Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
3
2. Introduce a novel third harmonic calculation method to
Copper Cost ($/lb)
3
the input voltage unbalance effects [19], [20] have been
2.5
evaluated. Quantification of many of these parameters is not
found in present literature. Simulations and experimental
2 tests are used to verify the accuracy and effectiveness of the
analysis using a 75 hp “windmill” 18-pulse clean power ASD
1.5 system.
1
Overall Practical System Model
0.5
In this 18-pulse converter system, a 3-phase input to 9-phase
0 output autotransformer with 6 coils per phase is used to
1998 1999 2000 2001 2002 2003 2004 2005 2006 power a 9-phase AC to DC converter as shown in Figure 3.
Year The 3-phase input voltages feed through input line
impedances (La and Ra) and source inductance (Lsa). It is
Figure 2. Aluminum Cost Increase vs. Time [23] assumed that the 3-phase input impedances are balanced,
i.e., La = Lb = Lc, Ra = Rb = Rc and Lsa = Lsb = Lsc. The
9-phase AC output voltages are fed to a 9-phase rectifier
Most modern adjustable-speed drives (ASDs) use bridge comprising diodes (D1 – D18). The DC link voltage is
electrolytic capacitors to provide ride-through energy smoothed by DC link capacitor (C). The inverter IGBTs
storage capacity on the DC bus. They provide a low (SW11 – SW16) deliver 3-phase PWM voltage waveforms
impedance path for ripple currents generated by the rectifier with variable frequency and amplitude to the motor load.
and PWM inverter stages [14]. It is important to limit DC link
voltage ripple to prevent generation of pulsating torque in
the induction machine, which could produce undesirable
mechanical vibration and acoustic noise [15]. These aspects
will be analyzed to maintain high product performance
integrity. Both rectifier and inverter ripple currents
contribute to the capacitor temperature rise and life span.
1 2 3 4 5 6 7 8 9
Id IL
Figure 3. Overall Circuit Diagram of the “Windmill” 18-Pulse Clean Power Adjustable Speed Drive System
Basic Performance Features of 18-Pulse Converters Source of 3rd Harmonic Currents in 9-Phase Converter
The small amount of AC line input harmonic currents drawn The ideal current wave drawn from each of the nine trans-
by 9-phase, 18-pulse converters is well known and described former outputs is shown in Figure 5.
in various books and papers [13]. In a pioneering
application, a 3-phase to 9-phase autotransformer described
in [6] was used to supply power for a 500 hp AC to DC Idc
converter feeding a variable frequency drive. Since that
time, numerous alternative means of transformer design
wt
have been proposed and implemented. The practical
“windmill” method discussed here has found widespread 0
application. Typical system results are given. -Φ Φ
2 2
9-phase 18-pulse converters not only have low harmonic
distortion in the AC input current, but they also provide a
Figure 5. Basic Current Waveform Drawn by 9-Phase Converter
smoother, higher average value of DC output. Without some
small reduction in the amplitude of the 9-phase output
voltage, the DC voltage associated with 480V systems would Using Fourier analysis it can be shown that the output
be too high. current wave is described by the following expression:
Practical transformer designs address this by slightly i( t) = IDC ∑
4 sin (n ø ) cos (n t)
(4)
reducing the 9-phase output voltage. The “windmill” design πn 2
shown in Figure 4 is a particularly efficient configuration and
will be used to establish basic parameters. where n is any odd positive integer such as 1, 3, 5, 7 … and ø
= conduction period = 2π/9.
Unlike a 3-phase system in which line-to-line voltage is √ 3
times the line-to-neutral voltage, the 9-phase output voltage The total rms value of current in each transformer output
has several possibilities. The line-to-line voltage of most lead is 0.471 IDC. Recognition of this relationship is
interest is the largest one. For example, this is the voltage especially important if the transformer output leads are
between terminals such as 1 and 5. Its value is: V1-N 0° – fused to protect the rectifiers.
V1-N -160°. The resulting amplitude is 1.969 V1-N. When the
9-phase output voltage is rectified, the DC output voltage is Applying n = 3, we find that the rms value of the third
further increased because there is less DC ripple voltage. harmonic in the 9-phase load current is 0.26 IDC .
To prevent excessive DC output voltage, the 9-phase output Third harmonic currents in the transformer output leads are
voltage in the “windmill” connection is reduced to 0.879 of particular concern in the transformer design. This current
times the source line-to-neutral voltage. flows within the transformer windings, and the transformer
design must allow for it. In the “windmill” design three delta
The resulting DC output voltage parameters are summarized circuits provide paths for these currents.
below in terms of the source line-to-neutral voltage V1-N. For
comparison the same parameters are given for a standard The “Windmill” Connection
3-phase bridge rectifier.
Figure 6 shows the “windmill” topology. As in all 3-phase
(1) V DC , 3ø = 3 √ 6 V L-N = 2.34 V L-N transformers with delta connections, there must be an equal
π number of turns on each phase of the delta to prevent
circulating fundamental current. Turns are shown for the
(2) V DC , “windmill” = 18 √ 2 sin π •
sin60°
V = 2.44 V L-N A phase, phases B and C have identical turns.
π 9 sin80° L-N
For ensuing analyses, several assumptions are made,
(3) V DC, peak = 2.45 V L-N namely,
1. Magnetizing current is neglected.
The average DC output voltage of a 9-phase bridge rectifier
2. Coil leakage and resistance are neglected.
fed by the “windmill” transformer is observed to be about
4.2% higher than that of a 3-phase bridge. This somewhat 3. The sum of ampere-turns on each limb is assumed to
greater average DC voltage is especially useful for PWM equate to zero at all instants. As noted previously this is
inverter systems where it facilitates obtaining an AC output not true for all topologies, but is a reasonable,
voltage equal to the AC input voltage. The peak DC output conservative assumption for connections like those in
voltage is the same, as defined in Equation (3). the “windmill” that include direct delta paths.
4. The 3-wire power source is balanced in voltage.
5. The fundamental currents in each output phase are
shifted by 40°. Third harmonic currents are shifted by
three times this amount, namely, 120°.
This current flows in N6A (0.653 turns) and N2A (0.532 Other Topologies
turns). Distribution of the third harmonic currents is shown Figure 7 shows another 3-phase to 9-phase autotransformer
in Table 1; also the total rms current is given relative to IDC. connection. It is given here as another example to use the
The current id is about 10% of the DC load current and simple analysis method for defining third harmonic currents.
extraneous third harmonic flux is not an issue with these This and modified versions of the topology are further
designs. described in US patent 5,124,904 [6]. As in the “windmill”
design, the hidden delta path is not shown because there is
an obvious delta path to carry third harmonic current.
i30°
0.27
i3120° A 0.5077
i3-120°
Figure 7. Basic 18-Pulse Configuration Using a Delta with Stub
Windings 0.684
ib +i3-120°
Typical fractional turns are based on 1.0 turn to support voltage
from apex to virtual neutral. ib
i3-120° ib i3120°
As in the “windmill” analysis, assume the amplitude of the
third harmonic component of current in each output lead is
i3. Relative phase positions are shown in the figure.
Assuming a vertical reference vector position of 0°, the
fundamental output voltage V2 at terminal 2 is given by:
Hidden Delta
(9) V2 = (1 – 0.2730° + 0.5077 -90°) = 1-40°
C B
The total 3rd harmonic turns acting on any phase coil are
assumed to be zero, thus: ib
0.27 ( ia + i3 -120°) + 1.192 ia + 0.27 ( ia – i3 -120°) +
(10)
0.5077 i3120° – 0.5077 i3 -120° = 0 i3120°
From which we get, third harmonic ia = 0.238 i3 -90°. In the
upper 0.27 turns, the third harmonic of current is (ia + i3 Figure 8. Original Delta Connection with Long Side Moved to Connect
-120°), namely 1.212 i3 -114.36°. In the lower 0.27 turns, with Windings so as to Form a Polygon Connection
the third harmonic of current is (ia -i3 -120°), namely 1.212 Typical fractional turns are based on 1.0 turn to support voltage
i3 -65.64°. Each stub winding with 0.5077 turns carries third from apex to virtual neutral.
harmonic current of magnitude i3. Thus, for the transformer
in Figure 7, we obtain: The apparently harmless rearranging of one winding makes
little difference to the 9-phase output, but greatly impacts
VA3 = (1.192 0.238) + (2 0.27 1.212) + the paths for third harmonic current flow. But if the same
(11)
(2 0.5077 1) = 1.953 topology is used for the secondary of a double-wound
It is noted that the output voltage in the Figure 7 schematic transformer with primary connected in delta, as in [12], the
is somewhat greater than that in Figure 6. If a correction is primary winding provides a low impedance path for third
made to compare identical power loading, the VA3s of the harmonic currents.
schemes shown in Figures 6 and 7 are very similar. Both
topologies are effective and efficient.
For 480V systems, the topology of Figure 7 usually requires
an extender winding to reduce the DC output voltage by
about 11.4%. In contrast, the reduced voltage is an inherent
feature of the “windmill” topology.
General Design Considerations capacitor ripple current profiles of a 6-pulse ASD and the
“windmill” 18-pulse ASD at the same power level. The
In all practical transformer designs the actual currents are current ripple components of the 18-pulse system are
modified by the various winding-to-winding coupling factors greatly reduced, particularly in the low frequency range.
and coil winding resistance. As noted previously, computer
simulations of the “windmill” topology incorporate these From the time-series representation of the dc capacitor
factors. Calculated results in conjunction with 18-pulse ripple currents, the rms value of a particular ripple current
converters agree very satisfactorily with complete systems harmonic component can be calculated using Fourier
tests. transform functions of any numerical mathematical analysis
tool such as Matlab:
All phase-shifting autotransformers should include thermal
overload trips in each phase. These provide protection in the
Icaph =
|fft(Icaph)|
event of a partial loss of load, for example if any of the 18 (12)
√ 2 • N/2
converter devices become inoperative.
where N is the number of time series points in the ripple
Phase-shifting autotransformers can provide substantial size current time series. The total capacitor power loss is
and weight savings compared with double-wound designs. calculated using the capacitor ripple current harmonic
Typically, a 3-phase to 9-phase transformer for converter spectrum as:
operation requires only about 45% as much kVA as a double-
Nh
wound transformer. Also, it is more efficient. 2
(13) Ploss = ∑Icaph, n • ESR(fn)
n=1
Summary of 9-Phase Autotransformer Design Issues
where ESR (fn) is the value of the equivalent series resistance
Idealized performance factors of a 9-phase, 18-pulse at a particular frequency fn.
converter fed by a “windmill” transformer configuration are
defined. The value of the total rms ripple current can be determined
from the harmonic spectrum as:
A simplified analytical method is described that gives insight
into third harmonic circulating currents. If not adequately Nh
controlled these currents can create additional extraneous
losses. The method enables topologies to be selected that
offer high efficiency and good utilization of iron and copper.
(14) Icaph, rms =
The procedure has been found of considerable value in [hours] are calculated as follows [24]:
evaluating efficient phase-shifting autotransformer designs,
(15) Th = Ta + Ploss • Rth
such as the “windmill” connection.
85 – Th
Simulation and Experimental Evaluation (16) Lop = A • 2 c
harmonics has been made between the 6-pulse ASD system 150
and the “windmill” 18-pulse topology [21]. The operating Conditions: 6-Pulse 75 hp ASD with Lin = 525 uH
100 C = 2800 uF, Full Load
point parameters consist of La = 525uH, C = 2800uF, 75 hp
inverter driven induction machine load. The simulated input 50
current waveforms are depicted in Figure 14 for both steady 0
state and step load operating conditions. A typical 75 hp, -50
6-pulse ASD with 450uH line inductor has input current total
-100
harmonic distortion (THD) of ~33%, while the “windmill”
0.584 0.586 0.588 0.59 0.592 0.594 0.596 0.598 0.6
18-pulse has ~5% input current THD. The 18-pulse solution
Time (Sec)
is clearly more suitable for applications where meeting IEEE-
519 is required. 40
Conditions: 6-Pulse 75 hp ASD with Lin = 525 uH
Harmonics (A)
+ +
150 iqds iqdr
Bus Capacitor Current (A)
Conditions: W
ì i ndmill”18-Pulse 75 hp ASD with Lm
100 Vqds Vqdr
Lin = 525 uH, C = 2800 uF, Full Load
50
0 – –
-50
-100
Figure 11. Complex dq Equivalent Circuit of a Three-Phase Induction
0.584 0.586 0.588 0.59 0.592 0.594 0.596 0.598 0.6
Machine in a Rotating Reference Frame ( ).
Time (Sec)
40
Conditions: “Windmill”18-Pulse 75 hp ASD with The definitions of the complex variables include [22]:
Harmonics (A)
0
0 200 400 600 800 1000 1200 1400 1600 1800 2000
Frequency (Hz)
800
200 0
0.57 0.575 0.58 0.585 0.59 0.595 0.6 0.04 0.045 0.05 0.055 0.06 0.065 0.07 0.075 0.08 0.085 0.09
Time (Sec) Time (Sec)
Torque Spectrum (Nm)
20
Figure 13. Simulated Induction Machine Torque Profile of the 75 hp Figure 14. Simulated 75 hp 18-Pulse System Load Step Response
18-Pulse System Including Inverter SVPWM Effect
800
Dynamic Load Step Change Response DC Link Voltage (V) 600
As seen in Figure 3, the DC link voltage is supplied by the
400
uncontrolled rectifier bridge(s) (D1 – D18). It is important to
maintain the DC link voltage as steady as possible to prevent 200 Conditions: “Windmill” 18-Pulse ASD with Lin = 525 uH
any disturbance to the ASD inverter and load operation.
Figure 14 shows the effect of a step increase in load from 0
0.12 0.125 0.13 0.135 0.14 0.145 0.15
40A output to 80A. The DC link voltage drops from 665V to Time (Sec)
639V and reaches a new steady state value of 655V within
one cycle of 60 Hz. This rapid response decreases capacitor
Input Currents (A)
Conclusions
75 hp ASD
In this paper, an improved 3-phase to 9-phase “windmill”
18-pulse clean power ASD system is presented. A novel third
harmonic circulating current calculation method is introduced
and used to investigate different topologies. A system
evaluation demonstrates the steady state and dynamic
performance of a complete rectifier and PWM motor drive. It
is shown through modeling, analysis, simulation, and
experimentation that the “windmill” topology improves the
input current THD, increases the DC link capacitor life span,
reduces the induction machine torque ripple, and provides
good step load response. Further, the arrangement performs
well under moderate input voltage unbalance conditions
encountered in practical power distribution systems. The
state-of-the-art simulation is built on the complete system
consisting of the utility source, “windmill” 9-phase auto-
Input “Windmill” transformer, 9-phase rectifier bridge, DC link capacitor,
Inductors 18-Pulse inverter with space vector pulse width modulation (SVPWM)
Autotransformer and induction machine with load. A complete 75 hp ASD
system has been manufactured and used to verify the
accuracy and effectiveness of the analysis. Predictions from
the analysis compare favorably with experimental results. The
thorough evaluation presented in this paper will be useful to
guide the 18-pulse ASD selection in applications where
excellent input power quality, long life, and reliable ASD load
performance are essential.
B
1.00 V/Div 2.1 msec/Div 30.0 A/Div
Dranetz 8000 Dranetz Model 8000 Dec-05-05 17:23:02
Harmonics:CH A Ref 80.12 A. 60.0Hz
%Fund Ithd 5.949 %
3.33
2.67
2.00
1.33
0.57
0.00
5 10 15 20 25 30 35 40 45 50
References
[1] “IEEE recommended practice and requirements for harmonic control in
electrical power systems,” IEEE Standard 519, 1992.
[2] R. G. Ellis, “Harmonic analysis of industrial power system,” IEEE Trans. on
Industry Applications, vol. 32, no. 2, pp. 417 – 421, Mar./Apr. 1996.
[3] M. F. McGranaghan, and D. R. Mueller, “Designing harmonic filters for
adjustable-speed drives to comply with IEEE-519 harmonic limits,” IEEE
Trans. on Industry Applications, vol. 35, no. 2, pp. 312 – 318, Mar./Apr. 1999.
[4] D. A. Paice, “Multi-pulse converter system,” U.S. Patent #4,876,634,
Oct. 1989.
[5] J. Traver et al, “Multiphase low harmonic distortion transformer,” U.S. Patent
#4,779,181, Oct. 1988.
[6] D. A. Paice, “Optimized 18-pulse type ac/dc, or dc/ac, converter system,”
U.S. Patent #5,124,904, Jun. 1992.
[7] D. A. Paice, “Symmetrical, phase-shifting, fork-transformer,” U.S. Patent
#5,455,759, Oct. 1995.
[8] P. Hammond, “Autotransformer,” U.S. Patent #5,619,407, Apr. 1997.
[9] D. A. Paice, “Wye connected 3-phase to 9-phase auto-transformer with
reduced winding currents,” U.S. Patent #6,191,968B1, Feb. 2001.
[10] D. Zhou, G. L. Skibinski, and N. Guskov, “Nine phase transformer,”
U.S. Patent #6,249,443, Jun. 2001.
[11] D. Zhou, G. L. Skibinski, and N. Guskov, “Nine phase transformer,”
U.S. Patent #6,335,872, Jan. 2002.
[12] G. L. Skibinski, N. Guskov, and D. Zhou, “Cost effective multiple pulse
transformer solutions for harmonic mitigation in ac drives,” IEEE 38th IAS
Conference, vol. 3, pp. 1488 – 1497, Oct. 2003.
[13] D. A. Paice, “Clean Power Electronic Converters: Engineering Design and
Application Guides,” Paice & Associates, Inc., 2005.
[14] D. Rendusara, E. Cingelci, P. N. Enjeti, and D. C. Lee, “An evaluation of the
DC-link capacitor heating in adjustable speed drive systems with different
utility interface options,” Applied Power Electronics Conference and
Exposition (APEC), vol. 2, pp. 781 – 787, 1999.
[15] A. Nystrom, J. Hylander, and K. Thorborg, “Harmonic currents and torque
pulsations with pulse width modulation methods in AC motor drives,” 3rd
International Conference on Power Electronics and Adjustable-Speed Drives,
pp: 378 – 381, July 1988.
[16] D. A. Paice, “Simplified Wye connected 3-phase to 9-phase auto-
transformer,” U.S. Patent #6,525,951B1, Feb. 2003.
[17] K. Lee, T. M. Jahns, G. Venkataramanan, and W. E. Berkopec, “DC bus
electrolytic capacitor stress in adjustable-speed drives under input voltage
unbalance and sag conditions,” 39th IEEE Industry Applications Society
Annual Meeting (IAS), vol. 4, pp. 2560 – 2567, Oct. 2004.
[18] S. G. Parler, Jr., “Deriving life multipliers for electrolytic capacitors,” IEEE
Power Electronics Society Newsletter 11, 1st Quarter. 2004.
[19] M.H.J. Bollen, “Understanding Power Quality Problems – Voltages and
Interruptions,” IEEE Press, 1999.
[20] L. Wei, N. Guskov, R. A. Lukaszewski and G. L. Skibinski, “Mitigation of
current harmonics for multi-pulse diode front end rectifier systems,” IEEE
40th IAS Conference, vol. 1, pp. 129 – 137, Oct. 2005.
[21] D. A. Paice, “Power Electronic Converter Harmonics: Multipulse Methods for
Clean Power,” IEEE Press, 1996.
[22] D. W. Novotny, T. A. Lipo, “Vector Control and Dynamics of AC Drives,”
Oxford University Press Inc., New York, 1998.
[23] Web site: http://www.lme.co.uk/.
[24] “Electrolytic capacitor catalog 2003, North America,” Evox Rifa, 2003.
[25] J. Shaefer, “Rectifier Circuits: Theory and Design,” New York: Wiley,
1965-Interscience.
[26] Westinghouse Electrical Transmission and Distribution Reference Book,
4th edition, 1964.