CABLE SIZE AND VOLTAGE DROP CALCULATION

PROJECT NO.: CSP # LOCATION: AREA : RM.NO.: DATE: 12/11/2018 16:51

Cable Tag No. --- D2-5_1 From --- SS5 To --- D2-5_1

Cable Description --------------- Cu. / XLPE / PVC / PVC

Load on Cable ( P ) ------------- = 59.28 KW 62.40 KVA - HP

Length of Cable ( L ) ----------- ( one way ) = 5.0 Mtrs. 245


Power Factor ( P.F.) ------------ = 95%
System Voltage ( V ) ---------- = 380 / 220 Volts
Supply Voltage to -------------- D2-5_1 = 380 Volts, 3 Ø, 60 Hz.

Therefore, Line Current - in Amps. ( I ) P × 1000


= [FORMULA]
SQRT(3) × V × P.F.

59.28 × 1000
=
1.732050808 × 380 × 0.95

= 94.81 Amps.

The total no. or set of cables required or preferred per phase ( n ) = 1


Therefore Net Current Passing Through the Cable ( Io = I / n ) = 94.81 Amps.

Checking for Current Carrying Capacity of the XLPE Multicore Cable, 0.6 / 1 kV --- ( Ref. Cat.: RIYADH CABLES )
For Cable Ampacity Req'd @ 125% of Line current = 118.5 Amps. ( Installed in Duct Bank )

For 35 mm Cable Ampacity (Iamp)


2
= 160.0 Amps. ( From Table 2 , Page 5 of Catalogue )

Derating Factors :
Temperature Factor ( ft ) ---------- XLPE = 0.87 ( From Table 10, Page 11 of Catalogue -for 45 ° C - Ambient)
Group Factor ( fg ) ------------------ = 0.92 ( From Table 1212
, , Page 14 & 15 of Catalogue )

Cable Spacing ( d ) ----------------- = cable diameter No. of Cables = 2 -- side by side

Cable to Wall ( = or > ) ----------- 200 mm. No. of Ground = 1 -- layer Laid on Ground

Therefore, Derating Factor ( fd ) = ft × fg = 0.87 × 0.92

( fd ) = 0.800
Cable Derated Current ( Ider ) = Pre-Selected Cable Ampacity × Derating Factor = Iamp × fd = 160.0 × 0.800

( Ider ) = 128.06 Amps.

The NEW Current Carrying Capacity of above Cable is Still Higher than the Cable Ampacity reqd. @ 125% -- Which suits the requirement

Verification / Cross Checking of Voltage Drop


Maximum Permissible Voltage Drop Desired ( VDp ) = 2.50 % (as required)

Pre-Selected Cable -- Derated Current Carrying Capacity ------- ( Ider ) = 128.06 Amps.

Length of Cable ------- ( L ) = 5.0 Mtrs. ( one way )

= 1.030 mV / A · Mtr. ( From Page 23 of Catalogue )


.
VDp × V × 1000 2.50 × 380 × 1000
Therefore, Applicable (VDap) = =
Ider × L × 100 128.06 × 5.0 × 100

= 14.836 mV / A · Mtr. .

From table on Page 23 of Catalogue, the Voltage Drop of the pre-selected -- 35 mm2 XLPE insulated 90 o
C multi core cable is equal to

1.030 mV / A · Mtr. --- Which is within the limit ( means < the requirement of 14.836 mV / A · Mtr. )

Therefore, Suitable Cable Size is 50 mm2

Hence, Recommended Cable Size is 1 no. 4C x 50 mm2 + 25 mm2 E

ALTERNATIVE : 1 no. 3C x 35 mm2 + 16 mm2 N + 16 mm2 E


The Actual Voltage Drop of the Recommended Cable = 0.13 % ≈ 379.50 V (WORKING VOLTAGE)

This software package will calculate the required cable size & voltage drop installed in free air or enclosed run & raceway, and display the amount of actual voltage, and the equivalent voltage drop in percentage of this amount.
The data used are constants based on an ambient temperature that the designer selects, ranging from 10 oC to 60 oC and group factor for different cable installation condition and formation requirement.
The size of cable may range from 1.5 mm2 to 500 mm2 in the industry standard increments. Distances must be entered in meter units, this length also must be the one way distance from the source to the load.
ENAJR-I ® (C) 2004-2005 RTCC - Riyadh, KSA
The author makes no warranty, either expressed or implied, including but not limited to any implied warranties of fitness for a particular purpose regarding the software, and makes the software available solely on an "as is" basis.
You accept full responsibility for the application of this software and the use of any information obtained from the software. This software is not intended to replace the need for a qualified person, versed in the requirements of any applicable local
and or national codes and regulations. This material is under constant development and subject to change without prior notice. If you have any comments or suggestions, please e-mail these to: eligio@rtcc.com.sa or eligioamaranto@yahoo.com

404429645.xls D2-5_1
of this amount.

404429645.xls D2-5_1
CABLE SIZE AND VOLTAGE DROP CALCULATION
PROJECT NO.: CSP # LOCATION: AREA : RM.NO.: DATE: 12/11/2018 16:51

Cable Tag No. --- D2-5_2 From --- SS5 To --- D2-5_2

Cable Description --------------- Cu. / XLPE / PVC / PVC

Load on Cable ( P ) ------------- = 275.00 KW 323.53 KVA - HP

Length of Cable ( L ) ----------- ( one way ) = 60.0 Mtrs. 245


Power Factor ( P.F.) ------------ = 85%
System Voltage ( V ) ---------- = 380 / 220 Volts
Supply Voltage to -------------- D2-5_2 = 380 Volts, 3 Ø, 60 Hz.

Therefore, Line Current - in Amps. ( I ) P × 1000


= [FORMULA]
SQRT(3) × V × P.F.

275.00 × 1000
=
1.732050808 × 380 × 0.85

= 491.55 Amps.

The total no. or set of cables required or preferred per phase ( n ) = 2


Therefore Net Current Passing Through the Cable ( Io = I / n ) = 245.78 Amps.

Checking for Current Carrying Capacity of the XLPE Multicore Cable, 0.6 / 1 kV --- ( Ref. Cat.: RIYADH CABLES )
For Cable Ampacity Req'd @ 125% of Line current = 307.2 Amps. ( Installed in Duct Bank )

For 150 mm Cable Ampacity (Iamp)


2
= 407.0 Amps. ( From Table 2 , Page 5 of Catalogue )

Derating Factors :
Temperature Factor ( ft ) ---------- XLPE = 0.87 ( From Table 10, Page 11 of Catalogue -for 45 ° C - Ambient)
Group Factor ( fg ) ------------------ = 0.92 ( From Table 1212
, , Page 14 & 15 of Catalogue )

Cable Spacing ( d ) ----------------- = cable diameter No. of Cables = 2 -- side by side

Cable to Wall ( = or > ) ----------- 200 mm. No. of Ground = 1 -- layer Laid on Ground

Therefore, Derating Factor ( fd ) = ft × fg = 0.87 × 0.92

( fd ) = 0.800
Cable Derated Current ( Ider ) = Pre-Selected Cable Ampacity × Derating Factor = Iamp × fd = 407.0 × 0.800

( Ider ) = 325.76 Amps.

The NEW Current Carrying Capacity of above Cable is Still Higher than the Cable Ampacity reqd. @ 125% -- Which suits the requirement

Verification / Cross Checking of Voltage Drop


Maximum Permissible Voltage Drop Desired ( VDp ) = 2.50 % (as required)

Pre-Selected Cable -- Derated Current Carrying Capacity ------- ( Ider ) = 325.76 Amps.

Length of Cable ------- ( L ) = 60.0 Mtrs. ( one way )

= 0.316 mV / A · Mtr. ( From Page 23 of Catalogue )


.
VDp × V × 1000 2.50 × 380 × 1000
Therefore, Applicable (VDap) = =
Ider × L × 100 325.76 × 60.0 × 100

= 0.486 mV / A · Mtr. .

From table on Page 23 of Catalogue, the Voltage Drop of the pre-selected -- 150 mm2 XLPE insulated 90 o
C multi core cable is equal to

0.316 mV / A · Mtr. --- Which is within the limit ( means < the requirement of 0.486 mV / A · Mtr. )

Therefore, Suitable Cable Size is 150 mm2

Hence, Recommended Cable Size is 2 nos. 4C x 150 mm2 + 150 mm2 E

ALTERNATIVE : 2 nos. 3C x 150 mm2 + 150 mm2 N + 150 mm2 E


The Actual Voltage Drop of the Recommended Cable = 1.63 % ≈ 373.82 V (WORKING VOLTAGE)

This software package will calculate the required cable size & voltage drop installed in free air or enclosed run & raceway, and display the amount of actual voltage, and the equivalent voltage drop in percentage of this amount.
The data used are constants based on an ambient temperature that the designer selects, ranging from 10 oC to 60 oC and group factor for different cable installation condition and formation requirement.
The size of cable may range from 1.5 mm2 to 500 mm2 in the industry standard increments. Distances must be entered in meter units, this length also must be the one way distance from the source to the load.
ENAJR-I ® (C) 2004-2005 RTCC - Riyadh, KSA
The author makes no warranty, either expressed or implied, including but not limited to any implied warranties of fitness for a particular purpose regarding the software, and makes the software available solely on an "as is" basis.
You accept full responsibility for the application of this software and the use of any information obtained from the software. This software is not intended to replace the need for a qualified person, versed in the requirements of any applicable local
and or national codes and regulations. This material is under constant development and subject to change without prior notice. If you have any comments or suggestions, please e-mail these to: eligio@rtcc.com.sa or eligioamaranto@yahoo.com

404429645.xls D2-5_2
of this amount.

404429645.xls D2-5_2
CABLE SIZE AND VOLTAGE DROP CALCULATION
PROJECT NO.: CSP # LOCATION: AREA : RM.NO.: DATE: 12/11/2018 16:51

Cable Tag No. --- D2-3_1 From --- SS5 To --- D2-3_1

Cable Description --------------- Cu. / XLPE / PVC / PVC

Load on Cable ( P ) ------------- = 275.00 KW 323.53 KVA - HP

Length of Cable ( L ) ----------- ( one way ) = 72.0 Mtrs. 245


Power Factor ( P.F.) ------------ = 85%
System Voltage ( V ) ---------- = 380 / 220 Volts
Supply Voltage to -------------- D2-3_1 = 380 Volts, 3 Ø, 60 Hz.

Therefore, Line Current - in Amps. ( I ) P × 1000


= [FORMULA]
SQRT(3) × V × P.F.

275.00 × 1000
=
1.732050808 × 380 × 0.85

= 491.55 Amps.

The total no. or set of cables required or preferred per phase ( n ) = 2


Therefore Net Current Passing Through the Cable ( Io = I / n ) = 245.78 Amps.

Checking for Current Carrying Capacity of the XLPE Multicore Cable, 0.6 / 1 kV --- ( Ref. Cat.: RIYADH CABLES )
For Cable Ampacity Req'd @ 125% of Line current = 307.2 Amps. ( Installed in Duct Bank )

For 150 mm Cable Ampacity (Iamp)


2
= 407.0 Amps. ( From Table 2 , Page 5 of Catalogue )

Derating Factors :
Temperature Factor ( ft ) ---------- XLPE = 0.87 ( From Table 10, Page 11 of Catalogue -for 45 ° C - Ambient)
Group Factor ( fg ) ------------------ = 0.92 ( From Table 1212
, , Page 14 & 15 of Catalogue )

Cable Spacing ( d ) ----------------- = cable diameter No. of Cables = 2 -- side by side

Cable to Wall ( = or > ) ----------- 200 mm. No. of Ground = 1 -- layer Laid on Ground

Therefore, Derating Factor ( fd ) = ft × fg = 0.87 × 0.92

( fd ) = 0.800
Cable Derated Current ( Ider ) = Pre-Selected Cable Ampacity × Derating Factor = Iamp × fd = 407.0 × 0.800

( Ider ) = 325.76 Amps.

The NEW Current Carrying Capacity of above Cable is Still Higher than the Cable Ampacity reqd. @ 125% -- Which suits the requirement

Verification / Cross Checking of Voltage Drop


Maximum Permissible Voltage Drop Desired ( VDp ) = 2.50 % (as required)

Pre-Selected Cable -- Derated Current Carrying Capacity ------- ( Ider ) = 325.76 Amps.

Length of Cable ------- ( L ) = 72.0 Mtrs. ( one way )

= 0.316 mV / A · Mtr. ( From Page 23 of Catalogue )


.
VDp × V × 1000 2.50 × 380 × 1000
Therefore, Applicable (VDap) = =
Ider × L × 100 325.76 × 72.0 × 100

= 0.405 mV / A · Mtr. .

From table on Page 23 of Catalogue, the Voltage Drop of the pre-selected -- 150 mm2 XLPE insulated 90 o
C multi core cable is equal to

0.316 mV / A · Mtr. --- Which is within the limit ( means < the requirement of 0.405 mV / A · Mtr. )

Therefore, Suitable Cable Size is 150 mm2

Hence, Recommended Cable Size is 2 nos. 4C x 150 mm2 + 150 mm2 E

ALTERNATIVE : 2 nos. 3C x 150 mm2 + 150 mm2 N + 150 mm2 E


The Actual Voltage Drop of the Recommended Cable = 1.95 % ≈ 372.59 V (WORKING VOLTAGE)

This software package will calculate the required cable size & voltage drop installed in free air or enclosed run & raceway, and display the amount of actual voltage, and the equivalent voltage drop in percentage of this amount.
The data used are constants based on an ambient temperature that the designer selects, ranging from 10 oC to 60 oC and group factor for different cable installation condition and formation requirement.
The size of cable may range from 1.5 mm2 to 500 mm2 in the industry standard increments. Distances must be entered in meter units, this length also must be the one way distance from the source to the load.
ENAJR-I ® (C) 2004-2005 RTCC - Riyadh, KSA
The author makes no warranty, either expressed or implied, including but not limited to any implied warranties of fitness for a particular purpose regarding the software, and makes the software available solely on an "as is" basis.
You accept full responsibility for the application of this software and the use of any information obtained from the software. This software is not intended to replace the need for a qualified person, versed in the requirements of any applicable local
and or national codes and regulations. This material is under constant development and subject to change without prior notice. If you have any comments or suggestions, please e-mail these to: eligio@rtcc.com.sa or eligioamaranto@yahoo.com

404429645.xls D2-3_1
of this amount.

404429645.xls D2-3_1
CABLE SIZE AND VOLTAGE DROP CALCULATION
PROJECT NO.: CSP # LOCATION: AREA : RM.NO.: DATE: 12/11/2018 16:51

Cable Tag No. --- D2-3_2 From --- SS5 To --- D2-3_2

Cable Description --------------- Cu. / XLPE / PVC / PVC

Load on Cable ( P ) ------------- = 275.00 KW 323.53 KVA - HP

Length of Cable ( L ) ----------- ( one way ) = 105.0 Mtrs. 245


Power Factor ( P.F.) ------------ = 85%
System Voltage ( V ) ---------- = 380 / 220 Volts
Supply Voltage to -------------- D2-3_2 = 380 Volts, 3 Ø, 60 Hz.

Therefore, Line Current - in Amps. ( I ) P × 1000


= [FORMULA]
SQRT(3) × V × P.F.

275.00 × 1000
=
1.732050808 × 380 × 0.85

= 491.55 Amps.

The total no. or set of cables required or preferred per phase ( n ) = 2


Therefore Net Current Passing Through the Cable ( Io = I / n ) = 245.78 Amps.

Checking for Current Carrying Capacity of the XLPE Multicore Cable, 0.6 / 1 kV --- ( Ref. Cat.: RIYADH CABLES )
For Cable Ampacity Req'd @ 125% of Line current = 307.2 Amps. ( Installed in Duct Bank )

For 150 mm Cable Ampacity (Iamp)


2
= 407.0 Amps. ( From Table 2 , Page 5 of Catalogue )

Derating Factors :
Temperature Factor ( ft ) ---------- XLPE = 0.87 ( From Table 10, Page 11 of Catalogue -for 45 ° C - Ambient)
Group Factor ( fg ) ------------------ = 0.92 ( From Table 1212
, , Page 14 & 15 of Catalogue )

Cable Spacing ( d ) ----------------- = cable diameter No. of Cables = 2 -- side by side

Cable to Wall ( = or > ) ----------- 200 mm. No. of Ground = 1 -- layer Laid on Ground

Therefore, Derating Factor ( fd ) = ft × fg = 0.87 × 0.92

( fd ) = 0.800
Cable Derated Current ( Ider ) = Pre-Selected Cable Ampacity × Derating Factor = Iamp × fd = 407.0 × 0.800

( Ider ) = 325.76 Amps.

The NEW Current Carrying Capacity of above Cable is Still Higher than the Cable Ampacity reqd. @ 125% -- Which suits the requirement

Verification / Cross Checking of Voltage Drop


Maximum Permissible Voltage Drop Desired ( VDp ) = 2.50 % (as required)

Pre-Selected Cable -- Derated Current Carrying Capacity ------- ( Ider ) = 325.76 Amps.

Length of Cable ------- ( L ) = 105.0 Mtrs. ( one way )

= 0.316 mV / A · Mtr. ( From Page 23 of Catalogue )


.
VDp × V × 1000 2.50 × 380 × 1000
Therefore, Applicable (VDap) = =
Ider × L × 100 325.76 × 105.0 × 100

= 0.278 mV / A · Mtr. .

From table on Page 23 of Catalogue, the Voltage Drop of the pre-selected -- 150 mm2 XLPE insulated 90 o
C multi core cable is equal to

0.316 mV / A · Mtr. --- ( which is higher than the requirement of 0.278 mV / A · Mtr. )

However, The Voltage Drop of 185 mm2 Cable is 0.273 mV / A · Mtr. --- Which is within the limit.

Therefore, Suitable Cable Size is 185 mm2

Hence, Recommended Cable Size is 2 nos. 4C x 185 mm2 + 185 mm2 E

ALTERNATIVE : 2 nos. 3C x 185 mm2 + 185 mm2 N + 185 mm2 E


The Actual Voltage Drop of the Recommended Cable = 2.46 % ≈ 370.66 V (WORKING VOLTAGE)

This software package will calculate the required cable size & voltage drop installed in free air or enclosed run & raceway, and display the amount of actual voltage, and the equivalent voltage drop in percentage of this amount.
The data used are constants based on an ambient temperature that the designer selects, ranging from 10 oC to 60 oC and group factor for different cable installation condition and formation requirement.
The size of cable may range from 1.5 mm2 to 500 mm2 in the industry standard increments. Distances must be entered in meter units, this length also must be the one way distance from the source to the load.
ENAJR-I ® (C) 2004-2005 RTCC - Riyadh, KSA
The author makes no warranty, either expressed or implied, including but not limited to any implied warranties of fitness for a particular purpose regarding the software, and makes the software available solely on an "as is" basis.
You accept full responsibility for the application of this software and the use of any information obtained from the software. This software is not intended to replace the need for a qualified person, versed in the requirements of any applicable local
and or national codes and regulations. This material is under constant development and subject to change without prior notice. If you have any comments or suggestions, please e-mail these to: eligio@rtcc.com.sa or eligioamaranto@yahoo.com

404429645.xls D2-3_2
of this amount.

404429645.xls D2-3_2