pressurized holding charge to
equipment. Take care not to damage the tubing
keep contaminants out. To release the pressure,
connections when removing the carton.
read the indoor section installation instructions
carefully. Inspect for Damage — Inspect the equipment
for damage prior to installing the equipment at
Liquid and Suction Lines — Refrigerant grade
the job site.
copper tubing should be used when installing
the system. Suction line tubing should be fully Preferred Location of the Outdoor Unit —
insulated. Conduct a survey of the job site to determine the
optimum location for installing the outdoor unit.
Field Connections for Electrical Power
Overhead obstructions, poorly ventilated areas
Supply — All wiring must comply with latest
and areas subject to accumulation of debris
version of the “National Electrical Code” (ANSI/
should be avoided. The outdoor unit must be

2
installed in such a manner that airflow through 6. CONNECTING REFRIGERANT
the chassis is not obstructed and that unit can TUBING
be serviced.

Facility Prerequisites — Electrical power


must be supplied to the equipment. Electrical CAUTION:
power supplied must be adequate for proper
operation of the equipment. The system must This system utilizes R-410A refrigerant
be wired and provided with circuit protection in with PVE oil. When servicing, cover
accordance with local building codes and the or seal openings to minimize the
National Electrical Code. exposure of the refrigerant system
to air and prevent accumulation of
Minimum Circuit Ampacity — Electrical wir- moisture and other contaminants.
ing to the equipment must be compatible and in
compliance with the minimum circuit ampacity General — Once the outdoor and indoor unit
listed on the outdoor unit data label. placement has been determined, route refrig-
erant tubing between them in accordance with
Maximum Fuse/ Circuit Breaker Size — Circuit sound installation practices. Refrigerant tubing
protection for the outdoor unit must be compat- should be routed in a manner that minimizes the
ible with the maximum fuse/ circuit breaker size length of tubing and the number of bends in the
listed on the outdoor unit data label. tubing. Refrigerant tubing should be supported
in a manner that the tubing will not vibrate or
abrade during system operation. Tubing should
4. INSTALLING THE OUTDOOR UNIT be kept clean of foreign debris during instal-
lation. Refrigerant lines that exceed 75 ft in
Slab Mount — The site selected for a slab length and 20 ft in vertical elevation difference
mount installation requires a stable foundation are not recommended. The maximum inter-
not subject to erosion. The slab should be level connecting refrigerant line length is 100 feet,
and anchored (if necessary) prior to placing the and the maximum vertical elevation difference
unit on the slab. between the indoor and outdoor sections shall
not exceed 50 feet.
Cantilever Mount — The cantilever mount
should be designed with adequate safety factor Filter Dryer Installation—A liquid line filter dryer
to support the weight of the unit, and for loads is supplied with unit and must be installed in the
subjected to the mount during operation. Installed liquid line of the system. If the installation replaces
equipment should be adequately secured to the a system with a filter dryer already present in
cantilever mount and leveled prior to operation the liquid line, the filter dryer must be replaced
of the equipment. with the one supplied with the unit.
Roof Mount — The method of mounting
should be designed so as not to overload roof 7. MAKING ELECTRICAL
structures nor transmit noise to the interior of CONNECTIONS
the structure.

Refrigerant and electrical lines should be routed


through suitably waterproofed openings to pre-
WARNING:
vent leaking into structure. Turn off all electrical power at main
circuit box before wiring electrical
5. INSTALLING THE INDOOR UNIT power to the outdoor unit. Failure to
comply may cause severe personnel
The indoor section should be installed before injury or death.
proceeding with routing of the refrigerant piping.
Consult the installation instructions of the indoor Wiring Diagram — A wiring diagram/ schematic
unit (i.e.; air handler, indoor coil and furnace) for is located on the inside cover of the electrical box
details regarding installation. of the outdoor unit. The installer should become
familiar with the wiring diagram/ schematic before

3
making any electrical connections to the outdoor from obstructions and debris, and all equipment
unit. Refer to wiring diagrams in this literature for access/control panel cover is in place.
wiring of system components.
Indoor Unit — Consult the installation instruc-
Outdoor Unit Connections — The outdoor unit tions of the indoor unit (i.e.; air handler, indoor
requires both power and control circuit electrical coil and furnace) for details regarding installation.
connections. Refer to the unit wiring diagram/ Ensure wiring is secure and correct.
schematic for identification and location of out-
door field wiring interfaces. Air Filters — Ensure air filters are clean and in
place prior to operating the equipment.
Control Circuit Wiring — The outdoor unit is
Ensure that the unit has been properly and
designed to operate from a 24 VAC Class II
securely grounded and that power supply con-
control circuit. Control circuit wiring must comply
nections have been made at both the facility
with the latest version of the “National Electrical
power interface and outdoor unit.
Code” (ANSI/NFPA 70) and with applicable local
codes having jurisdiction.
Controller Thermostat — Connect the Outdoor
Controller Thermostat Connections — Con- section low voltage wiring to the Indoor section
nections to controller unit should be made in interface board. Using standard 4-wires thermo-
accordance with the instructions supplied with stat cable, connect controller thermostat to the
unit, and with the instructions supplied with the indoor section interface board.
indoor equipment. System requires the use of
shielded cable. Using extreme caution, apply power to the sys-
tem and inspect the wiring for evidence of open,
Electrical Power Wiring — Electrical power shorted, and/or improperly wired circuits.
wiring shall comply with the current provisions
of the National Electrical Code (ANSI/NFPA 70) Controller Thermostat screen will be lit and
and with applicable local codes having jurisdic- calibration of indoor blower assembly will begin.
tion. Use of shielded (metal lined sealtite or Initial screen will display indoor and outdoor
rigid ) conduit is required. Electrical conductors temperatures and installer will be able to select
shall have minimum circuit ampacity in compli- functions and program all modes of operation.
ance with the outdoor unit rating label. The
facility shall employ electrical circuit protection NOTE: The Controller Thermostat is designed
at a current rating no greater than that indicated to display information screens for use by the
on the outdoor unit rating label. installer and homeowner.

At initial installation, from “OFF” screen, press


Disconnect Switch — An electrically compatible
the Up and Down buttons simultaneously for
disconnect switch must be within line of sight of
5-10 seconds to display the “Installer Settings
the outdoor unit. This switch shall be capable of
Menu Screen”. This screen prompts the installer
electrically de-energizing the outdoor unit.
to input system configuration, unit size, furnace
information, accessories installed, desired set-
8. STARTUP AND CHECKOUT tings in cooling and heating, and humidity setting
if different from default setting. Installer may also
input recommended service schedule and dealer/
WARNING: contractor information for future use.

Ensure electrical power to the unit is The controller screens display all pertinent
off prior to performing the following system information in normal operation. When
steps. Failure to do so may cause necessary, important messages may be se-
personal injury or death. quenced along the top line to indicate conditions
that need attention.
Outdoor Unit — Ensure the outdoor coil, the
inverter heat sink and the top of the unit are free The controller is also designed to function as an
important service and troubleshooting tool.

4
INSTALLER SETTINGS SCREEN: FAN Option:
Select this option to set desired indoor blower op-
1- From “Installer Settings”, select “Model eration mode (Auto, On or Programmed). If “On”
Configuration”. Screen will display is selected, blower will run at heating speed.
“single stage” or “multi stage”.
2- Select appropriate option. Screen will MENU Option:
display “Input rate” and “temp rise” for Select “MENU” option to input the following:
the installed furnace. Set Date & Time, Hold Temp info, Program of
3- Input data from furnace installed. Operation, Fan, Mode, Settings and Security
4- Press “select button” following each Lockout).
selection or the up and down arrows
to access displayed options. Press Note: “Fan” and “Mode” may be selected from
“Previous arrow” to scroll between Main Screen directly.
screens.
5- From “Installer Settings”, select “Acces- 1- SET DATE AND TIME: Follow prompted
sories” option. Screen will display ac- screens after each selection is made.
cessories. Input pertinent selections 2- HOLD: Select from “Vacation” or “Per
6- Each accessory selected will be manent”
followed with additional screens for 2A- From “Vacation Hold Screen” set
scheduling maintenance and service. desired “Hold temperatures for “Heat”
Input appropriate recommended ser- and/or “Cool”.
vice schedules. 2B- The following screen prompts the date
7- From “Installer Settings”, select “Input and time entry for the desired hold.
Dealer Info” option. Screen will display Follow same steps for “Permanent
pertinent selections. Follow screen Hold”.
prompts and save “Completed Dealer 3- PROGRAM: Select to set weekdays,
Info Screen”. weekends, every day or individual days
8- From “Installer Settings”, select “Hu- programming. The prompted screens
midity Settings” option. Screen will allow four settings per day. Input desired
display available selections. Select program and save.
from “Humidify only”, “Dehumidify 4- FAN: Select from “Auto”, “On” or “Pro-
only”, “Both” or “None”. grammed Fan”. The “Programmed
9- From “Installer Settings”, select “Re- Fan Settings” allows fan to run as
store Factory Defaults” if so desired. programmed in step 3.
10- From “Installer Settings”, select “Charg- 5- MODE: Select from “OFF”, “AUTO”,
ing Mode” to run system at nominal set- “COOL” or “HEAT”.
ting for proper charging conditions. 6- SETTINGS: Use this screen to scroll
through options such as:
MAIN SCREEN: 6A- SCREEN SETTINGS: Set preferred
screen settings such as “Temp scale”,
The iQ Drive controller thermostat main screen “Clock setting”, “Language”, “Contrast”
displays system normal operating information. It and “Backlight On Time”.
displays Outdoor and Indoor temperatures, Set 6B- OFFSET: Set temperature offsets,
points in cooling and heating, humidity and mode humidity offset, heat anticipator and
of operation for system and indoor fan. In addition, heat differential.
it displays four options to select from: 6C- CYCLES PER HOUR: Set the
maximum allowed heating cycles per
TEMP Option: hour.
Select this option to temporarily override program 6D- AUTO CHANGEOVER: Select “Auto or
setting until next program interval is activated. Manual Change” and select the “Auto
Changeover Time” to input desired time
MODE Option: interval between cooling and heating
Select this option to choose operating mode changeover.
(Cool, Heat, Auto or Off ). 6E- PROGRAM SETTINGS: Select “Smart
Recovery”, “Events per Day” and “In-
termittent Fan”.

5
When Smart recovery is selected, the comfort, adequate matched to load capacity and
controller adjusts operating span to maximum efficiency. It will turn off automatically
match set program. Events per day if required. However if there is a need to shut off
selection define number of daily air the system, select OFF from Operating Mode
changes required based on residential Screen.
or business choices.
To Operate Indoor Blower Only:
When Intermittent Fan is selected, the
fan may be programmed to turn on for Select FAN from MAIN menu screen, then
selected periods of time at selected select ON for continuous blower operation or
time intervals if no call for cooling or Programmed Fan for intermittent option.
heating is present. Follow instructions
of each option to set program. NOTE: The controller is programmed to start
a Fan Calibration occurrence every week and
6F- SERVICE INFORMATION:This screen every time the power is lost. This function starts
lists components status and faults if the indoor blower and calibrates air volume to
any. Scroll up and down to obtain “Fault motor speed.
Status” showing active fault and last 5
faults, “Compressor Status”, “Outdoor 10. SYSTEM PROTECTION
fan Status”, “Indoor fan Status”, “Tem-
MEASURES
perature Status” and option to “Clear
Fault History”.
The Inverter Driver is designed to provide a full
scale of protection measures against conditions
7. SECURITY LOCKOUT: Select from
that may cause compressor and/or other
“Temp Adjust Only” or “Total Keypad
components failure. When a protection function
Lockout” options. A PIN number may be
is triggered, the Inverter trips and communicates
input. This PIN number will be needed
the fault description to the controller which will
for future system settings and adjust-
display an error code or component fault status.To
ments.
release the trip, correct the fault cause, turn power
off, and then turn it on after few seconds.
9. OPERATING INSTRUCTIONS
To Operate System in Cooling: Protection Functions:

From MODE Screen, select AUTO or COOL. 1- Low Voltage Protection: If the voltage
From Main Screen use the down arrow to set becomes lower than design minimum,
cooling temperature below room temperature. the output of inverter is interrupted.
Verify that the indoor fan calibration is performed
and that system starts running. 2- Over Voltage Protection: Inverter will
trip if voltage becomes higher than design
To set system operation, select MENU from the maximum.
Main Screen and follow the instructions listed
under previous section. 3- Over Current Protection: Inverter will
trip if the converter output current is
To Operate Furnace in Heating: exceeded due to load short circuit or
ground fault.
From MODE Screen, select AUTO or HEAT.
From Main Screen use the up arrow to set heating 4- Over Heat Protection: Inverter has
temperature above room temperature. a heat sink that rids it from excessive
temperatures. If temperature sensor
If system has been properly configured, heating exceeds 194 Fahrenheit, Inverter will
will start to operate. trip.

To Shut Off the System: 5- Over Speed Protection: Inverter will trip
if compressor speed is increased to 1.5
The system is designed to continuously operate times the allowed rated speed.
within a wide range of speeds to provide ultimate
6
6- Abnormal Rotation Protection: Inverter the switch is closed. If the discharge pressure
will trip if abnormal rotation of compressor rises above 575 psig, then the switch will open
is detected due to improper wiring. and de-energize the outdoor unit. The switch
will close again once the discharge pressure
7- Sensors Error Protection: The out- decreases below 460 psig.
door air temperature sensor controls
maximum compressor speed allowed Diagnostics and Troubleshooting:
for safe operation and the compressor
discharge temperature sensor monitor The controller Thermostat Unit is designed to
maximum allowed compressor tempera- provide service personnel with detailed descrip-
ture. Inverter will trip if these sensors are tion of faults that may cause system malfunction,
open or shorted. as well as messages indicating maintenance
required.
8- Microprocessor Error Protection: If
abnormality of the CPU is detected, Only qualified service personnel shall get into
the inverter will trip. Abnormality may “Service Information Menu” screen to define the
be caused by external electromagnetic fault and make the appropriate correction.
noise.
“SERVICE NEEDED” Display:
9- Communication Error Protection: The controller will change screen color to RED
Inverter will trip if communication with and displays “SERVICE NEEDED”, System
the main controller fails. information and Fault detected in the Service
needed menu screen.
NOTE: Tripping of the Inverter is input into the
controller memory up to 5 times occurrences. If Compressor error is detected, it displays
“COMP ERROR” followed by code number
Other System Protections: (see below).

Low Pressure Switch — A low pressure switch If Blower error is detected, it displays “BLOWER
is factory installed and located in the suction line ERROR” followed by code number (see be-
internal to the outdoor unit.The switch is designed low).
to protect the compressor from a loss of charge.
Under normal conditions, the switch is closed. Other possible errors displayed are:
If the suction pressure falls below 35 psig, then Too Hot Out
the switch will open and its signal to the inverter Comp Overload
will open. The inverter will then send signal to Low Gas Pressure
the controller to turn unit off and displays fault COMM Error 10, for indoor motor
message. The switch will close again once the COMM Error 20, for outdoor motor
suction pressure increases to 60 psig. COMM Error 30, for Furnace

High Pressure Switch — A high pressure An Inverter Keypad diagnosis tool may be used to
switch is factory installed and located in the help service the outdoor unit at site. See column
compressor discharge line internal to the outdoor “Display of Inverter panel” for fault codes.
unit. The switch is designed to de-energize the
unit when excessive pressure occurs due to Table 1 describes possible errors and corrective
abnormal conditions. Under normal conditions, measures.

7
Fault Possible Display of Finding and
Code No. Indication Cause inverter panel Check item correction
1- Check thermistor resistance at Out of range
Outdoor temp normal temperature (60~95°F) 10~25k.ohms,
thermistor shorted E.-A1 (1-2pin of CN7) Replace thermistor.
or disconnected. 2- Reset the power supply and Display E-A1,
run. Replace inverter
1- Check thermistor resistance at Out of range
Discharge temp normal temperature (60~95°F) 30~80k.ohms,
1 Sensor error thermistor shorted E.-A2 (1-2pin of CN8) Replace thermistor.
or disconnected. 2- Reset the power supply Display E-A2,
and run Replace inverter
1- Check thermistor resistance at Out of range
IPM temp thermistor normal temperature (60~95°F) 30~80k.ohms,
shorted or E.-A3 (1-2pin of CN9) Replace thermistor.
disconnected. 2- Reset the power supply Display E-A3,
and run Replace inverter.
Equal or over 187V
AC, possible power
1- Check supply voltage interruption
Low voltage of Less than 187VAC,
2 Under voltage E.-LV
inverter Check power supply.
2- Reset to the rated voltage Display E-LV, Replace
and run inverter.
Under 253VAC,
possible strong wind
1- Check supply voltage
High voltage of Over 253VAC, check
3 Over voltage O.V.
inverter power supply.
2- Reset to the rated voltage Display O.V., Replace
and run inverter/fan motor
Compressor over Reset to the rated voltage and Display O.S., Replace
5 Over speed O.S.
speed run inverter.
Out of range
1- Check compressor resistance 0.3~1.ohms,
Replace compressor.

Over current of Display O.C.,


2- Disconnect comp wires
power module O.C. Replace inverter.
(hardware) Display E.ROT.,
Reset power supply and run
Check wiring.
Display O.C.,
Replace inverter and run
8 Over current Replace compressor.
Out of range
1- Check compressor resistance 0.3~1.ohms,
Replace compressor.
Display O.C.,
Over current of 2- Disconnect comp wires
Replace inverter.
power module O.C.-C.
(software) Display E.ROT.,
Reset power supply and run
Check wiring.
Display O.C., Replace
Replace inverter and run
compressor.
Equal or above 125F,
1- Check outdoor temperature unit not allowed to
run.
2- Check the screws of power
Secure loose screws
module
3- Check IPM heat sink fins Clear obstructions
Over heat of power Secure fan to motor
9 Over heat O.H. 4- Check fan rotation
module shaft if screw is loose.
5- Check IPM thermistor Out of range
resistance at normal temperature 30~80k.ohms,
(60~95°F) (1-2pin of CN9) Replace thermistor.
Display O.H., Replace
6- Reset power supply and run
inverter.

Table 1. Interpreting the Diagnostic Codes


8
Fault Possible Display of Finding and
Code No. Indication Cause inverter panel Check item correction

1- Check comp wiring Secure loose wiring/


connection (TA4,TA5,TA6) terminals.
Abnormal comp Display E.ROT.,
E.ROT.
rotation 2- Reset power supply and run Replace inverter.
Display E.ROT.,
10 Rotation error 3- Replace inverter and run Replace compressor.
1- Check connection of FM
Abnormal rotation of wiring (CN3) Secure connection
E.-FAn Display E.-Fan,
outdoor FM
Replace inverter/ fan
2- Reset power supply and run motor
1- Check connection of
communication cable Verify and secure
(CN11,CONTROLLER) loose Connections
Set SW2 to ON (lower
Communication 2- Check SW2 position side)
Communication
20 error at indoor or E.-485
error Display E.-485,
outdoor
3- Reset power supply and run Replace inverter.
Display E.-485,
Replace controller or
4- Replace inverter and run Indoor fan motor.
1- Check the setting of DSW Set the DSW switch to
DIP-SW switching tonnage match tonnage.
E.-DS.
error
2- Reset the power supply Display E.-DS,
System Parameter and run Replace inverter.
91
error
EEPROM data Display E.-PR.,
E.-PR.
failure Reset power supply and run Replace inverter.

CAU trip CAU. Display CAU.,


Reset power supply and run Replace inverter.

System Error E.-CT Display E.-CT,


Reset power supply and run Replace inverter.
99 CPU error
CPU Error Err. Display Err., Replace
Reset power supply and run inverter.

Table 1. Interpreting the Diagnostic Codes (Continued)

Adjustment of Refrigerant Charge: NOTE: The unit MUST be charged at nominal


speed setting. See “Installer Settings Screen”
and select “Charging Mode” to run system at
CAUTION: nominal speed.
Split system air conditioner equipment
contains liquid and gaseous refrigerant
under pressure. Adjustment of
System Charge
refrigerant charge should only be
done by qualified, trained personnel
Unit Tonnage R-410A Oz.
thoroughly familiar with this type of 2 Ton 160
equipment. Under no circumstances
3 Ton 168
should the homeowner attempt to
install and/or service this equipment. 4 Ton 188
Failure to comply with this warning
Table 2. System Charge
could result in equipment damage,
personal injury or death.

9
Procedure for charging outdoor unit at out- 4. If the pressure measured in step 1 is
door temperatures above 65 F: less than the required liquid refrigerant
pressure determined in step 4, then
1. With the system at nominal speed there is too little charge in the system.
steady state, measure the liquid refrig- Add refrigerant and repeat steps 1
erant pressure in psig at the service through 3 until the system is correctly
valve. charged.
2. Measure the liquid refrigerant tem- 5. If the pressure measured in step 1 is
perature in Fahrenheit at the service greater than the required liquid refrig-
valve. erant pressure determined in step 4,
3. For the temperature measured, de- then there is too much charge in the
termine the liquid refrigerant pressure system. Remove refrigerant and repeat
from the appropriate charging chart steps 1 through 3 until the system is
below. correctly charged.

Refrigerant Charging Charts


For Cooling Mode of Operation

550
525
500
Remove refrigerant when above the curve
475
Liquid Pressure (psig)

450
425
400
375
350
325
300
275
250 Add refrigerant when below the curve
225
200
60 65 70 75 80 85 90 95 100 105 110 115 120 125 130
Liquid Temperature (F)

2,3, and 4 Ton iQ Drive Charging Chart

10
*TERMINALS ON COMPRESSOR
ARE NOT MARKED. USE RELATIVE
CABLE
LOCATION OF TERMINALS TO THE
GREEN
MARK STAMP TO IDENTIFY PROPER
RED
MARKING. BLACK O.D.
ORANGE FAN MOTOR
BLUE
“TO W” YELLOW
T REACTOR

LPS
YELLOW BLACK

YELLOW BLACK
S MARK R
STAMP “TO U”
TA6 TA5 TA4
1 2 3 4 5 6 7

BLACK
BLACK
“TO V” CN3 6 5 4 3 2 1
CN6 PLUG
THRU CORE TEMP BLACK
CONNECTOR
RED RING SENSOR RED
YELLOW COIL
1 BLACK OUTDOOR TEMP CONTROL
THRU TORIODAL 2 THERMISTOR CABLE
CN7
CONTROLLER
RING 3 P3
COIL
THERMOSTAT
4
THERMISTOR MOTOR
1 BLACK COMP DISCH TEMP

I.D. BLOWER
CN8 2 THERMISTOR INTERFACE C
INVERTER THRU CORE
BOARD W2
RING
DX+ POWER RH
GND GREEN
DX- CABLE R
DX- WHITE A
GRD W1
DX+ RED O.D. UNIT B
THRU CORE H
GD
CN11
BLACK
WHITE

RING
GREEN

OD
R RED 0 ID
DX+ YELLOW Y2 GD
Y1
THRU TORIODAL RING DX- WHITE
G
TO L.V. BARRIER
THERMOSTAT

TA8 TA1 24 VAC GND GREEN L


V
TA7 TA2 R C W2 W H

TWIN
TA3 RED

YELLOW

BLACK
YELLOW BLACK
WHITE

BLACK
HPS GREEN 24V 120V
FUSE
CABLE TEMP.
WHITE
BLACK

RED

BLUE
BLUE
WHITE

SENSOR GREEN
BROWN
BROWN
YELLOW

BLACK
SUCTION

BLACK
BLACK
BLACK

GREEN

YELLOW
FUSE (I.D. COIL)

T1 T2 PRESSURE
NOISE
CONTACTOR
CABLE

WHITE
FILTER

GREEN
BLACK
TRANSDUCER FOR FUTURE USE
20 21 22 23 24
WHITE W/BLACK STRIPE
BLACK W/ WHITE STRIPE

L1 L2
KELVIN
GRD.

Outdoor Unit/Furnace Wiring Diagram


CONTROLLER 3 Amp Fuse
COM TWIN
R
1 2 3 4 5 6 7 8 9 10 11 12
24 V
C

Y
ESX COIL
CABLE
ORANGE

GRAY
BLACK
RED
YELLOW

G
OUTDOOR POWER
SUPPLY W

9 6 3
BLACK

8 5 2
7 4 1
WHITE

Legend
Field Wiring Neutrals
Unused Motor
Factory Wiring: Leads
BLACK

Low Voltage 6 3
EAC HUM
M1
M2
M3

5 2
HEAT
EAC
COOL
L1

High Voltage
XFMR

HUM

4 1

11
*TERMINALS ON COMPRESSOR
ARE NOT MARKED. USE RELATIVE
CABLE
LOCATION OF TERMINALS TO THE
GREEN
MARK STAMP TO IDENTIFY PROPER
RED
MARKING. BLACK O.D.
ORANGE FAN MOTOR
BLUE
“TO W” YELLOW
T REACTOR

708592A
LPS
YELLOW BLACK
CONTROLLER
YELLOW BLACK THERMOSTAT
S MARK R
STAMP “TO U”
TA6 TA5 TA4 TEMP
1 2 3 4 5 6 7

BLACK
BLACK
“TO V” CN3 6 5 4 3 2 1
SENSOR
COIL CABLE C
CN6
THRU CORE BLACK
W2
RED RING RH

¢708592A¤
YELLOW RED
1 BLACK OUTDOOR TEMP R
THRU TORIODAL RING A
2 THERMISTOR W1
TO L.V. BARRIER CN7 COIL B
3 H
THERMISTOR P3 GD
4
DX+ OD
1 BLACK COMP DISCH TEMP INTERFACE DX- 0 ID
CN8 2 THERMISTOR THRU Y2
BOARD GND GD
CORE Y1
INVERTER
RING G
DX+
GND GREEN
DX- L
DX- WHITE
GND V
DX+ RED
CN11 CABLE THRU
BLACK CORE

WITH THE HOMEOWNER


TEMP. RING
BLACK SENS. R RED INDOOR
THRU TORIODAL RING SUC. DX+ YELLOW POWER
TA8 TA1 TO L.V. BARRIER WHITE
WHITE

INSTALLATION INSTRUCTIONS
GREEN DX- SUPPLY
TA7 BLACK GND GREEN
TA2
CABLE 24 VAC
TA3

INSTALLER: PLEASE LEAVE THESE


PRESSURE

YELLOW

BLACK
R C W2 W H
TWIN

YELLOW BLACK TRANSDUCER PLUG


20 21 22 23 24 CONNECTOR CUT WIRES TO
POWER FILTER REMOVE PLUG
CONTROL
RED

HOUSING WHEN
BLACK

HPS KELVIN CABLE


FUSE HEATER KIT IS
POWER PLUG
CONTROLLER NOT INSTALLED.
CABLE CONNECTOR

BLACK
BLACK
GREEN
1 2 3 4 5 6 7 8 9 10 11 12 WHITE

YELLOW
FUSE
I.D. BLACK
MOTOR
T1 T2 ESX
CONTACTOR
GREEN
WHITE

RED
BLACK

GREEN

BLACK
GRAY

COIL
ORANGE
YELLOW

CABLE
L1 L2

GRD.
L1
L1

L2
L2

GRAY
XFMR

RED
L2 COM

Y1
WHITE W2

Outdoor Unit/Air Handler Wiring Diagram


BLUE W1
O
OUTDOOR POWER Y/Y2 HEATER PLUG
G KIT
SUPPLY R
C
BLACK

P3
WHITE

1 2 3 4 5 6 7
COM

Legend
24 VAC

Field Wiring
Factory Wiring: RED
Low Voltage
208V/240V 24V
High Voltage
GRAY
TRANSFORMER
GRAY

RED

Printed in U.S.A. (06/06)


Specifications and illustrations subject to change
708592A (Replaces 7085920)

without notice and without incurring obligations.

Potrebbero piacerti anche