Calculation Formula

Heat Rejected (kW)


Cooling Tower 1 HR = CWRF1 (L/s) x 4.19 (kJ/kg oC) x [CWTR1 - CWTS1] ( oC)
Cooling Tower 2 HR = CWRF2 (L/s) x 4.19 (kJ/kg oC) x [CWTR2 - CWTS2] ( oC)
Cooling Tower 3 HR = CWRF3 (L/s) x 4.19 (kJ/kg oC) x [CWTR3 - CWTS3] ( oC)

Total Heat Rejected (kW)


= Cooling Tower 1 HR + Cooling Tower 2 HR + Cooling Tower 3 HR
= [ CWRF1 x 4.19 x (CWTR1 - CWTS1) ] + [ CWRF2 x 4.19 x (CWTR2 - CWTS2) ] + [ CWRF3 x 4.19 x (CWTR3 - CWTS3) ]

Cooling Load (kW)


Chiller 1 CL = CHWRF1 (L/s) x 4.19 (kJ/kg oC) x [CHWTR1 - CHWTS1] ( oC)
Chiller 2 CL = CHWRF2 (L/s) x 4.19 (kJ/kg oC) x [CHWTR2 - CHWTS2] ( oC)
Chiller 3 CL = CHWRF3 (L/s) x 4.19 (kJ/kg oC) x [CHWTR3 - CHWTS3] ( oC)
Chiller 4 CL = CHWRF4 (L/s) x 4.19 (kJ/kg oC) x [CHWTR4 - CHWTS4] ( oC)

Total Cooling Load (kW)


= Chiller 1 CL + Chiller 2 CL + Chiller 3 CL + Chiller 4 CL
= [CHWRF1 x 4.19 x (CHWTR1 - CHWTS1)] + [CHWRF2 x 4.19 x (CHWTR2 - CHWTS2)] + [CHWRF3 x 4.19 x (CHWTR3 - CHWTS3)]
+ [CHWRF4 x 4.19 x (CHWTR4 - CHWTS4)]

Total Cooling Load (RT)


= Total Cooling Load (kW)
3.517

Power Consumption by component (kW)


Chillers Power = PM (Chillers_kW)
Chilled Water Pumps Power = PM (CHWPs_kW)
Condenser Water Pumps Power = PM (CWPs_kW)
Cooling Towers Power = PM (CTs_kW)
Heat Exchamger Pumps Power = PM (HXP35s_kW) + PM (HXP11s_kW)

Total Power Consumption (kW)


= Chillers Power + Chilled Water Pumps Power + Condenser Water Pumps Power + Cooling Towers Power + Heat Exchanger Pumps Power
= PM (Chillers_kW) + PM (CHWPs_kW) + PM (CWPs_kW) + PM (CTs_kW) + [PM (HXP35s_kW) + PM (HXP11s_kW)]

Total System Efficiency (kW/RT)


= Total Power Consumption (kW)
Total Cooling Load (RT)
≤ 0.66 kWRT

Component Efficiency (kW/RT)


Chiller Eff = Chillers Power (kW)
Total Cooling Load (RT)

CHWP Eff = CHWPs Power (kW) + HXPs Power (kW)


Total Cooling Load (RT)

CWP Eff = CWPs Power (kW)


Total Cooling Load (RT)

CT Eff = CTs Power (kW)


Total Cooling Load (RT)

Percent Heat Balance


% HB = [Total Cooling Load (kW) + Chillers Power (kW)] - Total Heat Rejected (kW) x 100%
≤ 5%
Total Heat Rejected (kW)

Raw Data Required from the Logging System


7 days @ 1 minute Interval
- dd/mm/yyyy hh:mm Date & Time (1 Parameters)
- CHWRF1 (L/s) - CHWTS1 (oC) - CHWTR1 (oC) Chilled Water (Flow, Suply and Return Temp) For Each Chiller
- CHWRF2 (L/s) - CHWTS2 (oC) - CHWTR2 (oC) (12 Parameters)
o
- CHWRF3 (L/s) - CHWTS3 ( C) - CHWTR3 (oC)
- CHWRF4 (L/s) - CHWTS4 (oC) - CHWTR4 (oC)

- CWRF1 (L/s) - CWTS1 (oC) - CWTR1 (oC) Condenser Water (Flow, Suply and Return Temp) For Each Cooling Tower
- CWRF2 (L/s) - CWTS2 (oC) - CWTR2 (oC) (9 Parameters)
- CWRF3 (L/s) - CWTS3 (oC) - CWTR3 (oC)

- PM (Chillers_kW) Power for Each Components


- PM (CHWPs_kW) (6 Parameters)
- PM (CWPs_kW)
- PM (CTs_kW)
- PM (HXP35s_kW)
- PM (HXP11s_kW)