Qc=Vfa*ρ*(hfa-hsa)/3600+Qs/1000,
Where
External Heat caused
by Fresh air need to
3 6 &7 Qc: Total heat load
calculate
Vfa: Fresh air volume
ρ: Density
hfa= Fresh air enthalpy
hsa: AC supply enthalpy
Qs: sensible heat load
Where
Qc=122*1,2*(147,76-
31,4)/3600+7717/1000=12,5 kW
Qc=515,4*1,2*(147,7631,4)/3600+30431/10
00=50,4kW
Date : 16/11/2018
Date: 15-11-2018
PREP. BY : BW.
PT.STARINDO TUNGGAL PRATAMA
Head Office :"
Batu Merah Industrial komplek
AIR COND. CALCULATION CHK. BY :
No. 4 Batu SHY.
Ampar, Batam – Indonesia 29432"
Phone / Fax : 62 778 412392 / 62 778
412390 Email : shanty@starindotp.com
Client Doc No:
/ stp.batam@gmail.com
COVER SHEET
LDP-30291-EH-16
Document No : LDP-AC-CAL-001
Date : 15-11-2018
AIR COND. CALCULATION Rev. D Status: Issued for Approval
Project Doc. No. : LDP-30291-EH-16 Page : 2 of 10
TABLE OF CONTENTS
1. INTRODUCTION
2. DESIGN INPUT
4. CATALOGUE ------------------------------- 9
Document No : LDP-AC-CAL-001
Date : 15-11-2018
AIR COND. CALCULATION Rev. D Status: Issued for Approval
Project Doc. No. : LDP-30291-EH-16 Page : 3 of 10
1. INTRODUCTION
1.1 General
The purpose of this document is to calculate the ventilation air flow, cooling
load, heating load, humidifying load and fresh air rate for rooms/spaces at
Lampunut Development Plant. HVAC system will serves the utility building.
Following shows the served area.
• Control Room
• Switchgear Room
1.2 Abbreviations
EQT : Equivalent Temperature
DB : Dry Bulb Temperature
WB : Wet Bulb Temperature
RH : Relative Humidity
K-value : Heat Transfer Coefficient
SA : Supply Air
EA : Exhaust Air
RA : Return Air
hfa : Fresh Air Enthalpy
hma : Mixed Air Enthalpy
hra : Room Air Enthalpy
hsa : AC Supply Air Enthalpy
ρ : Density
dfa : Fresh Air Humidity Ratio
dma : Mixed Air Humidity Ratio
dra : Room Air Humidity Ratio
dsa : AC Supply Air Humidity Ratio
Q : Heat
Vfa : : Fresh Airflow volume
V : Airflow volume
dT/ T : Temperature difference
Document No : LDP-AC-CAL-001
Date : 15-11-2018
AIR COND. CALCULATION Rev. D Status: Issued for Approval
Project Doc. No. : LDP-30291-EH-16 Page : 4 of 10
2. DESIGN INPUT
2.1 Design Condition
Design Input
TEMPERATURE
DESCRIPTION (DB) RH ENTHALPY
OUTSIDE CONDITION 40 ºC 86% 147,76 kJ/kg
ROOM CONDITION 23,0 ºC 55% 47,62 kJ/kg
RETURN AIR CONDITION 24,0 ºC 51.8% 48,65 kJ/kg
MIXED AIR CONDITION (10%) 25,6 ºC 58,56 kJ/kg
MIXED AIR CONDITION (15%) 26,5 ºC 63,91 kJ/kg
MIXED AIR CONDITION (20%) 27,2 ºC 68,67 kJ/kg
*SUPPLY AIR CONDITION 12,0 ºC 93% 32,60 kJ/kg
SUPPLY AIR DEW POINT 11,3 ºC 95% 31,40 kJ/kg
OUTSIDE CONDITION (WINTER) 15,0 ºC 100% 34,16 kJ/kg
CEILING HEIGHT 3,4 m
SPECIFIC VOLUME 0,82 m³/kg
FRESH AIR PER PERSON 35 CMH
Notes:
Supply air condition only for calculation reference. Design performance shall refer to
equipment/product data sheet.
Temperature Condition
Temperature
No Description (DB)
o
C
1 Ambient Air 40,0
2 Roof exposed 56,0
3 Wall exposed 52,0
4 Air Conditioning Space 23,0
5 Internal passage/corridor 25,0
6 No Air condition Space 40,0
Document No : LDP-AC-CAL-001
Date : 15-11-2018
AIR COND. CALCULATION Rev. D Status: Issued for Approval
Project Doc. No. : LDP-30291-EH-16 Page : 5 of 10
U-value
Length
Height
Width
Area
Leakage
Room Descrition No. Heat Load
(according to ASHREA HANDBOOK - APPLICATION)
m m m m² dT Q(Sens) Q(Lat) Area Ratio Pressure Difference Leak air flow rate
Room Dimension W/m²ºC
16,5 4,5 3,4 74,3 ºC Watts Watts Pa m³/h
1. Walls & Deck Heat Transfer (Q1)
North Exposed 16,5 3,4 56,1 0,44 29 716 1,70E-04 20 128,82
South Exposed 16,5 3,4 56,1 0,44 29 716 1,70E-04 20 128,82
East Unexposed 4,5 3,4 15,3 0,44 0 0 1,70E-04 0 0,00
West Exposed 4,5 3,4 15,3 0,44 29 195 1,70E-04 20 35,13
Roof Exposed 16,5 4,5 74,3 0,44 33 1.078 1,70E-04 20 170,50
Floor Unexposed 16,5 4,5 74,3 0,44 17 555 5,20E-05 20 52,15
Sub-Total: 3.260
2. Solar Heat Gain(Q2)
Window 0
Heat Gain From Persons(Q3)
Sensible(W) 75 150
Person 2
Latent(W) 55 110
3. Heat Gain From Lighting and Other Sources(Q4)
Lighting 15 W/m² 74,3 1.114
Equipment 16090 W 1 16.090
Sub-Total: 17.204
Total internal heat gain : ΣQ 20.614 110
Total with 10% Margin : 22.797 Watts
U-value
Length
Height
Width
Area Leakage
No.
Room Descrition Heat Load
(according to ASHREA HANDBOOK - APPLICATION)
m m m m² dT Q(Sens) Q(Lat) Area Ratio Pressure Difference Leak air flow rate
Room Dimension W/m²ºC
3 4,5 3,4 13,5 ºC Watts Watts Pa CMH
1. Walls & Deck Heat Transfer (Q1)
North Exposed 3 3,4 10,2 0,44 29 130 1,70E-04 20 23,42
South Exposed 3 3,4 10,2 0,44 29 130 1,70E-04 20 23,42
East Unexposed 4,5 3,4 15,3 0,44 0 0 1,70E-04 0 0,00
West Exposed 4,5 3,4 15,3 0,44 29 195 1,70E-04 20 35,13
Roof Exposed 3 4,5 13,5 0,44 33 196 1,70E-04 20 31,00
Floor Unexposed 3 4,5 13,5 0,44 17 101 5,20E-05 20 9,48
Sub-Total: 753
2. Solar Heat Gain(Q2)
Window 0 0
Heat Gain From Persons(Q3)
Sensible(W) 75 150
Person 2
Latent(W) 55 110
3. Heat Gain From Lighting and Other Sources(Q4)
Lighting 15 W/m² 13,5 203
Equipment 2900 W 2 5.800
Sub-Total: 6.003
Total internal heat gain : ΣQ 6.905 110
Total with 10% Margin : 7.717 Watts
3.3 Summary
SWITCH GEAR ROOM 22,80 42,79 515 303 14,26 4 X 50% (3-duty & 1-standby)
CONTROL ROOM 7,72 12,47 122 72 12,47 2 X 100% (1-duty & 1-standby)
Notes : Supply air flow and cooling capacity shall according to spilt unit package performance at 26 ºC DB / 55 % RH return air and 35ºC outdoor condition
Document No : LDP-AC-CAL-001
Date : 15-11-2018
AIR COND. CALCULATION Rev. D Status: Issued for Approval
Project Doc. No. : LDP-30291-EH-16 Page : 9 of 10
l e f or
u i t a b es
S ctori
fa
Page 5
Page 11
Page 5
Page 12
Page 15,16
Page 6
Page 13,14
Page 15,16
1
Nice,
cool air in the factory
or in the cafeteria
2
AIR COOLED PACKAGED AIR CONDITIONERS
FVGR10NV1
RUR10NY1 Factory Modificaion Lower drain pan – –
Front suction high efficiency filter chamber – –
Rear suction –
Drain pump –
Remote sensor(Thermistor for suction air) –
DUCT TYPE 3
Central control adapter kit and LCD remote controller is necessary for option connection.
Quiet Operation
Equipped with scroll compressor for
RUR10NY1 quiet operation
FDR10NY1
Smooth running, low
vibration, low operating
sound.
Sound level
Outdoor unit
380V 415V
RUR05NY1 59 dB 60 dB
RUR06NY1 59 dB 60 dB
3
Easy operation
Digital remote control comes standard Refrigerant pre charged for up to 7.5 metres
with indoor unit. Allowable refrigerant pipe length and level difference
Temperature setting is possible by button operation. The set Pre-charged 1 Max. length Max. level
difference
temperature is conveniently displayed on the LED. 50 m
RUR05NY1-20NY1 7.5 m (Equivalent length 70 m) 30 m
1
Floor standing type (Standard accessory) Note: Additional refrigerant charging is required if the refrigerant pipe is longer than the
indicated length.
9 8 Note.1 3
10 2 3 5 4 1
Space savings
1 Power 5 Next setting 9 Compressor 1 indicator lamp
2 Temperature scale 6 Fan indicator lamp 10 Temperature sensor Installation space is saved thanks to a more
3 Temperature setting 7 Cool indicator lamp compact outdoor unit. This also makes it
4 Mode setting 8 Compressor 2 indicator lamp
easier to install.
Previous 20HP outdoor unit
NEW 53%
RUR20NY1 space saved
RUG10AUY1 X 2
Design flexibility (20HP) compared to
previous model
Max. length
4
X X X X X X X X X X
X X X X X X
X X X X X X X X
X X X X X X
5
Control Room Switchgear Room
X X X X X X X X X X
X X X X X X
X X X X X X
X X X X
6
Fan Performance
7
8
Wiring and Piping
9
DIMENSIONS
10
DIMENSIONS
11
12
DIMENSIONS
13
14
DIMENSIONS
15
16
When there is an
obstruction only
on the inlet side
An obstruction
in the overhead space
When there are
obstructions on
both sides
An obstruction
in the overhead space
When there is an
obstruction on the
inlet side
An obstruction
in the overhead space
An obstruction
in the overhead space
An obstruction
in the overhead space
17
or more or more
or more or more
or more or more
or more or more
or more or more
or more or more
or more
or more or more or more
or more
or more or more or more
or more or more
mm
18
Warning