Sei sulla pagina 1di 59

Recognized as M cS7.

99-1990
American National Standard (ANSI) (Revision of
ANSIACEE C37.99-1980)

IEEE Guide for the Protection of


Shunt Capacitor Banks

Sponsor

Approved September 28,1990


IEEzstandardSBoard
Approved February 26,1991
American National Standards Institute

Abetrack IEEE C37.99-1990, IEEE Guide for the Protection of Shunt Capacitor Banks, assists in the
effective application of relays and other devices for the protection of shunt capacitors used in
substations. It covers the protective considerations, along with recommended and alternate
methods of protection for the most commonly used capacitor bank configurations. Capacitor bank
design trade-offs are also discussed. This guide covers protection of filter tanks and very large
EHV capacitor banks, but does not include a discussion of pole-mounted capacitor banks on
distribution circuits or application of capacitors connected to rotating apparatus.
Keywords: Bank connections, bus voltage, capacitor units, delta-connected banks, equipment
considerations, protection of banks, Y-banks, relaying methods.

The Institute of Electrical and Electronics Engineers, Inc.


346 Eaat 47th Street, New York,NY 10017-2394, USA
Q 1991 by the Institute of Electrical and Electronics Engineers, Inc.
All righb reserved. Published 1991
P M t d in the United States of America
ISBN 1-55937471-8
Library of Congress Number 91-066206
No part of this publication may be reproduced in any form,
in an electronic retrieval system or otherwise,
without the prior written permission of the publisher.
I I

Authorized licensed use limited to: CHILECTRA. Downloaded on August 05,2010 at 21:09:19 UTC from IEEE Xplore. Restrictions apply.
IEEE Standards documents are developed within the Technical
Committees of the IEEE Societies and the Standards Coordinating
Committees of the IEEE Standards Board. Members of the committees
serve voluntarily and without compensation. They are not necessar-
ily members of the Institute. The standards developed within IEEE
represent a consensus of the broad expertise on the subject within the
Institute as well as those activities outside of IEEE that have
expressed an interest in participating in the development of the
standard.
Use of an IEEE Standard is wholly voluntary. The existence of an
IEEE Standard does not imply that there are no other ways to produce,
test, measure, purchase, market, or provide other goods and services
related to the scope of the IEEE Standard. Furthermore, the viewpoint
expressed at the time a standard is approved and issued is subject to
change brought about through developments in the state of the art and
comments received from users of the standard. Every IEEE Standard
is subjected to review at least every five years for revision or r e a i r -
mation. When a document is more than five years old and has not
been reaffirmed, it is reasonable to conclude that its contents, al-
though still of some value, do not wholly reflect the present state of the
art. Users are cautioned to check to determine that they have the latest
edition of any IEEE Standard.
Comments for revision of IEEE Standards are welcome from any
interested party, regardless of membership affiliation with IEEE.
Suggestions for changes in documents should be in the form of a pro-
posed change of text, together with appropriate supporting comments.
Interpretations: Occasionally questions may arise regarding the
meaning of portions of standards a s they relate to specific applica-
tions. When the need for interpretations is brought to the attention of
IEEE, the Institute will initiate action to prepare appropriate re-
sponses. Since IEEE Standards represent a consensus of all con-
cerned interests, it is important to ensure that any interpretation has
also received the concurrence of a balance of interests. For this reason
IEEE and the members of its technical committees are not able to
provide an instant response to interpretation requests except in those
cases where the matter has previously received formal consideration.
Comments on standards and requests for interpretations should be
addressed to:
Secretary, IEEE Standards Board
445 Hoes Lane
P.O.Box 1331
Piscataway, N J 08855-1331
USA

IEEE Standards documents are adopted by the Institute of Electrical


and Electronics Engineers without regard to whether their adoption
may involve patents on articles, materials, or processes. Such adop-
tion does not assume any liability t o any patent owner, nor does it
assume any obligation whatever to parties adopting the standards
documents.

Authorized licensed use limited to: CHILECTRA. Downloaded on August 05,2010 at 21:09:19 UTC from IEEE Xplore. Restrictions apply.
Foreword

(This Foreword is not a part of IEEE (37.99-1990,IEEE Guide for the Protection of Shunt Capacitor Banks).
This revision of ANSI/IEEE C37.99-1980incorporates a number of additions and changes. Some of the
more significant changes were made in the sections dealing with the protection of very large EHV
capacitor banks and HVDC filter banks. Other changes were made to bring this guide up-to-date and
more in line with present-day requirements.
This guide was revised by the Shunt Capacitor Bank Protection Guide Revision Working Group of the
Substation Protection Subcommittee of the Power System Relaying Committee of the IEEE Power Engi-
neering Society. The working group membership at the time of completion of this revision was as follows:

C . J. Cook, Chair
H. N. Banerjee J. S. Komisarek G. C. Parr
A. A. Bunese W. C. Kotheimer L. J. Schulze
S. P. Conrad R. W. Ohnesorge W. M. Strang
L. L. Dvorak T. E. Wiedman

At the time this guide was approved, the Substation Protection Subcommittee membership was as
follows:

J. E. Stephens, Chair R. W.Dempsey, Vice Chair/ssCreta?y


J. K. Akamine L. L. Dvorak J. D. Huddleston, I11
E. A. Baumgartner S. E. Grier G. C. Parr
J. J. Bonk R. W. Haas L. J. Schulze
S. P. Conrad R. E. Hart J. Walton
C. J. Cook T. E. Wiedman

At the time the IEEE Power Systems Relaying Committee balloted and approved this guide, it had the
following membership:

J. R. Boyle, Chair J. A. Zulaski, Vice Chair


A. T.Giuliante, Secretmy
J. C. Akamine W. E. Feero R. W. Ohnesorge
J. C. Appleyard R. J. Fernandez G. C. Parr
R. F. Arehart S. E. Grier A. G. Phadke
H. N. Baqjeree C. H. Griffin' A. C. Pierce
C. W. Barnett E. A. Guro J. M. Postforoosh
E. A. Baumgartner R. W. Haas G. D. Rockefeller
R. W. Beckwith R. E. Hart M. S. Sachdev
B. Bozoki R. W. Hirtler E. T. Sage
J. A. Brlght J. W. Hohn D. E. Sanford
A. A. Bunese J. D. Huddleston, 111 L. Scharf
H. J. Calhoun J. W. Ingleson L. J. Schulze
J. W. Chadwick, Jr. R. H. Jones H. S. Smith
D. M. Clark E. W. Kahtein J. E. Stephens
S. P. Conrad T. L. Kaschak W. M. Strang
C. J. Cook K. J. Khunkhun A. Sweetana
A. N. Darlington J. S. Komisarek F. Y. Tajaddodi
D. C. Dawson W. C. Kotheimer R. P. Taylor
R. W. Dempsey J. R. Latham J. S. Thorp
H. Disante J. R. Linders J. R. Turley
P. R. Drum W. J. Marsh E. A. Udren
L. L. Dvorak R. J. Moran V. Varneckas
W. A. Elmore C. J. Mozina D.R. Volzka
J. T. Emery T. J. Murray C. L. Wagner
E. J. Emmerling K. K. Mustaphi J. Walton
M. K. Enns G. R. Nail T. E. Wiedman
J. Ezstergalyos S. L. Nilsson S. E. Zocholl

'Past Chair

Authorized licensed use limited to: CHILECTRA. Downloaded on August 05,2010 at 21:09:19 UTC from IEEE Xplore. Restrictions apply.
Contents
SECTION PAGE

1. Introduction ........................................................................... 7
2 References .............................................................................. 7
2.1 Standards References ............................................................... 7
2.2 Related References .................................................................. 7
3. Basic Considerations .................................................................... 8
3.1 Capacitor Unit Ratings .............................................................. 8
3.2 Arrangement of Capacitor Units ...................................................... 8
3.3 capacitor Bank Design .............................................................. 9
3.4 Overvoltage on Remaining Capacitor Units ............................................ 11
4. Bank Connections ...................................................................... 11
4.1 Delta-Connected Banks .............................................................. 12
4.2 Grounded Y-Connected Banks ........................................................ 12
4.2.1 One Series Group Per Phase .................................................... 13
4.2.2 Multiple Series Groups Per Phase -Single Y ...................................... 13
4.2.3 Multiple Series Groups Per Phase-Double Y ..................................... 13
4.3 Ungrounded Y-Connected Banks ..................................................... 13
4.3.1 One Series Group Per Phase ..................................................... 13
4.3.2 Multiple Series Groups Per Phase-Single Y ...................................... 13
4.3.3 Multiple Series Groups Per Phase-Double .....................................
Y 13
5. Other Considerations ................................................................... 13
5.1 Parallel Banks ...................................................................... 13
5.2 Neutral Grounding .................................................................. 15
6. Capacitor Bank Protection .............................................................. 15
6.1 Capacitor-Unit Fusing (To Prevent Case Rupture) ..................................... 16
6.2 Bank Overcurrent Protection ......................................................... 17
6.3 Protection for Rack Fault (Arc-Over Within the Capacitor Rack) ........................ 18
6.4 Bank Overvoltage Protection ......................................................... 22
7. Unbalance Relaying Methods ............................................................. 26
7.1 Introduction ........................................................................ 26
7.2 Inherent Unbalance and Other Errors ................................................ 26
7.3 General Unbalance Relay Considerations .............................................. 28
7.4 Neutral Current Unbalance Protection Method, Grounded-Y Bank ....................... 30
7.5 Summation of Intermediate Tap Point Voltages Method, Grounded-Y Bank ............... 32
7.6 Neutral Voltage Unbalance Protection Method, Ungrounded-Y Bank ..................... 33
7.7 Double-Y Unbalance Protection Method ............................................... 35
7.8 Neutral Unbalance Protection Method with Compensation for Inherent Unbalance ....... 37
7.9 Voltage Differential Protection Method, Grounded-Y Bank .............................. 39
8. Protection of Very Large E W Capacitor Banks ............................................ 39
8.1 Very Large EHV Capacitor Banks ..................................................... 39
\
8.2 Voltage-Differential Unbalance Protection of Very Large Grounded-Y Connected
Capacitor Banks .................................................................... 39
8.2.1 Backup Capacitor Bank Unbalance Protection .................................... 40
8.2.2 Alarm Levels .................................................................. 40
8.3 Bank Overcurrent Protection ......................................................... 40
8.4 System Overvoltage Protection ....................................................... 40
8.5 Loss of Bus Voltage ................................................................. 40
8.6 Capacitor Bank Breaker-Failure Protection ............................................ 41

Authorized licensed use limited to: CHILECTRA. Downloaded on August 05,2010 at 21:09:19 UTC from IEEE Xplore. Restrictions apply.
FIGURES PAGE

Fig 12 Special Protection Schemes for Very Large EHV Capacitor Banks.. . . . .. . . . . . . . . . . . . . . . . . 23
Fig 13 Typical Static VAR Generator Schematic . . . . . . . . . . . . . .... ..... . . . . .. . . . . . . . . . . . .. . . .. . 24
Fig 14 Opening the Circuit to a Single-phase Capacitor in One Step.. . . . .. . .. . . . . . .. . . . . . . . . .. . 24
Fig 15 Varistor V/I Curve Showing Voltage Turn-Up . . . .. . . . . ... ... .. . . . . . . . . . . . .. . . . . . .. . . . . . 25
Fig 16 One Line Diagram of 230 kV Station . . . . . . . . . . . . . . ... ... .. . .. . . . . . . . . . . . .. . . . . . .. . .. . . 25
Fig 17 Single Point Grounded Bank with Single-BushingV.T. . . . . . . . . . . .. . . . . .. . . . . . . . . . , .. .. . . 25
. .
Fig 18 Single Point Grounded Bank with Two-Bushing V,T. .. . . . . . . . . .. . . . . . . . . . . . .. . . , .. . . . . 26
Fig 19 Grounded Y-Connected Capacitor Bank Percentage of Allowable Inherent Neutral
Current Unbalance for Positive Detection of First Blown Fuse Versus Number of
Capacitor Units in Parallel per Group and Number of Series Groups . .. . . . .. .. . . . .. . . . . . 27
Fig 20 Ungrounded Y-Connected Capacitor Bank Percentage of Allowable Neutral
Voltage for Positive Detection of First Blown Fuse Versus Number of Capacitor
Units in Parallel per Group of Number of Series Groups . . . . . . . . . .. . . . . . . . . . . . . . . . .. . . . . 28
Fig 21 Ungrounded Double Y-Connected Capacitor Bank Percentage of Allowable
Inherent Neutral Current Unbalance for Positive Detection of First Blown Fuse
Versus Number of Capacitor Units in Parallel per Group and Number of Groups
in Series . . . . . . . .. . . . . . . . . ....... .. . . . . . . . . . . . . . . . . .. . . . . . . .. .. . . . . .. .. . . . . . . . . . . . .. 29
Fig 22 Grounded Y-Connected or Grounded Double Y-Connected Capacitor Banks:
Neutral Current (also change in intermediate tap-point voltage) Versus
Percentage of Capacitor Units Removed from Series Group .. . .. . . .. . . . . . . . . .. . .. . . .. . .. 31
Fig 23 Grounded Y-Connected, A, or Grounded Double Y-Connected Capacitor Bank
Voltage on Remaining Capacitor Units in Series Group Versus Percentage of
. . .
Capacitor Units Removed from Series Group . .. . . . . . .. . . . .. . . . . . . . . . . . . . . . .. . . . .. . 32 .
Fig 24 Ungrounded Y-Connected or Ungrounded Double Y-Connected (neutrals isolated)
Capacitor Bank Voltage Between Capacitor Bank Neutral and Ground Versus
Percentage of Capacitor Units Removed from Series Group . . . . .. . . . . . . . . . . . . . . . . .. .. . . . 34
Fig 25 Ungrounded Y-Connected or Ungrounded Double Y-Connected (neutrals isolated)
Capacitor Bank Voltage on Remaining Capacitor Units in Series Group Versus
Percentage of Capacitor Units Removed from Series Group . . . . . . . .. . . . . .. . . . . .. .. . .. . . 35 .
Flg 26 Ungrounded Double Y-Connected (neutrals tied together) Capacitor Bank
Neutral Current Versus Percentage of Capacitor Units Removed From Series Group . . .. . 36 .
Flg 27 Ungrounded Double Y-Connected (neutrals tied together) Capacitor Bank Voltage
Between Capacitor Bank Neutral and Ground Versus Percentage of Capacitor
Units Removed from Series Group.. . . . . . . . . . . . . . . . . . .. . .. . . . . . . . . . . . . . . .. . . . . . . . . . . . . 37
Fig 28 Ungrounded Double Y-Connected (neutrals tied together) Capacitor Bank
Voltage on Remaining Capacitor Units in Series Group Versus Percentage of
Capacitor Units in Series Group.. . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . .. . . . .. . . . . . .. . .. . 38
TABLES
Table 1 Y-Connected Capacitor Banks, Number of Series Groups .. . . . . . . . . . . . .. , . . . . .. . . . . . .. . 11
Table 2 Minimum Recommended Number of Units in Parallel per Series Group to Limit
Voltage on Remaining Units to 1 lo%,with One Unit Removed. .. . .. . . . . . . . . .. . . . . . ... .. 11
Table 3 Summary of Shunt Capacitor Protection Methods . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . .. . .. 16
Table 4 Limits of Short-Time Power Frequency Overvoltage at Subzero Temperatures . . .. . . . .. . . 22
APPENDIXES
Appendix A .
Symbol Definitions ..... .. . . . . . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . .. .. . .. .. .. . . . . 53
Appendix B Equations . . .. . . .. ..... .. . . . . . . .. . .. . . . . . . . . . . . . . , . . . . . . . . . . . . . .. .. . . . .. .. . . . . 55
Appendix C Equations for Effect of Inherent Unbalances.. . . . . . .. . . . . . .. . . . . . . . . . . . .. . . . .. . . . 57
Appendix D Inrush Current and Frequency for Switching Capacitor Banks . . . . . .. .. . .. .. .. . . . . 59
APPENDIX TABLES
Table B1 60 Hz Fault Current and Voltage with One Unit Shorted . . . . . .. . .. . .. . . . . . .. . . . . . .. . . 56
.
Table C1 Effect of Inherent Unbalance on Displacement Signal.. .. . .. . . . . . . .. . . . . , .. . . .. , .. . . 57

Authorized licensed use limited to: CHILECTRA. Downloaded on August 05,2010 at 21:09:19 UTC from IEEE Xplore. Restrictions apply.
SECTION PAGE
9. Protection of Filter Banks ............................................................... 41
9.1 Static VAR Control Filters ........................................................... 41
9.2 HVDC Converter Station Filters ...................................................... 42
10. Capacitor Bank Equipment Considerations ............................................... 43
10.1 Capacitor Bank Switching Devices ................................................... 43
10.2 Inrush Control Devices ............................................................. 44
10.3 Surge Arresters .................................................................... 45
10.4 Voltage Sensing Devices ............................................................ 45
10.5 Current Sensing Devices ............................................................ 45
10.6 Surge Protection ................................................................... 45
10.6.1 Surge Protection for Current Transformers .................................... 46
10.6.2 Surge Protection of Voltage Transformers, Capacitor-Coupled Voltage
Transformers and Resistance Potential Devices ................................. 48
10.6.3 Surge Protection of Relay Systems Associated with Capacitor Banks .............. 48
10.7 Control Cables ..................................................................... 49
11. System Considerations .................................................................. 49
11.1 Resonance ........................................................................ 49
11.2 Harmonics ........................................................................ 49
11.3 Telephone Interference ............................................................. 49
12. Practices ............................................................................... 49
12.1 Preparation for Initial Energizing .................................................... 49
12.1.1 Visual Inspection ............................................................ 50
12.1.2 Testing of Individual Capacitor Units .......................................... 50
12.1.3 Testing of Relay Protection ................................................... 50
12.1.4 Sensing Devices .............................................................. 50
12.1.5 Operational Test ............................................................ 50
12.1.6 Special Recording ........................................................... 50
12.1.7 Initial Energization .......................................................... 50
12.1.8 Additional Tests ............................................................. 50
12.2 Response to Alarm or Lockout ...................................................... 50
12.2.1 Inspection (after de-energizing bank) .......................................... 50
12.2.2 Capacitor Unit Removal and Replacement ..................................... 51
12.2.3 Returning Bank to Service After Lockout ...................................... 51
12.2.4 Servicing Bank Following Alarm Condition ..................................... 51
13. Bibliography ........................................................................... 51

FIGURES

Fig1 Y-Connected Capacitor Bank Showing Arrangement of Capacitor Units and


Fusing Options ..................................................................... 10
Fig2 Basic Capacitor Bank Connections ................................................... 12
Fig3 Methods of Neutral Grounding ....................................................... 14
Fig4 Capacitor Bank Overcurrent Protection ............................................... 17
Fig5 Shunt Capacitor Bank Protection Methods. Single Y-Connected Banks ................... 19
Fig6 Shunt Capacitor Bank Protection Methods. Double Y-Connected Banks .................. 20
Fig7 Neutral Voltage Unbalance Protection Method. Ungrounded Y-Connected Capacitor
Bank with Compensation for Inherent Unbalance ...................................... 21
Figs Neutral Voltage Unbalance Protection Method. Ungrounded Double Y-Connected
Capacitor Bank (Neutrals Isolated) with Compensation for Inherent Unbalance .......... 21
Fig9 Voltage Difference Protection Methods. Grounded Y-Connected Capacitor Banks ......... 21
Fig 10 Midrack Phase-to-Phase Arcing Fault ................................................. 22
Fig 11 Summation of Intermediate Tap-Point Voltage Protection Method ....................... 22

Authorized licensed use limited to: CHILECTRA. Downloaded on August 05,2010 at 21:09:19 UTC from IEEE Xplore. Restrictions apply.
IEEE Guide for the Protection of
Shunt Capacitor Banks

1. Introduction [5] IEEE C37.04-1979 (R 1988), IEEE Standard


Rating Structure for AC High-Voltage Circuit
This guide has been prepared to assist in the Breakers Rated on a Symmetrical Current Basis
effective application of relays and other devices (ANSI).
for the protection of shunt capacitors used in
[6] IEEE C37.90-1989, IEEE Standard for Relays
substations. It covers the protective considera-
and Relay Systems Associated with Electric Power
tions, along with recommended and alternate
Apparatus (ANSI).
methods of protection for the most commonly
used capacitor bank configurations. Capacitor [7] NEMA CPI-1976, Shunt Capacitors?
bank design trade-offs are also discussed since
bank design influences protection. This guide 2.2 Related References
covers protection of filter banks and very large [8] Abdulrahim, M. J., Anderson, P. M., and
EHV capacitor banks. This guide does not include Fouad, A. A. “Inrush Currents in a Switched
a discussion of pole-mounted capacitor banks on Parallel-Capacitor Bank,”IEEE Gbqfwm Paper,
distribution circuits or application of capacitors slCP 66-101, New York, NY.
connected to rotating apparatus.
[9] Cooper, J. R. and Zulaski, J. A. “Improved
Protection System Increases Capacitor Bank Util-
2. References ization,” presented at the Pennsylvania Electric
Association Relay Committee Meeting, Oct 27,
2.1 Standards References. This guide may be 1972, Hagerstown, MD.
used in conjunction with the following publica-
[ 101 Davis, W. L. and Brinker, H. F. “Static Var
tions:
System Control Line Voltage,” Electrical World,
[ l ] ANSI C37.06-1987, Preferred Ratings and Jul. 15, 1978, pp. 52-54.
Related Required Capabilities for AC High-Voltage
[ l l ] Emmerling, E. J. and Zulaski, J. A. “Power
Circuit Breakers Rated on a Symmetrical Current
Factor Capacitance Banks Guarded By Special
Basis.’
Filter Scheme,” SpsCfying Engineer, Oct. 1981,
[2] IEEE Std 18-1980, IEEE Standard for Shunt pp. 68-82.
Power Capacitors (ANSI).2
[12] Greenwood, A N., Kurtz, D. R., and Sofianek,
[3] IEEE Std 469-1988, IEEE Recommended J. C. “A Guide to the Application of Vacuum Cir-
Practice for Voice-Frequency Electrical-Noise cuit Breakers,” IEEE Transactions, vol. PAS 90,
Tests of Distribution Transformers (ANSI). 1971, p. 1589.
[4] IEEE C37.012-1979 (R 1988), IEEE Applica- [13] Harder, J. E. “Selection and Protection of
tion Guide for Capacitance Current Switching of Current Transformers for Use in Shunt Capacitor
AC High-Voltage Circuit Breakers Rated on a Banks,” IEEE Power Engineering socidy Paper,
Symmetrical Current Basis (ANSI). A 76 335-0.
[ 141 Harner, R. H. and Owen, R. E. “Neutral Dis-
placement of Ungrounded Capacitor Banks Dur-
ing Switching,” IEEE Transactions on Power
lANSI publications are available from the Sales Depart-
ment, American National Standards Institute, 1430 Broad-
way, New York, NY 10018.
21EEE publications are available from the Institute of Elec- 3NEMA publications are available from the National Elec-
trical and Electronics Engineers, Service Center, 445 Hoes trical Manufacturers Association, 2101 L Street, N.W., Wash-
Lane, Piscataway, NJ 08865. ington, DC 20037.

Authorized licensed use limited to: CHILECTRA. Downloaded on August 05,2010 at 21:09:19 UTC from IEEE Xplore. Restrictions apply.
IEEE
C37.99-1990 IEEE GUIDE FOR THE PROTECTION OF

Apparatus and Systems,no. 71 TP67,Jul./Aug., 3. Basic Considerations


1971,pp. 1631-1638.
[ 151 IEEE Power Engineering Society Switchgear Relay protection of shunt capacitor banks
Committee Report “Power Systems Transient requires an understanding of the capabilities and
Recovery Voltages,” 87THO176-8-PWR. Presented limitations of the individual capacitor units and
at the IEEE PES Winter Meeting,1987. associated electrical equipment including: individ-
ual capacitor-unit fuses, bank switching devices,
[16]Miller, D. F. “Application Guide for Shunt power fuses, and voltage or current sensing
Capacitors on Industrial Distribution Systems at devices. Applicable standards for this associated
Medium Voltage Levels,” IEEE Transactions on electrical equipment are referenced as discussed.
Industry Applications, vol. IA-12,no. 5,Sep./Oct.
1976,pp. 444- 459. 3.1 Capacitor Unit Ratings. IEEE Std 18-1980
[ 171 Moore, A. H. “Application of Power Capaci- [2]specifies the standard ratings of capacitors
tors to Electrochemical Rectifier Systems,”IEEE designed for shunt connection to alternating cur-
Transactionson Industry Applications, vol. A-13, rent transmission and distribution systems. Some
no. 5,Sep./Oct. 1977,pp. 399-406. of the ratings most significant to the relay engi-
neer are listed below:
[ 181 Pratt, R. A., Olive, W. W., Whitman, B. D., and (1) Capacitors should be capable of continu-
Brown, N. W. “Two-Fuse System Protects Capaci- ous operation at up to 110% of rated ter-
tors,” Elactrical World, Jun. 1977,pp. 46 - 48. minal rms voltage, including harmonics,
[ 191 Rogers, E. J. and Gillies, D. A. “Shunt Capac- and at up to 180% of rated rms current,
itor Switching EM1 Voltages: Their Reduction in including fundamental and harmonic cur-
Bonneville Power Administration Substations,” rents.
IEEE Transactions on Prnoer Apparatus and (2) Capacitors should give not less than 100%
Systems,vol. 93,Nov./Dec. 1974,pp. 1849-1860. and not more than 115% of rated reactive
power at rated sinusoidal voltage and fre-
[20]Sheppard, N. R. and Schultz, N. R. “Some quency, measured at a uniform case and
Considerations in the Protection of High-Voltage internal temperature of 25 “C.
Capacitor Banks,”AIEE Transactions, vol. 75,pt. (3) Capacitors mounted in multiple rows and
111, 1956,pp. 686-694. tiers should be designed for continuous
[21] Steepes, D. E. and Stratford, R. P. “Reactive operation for a normal annual tempera-
Compensation and Harmonic Suppression for ture of 25 “C (as defined in the reports of
Industrial Power Systems Using Thyristor Con- the U.S. Weather Bureau) and for a 24 h
verters,” IEEE Transactions on Industry Appli- average temperature of 40 “C during the
cations, vol. IA-12,no. 3, May/Jun. 1976, pp. hottest day expected at that location.
232 - 254. (4) Capacitors should be suitable for continu-
ous operation at up to 135% of rated reac-
[22]Stratford, R. P. “Rectifier Harmonics in tive power caused by the combined effects
Power Systems,”IEEE Transactions on Industry Of:
Applications, vol. IA-16,no. 2, Mar./Apr. 1980, (a) Voltage in excess of nameplate rating
pp. 271 - 276. at fundamental frequency, but not
[23]Taylor, E.R. Jr., Whyte, I. A., Brennan, M. B., over 110% of rated rms voltage.
and Bonk, J. J. “Static Var Generator Application (b) Harmonic voltages superimposed on
and Protection Considerations,” Capacitor Fro- the fundamental frequency.
tsctiOnPapers, May 1983,pp. 1-41. (c) Reactive power manufacturing toler-
ance of up to 115% of rated reactive
[24]“The Telephone Influence Factor of Supply power.
System Voltages and Currents,” Joint Subcommit- Capacitor units are available in standard volt-
tee on Development and Research, EEI Publica- age ratings shown in Table 1 and in standard
tion 60-68. EEI and Bell Telephone System; New reactive power ratings of 50, 100,150,200,300,
York, NY, 1960. and 400 kvar at most standard voltage ratings.
[25] Tom, M. 0.“A Static Voltage Differential
Relay for Protection of Shunt Capacitors,” N E E 3.2 Arrangementof CapacitorUnitS. Substation
Transactions, vol. 80, pt. 111, Feb. 1962, pp. type shunt capacitor banks are commonly con-
1086- 1089. figured using one or more series groups of

Authorized licensed use limited to: CHILECTRA. Downloaded on August 05,2010 at 21:09:19 UTC from IEEE Xplore. Restrictions apply.
IEEE
SHUNT CAPACITOR BANKS C37.99-1990

parallel-connected standard-voltage capacitor that isolation of one capacitor unit in a group


units per phase. Each capacitor unit is typically should not cause voltage unbalance sufficient to
protected by an individual fuse, externally place more than 110%of rated voltage on the
mounted between the capacitor unit and the remaining capacitors in the group. The value of
capacitor bank fuse bus. Also available are capac- 110%is the maximum continuous overvoltage rat-
itor units that employ internal fusible links on ing of capacitor units per IEEE Std 18-1980 [2].
each capacitor pack or element. Use of this The minimum recommended number of capac-
design can eliminate the need for external fuses itor units in parallel per series group, listed in
altogether. Figure 1(a) illustrates a typical capac- Table 2, may Mt the maximum capacitor unit
itor bank utilizing conventional capacitor units kvar rating that can be used for relatively small
with external fuses. Figure l(b) illustrates a banks. Moreover, it emphasizes the desirability of
typical capacitor bank utilizing internally-fused using capacitor units with the hlghest possible
capacitor units. In general, banks employing voltage rating and minimum number of series
internally-fused capacitor units are configured groups in order to obtain an adequate number in
with fewer capacitor units in parallel, and more each group.
series groups of units than are banks employing The maximum number of capacitor units that
externally-fused capacitor units. may be placed in a parallel per series group is
In internally fused capacitors, a fusible link is governed by a different consideration. When a
connected in series with each capacitor pack or capacitor unit fails, other capacitors in the same
element. Each capacitor unit is constructed with parallel group will contain some amount of
a large number of packs or elements connected in charge. This charge will then drain off as a high-
parallel, and with only a few groups of parallel frequency transient current that flows through
packs connected in series. This construction is the faulted unit and its fuse. The fuse holder and
just the opposite as that found in externally the failed capacitor unit should withstand this
fused capacitors, which typically employ a large discharge transient.
number of series groups of packs or elements, The discharge transient from a large number of
with correspondingly fewer packs connected in paralleled capacitors can be severe enough to
parallel per series group. With internally fused rupture the failed capacitor unit or the expulsion
capacitors, when a capacitor pack or element fuse holder, which may result in damage to adja-
fails, the current, through its individual fusible cent units or cause a major bus fault within the
link, will be considerably higher than the normal bank To minimize the probability of failure of the
current. This higher current will blow the fusible expulsion fuse holder, or rupture of the capacitor
link, thereby isolating the failed pack or element. case, or both, the total energy stored in a parallel-
connected group of capacitors should not exceed
3.3 Capacitor Bank Design. A capacitor bank 15 000 J for all-film capacitor units (10 000 J for
of a given size and voltage rating may be made up older capacitor units) at maximum peak voltage
of a number of series groups of capacitors, as (rated voltage 1.1- - a). For 60 Hz applications,
indicated in Table 1, and a number of parallel the maximum recommended limit for parallel-
capacitors per series group. connected kvar per series group is 4650 kvar for
Use of capacitors with the highest possible volt- all-film capacitor units (3100 kvar for older
age rating will result in a capacitor bank with the capacitor units). Refer to NEMA CP1-1976 [7].
fewest number of series groups. This generally If a capacitor bank having the minimum num-
provides the simplest and most economical rack ber of series groups requires more than 4650 kvar
structure and the greatest sensitivity for unbal- per series group, capacitors of a lower voltage
ance detection schemes. The available unbalance rating requiring more series groups and fewer
signal level decreases significantly as the number units in parallel per group may be a suitable solu-
of series groups of capacitors is increased, or as tion. However, this may reduce the sensitivity of
the number of capacitor units in parallel per the unbalance detection scheme, or it may result
series group is increased. in the bank being removed from service for a
The number of capacitor units in parallel per fewer number of isolated capacitor units due to
series group is governed by both a minimum and the voltage across the remaining units exceeding
a maximum Limitation. The minimum number of 110%of their rated voltage. Splitting the bank
capacitor units per group is determined by over- into two sections, as a double Y,may be the pre-
voltage considerations upon isolation of one ferred arrangement and may permit a better
capacitor unit in the group. The general rule is unbalance detection scheme. Another possibility

Authorized licensed use limited to: CHILECTRA. Downloaded on August 05,2010 at 21:09:19 UTC from IEEE Xplore. Restrictions apply.
IEEE
C37.99-1990 IEEE GUIDE FOR THE PROTECTION OF

1, U U U
I
I
I
I
I
I

n n n
U U- TT
I
I I I
I I I

n n n
U U U-
I I
I
i
n n
I
r

Fig 1
Y-Connected Capacitor Bank
(a) Externally-Fused Capacitor Units
(b) Internally-Fused Capacitor Units

10

Authorized licensed use limited to: CHILECTRA. Downloaded on August 05,2010 at 21:09:19 UTC from IEEE Xplore. Restrictions apply.
IEEE
SHUNT CAPACITOR BANKS C37.99-1990

Table 1
Y-Connected Capacitor Banks, Number of Series Groups*
Available Capacitor Voltages (kV per unit)
VLL VLN
kV kV 21.6 19.92 14.4 13.8 13.28 12.47 9.96 9.54 8.32 7.96 7.62 7.2 6.64
- -- - - - _ _ _ _ _ _ - _ _ - _ _ -
500.0 288.7 14 15 20 21 22 29 30 35 36 38
345.0 199.2 10 15 16 20 21 24 25 21
230.0 132.8 10 14 16 17 18 20
161.0 92.9 7 13 14
138.0 19.7 4 6 6 6 8 10 11 12

115.0 66.4 5 I 8 9 9 10
69.0 39.8 2 3 3 4 5 6
46.0 26.56 2 4
34.5 19.92 1 2 3
24.9 14.4 1 2

23.9 13.8 1
23.0 13.28 1 2
14.4 8.32 1
13.8 1.96 1
13.2 7.62 1
12.47 7.2 1

'This table shows, for a particular system voltage, the number of series-connectedcapacitors per phase of a Y-connected bank
that operates near rated capacitor unit voltage.

Table 2 of capacitor units per series group is increased.


Minimum Recommended Number of Units in For a given bank size, use of larger individual unit
Parallel per Series Group to Limit Voltage on capacitor kvar ratings decreases the number of
Remaining Units to 110%with One Unit Removed capacitor units per series group and increases
the overvoltage change due to isolation of a single
Number Double Y capacitor. Failure of additional capacitors is most
of series Grounded Ungrounded (Equal likely to occur in the same series group as the
Groups Y or A Y Sections)
first failure, since these remaining capacitor units
1 4 2 have the highest voltage stress. However, if two
2 6 8 7 capacitors fail in the same phase but not in the
3 8 9 8
4 9 10 9 same series group, the overvoltage percentage is
5 9 10 10 less than that of two capacitors failing within the
6 10 10 10 same series group.
7 10 10 10
8 10 11 10
9 10 11 10
10 10 11 11
11 10 11 11
1 2 and over 11 11 11 4. BankConnections

There are five common capacitor bank connec-


is the use of current limiting fuses in a single-Y tions. The connection selected depends upon the
configuration. best utilization of the standard voltage ratings of
capacitor units, fusing, and protective relaying.
3.4 Overvoltage on Remaining CapacitorUnits. Virtually all substation banks are connected in Y.
The overvoltage that occurs when an individual Distribution capacitor banks, however, may be
capacitor unit is isolated decreases as the number connected Y or A.

11

Authorized licensed use limited to: CHILECTRA. Downloaded on August 05,2010 at 21:09:19 UTC from IEEE Xplore. Restrictions apply.
IEEE
C37.99-1990 IEEE GUIDE FOR THE PROTECI'ION OF

The various types of connections illustrated in harmonic currents can flow in a A-connected
F g 2 are: capacitor bank. Additionally, where one series
(1) A group per phase is used, the individual capacitor
(2) Grounded Y fuses should be capable of interrupting the sys-
(3) Grounded double Y tem short-circuit phase-to-phase fault current.
(4) Ungrounded Y This often necessitates a current-limiting fuse.
(5) Ungrounded double Y Such fuses are significantly more costly than
expulsion fuses.
4.1 Delta-Connected Banks. Delta-connected
banks are generally used only at distribution volt- 4.2 Grounded-Y Connected Banks. Grounded-Y
ages and are configured with a single series group capacitor banks are most commonly used for volt-
of capacitors rated for line-to-line voltage. Wye- ages of 34.5 kV and above, and are composed of
connected banks are less complicated and more two or more series groups of parallel connected
economical, since A-connected banks require standard voltage capacitor units per phase.
either two-bushing capacitors with a grounded Figure 1 shows a typical bank arrangement. A
rack or single-bushing units with an insulated number of series group combinations are given in
rack. The greatest use of A-connected banks is at Table 1.
2400 V, since this is the lowest standard capacitor Grounded capacitor banks provide a low-imped-
voltage rating. Capacitor units for Y connection ance path to ground for hghtning surge currents
at 2400 V are not available as a standard unit and give some protection from surge voltages.
sue. Sometimes the bank may be operated without
With only one series group of units, no overvolt- surge arresters, taking advantage of this self-
age occurs across remaining capacitor units from protective feature.
isolation of a faulted capacitor unit and, there- Grounded capacitor banks also provide a
fore, unbalance detection is not required for pro- low-impedance path to ground for harmonic cur-
tection, but may be used to detect the outage of rents. These harmonic currents may cause com-
units within the bank. No zero sequence or third- munication facility interference, if such circuits

Fig 2
Basic Capacitor Bank Connections
(a) Delta (b) Grounded Y (c) Ungrounded Y
(d) Ungrounded Double Y-Neutrals (may or may not be tied)
(e) Grounded, Double Y

. I 0 I I

12

Authorized licensed use limited to: CHILECTRA. Downloaded on August 05,2010 at 21:09:19 UTC from IEEE Xplore. Restrictions apply.
IEEE
SHUNT CAPACITOR BANKS C37.99-1990

parallel power lines. Additionally, an open phase insulated rack. However, if two-bushing capacitor
produces zero sequence currents that may cause units with a grounded rack are used, the capaci-
ground relay operation. Also, harmonic resonance tor-unit fuse should be capable of interrupting
could be a problem. system phase-to-ground fault current. If lower
When the neutral is grounded, recovery volt- rated fuses are used, a fault to the capacitor case
ages encountered during switching are reduced, may not be cleared by the capacitor-unit fuse and
however, careful consideration should be given to will require that the fault be cleared by the capac-
the effect of inrush current on protective relay itor bank overcurrent protective devices. Un-
performance (see Section 10) and the method of grounded Y capacitor banks usually do not re-
grounding (see 5.2). quire current limiting capacitor-unit fuses since
4.2.1 One Series Group Per Phase. As with current through a faulted capacitor unit is limited
A-connected banks, no overvoltage across re- to three times normal phase current. However,
maining capacitor units occurs from isolation of caution needs to be exercised when re-fusing a
a faulted capacitor unit, and, therefore, unbal- bank of this type since faulted capacitors in dif-
ance relay protection is not required. Similarly, ferent phases could result in a phase-to-phase
the individual capacitor fuses should be capable system fault.
of interrupting the system available fault current. 4.3.2 Multiple Series Groups Per Phase-
4.2.2 Multiple Series Groups Per Phase- Single Y. Wye banks with multiple series groups
Single Y. Grounded-Y capacitor banks above may also be ungrounded. Such a bank cannot, in
34.5 kV are commonly composed of two or more and of itself, provide any surge voltage protec-
series groups of parallel connected capacitor tion, and provides no path to ground for third
units per phase. The presence of multiple series harmonic currents. The entire bank, including
groups of units limits the maximum fault current the neutral, should be insulated for line over-
so that individual current-limiting capacitor fuses voltage.
are usually not required unless the parallel kvar 4.3.3 Multiple Series Groups Per Phase-
exceeds 4650 kvar. Double Y. When a capacitor bank becomes too
4.2.3 Multiple Series Groups Per Phase- large for the 4650 kvar per group maximum for
Double Y. When a capacitor bank becomes too expulsion fuses, and is large enough to meet the
large for the 4650 kvar per group maximum for minimum units per group requirement as out-
expulsion fuses, or is large enough to meet the lined in 3.2, the bank may be split into two Y
minimum units-per-group requirement as out- sections. When the two neutrals are ungrounded,
lined in 3.2, the bank may be split into two Y the bank has some of the characteristics of the
sections. The characteristics of the grounded ungrounded single-Y bank. These two neutrals
double-Y bank are similar to a single grounded may or may not be tied together. As for any
Y bank. The two neutrals should be directly ungrounded Y bank, the neutral should be insu-
connected, with a single connection to ground. lated from ground for the full line-to-linevoltage.

4.3 Ungrounded Y-Connected Banks. Un-


grounded Y banks do not permit third harmonic 5. Other Considerations
currents or large capacitor discharge currents
during system ground faults. The neutral, how- The performance of the protection method can
ever, should be insulated for full-line voltage, be influenced by the design of the capacitor bank
since it is momentarily at phase potential when Therefore, protection begins with bank design
the bank is switched, or when one capacitor unit (see 3.3). In general, shunt capacitor bank design
fails in a bank configured with a single group of requirements necessitate an increase in minimum
units. bank size with system voltage. The higher the sys-
4.3.1 One Series Group Per Phase. For sys- tem voltage, the larger the bank investment and
tems with line-to-neutral voltages corresponding risk of costly damage. Although capacitors having
to standard capacitor ratings, Y-connected capac- larger kvar ratings may reduce the overall cost of
itor banks with a single series group per phase the bank, they may also reduce the choice of dif-
may be used. The capacitor bank neutral is usu- ferent capacitor combinations.
ally not grounded in order to avoid the need for 5.1 Parallel Banks. Where two or more
power fuses to interrupt system short-circuit grounded Y banks are at the same location, the
fault current (see 6.1). This also requires that neutrals should be directly connected, with a sin-
single-bushing capacitor units be mounted on an gle connection to ground. The design of the sub-

13

Authorized licensed use limited to: CHILECTRA. Downloaded on August 05,2010 at 21:09:19 UTC from IEEE Xplore. Restrictions apply.
IEEE
C37.99-1990 IEEE GUIDE FOR THE PROTECTION OF

station ground grid, and the connections of the With peninsula grounding, one or more ground
respective bank neutrals to the substation grid, is grid conductor(s) is carried underneath the
of prime importance. Improper grounding can capacitor rack of each phase of each group and
result in neutral current transformer, voltage tied to the main station ground grid at one point
transformer, or control cable failures. Two meth- at the edge of the capacitor area. All capacitor
ods of neutral grounding have been successfully bank neutral connections are made to this iso-
used single-point grounding and peninsula-type lated peninsula ground grid conductor(s) only
grounding (see Fig 3). [ 191. Although this arrangement allows the
With single-point grounding, the neutrals of all capacitor bank neutral potential (and associated
capacitor banks of a given voltage are connected current transformers and voltage transformers)
together with insulated cable, or an isolated bus, to rise during capacitor bank switching, it does
and tied to the substation ground grid at only one provide the lowest possible impedance between
point. This arrangement prevents high-frequency capacitor banks (see Fig 3).
currents, which flow between banks during back- If single-point grounding is used, there will be
to-back switching, from flowing in the ground substantial voltages (tens of kV) between the
grid. Unfortunately, in the event of a nearby ends of the neutral bus and the single-point
ground fault, this arrangement does not elimi- ground during switching. As a result, the primary
nate those high-frequency currents that flow to secondary insulation of neutral current trans-
back into the power system via the substation formers, or tap sensing voltage transformers, will
ground grid. be subjected to this voltage, increasing the possi-

Fig 3
Methods of Neutral Grounding
(a) Single Point Grounding (b) Peninsula Grounding

___________________ Insulated Capacitor Neutrals


1,2,3 3-Phase Capacitor Groups
5 Substation Ground Grid
6 H.V. Bus Capacitor bank neutral cables insulated, tied together
7 Single Point Capacitor Neutral Ground and connected t o station ground grid at one point; all
8 Capacitor Group Fence equipment grounds connected t o station ground grid.
(a)

___-_______________ Capacitor Grounding Conductors (Bare)


172, 3 3-Phase Capacitor Groups
5 Substation Ground Grid Capacitor bank neutrals and all equipment grounds tied
6 H. V. Bus together and connected to station ground grid at one
8 Capacitor Group Fence point; neutral leads routed beneath phase conductors.
(b)

14

Authorized licensed use limited to: CHILECTRA. Downloaded on August 05,2010 at 21:09:19 UTC from IEEE Xplore. Restrictions apply.
IEEE
SHUNT CAPACITOR BANKS C37.99-1990

bility of failure. Two bushing voltage transformers grounded capacitor bank neutral in an otherwise
should be used with the primary connected to the ungrounded system will allow phase-to-phase
capacitor bank neutral. voltage to appear across two phases of the bank,
This does not occur with peninsula grounding, in the event of a phase-to-ground fault in the
since all equipment at the neutral tends to rise to remaining phase.
the same potential. Peninsula grounding, coordi- One of the main advantages associated with
nated with control cable shielding and grounding, neutral grounding concerns the severity of the
will hold common mode voltages, appearing on recovery voltage across the first pole to clear of a
control cables in the control house, to safe levels. switch interrupting the charging current of a
Single-point grounding and peninsula ground- capacitor bank The recovery voltage across the
ing are not compatible. All capacitor banks of the first pole to open consists of trapped charges on
same system voltage should use the same ground- the capacitors and the variation in the 60 Hz volt-
ing scheme in the same substation. age of the system. Due to system parameters and
When de-energizing a capacitor bank, the mag- capacitor bank size, the recovery voltage can be
nitude of voltage disturbances on the system is approximately 2 times normal peak voltage when
greatly reduced by the presence of one or more the bank is grounded. On an ungrounded bank,
additional banks of comparable size connected to the magnitude of the first peak of the recovery
the same bus. During a closing operation or a voltage can be as high as 3 times the peak system
restrike, however, the transient inrush current line-to-ground voltage when the bank is switched.
through the switching device between the ener- Since recovery voltage is a most important fac-
gized banks and the one being switched can be tor in determining the capability of a switching
very large. These currents are oscillatory at very device t o switch capacitive reactive power, it may
high frequencies. The peak current may be on the be desirable, in terms of switch rating and cost, to
order of 50 to 100 times the normal peak of the ground the neutral of large shunt banks rated
capacitor bank current. Such a high instantane- above 100 kV. In fact, IEEE C37.04-1979 [5] and
ous current can produce high forces in the in- ANSI (337.06-1987 [ l ] require both the shunt
terrupter of the switching device that may be capacitor bank and the system to be grounded at
damaging to the contacts or structure. voltage levels of 121 kV and above. The circuit
Since the severity of parallel bank switching is breaker manufacturer should be consulted for
caused by the very sudden high current, which application of a breaker if these conditions are
initially is limited only by the very low resistance not met.
and inductance of the circuit between the banks, While many shunt capacitor banks are directly
it can be reduced by the addition of inductance to connected t o a high-voltage substation bus,
the circuit. An inductance with a 60 Hz reactance switched capacitor banks may be applied to ter-
of as little as $4 to 1%of the 60 Hz capacitive tiaries of power transformers that are connected
reactance of the banks, and placed in series with to the line, or possibly to the bus. Grounding the
them, will greatly reduce both the rate of rise and neutral of the wye-connected capacitor bank
the peak value of the inrush current that, in turn, should be done with caution. Since the A tertiary
greatly reduces the severity of the switching de- of the auto transformer represents an isolated
vice duty, Additional inductance may be obtained source, grounding the capacitor bank neutral
by increasing the length of the bus between the would make this side of the transformer capaci-
capacitor banks, or adding current-limiting reac- tive grounded. Overvoltages may be experienced
tors. The reactors may be of the wound type, or during line-to-ground faults for certain ratios of
may consist of magnetic cores surrounding the XO/X1 depending on system, transformer, and
leads or bus. Reinsertion resistors or inductors capacitor bank parameters. In those situations
on the capacitor switching device will also effec- where the neutral is grounded, the application
tively Limit the inrush current. should be specifically analyzed for proper appli-
cation of surge arresters, bank configuration, and
5.2 Neutral Grounding. The application of large bank switching devices.
shunt capacitor banks with switched parallel
banks in high-voltage transmission systems in-
volves a number of considerations, one of which 6. Capacitor Bank Protection
is grounding. It is generally recommended that
the neutral of capacitor banks be grounded only To ensure availability of a capacitor bank for
to systems t h a t are effectively grounded. A service requires reliable protection. This ensures

15

Authorized licensed use limited to: CHILECTRA. Downloaded on August 05,2010 at 21:09:19 UTC from IEEE Xplore. Restrictions apply.
IEEE
(37.99-1990 IEEE GUIDE FOR THE PROTECTION OF

minimal damage to the bank in the event of a discharge current from parallel capacitor units
fault. The bank should be removed from the sys- influences selection of fuse type. Unbalance relay
tem before it is severely damaged, or before a protection is covered in detail in Section 7.
fault is established on the system. When a single Each of the several types of faults or abnormal-
capacitor unit fails within a bank, the capacitor ities should be considered when the protection
unit should be isolated without transferring prob- for a shunt capacitw bank is evaluated.
lems to adjacent units.
The design of the capacitor bank protective 6.1 Capacitor-UnitFusing. The first line of pro-
system should reflect consideration of the influ- tection for a capacitor bank is the individual
ence of the following seven basic conditions: capacitor-unit fuse. The job of the fuse is to oper-
Overcurrents-due to capacitor bank bus ate in response to the failure of a single capacitor
faults; unit, and remove the unit from service fast enough
System surge voltages; to prevent case rupture and damage to adjacent
Overcurrents due to individual capacitor units. Removal of the faulted unit is important for
unit failure; protection of the remaining undamaged capaci-
Continuous capacitor unit overvoltages; tor units, and will allow the capacitor bank to
Discharge current from parallel capacitor remain in service. A proper fuse operation is
units; desirable in order to minimize the chance of cas-
Inrush current due to switching; and cading failure of additional capacitor units that
Arc-over within the capacitor rack. may, in turn, lead to a major bus fault within the
Table 3 summarizes the type of protection and capacitor bank.
preventive measures. Bus-fault and surge-voltage Proper operation of an individual capacitor-
protection are conventional in nature. Capacitor unit fuse depends largely upon the bank configu-
unit overcurrent protection is obtained through ration. In a large capacitor bank, the impedance
proper fuse coordination. Capacitor manufactur- of the other series groups of capacitor units in a
ers usually assist in this task, but a thorough particular phase leg will limit the current in a
understanding by the user, of capacitor unit and faulted capacitor unit. However,the energy stored
bank fusing, is recommended. Consideration of in other capacitor units in the series group will

Table 3
Summary of Shunt Capacitor Protection Methods

Type of Protection
Condition and Preventive Measures Remarks

Bus faults Supply breaker with overcurrent Conventional methods apply.


relays
Power fuses
System surge voltages Surge arresters Grounded capacitor banks partially
reduce surge voltages. Check arrester
rating.
Overcurrents due t o Individual capacitor unit fuses Coordination normally provided
individual capacitor (expulsion or current limiting by capacitor manufacturer.
unit failures tY Pes 1
Continuous capacitor Unbalance sensing with current The various schemes used have some
unit overvoltages or voltage relays for Y or limitations and suitability depends
double Y banks on bank arrangement and rating.
Periodic visual fuse inspection Not suitable for unmanned
substations.
Phase voltage relays For system overvoltage.
Discharge current Individual capacitor unit fuses Coordination normally by capacitor
from parallel capacitor (current limiting type) manufacturer.
units Proper bank design Limit number of parallel capacitors.
Inrush current Switched or fixed impedance To reduce inrush current. May not
in series with capacitor bank be necessary if only a single bank.
Rack faults Unbalance relaying Prompt relay action necessary t o
Overcurrent relaying limit fault damage.

16

Authorized licensed use limited to: CHILECTRA. Downloaded on August 05,2010 at 21:09:19 UTC from IEEE Xplore. Restrictions apply.
IEEE
SHLTNT CAPACITOR BANKS C37.99-1990

discharge into the faulted capacitor unit; this slower characteristics of the T-speed fuse link
discharge should be withstood by the faulted may permit use of a smaller ampere rating than
capacitor unit and its fuse. This limits the maxi- that with the K-speed fuse link. Where fault cur-
mum number of capacitor units that may be rents are high, current-limiting fuses, with their
placed in parallel in the same series group when higher interrupting ratings, can be used, but at a
expulsion fuses are used. higher cost. The large ampere ratings required
The capacitor-unit fuse should be selected to: with current limiting fuses, relative to the capac-
(1) Accommodate the maximum anticipated itor-unit current, may make it difficult to achieve
continuous capacitor-unit current, allow- protection against case rupture for low-magni-
ing for system overvoltage, capacitor-unit tude faults. The combination of expulsion fuses
tolerance, and harmonic currents. and current-limiting fuses provides for both con-
(2) Withstand the transient outrush current ditions. Where extremely large capacitor banks
from a healthy capacitor unit that occurs are required, it is recommended that double-Y
when: construction be employed in order to retain the
(a) a nearby capacitor bank is energized use of expulsion fuses. For additional informa-
(back-to-back switching); and tion on capacitor-unit fusing, refer to the fuse
(b) when an adjacent capacitor unit fails. manufacturer.
(3) Operate as promptly as possible in re-
sponse to an escalating capacitor-unit 6.2 Bank Overcurrent Protection. Protecting
failure, and in all cases respond to a com- against a major fault, such as a line-to-line fault
pletely shorted unit. or a line-to-ground fault, will generally require
(4) Protect the capacitor unit from case rup- some form of external protection for the capaci-
ture in accordance with applicable case- tor bank, such as power fuses, circuit breakers, or
rupture curves. circuit switchers with associated relay circuits
In some instances, it may be difficult to select a (see Fig 4). For grounded-Y capacitor banks, the
capacitor-unit fuse that will meet all of these backup protection need only respond to high-
objectives and, in such cases, trade-offs among magnitude faults. However, on an ungrounded Y
the various criteria should be made. Refer to the bank, a line-to-neutral fault will cause an increase
fuse manufacturer or the capacitor manufac- in the line current, in the faulted phase, of only 3
turer for specific fusing recommendations. times the normal phase current. Since capacitor
Expulsion fuses have provided excellent capac- banks can operate indefinitely at current levels in
itor-unit protection for many years at relatively excess of that based on rated kvar and voltage,
low costs. And when using such fuses, it is desir- the backup protection should allow 125%or 135%
able that the fuse link operate with failure of the of rated current to be carried continuously. At
fewest number of series packs shorted before the same time, the backup protection should iso-
complete capacitor-unit failure occurs. The late the b.ank in the event of the three-per-unit

Fig 4
Capacitor Bank Protection
(a) Using Phase Overcurrent Relays
(b) Using Bank Fuses

17

Authorized licensed use limited to: CHILECTRA. Downloaded on August 05,2010 at 21:09:19 UTC from IEEE Xplore. Restrictions apply.
IEEE
(37.99-1990 IEEE GUIDE FOR THE PROTECTION OF

phase current. It may be difficult to accomplish nied by heavy damage to the bank, including
this protection with power fuses. many blown fuses and a few ruptured capacitor
If step switching is used with ungrounded Y units. The nature of a capacitor unit rupture,
banks, external protection can be even more diffi- without the appearance of very much case swell-
cult to accomplish. The most economical protec- ing, is more typical of a high-energy type rupture
tion is usually provided by a power fuse, circuit than that due to merely 60 Hz fault current. This
breaker, or circuit switcher in the line supplying stored energy comes from the other units in the
all steps, rather than protection in the lines of same parallel groups that have been subjected to
each step. This is especially true if the switching a high overvoltage as a result of other groups
devices for the individual steps do not have suffi- being shorted. Instantaneous overcurrent relays
cient interrupting capacity to protect the bank are not effective for rack faults.
for line-to-line or line-to-ground faults. The main protection for an arc-over within the
Consider an ungrounded-Y connected bank capacitor bank is provided by fast timing of the
having only two steps. If the backup protection is unbalance relay. An unbalance time delay of 0.3
in the line supplying both steps, it should carry to 0.5 second will provide good protection for
270%of the rated current of one step when both rack faults and has had considerable use on
steps are in serivce. At the same time, it should power systems that are effectively grounded. The
remove both banks in the event of 300% of the unbalance time delay, however, should never be
rated current of one step. This would be a rela- less than the maximum clearing time of the
tively difficult task for relays, and would be virtu- capacitor-unit fuse for a completely shorted
ally impossible for power fuses. When three steps capacitor unit.
are considered, the situation becomes impossible On resistance-grounded and ungrounded power
for relays as well. If, on the other hand, each systems, an unusually long unbalance time delay
capacitor bank step has its own unbalance relay is required to coordinate with the line relays,
protection, to detect the line-to-neutral fault, unless the unbalance relay scheme is of the type
then the backup protection in the line supplying that does not respond to system voltage unbal-
the entire installation need only detect and ance. As noted in 5.2, resistance grounded and
respond to h g h magnitude faults. ungrounded power systems would utilize un-
Time-overcurrent relays can be applied with grounded capacitor banks. Some of the types of
normal settings without encountering false oper- unbalance relays for ungrounded capacitor banks
ations due to inrush currents. Instantaneous that do not respond to system voltage unbalance
relays, however, should be set high to override are shown in Figs 5(a), 6(a), 6(b), 6(d), 7, and 8.
these transients, or have tuned circuits so that The unbalance relays shown in Figs 9(a) and 9(b)
pickup increases with frequency. Successful oper- also do not respond to system voltage unbalance,
ation has been obtained by setting instantaneous but they are used only for grounded capacitor
relays at 3 times the capacitor rated current. banks.
Where capacitor banks are switched back-to- The sensitivity of the unbalance-trip relay is
back (that is, in parallel with other capacitor determined on the basis of protecting the capaci-
banks on the same bus) a setting of 4 times the tor units from continuous overvoltages, as a
rated capacitor bank current is commonly used result of individual failure and resultant fuse
for the instantaneous setting. This setting is used operation (see Section 7). When set on this basis,
regardless of the capacitor bank connection [20]. the resultant sensitivity is adequate to relay for
the initial rack fault, assuming the initial fault is
6.3 Protectionfor Rack Faults (Arc-OverWithin across one series section of one phase.
the Capacitor Rack). With a capacitor bank of If the timing relay does not have a definite time
the usual construction, where the individual characteristic, the 0.3 to 0.5 second time delay
phases are well separated, an arc-over within the setting is made at the multiple of pickup corre-
capacitor bank will begin as an arc-over of a sin- sponding to the initial rack fault. For a single
gle series section. Such a fault produces very little ungrounded-Y bank with an unbalance relay of
phase overcurrent and, if an unbalance relay pro- the type that detects neutral-to-ground voltage,
tection scheme is not provided, more and more the per-unit neutral-to-ground voltage, when one
series groups of the same phase can become complete series section is shorted, is given by
involved until the instantaneous relay trips the
bank or fuses clear. The total arcing time can be 1
on the order of a few seconds. This is accompa- VNS = 3s-2

18

Authorized licensed use limited to: CHILECTRA. Downloaded on August 05,2010 at 21:09:19 UTC from IEEE Xplore. Restrictions apply.
IEEE
SHUNT CAPACITOR BANKS (3'37.99-1990

where occasional operation on grounded Y banks may


give a warning of excessive harmonic currents.
S = number of series sections per phase
Time-overcurrent relays of the short-time char-
VN, = neutral-to-ground voltage in per-unit of
acteristic have ample time adjustment to ride
the applied line-to-neutral volts
through transients, while being capable of the
For a neutral current type of unbalance relay
faster timing to minimize damage from rack
on a single-Y bank with the neutral grounded
through a current transformer, the initial rack faults.
fault, assuming one series section is shorted, is: To analyze the performance of overcurrent
relays on rack faults that involve only one phase,
1 the following formulas are useful
IN = -
s- 1 S
where I N = neutral current expressed in per-unit
Single-groundedY, I = -
S-F
of normal phase current.
1.5s
An effective setting for the time-overcurrent Single-ungroundedy, I = -
1.5s-F
(TOC) relay is 1.35 times the rated capacitor cur-
rent. This setting has had considerable use and 6s
does not false-trip for ungrounded-Y banks; an Double-ungrounded Y, I = -
6S-5F

Fig 5
Shunt Capacitor Bank Protection Methods, Single Y-Connected Banks
(a) Summation of Line-to-Neutral Voltage Protection Method with Optional
Line-to-Neutral Overvoltage Protection, Ungrounded Y-Connected Capacitor Bank
(b) Neutral Voltage Unbalance Protection Method, Ungrounded Y-Connected Capacitor Bank
(c) Neutral Current Unbalance Protection Method, Grounded Y-Connected Capacitor Bank
(d) Neutral Voltage Unbalance Protection Method, Ungrounded Y-Connected Capacitor Bank
Using Capacitor Voltage Divider

I'

I - - - .
Surge
Arrester 4

19

Authorized licensed use limited to: CHILECTRA. Downloaded on August 05,2010 at 21:09:19 UTC from IEEE Xplore. Restrictions apply.
IEEE
(37.99-1990 IEEE GUIDE FOR THE PROTECTION OF

where performance is marginal, however, and becomes


S = number of series groups per phase useful only by using a short-time characteristic,
F = number of series groups flashed over and a low time-dial setting.
I = per unit of normal capacitor phase current Although the unbalance-trip relay is the most
effective protection for arc-over of a series sec-
NOTE: On a grounded-Ybank,where F = S, the current is the tion, the neutral voltage type of unbalance relay
system line-to-ground fault duty.
(Fig 5(b)) should not be relied upon for rack fault
It can be noted from the formulas that a TOC protection on capacitor banks where all three
relay, when set at 1.35times the rated capacitor phases are not well separated. For example, con-
current, cannot detect the initial rack fault (F=1) sider an ungrounded-Y capacitor bank with 2
on a single ungrounded Y bank that has more series groups per phase, wherein all three phases
than two series groups per phase, nor on a single- are installed upon a single steel structure. The
grounded Y bank that has more than three groups individual phases are stacked over each other so
per phase. Also, on a single-ungrounded Y bank that the initial fault may occur as a midrack
where S=2, and on a single-grounded Y bank phase-to-phase fault, as shown in Fig 10. This
where S=3,the current, I, is 1.5 for the initial fault does not cause an unbalance of the neutral
rack fault, that is 1.11times pickup with a setting voltage (or neutral current, if grounded) and,
of 1.35 times rated capacitor bank current. This therefore, an unbalance relay does not respond.

Fig 6
Shunt Capacitor Bank Protection Methods, Double Y-Connected Banks
(a) Neutral Current Unbalance Detection Method Ungrounded Double Y-ConnectedCapacitor Bank
(b) Neutral Voltage Unbalance Protection Method, Ungrounded Double Y-Connected Capacitor Bank
(Neutrals Isolated)
(c) Neutral Current Differential Protection Method, Grounded Double Y-ConnectedCapacitor Bank
(d) Neutral Voltage Unbalance Protection Method, Ungrounded Double Y-Connected Capacitor Bank
(Neutrals Tied Together)

0 I 1 I

NOTE. Be careful with (2and PT polarity marks (m). They sometimes look like wire connections (0).

20

Authorized licensed use limited to: CHILECTRA. Downloaded on August 05,2010 at 21:09:19 UTC from IEEE Xplore. Restrictions apply.
IEEE
SHUNT CAPACITOR BANKS (337.99-1990

59N
60V

Shifter
I
Fig 8
NOTE: Compensating voltage is system zero sequencevoltage Neutral Voltage Unbalance Protection Method
and a phase shifted voltage of one phase.
Ungrounded Double Y-Connected
Capacitor Bank (Neutrals Isolated)
Fig 7 With Compensation for Inherent Unbalance
Neutrd Voltage Unbalance Protection Method
Ungrounded Y-Connected Capacitor Bank
With Compensation for Inherent Unbalance

A4
E4
C4

(b)
Fig 9
Voltage Difference Protection Methods
(a) Single Grounded Y-Connected Capacitor Banks
(b) Double Grounded Y-Connected Capacitor Banks

21

Authorized licensed use limited to: CHILECTRA. Downloaded on August 05,2010 at 21:09:19 UTC from IEEE Xplore. Restrictions apply.
IEEE
C37.99-1990 IEEE GUIDE FOR THE PROTE(T1ON OF

The initial fault may spread until it becomes 6.4 Bank Overvoltage protection. Lghtning and
severe enough to operate the time or instantane- switching transient overvoltages may be curtailed
ous overcurrent relays up to 5 s later. However, with standard overvoltage protection equipment
by this time, there may be considerable damage such as surge arresters. A capacitor bank gener-
involving all three phases. ally absorbs overvoltages since it acts temporarily
The currents and neutral shift voltage can eas- as a short circuit for step voltage changes. Over-
ily be computed for the initial rack fault. First, the voltages around capacitor banks are greatly
impedance of each phase to the new neutral reduced, but complete protection is not assured.
point, the point of fault, is obtained. This results in The overvoltage on a bank depends upon the
a set of impedances, Y-connected, which are un- length of line between the shunt capacitor bank
equal. Using a Y-Atransformation, the equivalent and the point at which the transient voltage is
impedances can be found. The A currents are generated, as well as on the surge duration.
the line-to-line voltages divided by the A imped- The capacitor bank may also be subjected to
ances. The line currents can be computed from the overvoltages resulting from abnormal system
phasor addition of 2 A currents. In this manner, operating conditions. If it is felt that the over-
the per-unit currents (of normal phase current) voltage could be sufficient to damage the bank,
in Fig 10, with 2 series groups per phase, are: overvoltage relays should be considered. Table 4
lists recommended short-term overvoltage limits.
I, = 1.0
Ib = 1.8 Table 4
Limits of Short Time Power Frequency
I , = 1.8 Overvoltage at Subzero Temperatures
The voltage drop from phase A to the former Multiplying Factor
neutral, where the primary of the potential device Duration Times Rated rms Voltage
is connected, is la Za, which is the same as before
0.5 c 3.0
the fault. Therefore, there is no neutral shift. The 1.0 c 2.7
IZ drops can be added from one phase to another 6.0 c 2.2
and compared to the applied line-to-line voltage 15.0 c 2.0
1.0 s 1.7
as a check on the accuracy of the calculations. 15.0 s 1.4
Protection for rack faults on banks of this con- 1.0 min 1.3
30.0 min 1.25
struction with two series groups per phase can
best be obtained by using TOC relays having a NOTE. The short time power frequency overvoltage should be
short-time characteristic, a pickup setting of 1.35 limited to the values listed here at subzero temperatures.
times rated current, and a time setting of 0.2 s at Higher limits may be permissible with less severe conditions.
150%of tap value current.
Fig 11
Fig 10 Summation of Intermediate Tap-Point
Midrack Phase-to-PhaseArcing Fault Voltage Protection Method

VT. CCV T, or
Resistive
Potential
DWCe

If S 1s an even number. then


S - ST = ST = 5'2
I f S 8s an odd number then
sT=s;l and s ST =
~ '$'
NOTE: Summation may also be obtained by use of a summing
amplifier.

22

Authorized licensed use limited to: CHILECTRA. Downloaded on August 05,2010 at 21:09:19 UTC from IEEE Xplore. Restrictions apply.
IEEE
SHUNT CAPACITOR BANKS C37.99-1990

LEGEND
01 - Control Switch
278 - Undervoltage - Bus
50 - Instantaneous Overcurrent - Phase
51 - Very Inverse Time-Overcurrent - Phase
51N - Inverse Time-Overcurrent - Neutral
52 - Circuit Breaker
52TC - Circuit Breaker - Trip Coil
596 - Instantaneous Overvoltage - Bus
59N - Instantaneous Overvoltage - Neutral
59R - Instantaneous Overvoltage - Residual
60V - Voltage Differential
620V - Timer - Overvoltage
62UV - Timer - Undervoltage
62X - Auxiliary - Breaker Failure Initiate
62Y - Auxiliary - Breaker Failure Initiate
R - Red Lamp
NOTE: Relay contacts are shown with operating coil
* LOWVoltage Capacitor de-energized.

1 1

6 2 0 V q \62UVr

Fig 12
Special Protection Scheme for Very Large EHV Capacitor Banks:
(a) Functional Diagram (b) DC Schematic (Primary Tripping)
(c) DC Schematic (Backup Tripping)

23

Authorized licensed use limited to: CHILECTRA. Downloaded on August 05,2010 at 21:09:19 UTC from IEEE Xplore. Restrictions apply.
IEEE
(37.99-1990 IEEE GUIDE FOR THE PROTECTION OF

- -
1 - 1 -
--
-
W - PTs
--

I ri/ Capacitor Breaker

c-
Electronic
Control
c-

Main

(a) (b)
Opening the circuit to a single phase capacitor in one step. On the left an opening
without restrike. On the right, the maximum effect possible with one restrike.
Fig 14
Opening the Circuit to a Single-phase Capacitor in One Step
(a) No Restrike (b) One Restrike

24

Authorized licensed use limited to: CHILECTRA. Downloaded on August 05,2010 at 21:09:19 UTC from IEEE Xplore. Restrictions apply.
SHUNT CAPACITOR BANKS IEEE
(37.99-1990

t
Volts

01
,001
I
.01
I

.1

Fig 15
I

1
Amperes --
I

10
I

100
I
loo0 1Ok
I

Varistor V/I Curve Showing Voltage Turn-up

Line #1 Line #2 Line #3

Capacitor Bank
40 MVAR, 230 kV
Grounded w e

500 h

Fig 16
One Line Diagram of 230 kV Station

1s -
Single Bushing VT

k V T Case

Fig 17
Single Point Grounded Bank with SingleBushing VT

25

Authorized licensed use limited to: CHILECTRA. Downloaded on August 05,2010 at 21:09:19 UTC from IEEE Xplore. Restrictions apply.
IEEE
(237.99-1990 IEEE GUIDE FOR THE PROTECl'ION OF

1s - - Capacitor Bank

1
1

--
I "

fly

Bank Neutral

-
Single Point Ground Station Ground [I
Bank Ground Connection As VT Connected
to Station Ground
Secondary Ground

Fig 18
Single Point Grounded Bank with Two-BushingVT

7. Unbalance Relaying Methods will be reflected as unbalance in the bank, and


can be detected by schemes similar to those used
7.1 Introduction. Removal of a failed capacitor on banks with externally-fused units. However,
unit by its fuse results in an increase in voltage the degree of unbalance is less than that which
across the remaining units within the group. A occurs with externally fused units, since the
continuous excessive overvoltage should be pre- amount of capacitance removed by blown ele-
vented by means of protective relays that trip the ments or pack fuses is less. Therefore, a more
bank switching devices to remove the bank from sensitive unbalance protection scheme is nor-
service. Failure to provide protection may lead to mally required when internally-fused units are
one or more of the following situations: employed. This increased sensitivity can be
(1) Excessive damage to the capacitor bank achieved by use of protection methods that elim-
(2) Adverse system effects inate the inherent system-voltage unbalance from
(3) Spread of damage to adjacent equipment the detection of the unbalance voltage. The most
(4) Excessive period of unavailability of the commonly used bank configuration is the un-
damaged equipment grounded double-Y. The protective equipment
( 5 ) Possible undesirable discharge of dielectric used with that configuration, with external fus-
liquid ing, will normally work satisfactorily with internal
Most installations will require an individual fusing as long as it is sensitive enough. Normally
engineering analysis to determine the best and the capacitor bank supplier will determine and
most economical scheme. The engineer will want furnish the user with the required relay settings.
to take the systems approach since bank design,
fuse coordination, and selection of a sensing 7.2 Inherent Unbalance and Other Errors. In
device will directly affect sensitivity and timing practice, the unbalance seen by the unbalance
requirements of the protection scheme. Selection relay, due to loss of individual capacitor units, is
of the bank configuration and design should somewhat different than the calculated value
include an analysis of the amount of inherent because of inherent unbalance. This inherent
unbalance that can be expected. unbalance, which exists on all capacitor bank
Internally fused capacitor units are subject to installations, is primarily due to system voltage
overvoltage across elements within the unit, as unbalance, capacitor manufacturing tolerance
internal fuses blow and remove elements from a unbalance, or both. The inherent unbalance may
parallel group. The loss of capacitance in the unit be in a direction such as to prevent protective

26

Authorized licensed use limited to: CHILECTRA. Downloaded on August 05,2010 at 21:09:19 UTC from IEEE Xplore. Restrictions apply.
IEEE
SHUNT CAPACITOR BANKS (37.99-1990

relay operation, as well as to cause false opera- voltage applied to surviving capacitor units equals
tion. The amount of inherent unbalance for var- or exceeds 110%of rated voltage. If the estimated
ious configurations, resulting from system voltage inherent unbalance, as determined from equa-
unbalance, capacitor manufacturing tolerance tions of Appendix C, exceeds the allowable neu-
unbalance, or both, may be estimated by using tral unbalance as determined from the curves or
equations in Appendix C. A worst case estimate equations of Figures 19, 20, and 21, steps should
can be made by assuming the unbalance errors to be taken to compensate for the inherent unbal-
be additive. ance error.
Figures 19, 20, and 21 indicate the allowable Harmonic voltages can also influence the oper-
neutral unbalance for positive detection of the ation of the unbalance relay unless proper filter-
first blown fuse. The curves are based on the ing is provided. The third harmonic predomi-
relay being set to operate at a point half way nates, although special applications such as arc
between the critical step and the next lowest furnaces can produce a wide variety of harmonic
step. The critical step is the step for which the frequencies.

Fig 19
Grounded Y-Connected Capacitor Bank: Percentage of Allowable
Inherent Neutral Current Unbalance for Positive Detection of
First Blown Fuse Versus Number of Capacitor Units in
Parallel per Group and Number of Series Groups

100

\ I \ \ 4 2 L(P-1) S+lJ

27

Authorized licensed use limited to: CHILECTRA. Downloaded on August 05,2010 at 21:09:19 UTC from IEEE Xplore. Restrictions apply.
IEEE
(37.99-1990 IEEE GUIDE FOR THE PROTECTION OF

-ia
oc3
> I

W J
z
-I
~ - a
ZI:
w a
a o
w z
L
ZLL
- Q
wl-

NUMBER OF CAPACITOR U N I T S I N P A R A L L E L PER S E R I E S GROUP

Fig 20
Ungrounded Y-Connected Capacitor Bank:Percentage of Allowable Neutral
Voltage Unbalance for Positive Detection of First Blown Fuse Versus Number of
Capacitor UNts in Parallel per Group and Number of Series Groups

In addition, secondary errors may be intro- convenient visual means of locating the
duced by sensing device tolerances, temperature defective capacitor unit.
differences between capacitor units within the (2) Where possible, the unbalance relay should
bank, and partially deteriorated capacitor units be sensitive enough to alarm for the loss of
that have not yet blown their fuses. one unit within a group and trip and lock-
out on loss of sufficient or additional
7.3 General Unbalance Relay Considerations. capacitor units that will cause a group
General unbalance relay protection considera- overvoltage condition in excess of 110%of'
tions are discussed below. rated voltage.
(1) The unbalance relay should coordinate (3) The unbalance relay should have a time
with the individual capacitor unit fuses delay short enough to minimize damage
such that the fuses operate to isolate a due to an arcing fault within the bank
defective capacitor unit before the bank is structure, and prevent exposure of the
switched out of service, and thus provide a remaining capacitor units to overvoltage

28

Authorized licensed use limited to: CHILECTRA. Downloaded on August 05,2010 at 21:09:19 UTC from IEEE Xplore. Restrictions apply.
IEEE
SHUNT CAPACITOR BANKS (37.99-1990

I
.. II 1 \

1. 2 (6PS - 65 +T
I\ \ '

a
m
z
3
t-
z
W
a
a
3
0
-I
a
a
t-
3
W
z
t-
z
W
a
W
S
z
U

W
-I
m
a
x
Q
-I
J
a

Fig 21
Ungrounded Double Y-Connected Capacitor Bank: Percentage of
Allowable Inherent Neutral Current Unbalance for Positive Detection of
First Blown Fuse Versus Number of Capacitor Unita in Parallel
per Group and Number of Groups in Series

conditions beyond their permissible limits. ( 5 ) The unbalance relay should be protected
The time delay should also be short enough against transient voltages appearing on
to avoid damage to the current transformer control wiring (see IEEE C37.90-1989[6]).
or voltage transformer, and relay system, (6) The unbalance relay may require a filter to
for a single-phase or an open-phase con- minimize the effect of harmonic voltages.
dition. It should be recognized.that the relay may
(4) The unbalance relay should have a time not operate for excessive harmonic (reso-
delay sufficient to avoid false operations nant) currents.
due to inrush, ground faults on the line, (7) The unbalance relay scheme should have a
lightning, switching of nearby equipment, lockout feature to prevent automatic re-
and nonsimultaneous pole operation of closing of the capacitor bank switching
the energizing switch. For most applica- device in the event that an overvoltage trip
tions, 0.5 s should be adequate. has occurred. The unbalance relay trip cir-

29

Authorized licensed use limited to: CHILECTRA. Downloaded on August 05,2010 at 21:09:19 UTC from IEEE Xplore. Restrictions apply.
IEEE
(37.99-1990 IEEE GUIDE FOR THE PROTECTION OF

cuit components should be coordinated. relays. This may be several seconds for
For example, the 0.2 A target and seal-in some devices.
coil of the voltage relay has about 50 ohms (14) In an internally fused capacitor bank, the
of impedance at 60 Hz. The armature- unbalance detection gives an indication of
closed current of a 120 V ac lockout relay the total number of failed capacitor ele-
may not hold the seal-in unit operated. ments. The actual number of failed ele-
(8) Where neutral unbalance due to system ments will be determined by the settings
variations or capacitor manufacturing tol- of the relays. Individual failed capacitor
erances is not negligible, a compensating elements can only be detected by a capaci-
means should be provided to negate the tor measurement. A complete measure-
effect of this unbalance. Careful considera- ment of all units in a bank is recommended
tion of bank design may also remedy the only when a relay trip has occurred, and
problem. Before making changes, the load not as a part of the regular maintenance
current of each phase and the capacitance schedule.
(or load current) of each capacitor should
be checked for indication of failure of a 7.4 Neutral CurrentUnbalance Protection Meth-
single capacitor pack within the can. The od,Grounded-Y Bank. Figure 5(c) shows a neu-
unbalance relay should be set taking this tral unbalance relay protection scheme for a
unbalance into account (see 7.8). grounded-Y capacitor bank. An unbalance in the
(9) Since most unbalance detection schemes capacitor bank will cause current to flow in the
do not measure overvoltage on the system, neutral. The amount of neutral current due to
the unbalance relay should be set on the loss of individual capacitor units can be deter-
basis of maximum continuous system oper- mined from Fig 22 or Eq 5 of Appendix B. The
ating voltage. voltage on the remaining capacitor units can be
(10) To allow for the effects of inherent unbal- determined from Fig 23 or Eq 1 of Appendix B.
ance, the unbalance relay alarm should be The unbalance protective scheme consists of a
set to operate at one-half the level of current transformer, with rated 5 A secondary,
neutral displacement, or neutral current, connected from the capacitor bank neutral to
determined for the desired alarm condi- ground. A ct ratio providing a maximum of 10 A
tion. The alarm should have sufficient time of secondary current for rated capacitor bank
delay to override external disturbances. current in the primary will avoid excessive
(11) To allow for the effects of inherent unbal- secondary currents when the capacitor bank is
ance, the unbalance relay should be set to energized or when only one or two phases remain
operate at a level of neutral displacement, energized. For an electromechanical type relay,
or neutral current, halfway between the the current transformer secondary is loaded with
critical step and the next lowest step. The an adjustable resistor, usually 10 to 25 ohms
critical step is the number of removed maximum, and connected to a time delayvoltage
capacitor units that will cause a group relay having a third harmonic filter for reduced
overvoltage in excess of the manufactur- sensitivity at frequencies other than 60 Hz. The
er's recommended maximum continuous current transformer loading resistor should be
operating voltage. rated 200 W or higher to avoid damaging this
(12) All neutral unbalance schemes detect an resistor in the event that one or two phases of the
unbalance in the three phases. Overvolt- capacitor bank switching device are open due to
age, caused by loss of an equal number of failure or misoperation.
capacitor units in one or more groups in A typical voltage relay has 60 Hz pickup taps of
each phase, will not be detected. In prac- 5.4, 7.5, 12.5 and 20 V. The voltage relay operates
tice, this is not a significant limitation. a latching relay through a 52a contact on the
(13) With grounded capacitor banks, failure of capacitor bank switching device to initiate open-
one pole of the switching device, or single ing of the capacitor switch and block its closing.
phasing from a blown bank fuse, will allow Static-type voltage relays have much lower
zero sequence currents to flow in the sys- burden and can be more insensitive to harmonics
tem ground relays. Capacitor bank relay- than electromechanical type relays, and thus
ing, including the operating time of the have greater sensitivity. Therefore, lower value
switching device, should be coordinated burden resistors can be used that will avoid satu-
with the operation of the system ground ration of the current transformer.

30

Authorized licensed use limited to: CHILECTRA. Downloaded on August 05,2010 at 21:09:19 UTC from IEEE Xplore. Restrictions apply.
IEEE
SHUNT CAPACITOR BANKS C37.99-1990

0
0

CAPACITOR UNIlS REMOVED FROM ONE S E R I E S GROUP-


PERCENT OF T O T A L NUMBER OF C A P A C I T O R U N I T S PER SERIES GRCIUP

Fig 22
Grounded Y-Connected or Grounded Double Y-Connected Capacitor Bank:
Neutral Current (also change in intermediate tap-point voltage) Versus
Percentage of Capacitor Units Removed from Series Group

Each time the capacitor bank is energized, small- to medium-sized single-bank installations,
momentary capacitor charging currents, in one the neutral current unbalance protection method
phase and in the neutral current transformer, works quite well and is economical. If instan-
can approach the available ground fault value. taneous overcurrent relays are used, they should
Where a parallel bank is already energized, cur- not operate on the initial inrush current.
rents can be on the order of thousands of amperes To prevent protective equipment damage due
[81. Various undesirable effects have been re- to failure of the switching device, the latching or
corded, such as spurious relay operations, relay lockout relay should have contacts wired to the
failures, current transformer failures, charged current transformer cable terminals to short out
substation fences, and ground mat problems. the current transformer secondary after it has
(The neutral connection between banks should operated. The current transformer loading resis-
not be through the ground mat.) However, for tor should be able to withstand the rapid heating,

31

Authorized licensed use limited to: CHILECTRA. Downloaded on August 05,2010 at 21:09:19 UTC from IEEE Xplore. Restrictions apply.
IEEE
C37.99-1990 IEEE GUIDE FOR THE PROTECTION OF

in the event of single phasing, until the unbalance 7.6 Summationof Intermediate Tap Point Volt-
protection voltage relay and lockout relay operate. ages Method, Grounded-Y Bank. Figure 11
The voltage relay and current transformer load- shows an unbalance voltage protection scheme
ing resistor settings should be made to operate for a grounded-Y capacitor bank using capacitor
when the voltage across any capacitor exceeds tap-point voltages. An unbalance in the capacitor
110%of rated voltage. bank will cause an unbalance in the voltages at
the tap point of the three phases. The tap voltage
NOTE: The relay detects only the unbalance in the capacitor percent unbalance due to the loss of individual
bank and in supply voltage. However, this relay will not capacitor units can be determined from Fig 22
respond to capacitor overvoltage due to a balanced system
voltage above nominal. The maximum normal system voltage, (or Eq 6 of Appendix B) by considering the verti-
with capacitor bank energized, should be considered. cal scale as Tap Voltage Percent Unbalance. The

Fig 23
Grounded Y-Connected,A, or Grounded Double Y-Connected Capacitor Bank:
Voltage on Remaining Capacitor Units in Series Group Versus
Percentage of Capacitor Units Removed from Series Group

Number of S e r i e s Groups P e r Phase

CAPACITOR U N I T S REMOVED FROM ONE S E R I E S GROUP-


PERCENT OF TOTAL NUMBER OF CAPACITOR U N I T S PER S E R I E S GROUP

32

Authorized licensed use limited to: CHILECTRA. Downloaded on August 05,2010 at 21:09:19 UTC from IEEE Xplore. Restrictions apply.
IEEE
SHUNT CAPACITOR BANKS C37.99-1990

voltage of the remaining capacitor units can be 7.6 Neutral Voltage Unbalance Protection Meth-
determined from Fig 23 or Eq 1 of Appendix B. od, Ungrounded-Y Bank. Figure 5(b) shows a
The unbalance protective scheme consists of neutral unbalance relay protection scheme for an
three voltage sensing devices connected between ungrounded-Y capacitor bank Unbalance sens-
the capacitor intermediate point of each phase ing is accomplished by means of a potential sens-
and ground, and a time delay voltage relay with ing device connected between the bank neutral
the third harmonic filter connected to the series- and ground. An unbalance in the capacitor bank
connected (broken A) secondaries of the poten- will cause voltage to appear at the bank neutral
tial device. For an even number of series groups, a with respect to ground. The amount of neutral
midpoint tap is used. For an odd number of series voltage due to the loss of individual capacitor
groups, the number of series groups between the units is determined from Fig 24 or Eq 14 of
tap point and ground should be one less than the Appendix B. The voltage on the remaining capac-
number of series groups between the tap point itor units can be determined from Fig 25 or Eq 10
and the line. The voltage sensing devices may be of Appendix B.
voltage transformers, capacitor coupled voltage The unbalance protective scheme consists of a
transformers, or resistive potential devices. The time delay voltage relay with the third harmonic
relay may include provisions to compensate for filter connected across the potential device sec-
the tap point error voltages caused by inherent ondary. The voltage sensing device may be a volt-
capacitor bank unbalance, fixed system voltage age transformer, capacitive potential device, or
unbalance, and potential device ratio errors. resistive potential device. The voltage sensing
The tap voltage percent unbalance can be device should be selected for the lowest voltage
determined from Fig 22 for isolation of capacitor ratio attainable, while still being able to with-
units in any series group of a capacitor bank hav- stand transient and continuous overvoltage condi-
ing an even number of series groups per phase. tions in order to obtain the maximum unbalance
The values are also valid for isolation of capacitor detection sensitivity. However, a voltage trans-
units in series groups located between the tap former used in this application should be rated
point and the line of a capacitor bank having an for full system voltage, since the neutral voltage
odd number of series groups per phase. However, can be expected to rise to as high as 2.5 per unit
for isolation of capacitor units in series groups during switching. Under these conditions, a de-
between the tap point and ground of banks with rated voltage transformer will be driven into deep
an odd number of series groups per phase, the saturation [14].
values from Fig 22 should be multiplied by the With 3 or more series groups, the change in
following factors: neutral voltage obtained from the secondary of a
voltage transformer, rated for full system voltage,
Total No. of Adjustment Factor is very smaU A voltage transformer of lower
Series Groups For Percent Tap voltage rating and ratio can be used to obtain a
Per Phase Unbalance Voltage usable relay voltage if the primary is gapped.
Flashover of the primary gap will ground the
3 2.0
capacitor bank neutral, short out the voltage
5 1.5
transformer, and prevent operation of the over-
7 1.33
voltage relay. Protection for this condition can be
9 1.25
obtained by using a residual current relay con-
11 1.2
13 nected t o line-current transformers, or to a
1.16
15 neutral-current transformer in series with the
1.14
neutral-voltage transformer and voltage trans-
former gap.
For banks having only three or five series The use of an underrated resistance potential
groups per phase, this may affect the coordina- device, with secondaryvoltage limiter, can permit
tion of alarm and trip level settings. Loss of a relay operation with an open phase to the capaci-
second capacitor unit, in the same phase, but in a tor bank. The resistive potential device should
second series group on the opposite side of the be capable of withstanding this overvoltage con-
potential device tap, has a compensating effect dition.
on the overvoltage and may reduce the unbal- If switch failure could result in continuous volt-
ance signal to zero. In practice, this is not a signif- age exceeding the relay rating (single phasing
icant limitation. due to blown main fuse), operation of the lockout

33

Authorized licensed use limited to: CHILECTRA. Downloaded on August 05,2010 at 21:09:19 UTC from IEEE Xplore. Restrictions apply.
IEEE
C37.99-1990 IEEE GUIDE FOR THE PROTECTION OF

/
0

3s (P-Fl) + 2F1 ,_- - - -

P No of u n i t s i n group
s NO of series groups '

CAPACITOR U N I T S R E M O V E D FROM ONE SERIES GROUP


PERCENT O F T O T A L NUMBER O F CAPACITOR U N I T S PER SERIES GROUP

Fig 24
Ungrounded Y-Connected or Ungrounded Double Y-Connect
(Neutrals Isolated) Capacitor Bank: Voltage Between
Capacitor Bank Neutral and Ground Versus Percentage of
Capacitor Units Removed from Series Group

relay should de-energize the voltage relay. If chat- sized to provide the desired unbalance voltage to
tering of the seal-in unit is a problem when used the relay. If single phasing of the capacitor bank
on ac, a lockout relay contact can bypass the volt- is a possibility (blown primary fuse), and the volt-
age relay contact. age of the neutral relay exceeds its short-time
Another scheme, shown in Elg 5(d), consists of rating, some means of limiting this voltage should
standard capacitor units connected in series to be provided. If the voltage exceeds the continu-
form a voltage divider. A conventional inverse ous rating of the relay, a lockout relay contact
time voltage relay is connected across the should short out the relay through a resistor.
grounded end capacitor. This grounded end Without a transformer for isolation, the relay is
capacitor is a low-voltage unit, 2400 V or less, and connected directly to the capacitor bank ground.

34

Authorized licensed use limited to: CHILECTRA. Downloaded on August 05,2010 at 21:09:19 UTC from IEEE Xplore. Restrictions apply.
IEEE
SHUNT CAPACITOR BANKS (37.99-1990

CAPACITOR U N I T S REMOVED FROM ONE S E R I E S GROUP-


PERCENT OF TOTAL NUMBER OF CAPFICITOR U N I T S PER SERIES GROUP

Fig 25
Ungrounded Y-Connected or Ungrounded Double Y-Connected
(Neutrals Isolated) Capacitor Bank: Voltage on Remaining
Capacitor Units in Series Group Versus Percentage of
Capacitor Units Removed from Series Group

A capacitor voltage divider may also use a car- sensitivity over the single neutral-to-ground volt-
rier coupling type of capacitor with a low-energy age transformer scheme.
static relay. NOTE: Voltage transformers should be rated for line-to-line
Figure 5(a) shows a neutral unbalance relay voltage.
protection scheme using 3 line-to-neutral voltage
transformers with their secondaries connected in 7.7 Double-Y Unbalance Protection Method.
broken A to an overvoltage relay. This scheme has Figure 6 shows four methods of providing unbal-
the advantage of not being sensitive to system ance protection for double-Y banks. Schemes (a)
voltage unbalance. Also, the unbalance voltage to and (b) are ungrounded and use either a current
the overvoltage relay is 3 times the neutral shift transformer and overcurrent relay, or a voltage
voltage, as obtained from F‘lg 24. For the same transformer and overvoltage relay connected
voltage transformer ratio, there is a gain of 3 in between the two neutrals. The effect of system

35

Authorized licensed use limited to: CHILECTRA. Downloaded on August 05,2010 at 21:09:19 UTC from IEEE Xplore. Restrictions apply.
IEEE
(37.99-1990 IEEE GUIDE FOR THE PRO"ION OF

voltage unbalances are avoided by both schemes, The neutral voltage shift can be determined
both unaffected by third harmonic currents or from Fig 24 in the same manner as for a single-Y
voltages. The current transformer or voltage bank of the same rating as one section of the
transformer should be rated for system voltage. double-Y bank. Although a low-ratio voltage
The amount of neutral current due to the loss transformer would be desirable, a voltage trans-
of individual capacitor units, in a bank of two former rated for system voltage is required for
equal sections, can be determined from Fig 26. the ungrounded neutral and, therefore, a high
The neutral current is one-half that of a single turns ratio should be accepted. The resulting
grounded bank of the same size. However, the unbalance signal voltage may be very small.
current transformer ratio and relay rating may In Fig 6(c), the neutrals of the two sections are
be selected for the desired sensitivity, since they grounded through separate current transformers
are not subjected to switching surge currents or to a common ground. The current transformer
single-phase load currents, as with the grounded secondaries are cross-connected to an overcur-
neutral scheme. rent relay so that the relay is insensitive to any

Fig 26
Ungrounded Double Y-Connected (Neutrals Tied Together) Capacitor Bank:
Neutral Current Versus Percentage of Capacitor Units Removed from Series Group

36

Authorized licensed use limited to: CHILECTRA. Downloaded on August 05,2010 at 21:09:19 UTC from IEEE Xplore. Restrictions apply.
IEEE
C37.99-1990

CAPACITOR U N I T S REMOVED FROM ONE SERIES GROUP


PERCENT OF T O T A L NUMBER OF CAPACITOR U N I T S PER SERIES GROUP

Fig 27
Ungrounded Double Y-Connected (Neutrals Tied Together) Capacitor Bank:
Voltage Between Capacitor Bank Neutral and Ground Versus
Percentage of Capacitor UNts Removed from Series Group

outside situation that affects both sections of the neutral and ground. The relay should have a
capacitor bank in the same manner. The current harmonic filter. The amount of neutral-to-ground
transformers can be subjected to switching tran- voltage derived due to the loss of individual
sient currents and, therefore, require surge pro- capacitor units can be determined from a curve
tection. They should be sized for single-phase of Fig 27, or from the equations in Appendix B.
load currents if this is a possibility. The relay does The voltage on remaining capacitor units can be
not require a harmonic filter. The unbalance cur- determined from the curves of Fig 28, or from the
rent can be determined from Fig 22, and the equations in Appendix B.
overvoltage on remaining capacitor units can be
determined from Fig 23. 7.8 Neutral Unbalance Protection Method with
In Fig 6(d), the neutrals of the two-capacitor Compensation for Inherent Unbalance. The
sections are ungrounded but tied together. A volt- trend in recent years has been toward larger and
age transformer, or potential device, is used to larger capacitor banks at transmission voltage
measure the voltage between the capacitor bank levels. The neutral unbalance signal due to the

37

Authorized licensed use limited to: CHILECTRA. Downloaded on August 05,2010 at 21:09:19 UTC from IEEE Xplore. Restrictions apply.
IEEE
C37.99-1990 IEEE GUIDE FOR THE PROTECTION OF

W
c3
a
I-
-1
Q
w

CAPACITOR U N I T S REMOVED FROM ONE S E R I E S GROUP-


PERCENT OF TOTAL NUMBER OF CAPACITOR U N I T S PER S E R I E S GROUP

Fig 28
Ungrounded Double Y-Connected (Neutrals Tied Together) Capacitor Bank:
Voltage on Remaining Capacitor Units in Series Group Versus
Percentage of Capacitor Units Removed from Series Group

loss of 1 or 2 individual capacitor units, for these To compensate for this fixed unbalance, it is
very large banks, is such that the inherent unbal- necessary to generate an equal and opposite
ance can no longer be considered neghgible. phasor to be summed with the fixed inherent
Ungrounded banks can be split into two equal capacitor tolerance unbalance phasor, to yield a
banks as illustrated in Fig 8. This bank configura- null or zero signal output. The inherent unbal-
tion inherently compensates for system voltage ance at the neutral of the capacitor bank still
unbalances because the neutral current or volt- exists, but the relay is no longer responsive to this
ages are sensed differentially.However,the effects fixed unbalance component.
of manufacturer’s capacitor tolerance will affect A phase-shifting network with amplitude and
relay operation unless steps are taken to com- phase adjustment is used to generate the com-
pensate for this error. The equations in Appendix pensating phasor. The input for the phase shifter
C may be used to estimate the possible effect of should be bus derived to reduce the effect of nom-
the inherent capacitor bank unbalance. inal system voltage changes. The output of the

38

Authorized licensed use limited to: CHILECTRA. Downloaded on August 05,2010 at 21:09:19 UTC from IEEE Xplore. Restrictions apply.
IEEE
SHUNT CAPACITOR BANKS C37.99-1990

phase shifter, along with the inherent unbalance bank tap. Any subsequent voltage difference
signal, are summed by means of transformers or between capacitor tap voltage and bus voltage
a summing amplifier. will be due to unbalances caused by loss of capac-
It may not be possible or desirable to go to a itor units within that particular phase (see Fig
split bank arrangement, depending on the indi- 9(a)). Loss of capacitor units in each phase is
vidual circumstances of the application. For detected independently [9], [25].
compensation of system voltage unbalance on The sensitivity of this method is h g h and is
single, ungrounded banks, use is made of the fact used, in particular, for high-voltage banks, or
that the voltage appearing at the capacitor bank banks that consist of a large number of individual
neutral due to system unbalance is the zero capacitors.
sequence component. A zero sequence compo-
nent can be derived utilizing three voltage sensing
devices with their high-side Y connected from
line-to-ground, and the secondaries connected in
a broken A (see Fig 7). Very often, the voltage 8. Protection of Very Large
transformers are already available for station EHV Capacitor Banks
relaying, and all that is needed are low-voltage
isolation transformers to derive the broken A. 8.1 Very Large E W Capacitor Banks. A very
The difference voltage between the neutral unbal- large EHV capacitor bank is generally defined as
ance signal due to system unbalance and the one having more than 15 capacitor units in paral-
broken delta output of the voltage transformers lel per series group, and applied at system volt-
is then adjusted to zero by means of an amplitude ages of 345 kV and higher. Figure 12 illustrates a
control. Once this adjustment is made, the effect typical protection scheme. This section describes
of system voltage unbalance will be compensated the special protection schemes applied to very
for all conditions of system unbalance. The large EHV capacitor banks, beyond what is de-
remaining error appearing at the neutral due to scribed in Section 6 and listed in Table 3.
manufacturer’s capacitor tolerance, can be com-
pensated for by means of the phase shifter circuit 8.2 Voltage-Differential Unbalance Protection
previously described. of Very Large Grounded-YConnected Capacitor
Banks. The advent of very large grounded Y-
7.9 Voltage Differential Protection Method, connected capacitor banks at voltages of 345 kV
Grounded Y Bank. A means of compensation for and above has created the need for a protective
inherent unbalance in grounded-Y capacitor device sensitive enough to detect the loss of a
banks is illustrated in Figs 9(a) and 9(b) for single failed capacitor unit, without being a€fected
a single-Y connected bank and a double-Y con- by variable system voltage unbalance. Protective
nected bank, respectively. This approach is, in relay schemes that can compensate for inherent
essence, three single-phase voltage differential capacitor bank voltage unbalance, and fixed sys-
relays for each bank, as applicable. tem voltage unbalance, were covered in Section 7.
A signal responsive to the loss of individual Most of these protection methods cannot com-
capacitor units is derived by comparing capacitor pensate for variable system voltage unbalance
bank tap voltage with the bus voltage. The capac- and are, therefore, not useful for very large EHV
itor bank tap voltage is obtained by connecting a capacitor banks, where the effects of variable sys-
voltage sensing device between the lowest paral- tem voltage unbalance cannot be ignored. For
lel group (or groups) of capacitors and ground. very large EHV capacitor banks, the loss of a sin-
The bus voltage is usually available. Initially, the gle capacitor unit produces a voltage unbalance
voltage levels are adjusted to be equal, assuming that is small compared to the variable system volt-
that all capacitors are good and no fuses have age unbalance, making detection of a single failed
operated. Therefore, the initial difference signal capacitor unit very difficult (see F’lgs 9(a) and
between the capacitor bank tap voltage and the 9(b)). The voltage differential relay, Device 60V in
bus voltage signals is zero, and the capacitor tol- Fig 12, compares the output of the capacitor
erance and initial system voltage unbalance is banKs tap-point voltage monitoring device against
compensated. If the system voltage unbalance the output of the corresponding bus voltage
should vary, the relay system is still compensated, (phase-to-ground) monitoring device for each
since a given percent change in bus voltage results phase. With this method, inherent variable sys-
in the same percent change on the capacitor tem voltage unbalance is readily compensated.

39

Authorized licensed use limited to: CHILECTRA. Downloaded on August 05,2010 at 21:09:19 UTC from IEEE Xplore. Restrictions apply.
IEEE
C37.99-1990 IEEE GUIDE FOR THE PROTECTION OF

8.2.1 Backup Capacitor Bank Unbalance Pro- The low burden for the overcurrent relay,
tection. For very large EHV capacitor banks, Device 51N, is suggested so that if a ground fault
a backup capacitor bank unbalance protection occurs on the bus in the substation, the discharge
scheme may be used. An overvoltage relay, Device of high-frequency currents will not impose a high
59N in Fig 12, is connected to a voltage trans- voltage on the secondary of the current trans-
former (VT) that measures the voltage across a formers to which the protective relays are con-
low-voltage capacitor unit in the capacitor bank nected. Moreover, the time-overcurrent relay,
neutral. Device 59N is set to detect and alarm for Device 51N, should be set on a low tap (for exam-
the removal of a specified number of capacitor ple, 0.1 A) to provide very fast clearing for ground
units that produce 105%or less of rated voltage faults of low magnitudes. These faults normally
as described in 7.3.2. A second or redundant would not operate the phase-overcurrent relays.
overvoltage relay (not shown) can be used, if The ha-frequency outrush current into an
desired, for a second alarm, and can be set to trip external ground fault will not operate the 51N
after a suitable time delay of several hours. The ground relay, however, the unbalanced capacitor
degree of redundancy and required sensitivity bank load current due to the external fault may
affects the cost and, therefore, requires engineer- be sufficient to cause this relay to pickup, thereby
ing as well as economic judgment. tripping the capacitor bank. To prevent this
The overvoltage relay mentioned above should inadvertent tripping, a normally closed contact of
be equipped with a 60 Hz narrow bandpass filter an overvoltage relay, Device 59R, (set to pick up
to avoid false operations due to harmonic cur- at 15 V secondary) is connected in series with the
rents. A third-harmonic-blocking filter may not trip circuit of the ground relay. This voltage relay
prevent all false operations of this relay. prevents bank tripping for faults involving high
8.2.2 Alarm Levels. In cases where an un- values of ground current. It is important that the
planned trip and lockout of the capacitor bank time-overcurrent relay be properly coordinated
can adversely affect the system, it may be desir- with the overvoltage relay. The overvoltage relay
able to have two alarm levels. The first alarm level should open its contact before the time-overcur-
is selected to respond to the isolation of a single rent relay closes its contact. It is also important
capacitor unit, serving as an alert for scheduling that the time-overcurrent relay resets before the
maintenance. The second alarm level, accompa- overvoltage relay.
nied by a time-delayed trip after several hours,
will warn system operators of an impending lock- 8.4 System Overvoltage Protection. For very
out. This time delay is intended to allow the user large EHV capacitor banks, it is advisable to
to de-energize the bank in an orderly fashion. install overvoltage relays on the bus capacitor-
Normally, the capacitor bank voltage unbalance coupled voltage transformers (CCVT), or bus VT
relay would be set to trip when the remaining to de-energize the bank if the bus voltage exceeds
capacitor units in the affected series group of predetermined levels. Three relays, Devices 59B
units are exposed to more than 110%the rated in Fig 12, may trip the bank switching device
capacitor-unit voltage. However, capacitor manu- instantaneously for extreme overvoltage condi-
facturers may permit even greater overvoltages tions. It may be desirable to time delay operation
for a few hours. of Device 59B to prevent nuisance tripping of the
capacitor bank due to transient overvoltages. A
8.3 Bank Overcurrent Protection. Two sets of time-delay overvoltage relay may be used in lieu
three very-inverse nondirectional time-overcur- of the instantaneous overvoltage relay and sepa-
rent relays with instantaneous attachments, rate timer.
Devices 50/51 in Flg 12, are used to provide
primary and backup protection for the capacitor 8.6 Loss of Bus Voltage. Undervoltage relay,
bank for phase faults, as well as ground faults. A Device 27B in Fig 12, connected to the bus VT,will
single non-directional time-overcurrent relay, detect the loss of the supply bus voltage and will
with an inverse time-current characteristic, De- trip the capacitor bank switching device. Trip-
vice 51N in Fig 12, and connected in the neutral ping of the undervoltage relay is delayed by the
of the current transformers associated with the 62UV timer to prevent de-energization of the
phase-overcurrent relays, may be used. This relay bank for transient undervoltage conditions such
should be very sensitive and have a very low as m a t occur when a source-side switching
burden. A solid-state relay may be necessary to device operates to clear a fault and then auto-
obtain the desired sensitivity and low burden. matically recloses. The undervoltage relay should

40

Authorized licensed use limited to: CHILECTRA. Downloaded on August 05,2010 at 21:09:19 UTC from IEEE Xplore. Restrictions apply.
IEEE
SHUNT CAPACITOR BANKS C37.99-1990

be set such that the relay will not operate for breakers may have phase and ground inverse-
voltages that require the capacitor bank to be time overcurrent protection and the reactor bank
placed in service. and capacitor bank switching devices may have
instantaneous and inverse-time overcurrent and
8.6 Capacitor Bank Breaker-FailureProtection. overvoltage protection. Operation of any of these
If the capacitor bank is connected to the bus by a devices will trigger the static-var-system control,
circuit breaker or circuit switcher that is used for resulting in an alarm and trip. Additionally, the
both protecting the bank and switching the bank static-var-system control itself, will produce an
in service, a breaker-failure scheme may be pro- alarm and trip situation for a number of condi-
vided to remove the bank from the system in the tions. These are loss of dc control power, loss of
event that the bangs switching device fails to gate pulse, emergency trip, instantaneous over-
operate correctly for a fault within the capacitor current, time overcurrent, line undervoltage, and
bank. The breaker-failure protection scheme is loss of reference [lo].
initiated by auxiliary relay 62X (or 62Y) in Fig 12, Certain other protective functions may only
which starts the breaker-failure timer. If the fault require an alarm. From the thyristor section,
has not been cleared by the time the breaker- alarms are initiated for maximum air tempera-
failure timer has timed out, other devices in the ture, minimum air flow, dirty filter, or standby
substation will be tripped by the breaker-failure blower rotating in the opposite direction (due to
protection scheme to clear the capacitor bank the backdraft damper being open). Within the
and its switching device from the system. The static-var-system control, an alarm may be initi-
capacitance switching capability of these other ated when there is loss of one dc power source,
devices should be considered. loss of one line-driver pulse, loss of one gate-
driver pulse, or loss of one filter-capacitor unit.
In general, failures can be divided into two
main classes:
(1) Failures or malfunctions that require that
9. Protection of Filter Banks the entire SVG system be disconnected
from the line; and
9.1 Static VAR Control Filters. Static VAR Gen- (2) Failures or malfunctions that require only
erators (SVG) are being used as replacements for part of the SVG system be removed from
synchronous condensers applied to reduce trans- operation.
ient-voltage flicker in arc furnace circuits. They Capacitor banks, switched by conventional
are also being used by an increasing number of means, but used as an integral part of the SVG,
utilities to rapidly supply leading or lagging VARs can be protected by using the unbalance protec-
on transmission systems [23]. F'gure 13 illus- tion methods as described in Section 7.In addi-
trates a typical SVG schematic. tion, the capacitor banks may be tripped as a
Static VAR Generators usually include a number result of a station overvoltage condition.
of internal circuits that protect the SVG in the Similar protective relay schemes can be applied
event of a variety of unique malfunctions. A to thyristor-switched capacitors, modified where
representative list of such malfunctions is shown required by the switching function. Capacitor
below: unbalance protection is still employed in these
(1) Loss of power; latter schemes, but the switched capacitor banks
(2) Loss of line voltage; are usually of a lower voltage than discussed
(3) Loss of synchronism; above, and are not grounded.
(4) Overvoltage on switch; Harmonic problems have been solved by adding
( 5 ) Overcurrent in switch; inductance in series with the capacitor bank,
(6) Unequal current division in switch; thus creating an L-C filter to divert the dominant
(7) Unequal current division in capacitor bank; harmonic currents from the distribution system
(8) Overcurrent in capacitor banks; [ 111. This precludes amplification of the harmon-
(9) Incorrect water temperature; ics, and the possibility of destructive currents, of
(10) Inadequate water flow; and those frequencies oscillating between the capaci-
(11) Incorrect water purity. tor banks and the power system.
Some of the protective capabilities of the SVG In a majority of SVG applications, a trans-
control circuitry are used for both tripping and former is used to connect the relatively low-
alarm. For example, the incoming line circuit voltage thyristor to the high-voltage supply lines.

41

Authorized licensed use limited to: CHILECTRA. Downloaded on August 05,2010 at 21:09:19 UTC from IEEE Xplore. Restrictions apply.
IEEE
C37.99-1990 IEEE GUIDE FOR THE PROTECTION OF

Differential protection of this transformer, the tive sequence currents. Some percentage of nega-
SVG, and the low-voltage bus are often provided. tive sequence current will appear in generators
Backup protective relaying for the SVG is usually and, if it is high enough, it may be detected by
provided just like any other apparatus on the negative sequence relays. It may be prudent,
power system. therefore, to check the magnitude and distribu-
A first consideration is whether to trip the tion of unbalance currents for typical operating
entire SVG in the event of an internal fault, or to conditions if this control mode is used.
arrange for a number of protective zones within
the SVG. For example, a failure in one of the
harmonic filters may only require tripping that 9.2 HVDC Converter Station Filters. All HVDC
branch, provided that particular harmonic cur- converter installations need a reactive power
rent, flowing in the external system for a period supply. Reactive power from power capacitors is
of time, does not cause additional problems such the most economical, and they can act as a shunt
as resonance with the remaining filters. filter with the addition of tuning reactors at a
Also, consideration should be given for backup modest additional cost. These filters, which are
protection. Since the SVG control provides the connected to the ac side of the HVDC converter
basic protective functions for all components of station, are typically tuned for the 1l t h and 13th
the SVG, including the auxiliaries, backup protec- harmonic, plus a high-pass filter [21]. Older
tion for electrical faults in the main components schemes also require filters tuned for the 5th and
should be sufficient. Basically) this is 60 Hz fault 7th harmonic.
current protection for phases and ground. As Protection of the filter banks is accomplished
previously stated, this may require individual by using the same protection methods as for
protection subsystems to obtain desired sensitiv- shunt capacitor banks. However, the filtering
ity and to provide flexibility in system operation. requirements for the unbalance relays can be
Any relays used, of course, should be coordinated more demanding.
with the SVGs control system's protective func- Voltage of the filter capacitors should be rated
tions. high enough to allow for the effect of the har-
Finally, the protection engineer might examine monic current flowing in the capacitor bank [22].
the characteristics of the SVG to determine if Capacitor voltage rating is the arithmetic sum
they could adversely influence the protective of the fundamental and harmonic voltage across
relaying existing in the utility system external to the capacitor:
the SVG.
The most obvious and unique characteristic of
the SVG is the generation of harmonic currents.
In general, the low level of harmonics passed into where
the power system (normally about 4% maximum
as a composite of all harmonics) should not E, =voltage rating of the capacitor
influence the protective relaying. However, spe- Il =fundamental current
cific cases may need to be examined, especially I h = current of the harmonic to which it is
those where harmonics are used for either re- tuned
straint or operation of the relay. For example, XI = fundamental reactance
transformer differential relays use harmonic re- x h = reactance of the harmonic to which it is
straint to prevent operation during inrush condi- tuned
tions. In terms of operating current, a minimum Where both power factor correction capacitor
7.5% second harmonic content is required to banks and thyristor power supplies are used on
restrain some relays. (In these relays, however, the same power system, the capacitor banks may
the majority of applications use 15%minimum.) resonate with the system inductance at harmonic
This is more than the SVG would produce in the frequencies generated by the thyristors. The
transformer for the typical case. It is unlikely that resulting amplification of system harmonic volt-
any existing relaying system will operate falsely ages and currents can create detrimental effects
due to harmonics generated by the SVG with on the power system, as well as in the station
proper filtering. equipment. Capacitor banks and capacitor unit
The SVG can be applied to control each phase fuses may fail when excessive harmonic currents
independently. If operated in this mode, phase oscillate between the capacitor bank and the
currents may be unbalanced, thus producing nega- power system.

42

Authorized licensed use limited to: CHILECTRA. Downloaded on August 05,2010 at 21:09:19 UTC from IEEE Xplore. Restrictions apply.
IEEE
SHUNT CAPACITOR BANKS C37.99-1990

10. Capacitor Bank Equipment Fig 14(a)). If a breakdown were to occur at T2


Considerations in Fig 14(b), the capacitor voltage immediately
attempts to equalize with the system voltage, but
10.1 Capmitor Bank switching Devices. Capac- the circuit is oscillatory and, at the first peak of
itor switching devices require special attention the transient, the capacitor voltage will overshoot
since more severe switching duties exist for the by an amount nearly equal to the difference
interruption of shunt capacitor banks than for between the two voltages immediately prior to
other forms of switching. The various devices that the restrike. If the current is interrupted at the
may be used for capacitor switching include the first high-frequency current zero (T3), the tran-
following. sient voltage peak is trapped on the capacitor
bank The recoveryvoltage reaches avalue greater
Circuit Breakers Interrupter Switches than that following the first interruption, but the
contacts have moved farther apart, and the build-
Air Oil
up of dielectric strength may prevent additional
Air-magnetic sF6 restrikes.
Oil Vacuum
If the gap between the open contacts breaks
sF6 down less than '/4 cycle after a current zero, the
Vacuum
amplitude of the voltage oscillation will not
exceed the normal transient voltage that occurs
Reference should be made to IEEE C37.04-1979 when the bank is first energized. This is defined
(51, ANSI C37.06-1987 [l],and IEEE C37.012- as a reignition rather than a restrike.
1979 (R1988) (41 for rating and application In Fig 14(b), the restrike is shown to occur a
information. full % cycle after current interruption. This is the
All capacitor switching devices should be ap- worst possible condition for the first restrike
plied within their maximum voltage, frequency, because the recovery voltage has reached its
and current ratings, including transient inrush maximum and the resultant surge voltage can,
current and frequency. Since capacitors can be theoretically, reach three times normal line-to-
operated continuously at up to 10% above the ground crest voltage. In actual practice, it seldom
capacitor rated voltage, the switching device exceeds 2% times normal. Additional restrikes
should have at least this voltage rating. can produce hgher crest voltages, and the sudden
The current rating of the switching device voltage changes and high frequency oscillations
should include the effects of system overvoltage may produce other relatively higher voltages else-
(l.lO), capacitor-unit tolerance (1.05 to 1.15), where on the system. Therefore, it is desirable to
and harmonics (1.05 for ungrounded capacitor limit restrikes, or the voltage phenomenon result-
bank, 1.10 for grounded capacitor bank). It is ing from them, in order to protect the entire
usually considered adequate to use a total mul- system.
tiplier of 1.25for ungrounded operation, and 1.35 Under special circuit arrangements, it may be
for grounded operation. Most switching devices possible for some switching devices to interrupt
are derated, for capacitor switching duties, to a the transient current caused by a prestrike when
value well below their continuous current rating. energizing a capacitor bank. The resulting tran-
An important consideration involving applica- sient, when the contacts close, can produce
tion of circuit breakers or circuit switchers for overvoltages.
capacitor switching is the transient overvoltage In a station where large capacitor banks are
that may be generated by restrikes during the connected to a common bus, it may be prudent to
opening operation. At current zero, the capacitor verify that the transient capacitor discharge cur-
is left charged to nearly full peak line voltage. rent into a nearby fault does not exceed the capa-
Very little recovery voltage appears across the bility of any circuit breakers or circuit switchers
switching device contacts at this instant and the connected to the bus. The peak discharge current
capacitance-current arc is usually interrupted at of an individual capacitor bank for a 60 Hz sys-
the first current zero after the switching device tem is:
contacts open. After interruption, the normal
frequency alternation of the voltage on the source
side of the switching device results in a recovery
voltage across the open contacts, % cycle later,
approaching twice the peak line voltage (refer to

43

Authorized licensed use limited to: CHILECTRA. Downloaded on August 05,2010 at 21:09:19 UTC from IEEE Xplore. Restrictions apply.
IEEE
C37.99-1990 IEEE GUIDE FOR THE PROTECTION OF

where connected to the same bus), transient currents of


h g h magnitude and h g h frequency may flow
Ipk = peak discharge current, amperes between the banks on closing of the switching
CB = farads device, or in the event of a restrike on opening.
LS = henrys (total inductace, capacitor bank The oscillatory current is limited only by the
to fault)
impedance of the capacitor banks and the circuit
V u = line-to-line voltage, kV between them. The transient current usually
Transient inrush currents through a switching decays to zero in a fraction of a cycle of the power
device, in addition to involving the contact capa- frequency. The component supplied by the power
bility, may also cause secondary flashover of source is usually so small that it may be neglected.
bushing current transformers (BCT). The voltage The magnitude of inrush current, and its sub-
developed in the secondary circuit is propor- sequent effects to a switched capacitor bank, may
tional to the frequency and magnitude of the be greatly reduced by use of series reactors, or a
transient inrush current: capacitor switching device furnished with prein-
sertion resistors or inductors. When used for
BCT secondary - - transient current (crest) daily switching of back-to-back capacitor banks,
voltage (crest) BCT ratio the life of the switching device contacts can be
X current transformer burden extended by increasing the inductance between
reactance (at 60 Hz) banks. This lowers the inrush current below the
maximum allowable level to reduce contact ero-
Y
transient freauency sion. However, for a given reduction in transient
I\

system frequency current, the preinsertion resistor is more effective


NOTE: The current transformer burden reactance is the sum
in reducing the transient overvoltage.
of the reactances of the current transformer, leads, and the The phenomenon of inrush to a single switched
relay. shunt capacitor bank, and to a bank switched
back-to-back with a parallel energized bank or
The switching equipment manufacturer should
be consulted if the dI/dt or crest values of the banks, has been discussed in 5.1. In a given appli-
inrush currents exceed the limits specified in cation, the currents and voltages associated with
Tables 1A through 3A of ANSI C37.06-1987 [ 11. inrush to a capacitor bank may precipitate unde-
sirable resonant effects with other parts of the
system, induce hazardous surges in station con-
10.2 Inrush Control Devices. The energizing of trol cable, and cause interference with communi-
a capacitor bank will result in a transient inrush cation facilities in the area.
current. The magnitude and frequency of this Closing resistors or inductors on the bank
inrush current is a function of the applied voltage switching device, or current-limiting reactors
(point on the voltage wave at closing), the capac- installed in series with a switched capacitor bank,
itance of the circuit, the inductance of the circuit, will serve to alter the frequency of the inrush
the initial charge of the capacitor bank at the transients, and reduce the magnitude of the
instant of closing, and the damping of the circuit transients. The reactors applied should have a
due to closing resistors or other resistance in the sufficiently high basic impulse level (BIL) rating
circuit. See Appendix D for inrush current calcu- so that gaps or surge arresters, required for reac-
lations. tor protection, will not short out the reactors
The transient inrush current to a single iso- during energization of the capacitor bank
lated bank is less than the available short-circuit In back-to-back switching applications, the
current at the capacitor location. Since a switch- addition of even a minimal amount of inductance
ing device should meet the momentary current between banks will significantly reduce the mag-
requirement of the system, transient inrush cur- nitude of inrush currents flowing from the ener-
rent is not a limiting factor in applying switching gized bank(s) to the bank being energized.
devices on isolated capacitor banks. However, the Grounded-Y shunt capacitor banks, as well as
momentary rating of other switching devices not other substation equipment capable of generat-
intended for fault current interruption should be ing or transmitting high-frequency transients to
checked. the ground mat, should be installed as far away
When capacitor banks are switched back-to- as practical from the control building and cable
back (one or more energized when another is trenches.

44

Authorized licensed use limited to: CHILECTRA. Downloaded on August 05,2010 at 21:09:19 UTC from IEEE Xplore. Restrictions apply.
IEEE
SHUNT CAPACITOR BANKS (37.99-1990

10.3 Surge Arresters. Lightning surges and the secondary winding could be eliminated by ground-
switching of capacitors can result in significant ing the secondary circuit at the CT location, this
system overvoltages. In regions where the light- is not recommended. To do so would impress the
ning activity is high, or in applications where the bank transient potential rise on the secondary
capacitor bank is switched many times daily, cable and present hazardous voltages at the relay
surge arresters may be applied at the capacitor location. Generally, the secondary winding can
bank to limit these transient overvoltages. The withstand these short duration transients with-
ability of the surge arrester to dissipate energy out difficulty. Also, coupling of this transient
that results during capacitor switching opera- voltage to the secondary cable can be greatly
tions is of particular importance to assure proper reduced by routing the cable closely parallel
surge arrester selection. Prestrike and/or re- to the primary ground conductor down to the
strikes in the capacitor bank switching device ground mat and then closely paralleling the
generally cause the highest transient overvoltages, ground mat conductors en route to the relay
particularly for isolated banks. Significant tran- location. In special instances where excessive
sient overvoltages can also occur at the capacitor neutral transient voltages are encountered, it
bank due to surge magnification of resonant may be necessary to insulate the transformer
circuits on the power system associated with case from the local ground to allow connection of
switching of a remote capacitor bank, cable, or one side of the secondary winding to the trans-
transmission line. Metal-oxide type surge arrest- former case. This approach will eliminate the
ers are generally better than silicon-carbide type stress between the secondary winding and the
arresters because they usually have a higher core and will increase the stress between the pri-
energy duty for the same arrester rating, and mary winding and the core. However,the primary
typically absorb less energy per transient event. insulation can generally be expected to be more
robust than the secondary insulation.
10.4 Voltage Sensing Devices. If a voltage trans- To protect the primary winding insulation of a
former, capacitor-coupled voltage transformer, wound primary CT, it is common practice to
or potential device, connected from the bank install a rod gap of 3/s4 to l/i6 in. connected
neutral to ground, is used for unbalance detec- directly across the primary terminals. This will
tion, it should be capable of withstanding switch- limit the voltage impressed across the winding
ing surge voltages of 0.5 to 2.4 times system and prevent primary turn-to-turn breakdown. A
phase-to-neutralvoltage without saturation [ 141. low-voltage surge arrester (varistor) should be
At higher system voltages, higher ratio voltage connected across the secondary terminals to pro-
transformers are required. The use of these higher tect the secondary winding from turn-to-turn
ratio VTs can make the neutralvoltage unbalance breakdown. This device should be insulated from
detection methods become very insensitive. Spe- local ground, again to avoid impressing the bank
cial relaying techniques may be required (see transient potential on the secondary circuit. The
7.6). surge arrester should be chosen to limit the CT
secondary voltage to coordinate with the secon-
10.6 Current Sensing Devices. A reasonably dary circuit insulation voltage rating.
conservative voltage rating for the neutral cur- Nonsimultaneous making and breaking times
rent transformer to withstand the surge voltages of the three poles of the capacitor bank switching
appearing at the bank neutral is 0.2 times the device may allow full phase current to flow in the
system line-to-ground voltage [13]. However, CTs neutral current transformer and relay during the
rated 0.1 of system voltage have been applied switching time. This current can flow for an indef-
without trouble. On small banks, these CTs are initely long period of time if one or two poles of
often wound primary types with low ratios. Dur- the bank switching device fail to operate. For this
ing switching, the bank neutral transient voltage reason, it is important to select the ratio of the
rise can stress the insulation across the (3"s neutral current transformer to result in a secon-
wound primary. It can also stress the insulation dary current of not more that 10 A with full
between the case, which is usually grounded to a capacitor line current in the primary.
local support structure, and the secondary wind-
ing due to the fact that the secondary neutral is 10.6 Surge Protection. The transient current
usually grounded at the remote end (i.e., at the circulating in a capacitor bank during switching
relay location) for safety reasons. Although the is accompanied by an electromagnetic field that
voltage stress between the grounded case and the can induce transient overvoltages in associated

45

Authorized licensed use limited to: CHILECTRA. Downloaded on August 05,2010 at 21:09:19 UTC from IEEE Xplore. Restrictions apply.
IEEE
C37.99-1990 IEEE GUIDE FOR THE PROTECTION OF

apparatus, control systems, and cables. This sec- voltage across the switch before closing, and the circuit-loop
tion will discuss the techniques that experience inductance:
has shown to be effective in minimizing the effects dI/dt = V/L
of these transients. Surge protection techniques for capacitor bank
It is well documented that the switching of applications should take into consideration the
capacitive currents produces transients that are different character of the transient currents pro-
markedly different from those produced by other duced during bank-switching; higher peak cur-
power system switching operations [12]. In the rents and lower oscillation frequencies result,
case of capacitor bank switching, the differences as compared to other power system switching
operations.
Highly damped, non-oscillatory, transient- The circulating paths of the transient currents
current pulses are produced when pre- are also important. These currents flow in the
insertion resistors are employed in the capacitor bank buses, bank ground connections,
bank switching device. Peak currents range capacitor bank ground grid, and, for some condi-
from 1000 to 3000 A. The rise time is about tions, in the bus interconnections between the
1 ps and the fall time is about 600 ps. main switching station and the capacitor bank,
Initial dI/dt is about 3000 A/ps. and in the main station buses and ground grid.
When the main contacts of the capacitor Due to the combination of high current and high
bank switching device close, shorting the frequency, significant transient potential differ-
pre-insertion resistor, oscillatory transient ences can appear across portions of the ground
currents carrying a frequency of 1000 Hz grid due to the grid inductance. The currents are
t o 20000 Hz, a peak current of 1000 to also accompanied by strong high-frequency mag-
2500 A, and a subsequent dI/dt of about netic fields. Therefore, control cables in these
100 Alps are produced. areas are prone to inductive interference and
If resistor pre-insertion is not employed, require careful attention to routing, shielding,
the transient will be oscillatory at frequen- and grounding.
cies in the range of 1000 to 20 000 Hz and 10.6.1 Surge Protection for Current Trans-
the initial dI/dt will be about the same as formers. When the transient currents produced
with resistor pre-inserdon; 1000 Alps. during capacitor bank switching pass through
However, the peak current will be much the primary of the current transformer, its
greater. A typical value is 25 000 A crest. secondary circuit can experience a very large
Similar transient current components can transverse-mode interference voltage. It is not
be superimposed on 60 Hz fault current induced through stray coupling, but rather by the
waveforms for faults in the bank, for bus normal transformer action of the current trans-
faults in the station, and for close-in line former. This can present a serious problem for
faults. both the current transformer and the equipment
If pre-insertion inductors are utilized, peak and instruments that make up its secondary
transient currents are generally less than burden, such as protective relays and data trans-
3000 A. The oscillatory frequency is on the ducers. It is important to note that the reactance
order of several hundred hertz. The maxi- of the burden components at these frequencies
mum dI/dt is, therefore, less than 10 A/ps. can be over 100 times their 60 Hz values. As a
One source [3] has pointed out that additional consequence, high-frequency transient currents,
very high-frequency switching transients of sev- which can be a few hundred amperes, can pro-
eral megahertz (due to traveling waves on the duce extremely high voltages across inductive
capacitor bank bus) will also be produced and burdens.
superimposed on the transients already described. The suggestion is sometimes made that current
This is similar, if not identical, to the transients transformer saturation will prevent the produc-
generated by switching a length of HV bus with a tion of such high secondary voltages. This is not
disconnect switch. true for this situation, however. The secondary
The rate of change of the current, dI/dt, is a volt-second product for each half cycle of the
useful indicator of the potential for inducing high-frequency oscillation is very small compared
interference in nearby control circuits. to that required to produce current transformer
NOTE: Although switching with pre-insertion resistors re-
core saturation at 60 Hz. Therefore, voltage limit-
duces the peak current and eliminates the oscillation,it does ing by current transformer saturation is not likely
not reduce the initial dI/dt. This is determined only by the to occur.

46

Authorized licensed use limited to: CHILECTRA. Downloaded on August 05,2010 at 21:09:19 UTC from IEEE Xplore. Restrictions apply.
IEEE
SHUNT CAPACITOR BANKS
C37.99-1990

Overvoltage protection of the current trans- CB = 2.0 /JF


former secondary circuit is thus required to pre-
vent damage to the current transformer winding The frequency of oscillation is:
and the connected burdens. This usually takes 106
the form of high-current rated varistors or spark f =
27rdWB
gaps connected directly across the current trans-
former terminals. If the current transformer has 106
f =
a wound primary, a gap or an arrester may also
be needed across the primary [20].Varistors ap-
27r &znzi-l
plied to the secondary should be selected with a f = 6015Hz
sufficient energy-absorbing rating to withstand
the secondary current oscillations. Also, to main- The peak current is:
tain voltage limiting action, the varistor size
should be selected so that the peak current does l,, =
Jz
- -103.kvu
not drive it deep into the voltage turn-up region &
on the varistor's V/I curve. Fgure 15 illustrates
this point. Manufacturers of varistors can supply
V/I characteristic curves suitable for checking
this condition.
l,, = Jz
- -103.230
&
E
To a degree, the secondary high-voltage prob- i, = 14 196 A @ 6015 Hz
lem can be minimized by selecting the current
transformer ratio and burden to reduce the level
of the secondary current. Also, eliminating induc- The peak secondary current is:
tive components in the secondary burden will i, (secondary) = 14 196/( 1200:5)
reduce the secondary voltage. Solid-state relays
are particularly beneficial in this respect because = 59.1 A @ 6015 Hz
their current burdens are low and essentially
resistive. The current transformer secondary burden
The foregoing discussion is best illustrated by a impedance, at 60 Hz,is 1 + j l ohms. At 6015 Hz,
numerical example. Fgure 16 shows a one-line the burden impedance is about 1 + jl00 ohms.
diagram for a 230 kV station with a shunt capaci- The peak magnitude of the oscillatory voltage
tor bank. The bank is rated 40000 kvar and is transient across the secondary of the current
Y-connected with a grounded neutral. In the dia- transformer is then:
gram, the line circuit breakers have 1200:5 ratio
current transformers, and the capacitor bank is
in service when a phase-to-ground fault occurs Vmax = d [59.1 ( 1 ) ] 2 + (59.1 (100)12
on line 3, just outside the station. The distance = 5910 V @ 6015 Hz
along the 230 kV circuit from the capacitor bank
to the fault is about 500 feet.
Upon occurrence of the fault, the capacitor This is too much voltage to allow across the
bank discharges through the bus-ground loop relay and instrument burdens, or the current
inductance, which is about 350 pH. Because transformer secondary winding insulation. Some
there is very little resistance in the loop, the cur- means to clamp or limit the voltage to a lower
rent is oscillatory. The frequency of the oscillation amount is required, such as a spark gap or high-
depends on the loop inductance and the bank current varistor.
capacitance. The capacitance of the bank can be Protective relays operating from these current
found from its voltage rating and its 60 Hz kvar transformers, or from the bank-tie current trans-
rating: formers, should also have a filter to exclude the
6 kHz discharge current calculated previously, or
be designed to ignore its presence.
CB = 2.65 kvar
(- *
Vu?03)2
106 The peak voltage, peak current, and frequency
produced in a given installation will vary some-

- (-)
what from this example depending on the bank
(3)
CB = 2.65 40 000 '. 106 capacitance, current transformer ratios, system
230 103 voltage, and burden impedance.

47

Authorized licensed use limited to: CHILECTRA. Downloaded on August 05,2010 at 21:09:19 UTC from IEEE Xplore. Restrictions apply.
IEEE
(37.99-1990 IEEE GUIDE FOR THE PROTECTION OF

10.6.2 Surge Protection of Voltage Transform- formers, and resistance potential devices can,
ers, Capacitor-Coupled Voltage Transformers with some loss in fidelity, reproduce the capaci-
and Resistance Potential Devices. AC voltage tor bank switching transient voltage. It will
signal sources of various types are used in capaci- appear in the transverse mode at the output
tor bank protection schemes to detect abnormal terminals of the device. This, too, may affect the
conditions in the bank Because they are located operation of relay systems.
close to the capacitor bank, these devices can be 10.6.3 Surge Protection of Relay Systems
directly exposed to the transients or surges pro- Associated with Capacitor Banks. It has already
duced during capacitor bank switching. Surge been mentioned that capacitor bank switching
protection of these devices is mainly a concern of produces the same megahertz-type transients
preventing overstressing of the primary-to-sec- that occur in other Hv switching operations, as
ondary insulation, and the secondary-to-ground well as its characteristic high-energy kilohertz-
(case) insulation by the transient ground poten- type transients. Protective relay systems for
tial differences produced in the bank area during capacitor-bank applications should incorporate
switching. surge protection that is effective for both types of
A peninsula grounding arrangement for the interference.
capacitor bank, along with proper control cable Experience has shown that interference in
shielding, grounding, and routing, provides better control circuits, caused by HV switching opera-
surge protection for ac voltage signal sources tions, is always stronger in the common mode
than the single-point grounding scheme. The than in the transverse mode. Surge protection
higher cost of peninsular grounding may be justi- techniques have been directed mostly toward
fied for very large EHV capacitor bank instal- reducing the common mode. Some of these tech-
lations. niques, such as control cable routing, cable
With the single-point grounding arrangement, shielding and grounding, and isolation, which are
the bank neutral transient potential will be about hlghly effective at megahertz frequencies, are also
1/4 that on the capacitor bank bus (20 kV to 60 kV, effective against the kilohertz common mode
or higher). In this case, a voltage transformer interference due to capacitor bank switching,
connected to measure the capacitor bank volt- and are, therefore, recommended for such instal-
age, bus to neutral, would need to be a two- lations.
bushing design so the case could be safely On the other hand, the surge filters (passive
grounded to the station ground grid (see 5.2). Use EM1 filters) used in the inputs to relay systems,
of a single bushing type, with the case (primary although highly effective at megahertz frequen-
ground) connected to the bank neutral, would cies, are ineffective against capacitor bank switch-
impress the neutral transient voltage between ing transients in the kilohertz frequency range.
the case and the secondary winding, which is Passive kilohertz surge filters for relay input
grounded through the control cable at the relay circuits would require much larger inductors and
location. Failure of the secondary winding insula- capacitors, which could present severe loading
tion would be a strong possibility. Figures 17 and problems for current transformers and voltage
18 illustrate the situation. transformers. Such filters are often not practical.
Conventional HV and EHV magnetic type volt- In capacitor bank switching, the kilohertz in-
age transformers often have primary-winding self- terference in the secondary circuits is strongest
resonant frequencies in the range 500 to 2000 Hz. in the transverse mode because, as already de-
If the bank switching frequency coincides with scribed, it is coupled to the secondary circuits
this self resonance, the capacitor bank transient of current transformers and voltage transformers
may be strongly amplified in the voltage trans- by the normal transformer action of these de-
former output voltage. There is probably little vices. Because it is not practical to use passive
risk of damage to the voltage transformer, but the kilohertz filters in the current transformer and
operation of relays and controls connected to the voltage transformer secondary ac relay input cin-
voltage transformer may be adversely affected. A cuits, the required filtering action should be
resistor in series or parallel with the secondary of achieved by other means. One approach is to
the transformer can be used to dampen the oscil- design active filters as an integral part of the
lation. The resistor value should be such that it relay analog signal processing circuits.
does not influence the signal level to the relay. Finally, all ac input connections to the relay
Finally, all types of voltage transducers, voltage system should be protected against overvoltages
transformers, capacitor-coupled voltage trans- by varistors or spark gaps.

48

Authorized licensed use limited to: CHILECTRA. Downloaded on August 05,2010 at 21:09:19 UTC from IEEE Xplore. Restrictions apply.
IEEE
SHUNT CAPACITOR BANKS C37.99-1990

10.7 Control Cables. All control cable duct runs, Such phase-controlled thyristors generate har-
cable trenches, or direct buried control cables not monics, particularly3rd, 5th, 7th, and 11th. More
specifically associated with capacitor controls or instances of parallel resonance are occurring due
protection should be removed from the imme- to this cause. Some examples of harmonic series
diate area around the capacitor bank This is to resonance with utilities, due to adjacent utility
avoid induction of surges into relaying systems, loads, have been noted. This also includes utility
or possible control cable failure during capacitor distribution circuits that have capacitors that
bank switching. supply medium-voltage industrial and commer-
The routing of control cables from neutral cur- cial loads. In most of the instances, some form of
rent transformers or voltage transformers should harmonic voltage and high-harmonic capacitor
be kept at right angles with respect to the com- currents are involved.Higher voltage-rated capac-
mon neutral for single-point grounding, and in itors may be used [IS], [17], [18], [21].
parallel with the tie to the substation ground for Arc furnaces, in the melt part of their cycle,
peninsular grounding to minimize induction. produce a similar array of troublesome harmon-
These induced voltages can also be minimized by ics, including even-ordered harmonics. While the
shielding the cables and using a radial configura- large furnaces are connected to stiff high-voltage
tion for circuits that are completely contained sources, there are, nevertheless, also small instal-
within one cable so that inductive loops are not lations on distribution circuits that produce the
formed. same effect.
Control cables entering the capacitor bank
area should be kept as close as possible to the 11.3 TelephoneInterference. Another objection
ground grid conductors (4/0copper minimum) to harmonics in the power system is the noise
in the cable trench, or on top of the duct run, or interference produced in communications cir-
in contact with the ground grid conductor if directly cuits. Voice frequency noise interference comes
buried. This is mandatory if a peninsula ground is primarily from the residual or zero sequence cur-
used. Multiple control cable shield grounds are rents that are odd multiples of the third (the
recommended: one at the cable termination in ninth and fifteenth harmonic of the fundamental
the capacitor area, another where the cable frequency). Grounded capacitor banks provide a
enters the main cable trench or duct run, and low-impedance path for these currents to flow.
another where the cable enters the control house, The measure of the capability of a power cir-
or at final termination. All spare control cables cuit to act as a noise source is the telephone
should be grounded at both ends, and at inter- influence factor (TIF). This is a dimensionless
mediate points, if available. quantity indicative of wave form [24] (see IEEE
Std 469-1987 [3]).
Before attempting to apply corrective measures
to a capacitor bank that is suspected of causing
11. System Considerations interference, it would be well to locate the source
of the noise. The best corrective measures are
11.1 Resonance. A shunt capacitor bank forms usually applied at the source. If corrections
a resonant circuit with system inductive elements. should be made at the capacitor bank, modifica-
The resonant frequency may be generated during tions to change the resonant frequency can be
the switching of a remote capacitor bank, giving made.
rise t o excessive voltages and currents and the
possible failure of equipment such as other
capacitors, surge arresters, instrument trans- 12. Practices
formers, and fuses. These undesirable resonant
effects are more likely to occur if the capacitor 12.1 Preparation for Initial Energizing
bank switching device has long arcing time and 12.1.1 Visual Inspection. Inspect all fuses for
multiple restrike characteristics. proper connection and clearance. All porcelain
insulators should be clean and have sufficient
11.2 Harmonics. The capacitor bank may also clearance. The bank switching device and ground
resonate with harmonic currents produced else- switch (if used) should be operable. AU asso-
where, such as remote loads. There is extensive ciated equipment should be carefully inspected
and growing use of thyristors in industry to to have no obvious flaws. Capacitor units should
derive variable potential dc from an ac source. be checked for the correct voltage for the desired

49

Authorized licensed use limited to: CHILECTRA. Downloaded on August 05,2010 at 21:09:19 UTC from IEEE Xplore. Restrictions apply.
IEEE
C37.99-1990 IEEE GUIDE FOR THE PROTECTION OF

number of series groups and parallel capacitor 12.1.7 Initial Energization. V e r a that all
units per series group. relaying systems are operational prior to energiz-
Secondary circuits should be checked for proper ing the capacitor bank. The oscillographic equip-
grounding of cable shields and spare control ment should be started immediately before the
wires (see 10.7). Spare control wires should be circuit breaker, circuit switcher, or equivalent
grounded as necessary. switching device is closed. If the relay protection
12.1.2 Testing of Individual Capacitor Units. operates to trip immediately after initial closing,
The capacitance of each capacitor unit may be the following procedure should be initiated
checked to verify that it is within specified toler- (1) Review oscillographic records to determine
ance. Usually, the capacitor manufacturer will the magnitude of the unbalance current or
maintain capacitor tolerances to within +2% of voltage and on what phase.
each other within a given bank. (2) Inspect the bank for blown fuses or possi-
12.1.3 Testing of Relay Protection. The un- ble flashover damage.
balance relay installation that detects the loss of (3) Test capacitors that are not obviously
individual capacitor units should be calibrated to defective, but have blown fuses.
verify proper pickup current and time delay. The (4) Replace the defective capacitors and/or
lockout and trip operation should also be checked. fuses. Capacitors can be removed from
Backup overcurrent relays should be tested to other phases in order to rebalance the
verify proper pickup current and time delay. The bank.
settings used should be compared with the desired (5) If no problem is found with the capacitor
values that have been calculated. bank or relay installation, review the set-
12.1.4 Sensing Devices. Current transformers ting of the relay that tripped with the oscil-
should be checked for ratio, polarity, excitation, lographic data and revise the setting, if
and dielectric strength to ground. The external appropriate.
circuits should be verified for correctness, conti- (6) If the sensitive unbalance relay is oper-
nuity, and dielectric withstand. ating on the inherent unbalance of the
Voltage transformers, capacitor-coupled voltage capacitor bank and should be calibrated, it
transformers, or potential devices should be may be necessary to raise its setting until
checked for ratio, polarity, and dielectric strength the capacitor bank is energized and the
to ground. The nameplate information should be relay is properly adjusted.
checked to reflect the actual settings of the de- With the bank energized, it may be necessary to
vices. All wiring should be checked and complete. calibrate the protection equipment with actual
When practical, the internal and external wiring system voltages and currents applied, especially
should be dielectric tested. if compensation for inherent unbalance is in-
12.1.6 Operational Test. The station control volved.
source voltage should be applied to all protective Secondary currents from the current trans-
devices, and these devices should be made to formers should be recorded along with phase
simulate response to a fault, such as closing the angles to verlfy that the installation is correct,
contacts of an electromechanical relay. The and to provide for future reference.
proper operation of the appropriate switching 12.1.8 Additional Tests. After the capacitor
device should occur. bank has been energized and all protection suc-
12.1.6 Special Recording. An oscillograph or cessfully placed into service, the alarm level (if
portable recorder can assist in diagnosing prob- used) and the lockout level should be checked.
lems associated with initial energization of a large Disconnect one capacitor unit and re-energize
capacitor bank The following parameters should the bank. The alarm should pickup. Verify opera-
be recorded tion of any remote displays, if used. Disconnect
(1) All three-phase currents; the critical number of capacitor units and verify
(2) All three-phase voltages (if voltages are that the sensitive relays will operate to trip and
available); lock out the bank. V e r a proper relay targets and
(3) Capacitor-bank neutral current (or volt- remote displays, if used.
age); and
(4) The outputs of the capacitor-bank sensing 12.2 Response to Alarm or Lockout
devices. 12.2.1 Inspection (after de-energizingbank).
A calibration trace should be run on each Immediately inspect the capacitor bank to deter-
channel used. mine the location of the fault. Identify blown

50

Authorized licensed use limited to: CHILECTRA. Downloaded on August 05,2010 at 21:09:19 UTC from IEEE Xplore. Restrictions apply.
IEEE
SHUNT CAPACITOR BANKS C37.99-1990

fuses and/or obvious capacitor unit failures. If Beehler, J. E. “Capacitance Switching with Power
available, review oscillographic traces. If inter- Circuit Breakers,” IEEE conferenceP a m , 68-CP-
nally fused units are used, the failed units should 161-PWR, 1968.
be located by measuring the capacitance of all
the units. Behrendt, K. C. and Ross, M. W. “Protection Dis-
12.2.2 Capacitor Unit Removal and Replace- tribution Substation Capacitor Banks at Low
ment. Remove the obviously defective capacitor Cost,” Transmission & Distribution, Sep. 1983,
units and test any other capacitor units that have vol. 35,no. 9, pp. 22, 24, 26, 28.
fuses blown. Boskamp, J. B. “Protection of Bulk Capacitor
Replace the removed capacitor units or relo- Banks,” Elsctrical h t h , Dec. 1963/Jan. 1964,
cate existing capacitor units in the bank in order parts I and 11, p. 41.
to rebalance the series parallel groups for capac-
itance and voltage. Relocation of capacitor units Keezer, D. C. and Downing, W. C. Jr. “Relay Pro-
and changes to the bank configuration may tects Floating Neutral Capacitors”, Electrical
require a change in the unbalance relay settings. World,Mar. 11, 1963, p. 86.
In cases where a large number of the capacitor Marek, J. R. “Innovative Fusing Techniques for
units in the bank have blown fuses, for example the Protection of Shunt Capacitor Banks,” IEEE
25% or more, it is advisable to test all capacitor Transactions and Distribution conference,Sep.
units and verlfy fuse ratings. The energizing pro- 1981, no. 81 TD 709-5, p. 5.
cedure noted in 12.1.7 should be followed.
12.2.3 Returning Bank to Service After Lock- Marek, J. R. “Improved Fusing Can Reduce Many
out. If only a few capacitor units have been PCB-Capacitor Problems,” Electric Light and
replaced, the bank can be returned to service R”, vol. 59, no. 11,Nov. 1981, pp. 50, 52.
with a minimum of readjustment of the unbal- McCauley,T. M., Pelfrey, D. L., Roettger, W. C., and
ance relay. These adjustments can be performed Wood, C. E. “The Impact of Shunt Capacitor
after the bank is energized. Installations on Power Circuit Breaker Applica-
If a large number of the capacitor units have tion,” IEEE Transactions on Power Apparatus
been replaced, attention may have to be given to and Systems, vol. PAS-99, no. 6, Nov./Dec. 1980,
recalibration of the sensitive protection after the p. 2210.
bank is re-energized. Refer to 12.1.7.
Additional tests, as noted in 12.1.8,may be per- Mikhail, S. S. and McGranaghan, M. F. “Evaluation
formed in order to verify full protection and of Switching Concerns Associated With 345 kV
alarm. Shunt Capacitor Applications,” IEEE Trasac-
12.2.4 Servicing Bank Following Alarm Con- tions on Power Systems, vol. PWRD-1, no. 2, Apr.
dition. When system conditions permit, the bank 1986, p. 221.
should be taken out of service to replace defective Neumann, M. E. “Philosophy of Shunt Capacitor
capacitor units and/or capacitor fuses. If replace- Bank Protection,” Presented at the canferencefor
ment capacitor units are not available, the bank Protection Relay Enginsers, Allis-Chalmers Cor-
may be rebalanced by removing corresponding poration, Apr. 16- 18, 1973.
units from each series group in all phases. Such
rebalancing, or other changes to the bank confg- Newell, R. J., Risan, M. D., Raatz, D. D., and Hauth,
uration, may require a change in unbalance relay R. L. “Staged Field Testing of the Victory Hill
settings. Static VAR Control,”IEEE Transactions on Power
Apparatus and Systems,vol. PAS-99, no. 2, Mar./
Apr. 1980, p. 426.
Petrus, K. J. “Evaluation of Capacitor Protection,”
13. Bibliography The Line, 81-1, p. 21-8.
Pflanz, H. M. and Lester, G. N. “Control of Over-
Alexander, R. W. “Synchronous Closing Control voltages on Energized Capacitor Banks”, IEEE
for Shunt Capacitors,” IEEE Transactions on Transactions on Power Apparatus and Systems,
Power Apparatus and Systems, Sep. 1985, vol. May/Jun. 1973, T72 541-1, pp. 907-914.
PAS-104, no. 9, p. 2619.
Ransom, J. C. W. and Moulton, C. H. “Relay for
Application of Capacitors to Power Systems, 4th Shunt Capacitor Bank Protection,”Allis-CZws
ed., Westinghouse T & D, pp. 233 - 264. Engiwm-iw Reviau, vol. 31, no. 1, 1966.

51

Authorized licensed use limited to: CHILECTRA. Downloaded on August 05,2010 at 21:09:19 UTC from IEEE Xplore. Restrictions apply.
IEEE
C37.99-1990 IEEE GUIDE FOR THE PROTECTION OF

Saine, J. A., “Shunt Capacitor Bank Connections,” “Unbalance Protection of Large Capacitor Banks,”
Distribution, Jan. 1969,pp. 22-24. Design.Principles and M M ,McGraw-Edison
Company, Feb. 1962.
Schultz, D. E., Shelley, D. A., and Zulaski, J. A.
“Advanced Technology Solves Big Rivers Capaci- Walsh, G. W. “Power System Considerations Relat-
tor Protection Problems,” Electric Light and ing to Thyristor DC Drive Applications,” Indus-
pbwer,vol. 58,p. 51. trial POLoer Systems,vol. 2, no. 2, Jun. 1968.
Stone, H. C. “High-VoltageCapacitor Bank Design Whitman, B. D. ‘‘Internally Fused Capacitors Re-
Factors,” McGraw-Edison Company Technical duce Environmental, Reliability Problems,” Elm-
Bulletin, no. 104,pp. 2-61. tric L i g u and Power, May 1980,p. 39.

52

Authorized licensed use limited to: CHILECTRA. Downloaded on August 05,2010 at 21:09:19 UTC from IEEE Xplore. Restrictions apply.
Appendixes

(These Appendixes are not a part of IEEE C37.99-1990, IEEE Guide for the Protection of Shunt Capacitor Banks,but are
included for information only.)

These Appendixes contain tables, formulas, and currents and frequencies for switching capacitor
equations that will be a source of information to banks, in addition to useful data for evaluating
the relay engineer in determining voltages, inrush the protection of shunt capacitor banks.

Appendix A
Symbol Definitions

V, = line-to-line voltage, V IC = capacitor current at rated voltage, A


V, = line-to-ground voltage, V I@ = normal phase current, A
(use maximum value where appro-
priate) = phase current in one leg of double-
wye bank
AV,, = variation of VLG between phases,
per unit AI@ = change in phase current, A
IN = neutral current, A
S -
- -vm = number of series groups
VC - Vc2 Vc = capacitor
xc - kvar, --
S, = number of series groups, sensing tap IC impedance
to ground
P = number of parallel capacitors per Pmin = required minimum parallel capacitors
per series group t o limit overvoltage
series group to 10%
F, = number of eliminated capacitors
Pminl = for F , type capacitor elimination
within the same series groups
- - within
one phase Pmin2 = for F, type capacitor elimination

F2 = number of series groups within one 4 = variance of phase angle between two
phase which each have a single capac- phases from 120”
itor eliminated AC = per unit variation of capacitance
Vc = rated capacitor voltage, V between phases
VCl = voltage across the series group with VTG = voltage between intermediate tap
removed capacitors, V point and ground, V
AV,, = voltage change across the series vNG = neutral to ground
group with removed capacitors, V V” = voltage between neutrals, V

VCZ = voltage across the series group with kvaru = individual capacitor reactive power
the correct number of capacitors, V rating, kVA
AV,, = voltage change across series group with kvar, = capacitor bank reactive power rating,
the correct number of capacitors, V kVA

53

Authorized licensed use limited to: CHILECTRA. Downloaded on August 05,2010 at 21:09:19 UTC from IEEE Xplore. Restrictions apply.
THIS PAGE WAS
BLANK IN THE ORIGINAL

Authorized licensed use limited to: CHILECTRA. Downloaded on August 05,2010 at 21:09:19 UTC from IEEE Xplore. Restrictions apply.
Appendix B
Equations
(Refer to Appendix A for symbol definitions.)

The following equations have been derived


for the evaluation of shunt capacitor bank
protection.
The change of phase impedance of a bank
with series and parallel groupings is determined
by the location as well as the number of iso-
lated capacitors.
(for F1 = 1and P >> F1)
Approximation of Eq 5 yields for F 1 = 1and
and P >> F1
B1. Equations for Grounded Y Banks (Also A
Banks with V, substituted for VLG)

B2. Equations for Ungrounded Y Banks

P-FI
vc2 = vu S ( P - F l ) + F1

3vu; (P-F,)
vc2 = 3s (P-Fl) + 2F1

Minimum parallel capacitors per series group


are required to limit the capacitor overvoltage
to 10%.
VLG*Fl
For ( F , ) failures only in one series group: VNG = 3s (P-Fl)+ 2F1
11 (S-1)
P-1 = F1* 11 (3s-2)
S P h i = F1*
3s
For single capacitor failures in ( F 2 ) different
series groups:
B3. Equations for Ungrounded Double Y Bank
with Neutrals Tied Together

6Vu*P
'cl = 6s (P-F 1 ) + 5F1
Current and voltage change for F1 capacitor
failures in the same series group relative to
normal values:

55

Authorized licensed use limited to: CHILECTRA. Downloaded on August 05,2010 at 21:09:19 UTC from IEEE Xplore. Restrictions apply.
VLG F1 11 ( 6 s - 5 )
VNG = 6 s ( P - F , ) + 5F,
(Eq 18) Pml = F,
6s

Table B1
60 Hz Fault Current and Voltage with One Unit Shorted
___.

Voltage on Each
Y Bank Remaining Group in Series
Configuration
__-- Fault Current With Faulted Group
- __________

S VLG
Grounded -
s-1 I$* s-1
Single 3 VLG
Ungrounded 3s- 2

Double 6 vu;
Ungrounded 6s-5

*For S=l,the current is the system line-to-ground fault current.

B4. ShredEnergy kvar lo3 = 2.65 kvar


C =
Energy = CV2 = 2.65 X kvar J (W-s)
377 v2 V2

= 2.65 X kvar J (Was) (Eq 2 6 ) v = rms v

56

Authorized licensed use limited to: CHILECTRA. Downloaded on August 05,2010 at 21:09:19 UTC from IEEE Xplore. Restrictions apply.
Appendix C
Equations for Effect of Inherent Unbalances
(Refer to Appendix A for symbol definitions.)

Table C l is intended ils a rule of thumb for on the displacement signal of various bank
determining the effect of inherent unbalances protection schemes.

Table C1
Effect of Inherent Unbalance on Displacement Signal

Shunt Capacitor Effect of Capacitor Effect of System Voltage Effect of System Voltage
Bank Configuration Manufacturing Tolerances Maenitude Changes Phase Angle Change

Grounded Y with 2 P . v ~ ;(sin-)@ varU


Neutral Current AC var g
IN = ____ I& = 2-
Sensing 3 VLG
s.vc2
Ungrounded Y AC*Vu;
with Neutral Potential VNG =
3
Sensing

Ungrounded Double Y AC varg


with Neutral Differential IN = ~

Potential Sensing 6 VLG

Ungrounded Double Y AC-VU;


with Neutral Differential AV" = ~

Potential Sensing 3

Grounded Y with Rm
Differential Potential AVTG = A c * v , * y ( s - s T ) AVTG = 0
Sensing S

57

Authorized licensed use limited to: CHILECTRA. Downloaded on August 05,2010 at 21:09:19 UTC from IEEE Xplore. Restrictions apply.
THIS PAGE WAS
BLANK IN THE ORIGINAL

Authorized licensed use limited to: CHILECTRA. Downloaded on August 05,2010 at 21:09:19 UTC from IEEE Xplore. Restrictions apply.
Appendix D
Inrush Current and Frequency for Switching Capacitor Banks

D1. Energizing an Isolated Bank kvar, 3$ kVA of capacitor bank being


switched
I2 load current of capacitor bank
already energized (A)
kvar, 3~ kVA of capacitor bank already
energized
,i peak current without damping
(actual value about 90%)
106 kvarT kV=, + kvm,
Isc symmetrical rms short circuit cur-
rent (A)
D2. Energizing a Bank with Another on the
Same Bus NOTE: Above expressions for inrush current apply
only for energizing uncharged capacitors. If capacitors

imaX(A) = 1747 /= are charged, as during a restrike across an interrupting


switch, the inrush current may be twice these values.

D3. Typical Values of Inductance Between


= 1330 Capacitor Banks (ANSI / IEEE C37.012-1979)

Rated Inductance Typical


f (kHz) = 9.5 J
F
.=z&G Maximum per Phase Capacitor Bank
Voltage of Bus Inductance
(kV) (PH/ft) (PH)
CB bank capacitance ( p F )
15.5 and 0.214 5
LS system inductance (pH) below
fS system frequency (Hz) 38.0 0.238 5
48.3 0.256 10
Le, total equivalent inductance per phase 72.5 0.256 10
between capacitor banks (pH) 121.0 0.261 10
I1 load current of capacitor bank being 145.0 0.261 10
switched (A) 169.0 0.268 10
242.0 0.285 10
kVLL line-to-linevoltage (kv)
kVLG line-to-ground voltage (kv)

59

Authorized licensed use limited to: CHILECTRA. Downloaded on August 05,2010 at 21:09:19 UTC from IEEE Xplore. Restrictions apply.

Potrebbero piacerti anche