MAC0502033C1
Air Conditioner
CS-C9DKU CU-C9DKU
CS-C12DKU CU-C12DKU
CONTENTS
Page Page
1 Features 2 8.5. Indoor Fan Speed Control 21
2 Functions 3 8.6. Outdoor Fan Speed Control 23
3 Product Specifications 6 8.7. Vertical Airflow Direction Control 23
3.1. CS-C9DKU CU-C9DKU 6 8.8. Horizontal Airflow Direction Control 24
3.2. CS-C12DKU CU-C12DKU 8 8.9. Powerful Operation 24
4 Dimensions 10 8.10. Quiet Operation 25
4.1. Indoor Unit & Remote Control 10 8.11. Timer Control 26
4.2. Outdoor Unit 11 8.12. Random Auto Restart Control 26
5 Refrigeration Cycle Diagram 12 8.13. Remote Control Signal Receiving Sound 26
6 Block Diagram 13 8.14. Economy Mode Operation 27
7 Wiring Diagram 14 9 Operating Instructions 28
8 Operation Details 15 10 Installation Instructions 34
8.1. Cooling Operation 15 10.1. Safety Precautions 34
8.2. Soft Dry Operation 16 10.2. Attached accessories 36
8.3. Automatic Operation 17 10.3. Select the best location 36
8.4. Operation Control 18 10.4. Indoor/Outdoor Unit Installation Diagram 36
1 Features
• High Efficiency • Quality Improvement
− Random auto restart after power failure for safety restart
• Compact Design operation.
− Gas leakage protection.
• Wider range of horizontal discharge air. − Prevent Compressor reverse cycle.
− Inner protector to protect Compressor.
• Air Filter with function to reduce dust and smoke. − Noise prevention during soft dry operation.
− Blue Coated Condenser for high resistance to corrosion.
• Automatic air swing and manual adjusted by Remote
Control for vertical airflow. • Operation Improvement
− Quiet mode to provide quiet operation.
• Long installation piping. − Powerful mode to reach the desired room temperature
− CS/CU-C9DKU, long piping up to 33ft. quickly.
− CS/CU-C12DKU, long piping up to 49ft. − 24-hour timer setting.
• Serviceability Improvement
− Removable and washable Front Panel.
2
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
2 Functions
3
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
4
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
5
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
3 Product Specifications
3.1. CS-C9DKU CU-C9DKU
Unit Indoor unit Outdoor unit
Power Source (Phase, Voltage, Cycle) ø, V, Hz Single, 115, 60
Cooling Capacity kW (BTU/h) 2.58 (8,800)
Moisture Removal l/h (Pint/h) 1.0 (2.1)
INTAKE
6
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
Note:
• Specifications are subjected to change without prior notice for further improvement.
7
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
INTAKE
8
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
Note:
• Specifications are subjected to change without prior notice for further improvement.
9
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
4 Dimensions
4.1. Indoor Unit & Remote Control
10
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
11
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
12
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
6 Block Diagram
CS-C9DKU CU-C9DKU
CS-C12DKU CU-C12DKU
13
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
7 Wiring Diagram
CS-C9DKU CU-C9DKU REMARKS
CS-C12DKU CU-C12DKU B : BLUE
BR : BROWN
BL : BLACK
GRY : GRAY
O : ORANGE
P : PINK
R : RED
W : WHITE
Y/G : YELLOW/GREEN
14
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
8 Operation Details
8.1. Cooling Operation
15
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
16
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
• Then, the unit start to operate at determined operation mode, until it is switched off using remote control, with the setting
temperature as shown in below table.
• The setting temperature for all the operations can be changed one level up or one level down from the standard temperature
as shown in below table by pressing on the temperature up or temperature down button at remote control.
• The operation mode judging temperature and standard setting temperature can be increased by 3.6°F permanently, by open
the circuit of JX1 at indoor electronic controller.
17
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
18
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
19
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
• Narrowing
1. Vertical Airflow Direction
During Anti-Dew condensation prevention, Airflow Direction Auto-control angle from 0° - 32° to 20° - 30° under cooling and
Soft Dry operation mode.
20
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
During Anti-Dew condensation prevention, Airflow Direction Manual Control angle change from 10°, 15°, 20°, 26°, 32° to
22°, 24°, 26°, 28°, 30°.
21
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
22
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
23
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
24
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
25
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
8.11.1. ON Timer
• When ON Timer is set by using the remote control, the unit will start to operate slightly before the set time, so that the room will
reach nearly to the set temperature by the set time.
• For Cooling and Soft Dry operation, the operation will start 15 minutes before the set time.
• For Automatic operation, the indoor fan will operate at SLo speed for 25 seconds, 30 minutes before the set time to detect the
intake air temperature to determine the operation mode. The operation indication lamp will blink at this time.
26
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
27
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
9 Operating Instructions
28
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
29
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
30
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
31
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
32
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
33
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
10 Installation Instructions
Required tools for Installation Works
1. Philips screw driver 5. Spanner 9. Gas leak detector 13. Multimeter
2. Level gauge 6. Pipe cutter 10. Measuring tape 14. Torque wrench
13.3 lbf.ft
31.0 lbf.ft
40.6 lbf.ft
3. Electric drill, hole core drill 7. Reamer 11. Thermometer 15. Vacuum pump
(ø2 3/4”)
4. Hexagonal wrench (5/32”) 8. Knife 12. Megameter 16. Gauge manifold
This indication shows the possibility of causing injury or damage to properties only.
• Carry out test running to confirm that no abnormality occurs after the installation. Then, explain to user the operation, care and
maintenance as stated in instructions. Please remind the customer to keep the operating instructions for future reference.
1. Engage dealer or specialist for installation. If installation done by the user is defective, it will cause water leakage, electrical shock or fire.
2. Install according to this installation instruction strictly. If installation is defective, it will cause water leakage, electrical shock or fire.
3. Use the attached accessories parts and specified parts for installation. Otherwise, it will cause the set to fall, water leakage, fire or
electrical shock.
4. Install at a strong and firm location which is able to withstand the set’s weight. If the strength is not enough or installation is not properly
done, the set will drop and cause injury.
5. For electrical work, follow the local national wiring standard, regulation and this installation instruction. An independent circuit and single
outlet must be used. If electrical circuit capacity is not enough or defect found in electrical work, it will cause electrical shock or fire.
6. Use the UL listed or CSA approved AWG16 wire (or heavier wire) and connect tightly for indoor/outdoor connection. Connect tightly and
clamp the wire so that no external force will be acted on the terminal. If connection or fixing is not perfect, it will cause heat-up or fire at
the connection.
7. Wire routing must be properly arranged so that control board cover is fixed properly. If control board cover is not fixed perfectly, it will
cause heat-up at connection point of terminal, fire or electrical shock.
8. When carrying out piping connection, take care not to let air substances other than the specified refrigerant go into refrigeration cycle.
Otherwise, it will cause lower capacity, abnormal high pressure in the refrigeration cycle, explosion and injury.
34
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
1. The equipment must be earthed and installed with earth leakage current breaker. It may cause electrical shock if grounding is not
perfect.
2. Do not install the unit at place where leakage of flammable gas may occur. In case gas leaks and accumulates at
surrounding of the unit, it may cause fire.
3. Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water may enter the room and damage the
furniture.
35
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
OUTDOOR UNIT
• If an awning is built over the unit to prevent direct
sunlight or rain, be careful that heat radiation from the
condenser is not obstructed. • This illustration is for explanation purposes only.
• There should not be any animal or plant which could be The indoor unit will actually face a different way.
affected by hot air discharged.
• Keep the spaces indicated by arrows from wall, ceiling,
fence or other obstacles.
• Do not place any obstacles which may cause a short
circuit of the discharged air.
• If piping length is over the rated length, additional
refrigerant should be added as shown in the table.
36
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
The mounting wall is strong and solid enough to prevent it from Caution
the vibration. When the wall is hollow, please be sure to use the
sleeve for tube ass’y to prevent dangers caused by
mice biting the connecting cable.
37
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
(This can be used for left rear piping & left bottom piping also.)
38
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
• Secure the cable onto the control board with the holder
(clamper).
39
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
40
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
41
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
1. Connect a charging hose with a push pin to the Low side of a charging set and the service port of the 3-way valve.
• Be sure to connect the end of the charging hose with the push pin to the service port.
2. Connect the center hose of the charging set to a vacuum pump with check valve, or vacuum pump and vacuum pump adaptor.
3. Turn on the power switch of the vacuum pump and make sure that the needle in the gauge moves from O PSI to -14.5 PSI.
Then evacuate the air approximately ten minutes.
4. Close the Low side valve of the charging set and then turn off the vacuum pump. Make sure that the needle in the gauge does
not move after approximately five minutes.
Note: BE SURE TO FOLLOW THIS PROCEDURE IN ORDER TO AVOID REFRIGERANT GAS LEAKAGE.
5. Disconnect the charging hose from vacuum pump and from the service port of the 3-way valve.
6. Tighten the service port caps of the 3-way valve at a torque of 4.05 Pf with a torque wrench.
7. Remove the valve caps of both of the 2-way valve and 3-way valve. Position both of the valves to “OPEN” using a hexagonal
wrench (5/32”).
8. Mount valve caps onto the 2-way valve and the 3-way valve.
• Be sure to check for gas leakage.
Caution
• If gauge needle does not move from 0 PSI to -14.5 PSI, in step 3 above take the following measure:
• If the leak stops when the piping connections are tightened further, continue working from step 3.
• If the leak does not stop when the connections are retightened, repair the location of leak.
• Do not release refrigerant during piping work for installation and reinstallation. Take care of the liquid refrigerant, it may cause
frostbite.
42
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
10.6.5. OUTDOOR UNIT ELECTRICAL 4. Fix the conduit connectors to the conduit holes with lock-
nuts, then secure them against the side panel.
WIRING
5. Connecting wire between indoor unit and outdoor unit
should be UL listed or CSA approved 4 × AWG16 wire.
6. Secure the wire onto the control board with the holder
(clamper).
7. Wire connection to the power supply (115V 60 Hz) through
circuit breaker.
• Connect the UL listed or CSA approved wires (AWG14)
to the terminal board, and connect the other end of the
wires to circuit breaker.
43
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
CHECK ITEMS
44
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
45
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
WHEN INSTALLING AN AIR CONDITIONER, BE SURE TO If air remain in the indoor unit and refrigeration pipes, it will
EVACUATE THE AIR INSIDE THE INDOOR UNIT AND PIPES affect the compressor, reduce to cooling capacity, and could
in the following procedure. lead to a malfunction.
Procedure:
1. Connect a charging hose with a push pin to the Low 6. Tighten the service port cap at a torque of 4.05 Ibf with
side of a charging set and the service port of a 3-way a torque wrench.
valve. 7. Remove the valve caps of the 2-way valve and the 3-
• Be sure to connect the end of the charging hose with the way valve. Position both of the valves to “open” using
push pin to the service port. a hexagonal wrench (6/32 inch).
2. Connect the centre hose of the charging set to a 8. Mount the valve caps onto the 2-way and 3-way valves.
vacuum pump. • Be sure to check for gas leakage.
3. Turn on the power switch of the vacuum pump and
make sure that the needle in the gauge moves from 0
PSI (0 cmHg) to -14.5 PSI (-76 cmHg). Then evacuate the
Caution
air for approximately ten minutes. If gauge needle does not move from 0 cmHg to -76
4. Close the Low side valve of the charging set and turn cmHg in step (3) above, take the following measures:
off the vacuum pump. Make sure that the needle in the If the leaks stop when the piping connections are
gauge does not move after approximately five minutes. tightened further, continue working from step (3).
If the leaks do not stop when the connections are
BE SURE TO TAKE THIS PROCEDURE IN ORDER TO
retightened, repair the location of the leak.
AVOID GAS LEAKAGE.
46
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
Procedure:
1. Confirm that both the 2-way and 3-way valves are set to 6. Operate the air conditioner at the cooling cycle and
the opened position. stop it when the gauge indicates 0 PSI (0 kg/cm2G).
• Remove the valve stem caps and confirm that the valve If the unit cannot be operated at the cooling condition
stems are in the opened position. (weather is rather cool), short the Pumping Down pins
• Be sure to use a hexagonal wrench to operate the valve on the Main Control P.C.B.
stems. (Simply press the pumping down button if it is
2. Operate the unit for 10 to 15 minutes. equipped.)
3. Stop operation and wait for 3 minutes, then connect the So that the unit can be operated.
charge set to the service port of the 3-way valve. 7. Immediately set the 3-way valve to the closed position.
• Connect the charge hose with the push pin to the Gas • Do this quickly so that the gauge ends up indicating 14.5
service port. PSI (1 kg/cm2G) to 43.5 PSI (3 kg/cm2G).
4. Air purging of the charge hose. 8. Use refrigerant reclaiming equipment to collect
• Open the low-pressure valve on the charge set slightly refrigerant from indoor unit and pipes.
to purge air from the charge hose. 9. Disconnect the charge set, and mount the 2-way and 3-
5. Set the 2-way valve to the closed position. way valve’s stem caps and the service port caps.
• Use a torque wrench to tighten the service port cap to a
torque of 4.05 Ibf.
• Be sure to check for gas leakage.
10. Disconnect pipes from indoor unit and outdoor unit.
47
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
WHEN REINSTALLING AN AIR CONDITIONER, BE SURE TO If air remain in the indoor unit and refrigeration pipes, it will
EVACUATE THE AIR INSIDE THE INDOOR UNIT AND PIPES affect the compressor, reduce to cooling capacity, and could
in the following procedure. lead to a malfunction.
Procedure:
1. Connect a charging hose with a push pin to the Low 7. Tighten the service port cap at a torque of 18 N.m with
side of a charging set and the service port of the 3-way a torque wrench.
valve. 8. Remove the valve caps of the 2-way valve and the 3-
• Be sure to connect the end of the charging hose with the way valve. Position both of the valves to “open” using
push pin to the service port. a hexagonal wrench (6/32 inch).
2. Connect the centre hose of the charging set to a 9. Mount the valve caps onto the 2-way and 3-way valves.
vacuum pump. • BE SURE TO USE REFRIGERANT RECLAIMING
3. Turn on the power switch of the vacuum pump and EQUIPMENT WHILE DISCHARGING THE
make sure that the needle in the gauge moves from 0 REFRIGERANT.
PSI (0 cmHg) to -14.5 PSI (-76 cmHg). Then evacuate the • Purge the air from charge set’s centre hose.
air for approximately ten minutes.
• Be sure to check for gas leakage.
4. Close the Low side valve of the charging set and turn
off the vacuum pump. Make sure that the needle in the
Caution
gauge does not move after approximately five minutes. If gauge needle does not move from 0 PSI (0 cmHg) to
BE SURE TO TAKE THIS PROCEDURE IN ORDER TO -14.5 PSI (-76 cmHg) in step (3) above, take the
following measures:
AVOID GAS LEAKAGE.
If the leaks stop when the piping connections are
5. Disconnect the charging hose from the vacuum pump. tightened further, continue working from step 3.
6. Charge the pipes and indoor unit with gas refrigerant If the leaks do not stop when the connections are
from 3-way valve service port, and then discharge the retightened, repair the location of the leak.
refrigerant until low side (gas side) gauge needle
indicates 43.5 PSI (3 kg/cm2).
48
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
Procedure:
1. Confirm that both the 2-way and 3-way valves are set to
the open position.
2. Connect the charge set to the 3-way valve’s service
port.
• Leave the valve on the charge set closed.
• Connect the charge hose with the push-pin to the
service port.
3. Connect the charge set’s centre hose to refrigerant
reclaiming equipment.
• Purge the air from charge hose.
4. Open the valve (Low side) on the charge set and
discharge the refrigerant until the gauge indicates 7.25
PSI (0.5 kg/cm2G) to 14.5 PSI (1 kg/cm2G).
• If there is no air in the refrigeration cycle (the pressure
when the air conditioner is not running is higher than 0.1
PSI (1 kg/cm2G), discharge the refrigerant until the
gauge indicates 7.25 PSI (0.5 km/cm2G) to 14.5 PSI (1
kg/cm2G). If this is the case, it will not be necessary to
apply a evacuation.
• Discharge the refrigerant gradually; if it is discharged
too suddenly, the refrigeration oil will also be
discharged.
5. Turn on refrigerant reclaiming equipment.
49
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
11.5. Evacuation
(No refrigerant in the refrigeration cycle)
Procedure:
1. Connect the vacuum pump to the charge set’s centre
hose.
2. Evacuation for approximately one hour.
• Confirm that the gauge needle has moved toward -14.5
PSI (-76 cmHg) [vacuum of 4 mmHg or less.]
3. Close the valve (Low side) on the charge set, turn off
the vacuum pump, and confirm that the gauge needle
does not move (approximately 5 minutes after turning
off the vacuum pump).
4. Disconnect the charge hose from the vacuum pump.
• Vacuum pump oil
If the vacuum pump oil becomes dirty or depleted,
replenish as needed.
50
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
Procedure:
1. Connect the charge hose to the charging cylinder. This is different from previous procedures. Because you are
charging with liquid refrigerant from the gas side, absolutely do
• Connect the charge hose which you disconnected from no attempt to charge with large amount of liquid refrigerant
the vacuum pump to the valve at the bottom of the while operating the air conditioner.
cylinder.
2. Purge the air from the charge hose. 4. Immediately disconnect the charge hose from the 3-
• Open the valve at the bottom of the cylinder and press way valve’s service port.
the check valve on the charge set to purge the air (be • Stopping partway will allow the refrigerant to be
careful of the liquid refrigerant). discharged.
3. Open the valve (Low side) on the charge set and charge • If the system has been charged with liquid refrigerant
the system with liquid refrigerant. while operating the air conditioner, turn off the air
• If the system cannot be charged with the specified conditioner before disconnecting the hose.
amount of refrigerant, it can be charged with a little at a 5. Mount the valve stem caps and the service port cap.
time (approximately 0.33 Ib each time) while operating • Use torque wrench to tighten the service port cap to a
the air conditioner in the cooling cycle; however, one torque of 4.05 Ibf.
time is not sufficient, wait approximately 1 minute and
• Be sure to check for gas leakage.
then repeat the procedure. (pumping down-pin)
51
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
12 Servicing Information
12.1. Distinction of Lead Free (PbF) Printed Circuit Board
• Printed circuit boards (manufactured) using lead free solder will have a PbF stamp on the Printed Circuit board.
CAUTION
• Pb free solder has a higher melting point than standard solder; typically the melting point is 50 - 70°F (30 - 40°C) higher.
Please use a high temperature solder iron and set it to 700 ± 20°F (370 ± 10°C).
• Pb free solder will tend to splash when heated too high (about 1100°F/600°C).
• If you must use Pb solder, please completely remove all of the Pb free solder on the pin or solder area before applying Pb
solder. If this is not pratical, be sure to heat the Pb free solder until it melts, before applying Pb solder.
Fig. 1
Fig. 3
− Remove the 2 caps and 2 screws at the bottom of the − Release the hooks on top and on the left side of Control
Front Grille.(Fig.1) Board Front Cover.(Fig.3)
− Then remove the Control Board Front Cover.(Fig.3)
− Remove the earth wire.(Fig.3)
− Release the screw on the left side of the Control Board
Front Cover Complete.(Fig.3)
− Then remove the Control Board Front Cover
Complete.(Fig.3)
Fig. 2
52
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
Fig. 6
− Press the hook to the right then take out the PCB (Fig.6)
− Remove Ry-Pwr connector (black and brown) from the
terminal board. (Fig.6)
Fig. 4
− Remove AC-Wht connector from the PCB. (Fig.6)
− Remove the indicator complete screw, and then remove
the Indicator Complete.(Fig.4)
Fig. 5
53
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
12.3. Indoor Fan Motor and Cross Flow Fan Removal Procedures
Fig. 7 Fig. 9
− Remove the screw on the left side of the unit. (Fig.7) − Remove the cross flow fan bushing from the chassis.
− Pull the hook to the left and lift up the evaporator. (Fig. (Fig.9)
7) − Loosen the fan boss screw at the cross flow fan. (Fig.9)
− Pull down the Discharge Grille Complete. (Fig.7)
Fig. 10
54
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
• Under various setting mode, after select the transmission code combination of remote control, press any button of remote
control to transmit a signal to indoor unit. The transmission code will be stored in EEPROM.
• After signal is received, the various setting mode is cancelled and return to normal operation.
55
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
56
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
13 Troubleshooting Guide
13.1. Refrigeration cycle system
In order to diagnose malfunctions, make sure that there is no
electrical problem before inspecting the refrigeration cycle.
Such problems include insufficient insulation, problem with the
power source, malfunction of compressor or fan motor.
The normal outlet air temperature and pressure of the
refrigeration cycle depend on various conditions, the standard
values for them are shown in the table to the right.
57
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
Inefficient compression
• Carry out the measurements of pressure, electric current, and temperature fifteen minutes after an operation is started.
• Electric current during operation becomes approximately 20% lower than the normal value.
Insufficient compressing of a compressor • The discharge tube of the compressor becomes abnormally hot (normally 154 to 194°F).
• The difference between high pressure and low pressure becomes almost zero.
• Electric current reaches a high level abnormally, and the value exceeds the limit of an
ammeter. In some cases, a breaker turns off.
Locked compressor
• The compressor has a humming sound.
58
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
14 Technical Data
14.1. Thermostat characteristics
59
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
60
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
61
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
62
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
63
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
Note:
The above exploded view is for the purpose of parts disassembly and replacement.
The non-numbered parts are not kept as standard service parts.
64
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
(Note)
• All parts are supplied from PHAAM, Malaysia (Vendor Code: 061).
• “O” marked parts are recommended to be kept in stock.
65
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
Note:
The above exploded view is for the purpose of parts disassembly and replacement.
The non-numbered parts are not kept as standard service parts.
66
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
(Note)
• All parts are supplied from PHAAM, Malaysia (Vendor Code: 061).
• “O” marked parts are recommended to be kept in stock.
67
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
c
R55 b
1k
Q01
Auto C143XKTX
SW BZ
2
BZ01 e
SW01 1
R11 R07
C01
1k 10k
0.01
R12 R88
1k C02 5.1k
0.01
R78
10k
CN-SONIC
1
2
3
R68
100
DISPLAY COMPLETE
IC401
C24 0.01
1 R13 220
R401 47 C25 0.01
2 R14 220
C26 0.01
3
+ C401
R15
47
220
6.3V CN-DISP
8 1
TIMER/AIR SW(ORG) D404
7 2
POWER(GRN) D402 C29
6 3
5 4 0.1 R17
POWERFUL(ORG)
4 5 220
D403
3 6
QUIET(ORG) D405
2 7 R27 220
ECONOMY(GRN) D406
1 8
9
10 R73 c
C28 C27 C35 b
3.3k
0.01 0.01 0.01
CN-DISP
Q09
R31
1k
R56
1k
R58
C22
CN-HA 0.01 10k
R59 1k
4
3 JP5
2
1
C23 R60
0.01 10k
68
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
3XKTX
C38
1000p
R10
10k
R18 D12
R19 D11
R20 D10
R21 D09
R22 D08
R23 D07
R24 D06
R25 D05
64 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49
P67
P66
P65
P75
P47
P46
P45
P44
P43
P42
P41
P40
P64
P74
P73
P72
P71
1 48
P50
2 RY-PWR DRIVE SIGNAL STEPPING TOD 47
P51 MOTOR AUTO OPERATION
DRIVE TEST RUN P03 46
3 SIGNAL REMOTE CONTROL
P52
SOUND
INTP2
4 BUZZER 45
P53 POWER CLOCK INPUT
DISPLAY INTP1
5 44
P54
REMOTE-CONTROL
6 COMMAND INPUT INTP0 43
P55
7 Vss1 42
P56
IC01 X1 41
8 P57
R06 24k OSC X2 40
9 Vss0
JP2
10 VDD0 IC(VPP) 39
R75 1k
C39 11 P30 XT1 38
R76 1k
12 P31 XT2 37
R74 1k RESET 36
13 P32 RESET
INTAKE AIR TEMP
R77 1k AVDD
14 POWER 35
P33 PIPE TEMP
15
TIMER SHORTEN AVref 34
P34 AUTO RESTART GROU ND
AN10
16 33
P35
SCK30
AN17
AN16
AN15
AN14
AN13
AN12
AN11
VDD1
AV55
S130
S030
P36
P23
P24
P25
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
1 8 16
2 15
8 RY-PWR 5 DI
1 16 3 14 R09 SK 4
2 15
10k JX2
R05 4 13
6 DO CS 3
3 14 43 5 12
4 13 1/2W 6 11 7 GND Vcc 2
5 12 7 10 C05
R04 8 RS 0.1
6 11 R/B 1
43 9 16V
7 10 1/2W
9
IC02
IC05 IC06 C3EBDG000021
B1HBGGF00013
B1HBGGF00013 C04 R30 R33 C08
0.1 20k 15k 0.1
16V 16V
5 4 3 2 1 4 3 2 1
CN-STM1 (PH) CN-TH (RED)
5 4 3 2 1 (ZH5)
PIPE TEMP. SENSOR AIR TEMP. SENSOR
(20k 3950) (15k 3950)
VERTICAL
69
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
R66 R48
IC04 IC03
T01 REGULATOR REGULATOR
DB01
5 8 ~
+
2 13 I 12V O I 5V O
C17 C14 C11
~ 3300 G 470 G 100
35V 25V 16V
c
b R03 1.3k D16 R57 12k
Q02
C143XKTX c C07 RY-PWR
e R29
0.1 L
b 4.7k 1.6k D15
16V R47 12k
FUSE
P
10k T 2A L 250V
C03 TEMPERATURE
e ZNR01
0.047 FUSE
AC-WHT
Q03 SSR01
C143XKTX c
b 4.7k L01 1
125 H
TO
10k 2 OUTDOOR
e
3
SSR01
CR03
R32 X01
150k C19
0.047
4.096 MHz
(47pF X 2) CN-FM
1
C-FM 2
3 FAN MOTOR
R50 1.5 4
5
JP3 R49 1k 100k
R51
Z01 0.1
c 16V
JP4 10 k 7.5V
b Q06 C21
C10
C36 c C2412KTX R53 R52 10
0.1 Q05
C37 10k 6.2k 50V
16V R79 e b
0.01 C2412KTX
10k
+
e R54
6.2k
R38 C15 R43
0.01
CN-ION
JX1 4
3
2
R37 1
10k R61
R62 10 k
C31
D01
c Q08 0.01
TEST
R02 1k 1 2 b
R67
R01
Q07
10 k
e R64 c C32
6.2k 0.01
b
R63
6.2k e
70
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
C9DKU/C12DKU
B
FAN MOTOR
CAPACITOR
R
TO
Y
POWER
2 3 L1 L2
SUPPLY
SOURCE
BR COMPRESSOR
R
TO
BR
Y
B
OUTDOOR
UNIT
CAPACITOR
1
1
W
B
4
B
OUTDOOR UNIT MAGNETIC RELAY
TERMINAL
GRY Y
OVERLOAD
PROTECTOR
71
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
72
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
TIMER TABLE
Test Mode
Name Time (When test point Remarks
Short-circuited)
Real Timer 1 hr. 1 min.
10 min. 10 sec.
1 min. 1 sec.
Time Delay Safety Control 2 min. 58 sec. 0 sec.
Forced Operation 60 sec. 0 sec.
Time Save Control 7 min. 4.2 sec.
Anti-Freezing 4 min. 0 sec.
Auto Mode Judgement 20 sec. 0 sec.
Soft Dry OFF 6 min. 36 sec.
ON 10 min. 60 sec. Soft Dry: 10 min. operation
Cooling 40 sec. 4 sec.
70 sec. 7 sec.
Deodorizing Control 20 sec. 2 sec.
180 sec. 18 sec.
Soft Dry 40 sec. 4 sec.
360 sec. 36 sec.
Comp. Reverse Rotation Detection 5 min. 30 sec. Comp. ON 5 min. and above
2 min. 0 sec.
Comp./ Fan Motor Delay Timer 1.6 sec. 0 sec.
Powerful Mode Operation 15 min. 15 sec.
Random Auto Restart Control 0 ~ 62 sec. 0 ~ 6.2 sec.
73
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
74
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
75
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU
76
CS-C9DKU CU-C9DKU / CS-C12DKU CU-C12DKU