Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
3.1 INTRODUCTION
41
walls of the furnace. Coal and air are burnt in the furnace and the products of
combustion become the flue gas. The flue gas formed in the furnace transfers
the heat to various heat exchangers and leaves the furnace. The location of
various heat exchangers in the furnace is shown in Fig. 3.1.
Fig. 3.2 schematically represents the coal, primary air (PA) and
secondary air (SA) path of the boiler system. The furnace is a tangentially fired
system and the number of coal burner elevations depends on the capacity of the
boiler. For a typical 500 MW unit, there will be nine elevations out of which six
or seven will be functioning during full load conditions.
42
Fig. 3.2 Schematic diagram of Coal, Primary Air and Secondary Air path
The high pressure steam flow to the turbine is controlled to meet the
set load demand in three different ways. These are known as Boiler following
mode, Turbine following mode and coordinated mode. Depending upon the
mode of selection, the boiler demand signal which ultimately regulates the
combustion process is derived from the master pressure control of Boiler-
43
Turbine-Generator unit. The method of deriving the boiler demand signal
corresponding to different modes of operation is discussed in next section.
Fig. 3.3 schematically represents the steam and water path of the
boiler system. The main steam (MS) pressure at the boiler outlet remains
constant if the steam production in circulation system is equal to the demand of
steam at the outlet of the boiler.
44
Table 3.1 Generation of Boiler Demand Signal (BDS) for different modes of operation
Coordinated Mode
45
3.4 BASIC REQUIREMENTS FOR THE EVALUATION OF PID
CONTROLLER CONSTANTS
Once these two values are obtained, PID controller constants can be
calculated using any method of interest by referring to Table 3.2. In the case of
controlling the main steam pressure of a boiler, the input (manipulated) variable
is boiler demand and the main steam pressure is the system output (response).
It can be seen from Fig. 3.2 that manipulated variable (Boiler demand) controls
the fuel flow and the hot primary air which carries the powdered coal in the
mills to furnace.
46
Table 3.2 PID controller parameters for different tuning methods
47
Fig. 3.5 MSP variation to step change in Boiler Demand Signal
Tuning Methods
CHR method
PID Values
Ziegler Nichols CHR method with with 20%
method 0% overshoot Overshoot
P 12 9.5 12
I 80 96 80
D 20 16.8 16.8
48
The ProControl P13 platform of ABB has been used as distributed
control system in the 500 MW unit and the same has been emulated in the
simulator model. The PID structure of ProControl P13 in frequency domain is
given by Equation (3.1).
1
𝐺 (𝑠) = 𝐾𝑝 (1 + ( 𝑠 ) + (𝑇𝑉. 𝑠/(1 + 𝑇𝑠. 𝑠))) (3.1)
𝑇𝑁
where each of the four parameters (KP, TN, TV, TS) can be varied at will within
the valid range. Accordingly, the calculated values of KP, TN, and TV are
indicated in Table 3.4. One can choose the KP, TN and TV corresponding to
either Ziegler Nichols method or CHR method with 0% overshoot or 20%
overshoot as shown in Table 3.4. In this work, the controller parameters -
calculated based on 0% overshoot is used as the gain and derivative time are
smaller and integral time is larger for investigating the transient performance
behavior of main steam pressure and main steam temperature due to different
disturbances.
Tuning Methods
PID CHR method
Ziegler Nichols CHR method with with 20%
Values method 0% overshoot Overshoot
KP 12 9.5 12
TN 0.15 0.098 0.15
TV 1.66 1.768 1.40
49
3.5.1 Main Steam Temperature Control
50
Integral Derivative (PID) controller to control the main steam temperature in a
500 MW Utility Boiler.
51
Fig. 3.6 Super heater Steam Temperature Control
52
Table 3.5 Maximum deviation of MS pressure from set point
Allowable
S. No Load Change (% of TMCR per deviations in
minute) MS pressure
(kg/cm2)
1 ±
1. ± 3% for five minutes ±2
• Load is decreased from 500
MW to 425 MW in 5 minutes
• Load is increased from 425
MW to 500 MW in 5 minutes
2 ±
2. ± 5% for five minutes ±3
• Load is decreased from 500
MW to 375 MW in 5 minutes
• Load is increased from 375
MW to 500 MW in 5 minutes
3 ±
3. ± 10% for three minutes ±4
• Load is decreased from 500
MW to 350 MW in 3 minutes
• Load is increased from 350
MW to 500 MW in 3 minutes
54
implemented, the nature of transient response depends on the choice of the
controller parameters. In this work, the researcher has demonstrated the efficacy
of controller parameters obtained through classical tuning algorithm - in
yielding better transient performance of main steam pressure during load
variations.
55
Fig. 3.8 shows the boiler demand signal to correct the pressure variation to its
set value and Fig. 3.9 (blue colour) denotes the actual pressure variation with
respect to time. It is observed that undershoot and overshoot are well within the
desired values specified in the performance requirements in Table 3.5.
56
parameters as kp=5, ki=60.0 and kd=120. These parameters improved the
transient performance of the main steam pressure and temperature during load
variation when compared to the tuning map method. Fig. 3.9 and 3.11 (red
colour) denotes the actual pressure and temperature variation with respect to
time.
Fig. 3.10 Variation in Spray Water Flow Fig. 3.11 Variation in Super
Heater steam Temperature
In this research, based on the step response test, the values of ‘a’ and
‘L’ were extracted and CHR tuning method has been applied. Computer
simulations for load variations were carried out (with the controller parameters
as kp = 9.5, ki = 10.0 and kd = 16.8). The variations in main steam pressure
and temperature due to CHR tuning method is given in Fig. 3.9 and 3.11 (green
colour).
57
3.7 CONCLUSION
In this research, the ability of classical PID controller to meet the desired
transient performance requirements of complex systems during different
disturbances has been demonstrated. Towards this, the main steam pressure and
temperature control of a 500 MW unit has been considered as a case study. The
step response method enables the calculation of controller parameters through
Ziegler-Nichols and Chien-Hrones-Reswick (CHR) methods. Controller
parameters obtained based on CHR method has been used in the computer
simulations to obtain the transient characteristics of main steam pressure and
temperature during a worst load disturbance. An analysis on the transient
performance characteristics prove the applicability of classical tuning methods
to complex systems / processes in determining the PID controller parameters
and in turn providing due credit to PID controllers amidst upcoming modern
controllers. The thesis uses the PID controller parameters obtained using CHR
method for further simulation studies during fuel switching in the following
Chapter 4.
58