Replacement VRV
RXYQQ-T 8 ~ 42 HP 48
Heat Pump
For refurbishment of old R22 VRF
systems
Replacement VRV
RQCEQ-P 10 ~ 30 HP 48
Heat Recovery
1
08/06/2016
Heat Pump
Heat Recovery
Water-cooled
Heat Pump / Heat
Recovery
Replacement VRV
Heat Pump
Approximate cooling capacity [kW] 22 28 34 40 45 49 56 62 67 71 77 83 89 94 98 105 111 116 120 126 132 138 143 147
Approximate heating capacity [kW] 25 32 38 45 50 57 63 69 75 82 88 94 102 107 113 119 126 132 138 145 151 158 163 170
2
08/06/2016
Variable Refrigerant
Temperature control
requirement
throughout the season
Design
capacity
System
point
As outdoor temperature falls, the
capacity of the system is adjusted
merely by reducing the speed of 20° 25° 30° 35°
inverter compressors
Efficiency
3
08/06/2016
Refrigerant T
Variable Refrigerant Temperature Variable Tr
control
Fixed Tr
Automatic VRT mode
20° 25° 30° 35°
Cooling
Higher refrigerant temperature (Tr)
capacity
System
point
As outdoor temperature falls, the
capacity of the system is adjusted
by reducing the speed of 20° 25° 30° 35°
compressors AND by increasing
the evaporation temperature Efficiency
requirement
Design
capacity
System
point
+28%
Seasonal
20° 25° 30° 35°
cooling
Efficiency
Efficiency
4
08/06/2016
+28%
Seasonal Average ESEER of the VRV III range: 5.1
cooling Average ESEER of the VRV IV range: 6.6
Efficiency
Cycle specs.:
TE = 6°C
TC = 40°C
ΔTSH = 5K
ΔTSC = 20K
+17%
ηIS = 0.6
Heat loss factor = 10%
Cycle specs.:
TE = 11°C
TC = 40°C
ΔTSH = 5K
ΔTSC = 16K
ηIS = 0.6
Heat loss factor = 10%
10
5
08/06/2016
The previous example did not count on increased efficiency of the compressor – but this also has
significant impact
The previous example did not count on increased efficiency of the compressor – but this also has
significant impact
6
08/06/2016
Higher refrigerant temperature also means less dehumidification of the air and higher discharge air
temperatures
Dramatically reduced risk of cold draft feeling
Less dehumidification when it’s not necessary (CEE comfort applications)
Example (at these conditions):
FXSQ100P7
Total capacity 6.3 kW
Sensible capacity
6.2 kW
Reduction of temperature
Latent capacity 0.1 kW
Continuous Heating
during defrost
14
7
08/06/2016
… with a unique
technology
This ice needs to be melted
away every once in a while
… that provides
energy both for the
defrost operation VRV IV
defrost and for the
indoor units
15
Capsule Shell
As PCM absorbs
heat energy, it
melts
Temperature falls
16
8
08/06/2016
Capsule Shell
PCM Vessel
Capsule Shell
As PCM absorbs
heat energy, it
melts
Temperature falls
17
18
9
08/06/2016
The Benefit?
• Field piping and indoor unit heat exchangers don’t have to be pressurized and
heated up after the defrost
Return to full capacity after defrost is nearly instantaneous = no need for hot
start
19
45
Quick re-heat
IU Discharge temperature
40
35
Temperature [oC]
30
On VRV IV, the discharge
25 air stabilized at 29°C
Room temperature
20
15 On standard heat pump VRF systems, the
Defrost indoor unit stopped blowing air and the heat
10 exchanger cooled down to as low as -15°C
0
Outdoor temp WB [oC]
-5
17:25 17:30 17:35 17:40 17:45 17:50 17:55 18:00 18:05
20
10
08/06/2016
VRV Configurator
21
22
11
08/06/2016
23
DX heating and
cooling
Low temperature
water heating or
cooling
High temperature
water heating
(up to 80°C)
Ventilation
24
12
08/06/2016
Systems with only Mix of VRV and Split indoor Systems with only
VRV indoor units units (in any ratio) Split indoor units
25
26
13
08/06/2016
Up to 200%
connection ratio for
heat recovery into HT
water
27
28
14
08/06/2016
Details
Outdoor Units
29
30
15
08/06/2016
Inverter compressor – fluent capacity control 24% ~ 100% VRV IV does not have any On/Off compressors
The above modules are for single-module use only! A system with these modules cannot be
upgraded to higher capacity by adding another module!
What’s special about the single-use modules?
They contain the heat accumulation element (PCM vessel) – in order to defrost while
providing heating comfort to the indoor environment, the modules contain the heat
accumulation element. Multi-module systems defrost each module separately, thus they
don’t require the heat accumulation element
31
Inverter compressor – fluent capacity control 24% ~ 100% VRV IV does not have any On/Off compressors
The above modules are for multi-use only! A system with only one of these modules cannot work!
32
16
08/06/2016
Inverter compressor – fluent capacity control 24% ~ 100% VRV IV does not have any On/Off compressors
33
RYYQ10T •
RYYQ12T •
RYYQ14T •
RYYQ16T •
RYYQ18T •
VRV® IV Heat Pump with
continuous heating RYYQ20T •
RYMQ8T • •
RYMQ10T Possible,
• • • •
RYMQ20T • •
Approximate cooling capacity [kW] 11 14 16 22 28 34 40 45 49 56 62 67 71 77 83 89 94 98 105 111 116 120 126 132 138 143 147
Approximate heating capacity [kW] 13 16 18 25 32 38 45 50 57 63 69 75 82 88 94 102 107 113 119 126 132 138 145 151 158 163 170
Other combinations than specified are possible, but with limited piping length allowances!
A maximum of 3 modules can be connected together in one system!
Modules must be interconnected using Daikin piping kits (same as for VRV III)
34
17
08/06/2016
RXYQ10T • • • • •
RXYQ16T • • • •• • • •• •• •• ••• •• •
RXYQ18T • • • • • •• •••
RXYQ20T • • •
Approximate cooling capacity [kW] 11 14 16 22 28 34 40 45 49 56 62 67 71 77 83 89 94 98 105 111 116 120 126 132 138 143 147
Approximate heating capacity [kW] 13 16 18 25 32 38 45 50 57 63 69 75 82 88 94 102 107 113 119 126 132 138 145 151 158 163 170
Other combinations than specified are possible, but with limited piping length allowances!
A maximum of 3 modules can be connected together in one system!
Modules must be interconnected using Daikin piping kits (same as for VRV III)
35
BPMKS967A2 BPMKS967A3
Number of connectable
2 3
indoor units
Max. connectable
7.1 + 7.1 6.0 + 7.1 + 7.1
capacity [kW]
Dimensions [mm] 180 x 294 x 350
Weight [kg] 7.5 8
18
08/06/2016
40 30
30 Continuous operation 20
25 15
Continuous operation
20 10
Pull-up operation
15 5
10 0
0 -10
-5 -20
10 15 20 25 30 10 15 20 25 30
Indoor (on-coil) temperature [°CWB] Indoor (on-coil) temperature [°CDB]
Heating operation is blocked by software
Wet-bulb temperature! Capacity tables assume ~50% relative humidity. above 25°CDB outdoor temperature
37
40 30
Continuous operation
35 25
PRELIMINARY
30 20
25 15
Continuous operation
PRELIMINARY
20 10
15 5
10 0
5 -5
0 -10
-5 -20
5 10 15 20 25 25 30 35 40 45
Leaving water temperature [°C] Leaving water temperature [°C]
Heating operation is blocked by software
Dry-bulb temperature! above 25°CDB outdoor temperature
38
19
08/06/2016
VRV +
● ● 32 1 module only
Split / SkyAir
VRV + Ventilation
● ● ● ● ● 64 1~3 modules
units
Air Handling Unit
● 64 1~3 modules
(AHU) kits only
No other combinations than listed above are allowed! E.g. no VRV + RA + Hydrobox, or RA + Hydrobox.
39
Air
Combination VRV S Hydro -MF VKM AHU Total Special limits & notes
curt.
• 200% only possible with certain indoor units –
consults Daikin for details
VRV only ● ● 50~200%
• VKM units limit the total connection ratio to
130%
VRV + • VRV / Split / SkyAir indoor units can be mixed in
● ● ● 80~130%
Split / SkyAir any ratio within the total connection ratio limits
No other combinations than listed above are allowed! E.g. no VRV + RA + Hydrobox, or RA + Hydrobox.
40
20
08/06/2016
360° efficiency
… 8 10 12 13 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54
…
VRV® IV Heat Recovery REYQ-T
Approximate cooling capacity [kW] 22 28 34 36 40 45 49 56 62 67 71 77 83 89 94 98 105 111 116 120 126 132 138 143 147
Approximate heating capacity [kW] 25 32 38 41 45 50 57 63 69 75 82 88 94 102 107 113 119 126 132 138 145 151 158 163 170
41
42
21
08/06/2016
Inverter compressor – fluent capacity control 24% ~ 100% Standard compressor – On/Off
© Daikin ‹#›
© Daikin ‹#›
22
08/06/2016
40 30
30 Continuous operation 20
25 15
Continuous operation
20 10
Pull-up operation
15 5
10 0
0 -10
-5 -20
10 15 20 25 30 10 15 20 25 30
Indoor (on-coil) temperature [°CWB] Indoor (on-coil) temperature [°CDB]
Heating operation is blocked by software
Wet-bulb temperature! Capacity tables assume ~50% relative humidity. above 25°CDB outdoor temperature
45
1 module
VRV Classic ● ● 64
systems only
50 ~ 120% • In case of FXFQ20~25A units on 8HP and 10HP systems, the connection ratio is limited to 100%
No other combinations than listed above are allowed! E.g. no VRV + RA + Hydrobox, or RA + Hydrobox.
46
23
08/06/2016
… 4 5 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54
…
VRV III-C Cold Region
Heat Pump RTSYQ-P
Approximate cooling capacity [kW] 11 14 16 22 28 34 40 45 49 56 62 67 71 77 83 89 94 98 105 111 116 120 126 132 138 143 147
Approximate heating capacity [kW] 13 16 18 25 32 38 45 50 57 63 69 75 82 88 94 102 107 113 119 126 132 138 145 151 158 163 170
© Daikin ‹#›
RTSYQ10P
35 100% capacity
Heating Capacity (kW)
30 80% capacity
25
20 28 kW 28 kW
50% capacity RXYQ10P RTSYQ10P
15 18 kW 25 kW
10 34 kW
RXYQ12P
5 20 kW
0 40 kW
-25 -20 -15 -10 -5 0 5 10
RXYQ14P
27 kW
Outdoor temperature [°C]
© Daikin ‹#›
24
08/06/2016
The second stage compressor is active during heat-up and during defrost, providing extra
capacity and shortening both of the processes by about 50% the integrated heating
capacity is higher than on a standard heat pump.
Integrated heating capacity is the heating capacity the unit provides on average over a long period
of time, i.e. heating capacity corrected for the periods of no capacity during defrost.
© Daikin ‹#›
Only the above combinations are possible. Other combinations are not guaranteed to work.
© Daikin ‹#›
25
08/06/2016
35 30
Continuous operation
30 25
25 20
Pull-down operation
20 15
15 10
Continuous operation
10 5
Pull-up operation
5 0
0 -5
(short term only)
-5 -10
-10 -15
-15 -20
-20 -25
10 15 20 25 30 10 15 20 25 30
Indoor (on-coil) temperature [°CWB] Indoor (on-coil) temperature [°CDB]
Heating operation is blocked by software
Wet-bulb temperature! Capacity tables assume ~50% relative humidity. above 25°CDB outdoor temperature
© Daikin ‹#›
26
08/06/2016
… 4 5 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54
…
VRV IV-W Water Cooled RWEYQ-T
Approximate cooling capacity [kW] 11 14 16 22 28 34 40 45 49 56 62 67 71 77 83 89 94 98 105 111 116 120 126 132 138 143 147
Approximate heating capacity [kW] 13 16 18 25 32 38 45 50 57 63 69 75 82 88 94 102 107 113 119 126 132 138 145 151 158 163 170
© Daikin ‹#›
RWEYQ10T • • •• • •• •••
Approximate cooling capacity [kW] 11 14 16 22 28 34 40 45 49 56 62 67 71 77 83 89 94 98 105 111 116 120 126 132 138 143 147
Approximate heating capacity [kW] 13 16 18 25 32 38 45 50 57 63 69 75 82 88 94 102 107 113 119 126 132 138 145 151 158 163 170
© Daikin ‹#›
27
08/06/2016
© Daikin ‹#›
Of course, if the system is supposed to be also used for heating, then an alternative source
of heat in the water loop must be used – a dry cooler will not provide sufficiently warm water at low
ambient temperatures and it also cannot be defrosted. A source of heat can be a low-temperature
condensing boiler, for example.
© Daikin ‹#›
28
08/06/2016
45 45
Continuous operation
40 40
35 35
30 30
25 25
20 20
15 15
10 10
5 5
0 0
-5 -5
-10 -10
-15 -15
10 15 20 25 30 10 15 20 25 30
Indoor (on-coil) temperature [°CWB] Indoor (on-coil) temperature [°CDB]
COOLING HEATING
Inlet water temperature [°CWB]
50 50
45 45
Pull-down operation (short term only)
Continuous operation
40 40
Inlet water temperature [°CDB]
35 35
Pull-up operation (short term only)
30 30
Continuous operation
25 25
20 20
15 15
10 10
5 5
0 0
-5 -5
-10 -10
-15 -15
10 15 20 25 30 10 15 20 25 30
Indoor (on-coil) temperature [°CWB] Indoor (on-coil) temperature [°CDB]
29
08/06/2016
8 HP unit = 149 kg
10 HP unit = 150 kg
The electronics of the unit emit considerable heat – 640 W on the 8HP, 710 W on the 10HP – make
sure you account for this in the choice of location of the “outdoor unit” - the room must be sufficiently
ventilated and its temperature should not exceed 40°C (i.e. free-cooling is usually sufficient)
© Daikin ‹#›
Isolating valves
Flow switch
Service valves
Manometer Thermometer
Filter (included with unit)
= Required!
60
30
08/06/2016
Motor valve
First 15min.is always max.
Max
Motor valve step
During compressor
stop, valve always
close
VRV unit control the motor valve by
Motor valve opening ratio will be maximum 13 steps due to inverter
Min changed every 15 min. due to inverter
compressor frequency compressor frequency.
VRV unit change the valve step every 15
Inverter frequency
Geothermal system in open loop to keep water temperature within operation range
Open loop systems draw ground water directly into the building and heat or cool the heat pumps.
When ground water, lake water, river water or sea water is freely available it can be very economic to use it!
Remark: watch out for corrosion and dirt => if any doubt use heat exchanger!!
31
08/06/2016
Geothermal system in closed loop to keep water temperature within operation range
…
4 5 6 8 10 13 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54
…
VRV IV-Q Replacement
VRV Heat Pump RXYQQ-T
Approximate cooling capacity [kW] 11 14 18 22 28 36 40 45 49 56 62 67 71 77 83 89 94 98 105 111 116 120 126 132 138 143 147
Approximate heating capacity [kW] 13 16 20 25 32 40 45 50 57 63 69 75 82 88 94 102 107 113 119 126 132 138 145 151 158 163 170
© Daikin ‹#›
32
08/06/2016
… 4 5 6 8 10 13 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54
…
VRV III-Q Replacement
VRV Heat Recovery RQCEQ-P
Approximate cooling capacity [kW] 11 14 16 22 28 36 40 45 49 56 62 67 71 77 83 89 94 98 105 111 116 120 126 132 138 143 147
Approximate heating capacity [kW] 13 16 18 25 32 40 45 50 57 63 69 75 82 88 94 102 107 113 119 126 132 138 145 151 158 163 170
© Daikin ‹#›
Indoor Units
Features
Functions
Options
© Daikin ‹#›
6
33
08/06/2016
78
68
59
57
51
49
43
37
31
29
26
22
14
9 capacity sizes
© Daikin ‹#›
6
© Daikin ‹#›
6
34
08/06/2016
FXFQ-A
FXZQ-A
FXCQ-A
FXKQ-MA
FXHQ-A
FXUQ-A
FXAQ-P
FXLQ-P
FXNQ-MA
FXDQ-M9
FXDQ-A
FXSQ-P
FXMQ-P7
FXMQ-MA
Cooling capacity [kW] 1.7 2.2 2.8 3.6 4.5 5.6 7.1 8.0 9.0 11.2 14.0 16.0 22.4 28.0
Heating capacity [kW] 1.9 2.5 3.2 4.0 5.0 6.3 8.0 9.0 10.0 12.5 16.0 18.0 25.0 31.5
© Daikin ‹#›
6
CYV-DK-F-
Free-hanging air curtain
CYV-DK-C-
Cassette air curtain
CYV-DK-R-
Recessed air curtain
FXMQ-MF
Outdoor air processing unit Stops end of 2014
VAM-FA/FB/FC
Heat reclaim ventilation unit
VKM-GB-
Heat reclaim ventilation unit with
pre-cooling / pre-heating
EKEQ-
Air handling unit connection kit
HXY-A
Low temperature hydrobox
HXHD-A
High temperature hydrobox
35
08/06/2016
Details
Standard Units
© Daikin ‹#›
7
FXFQ-A
Cooling capacity [kW] 2.2 2.8 3.6 4.5 5.6 7.1 8.0 9.0 11.2 14.0 16.0 22.4 28.0
Heating capacity [kW] 2.5 3.2 4.0 5.0 6.3 8.0 9.0 10.0 12.5 16.0 18.0 25.0 31.5
© Daikin ‹#›
7
36
08/06/2016
BYCQ140DG
Auto-cleaning panel
1 year of operation (dusty location), ½
INDUSTRY FIRST! year filter cleaning
© Daikin
7 ‹#›
37
08/06/2016
Sensor option BRYQ140A 1) Uses an IR presence sensor to detect persons in the room,
and to…
… divert the air away from persons using the individually
controllable swing-flaps – Especially useful in heating
mode, where air is normally blown down to prevent
stratification
26
saving mode,
22
Sensor option BRYQ140A 2) Uses an IR floor temperature sensor to detect potential air
stratification and uses the individual swing flap control to
divert the air to compensate
Refrigerant
piping
• Requires the BRC1E52- series controller
© Daikin
7 ‹#›
38
08/06/2016
FFQ-C
Cooling capacity [kW] 2.5 3.4 5.0 5.7 6.8 9.5 12.0 13.4 20.0 24.1
Heating capacity [kW] 3.2 4.0 6.0 7.0 7.5 10.8 13.5 15.5 23.0 26.4
© Daikin
7 ‹#›
© Daikin
7 ‹#›
39
08/06/2016
Sensor option BRYQ60A(W/S) 1) Uses an IR presence sensor to detect persons in the room,
and to…
… divert the air away from persons using the individually
controllable swing-flaps – Especially useful in heating
mode, where air is normally blown down to prevent
stratification
26
saving mode,
22
Sensor option BRYQ60A(W/S) 2) Uses an IR floor temperature sensor to detect potential air
stratification and uses the individual swing flap control to
divert the air to compensate
Refrigerant
piping
40
08/06/2016
FXCQ-A
Cooling capacity [kW] 2.2 2.8 3.6 4.5 5.6 7.1 8.0 9.0 11.2 14.0 16.0 22.4 28.0
Heating capacity [kW] 2.5 3.2 4.0 5.0 6.3 8.0 9.0 10.0 12.5 16.0 18.0 25.0 31.5
© Daikin ‹#›
8
FXKQ-MA
Cooling capacity [kW] 2.2 2.8 3.6 4.5 5.6 7.1 8.0 9.0 11.2 14.0 16.0 22.4 28.0
Heating capacity [kW] 2.5 3.2 4.0 5.0 6.3 8.0 9.0 10.0 12.5 16.0 18.0 25.0 31.5
© Daikin ‹#›
8
41
08/06/2016
Easy maintenance
Electrical box and fan motors can be
accessed via the suction opening
FXHQ-A
Cooling capacity [kW] 2.2 2.8 3.6 4.5 5.6 7.1 8.0 9.0 11.2 14.0 16.0 22.4 28.0
Heating capacity [kW] 2.5 3.2 4.0 5.0 6.3 8.0 9.0 10.0 12.5 16.0 18.0 25.0 31.5
© Daikin ‹#›
8
FXUQ-A
Cooling capacity [kW] 2.2 2.8 3.6 4.5 5.6 7.1 8.0 9.0 11.2 14.0 16.0 22.4 28.0
Heating capacity [kW] 2.5 3.2 4.0 5.0 6.3 8.0 9.0 10.0 12.5 16.0 18.0 25.0 31.5
© Daikin ‹#›
8
42
08/06/2016
Fully loaded
Drain pump (500 mm lift) equipped as
standard
© Daikin ‹#›
8
Swing
Discharge outlets of the panel can be closed using an optional accessory KDBHP49B140 &
KDBTP49B140
© Daikin
8 ‹#›
43
08/06/2016
FXAQ-P
Cooling capacity [kW] 1.7 2.2 2.8 3.6 4.5 5.6 7.1 8.0 9.0 11.2 14.0 16.0 22.4 28.0
Heating capacity [kW] 1.9 2.5 3.2 4.0 5.0 6.3 8.0 9.0 10.0 12.5 16.0 18.0 25.0 31.5
© Daikin ‹#›
8
Flexible installation
Floor standing by wall
Wall mounted
Free standing (with optional back panel)
FXLQ-P
Cooling capacity [kW] 2.2 2.8 3.6 4.5 5.6 7.1 8.0 9.0 11.2 14.0 16.0 22.4 28.0
Heating capacity [kW] 2.5 3.2 4.0 5.0 6.3 8.0 9.0 10.0 12.5 16.0 18.0 25.0 31.5
© Daikin ‹#›
8
44
08/06/2016
Flexible installation
Floor standing
Wall mounted
FXNQ-P
Cooling capacity [kW] 2.2 2.8 3.6 4.5 5.6 7.1 8.0 9.0 11.2 14.0 16.0 22.4 28.0
Heating capacity [kW] 2.5 3.2 4.0 5.0 6.3 8.0 9.0 10.0 12.5 16.0 18.0 25.0 31.5
© Daikin ‹#›
8
Only 20 cm deep!
Powerful
Over 40Pa maximum ESP
Quiet
Targeted to be one of the most quiet units of
this type on the market
FXNQ-A
Cooling capacity [kW] 2.2 2.8 3.6 4.5 5.6 7.1 8.0 9.0 11.2 14.0 16.0 22.4 28.0
Heating capacity [kW] 2.5 3.2 4.0 5.0 6.3 8.0 9.0 10.0 12.5 16.0 18.0 25.0 31.5
© Daikin ‹#›
9
45
08/06/2016
Very compact
230 x 502 x 652 mm (HxWxD)
Very versatile
Suction from back or from bottom
Choice of drain outlet side
Air filter standard
FXDQ-M9
Cooling capacity [kW] 2.2 2.8 3.6 4.5 5.6 7.1 8.0 9.0 11.2 14.0 16.0 22.4 28.0
Heating capacity [kW] 2.5 3.2 4.0 5.0 6.3 8.0 9.0 10.0 12.5 16.0 18.0 25.0 31.5
© Daikin ‹#›
9
FXDQ-A
Cooling capacity [kW] 1.7 2.2 2.8 3.6 4.5 5.6 7.1 8.0 9.0 11.2 14.0 16.0 22.4 28.0
Heating capacity [kW] 1.9 2.5 3.2 4.0 5.0 6.3 8.0 9.0 10.0 12.5 16.0 18.0 25.0 31.5
© Daikin ‹#›
9
46
08/06/2016
FXSQ-P
Cooling capacity [kW] 2.2 2.8 3.6 4.5 5.6 7.1 8.0 9.0 11.2 14.0 16.0 22.4 28.0
Heating capacity [kW] 2.5 3.2 4.0 5.0 6.3 8.0 9.0 10.0 12.5 16.0 18.0 25.0 31.5
© Daikin ‹#›
9
47
08/06/2016
FXSQ-A
Cooling capacity [kW] 1.7 2.2 2.8 3.6 4.5 5.6 7.1 8.0 9.0 11.2 14.0 16.0 22.4 28.0
Heating capacity [kW] 1.9 2.5 3.2 4.0 5.0 6.3 8.0 9.0 10.0 12.5 16.0 18.0 25.0 31.5
© Daikin ‹#›
9
FXMQ-P7
Cooling capacity [kW] 2.2 2.8 3.6 4.5 5.6 7.1 8.0 9.0 11.2 14.0 16.0 22.4 28.0
Heating capacity [kW] 2.5 3.2 4.0 5.0 6.3 8.0 9.0 10.0 12.5 16.0 18.0 25.0 31.5
© Daikin ‹#›
9
48
08/06/2016
Versatile
Two ESP levels can be selected from
electrical box
FXMQ-MA
Cooling capacity [kW] 2.2 2.8 3.6 4.5 5.6 7.1 8.0 9.0 11.2 14.0 16.0 22.4 28.0
Heating capacity [kW] 2.5 3.2 4.0 5.0 6.3 8.0 9.0 10.0 12.5 16.0 18.0 25.0 31.5
© Daikin ‹#›
9
Details
Special Units
© Daikin ‹#›
9
49
08/06/2016
CYV-DK-
Heating capacity [kW] 2.5 3.2 4.0 5.0 6.3 8.0 9.0 10.0 12.5 16.0 18.0 25.0 31.5
© Daikin ‹#›
9
CYV S 150 DK 80 F B C
Capacity class (in terms of VRV capacity index): 80, 100, 125, 140, 200, 250
© Daikin ‹#›
1
50
08/06/2016
Cost effective …
Compact …
Highly efficient …
… solution to your
ventilation needs
Temperature exchange
efficiency up to 75%
Enthalpy exchange
efficiency up to 66%
Drastic reduction of heating
/ cooling loads due to
ventilation
Air-flow class 150 250 350 500 650 800 1000 1500 2000
VAM-FA
Ventilation rate [m 3/h] 150 250 350 500 650 800 1000 1500 2000
ESP [Pa] 69 64 98 98 93 137 157 137 137
© Daikin ‹#›
1
VKM-G-
Ventilation rate [m 3/h] 500 750 950
© Daikin ‹#›
1
51
08/06/2016
EKEQ(M/F)CB +
EKEXV-
Cooling capacity [kW] 2.2 2.8 3.6 4.5 5.6 7.1 8.0 9.0 11.2 14.0 16.0 22.4 28.0 44.8 56.0
Heating capacity [kW] 2.5 3.2 4.0 5.0 6.3 8.0 9.0 10.0 12.5 16.0 18.0 25.0 31.5 50.0 63.0
© Daikin ‹#›
1
HXY-A
Cooling capacity [kW] 2.2 2.8 3.6 4.5 5.6 7.1 8.0 9.0 11.2 14.0 16.0 22.4 28.0
Heating capacity [kW] 2.5 3.2 4.0 5.0 6.3 8.0 9.0 10.0 12.5 16.0 18.0 25.0 31.5
© Daikin ‹#›
1
52
08/06/2016
HXHD-A
Cooling capacity [kW] - - - - - - - - - - - - -
Heating capacity [kW] 2.5 3.2 4.0 5.0 6.3 8.0 9.0 10.0 12.5 16.0 18.0 25.0 31.5
© Daikin ‹#›
1
Applicable for:
VRV IV Heat Pump – single modules -
RYYQ-T / RXYQ-T
VRV III-S – RXYSQ-P8
VRV IV-SC – RXYSCQ-T
© Daikin ‹#›
1
53
08/06/2016
107
Capacity class 15 20 25 35 42 50 60 71
Connection to Connection to
Indoor
RYYQ-T / RXYQ-T RXYSQ-T / RXYCSQ-T
FTXV-AB
FTXN-MB
FTX-JV/GV
FTXS-K
CTXS-K
FTXS-G
FTXG-L
FTXZ-N
FVXG-K
FVXS-F
FLXS-B
FDXS-F
Approx. nominal Cooling capacity [kW] 1.5 2.0 2.5 3.5 4.2 5.0 6.0 7.1
Approx. nominal Heating capacity [kW] 1.7 2.5 2.8 4.0 5.4 5.8 7.0 8.2
© Daikin ‹#›
1
FCQG-F
FCQHG-F
FFQ-C
FHQ-C
FUQ-C
FAQ-C
FDBQ-B8
FBQ-C8
FDQ-C
FDQ-B
ACQ-C
AHQ-C
ABQ-C
Cooling capacity [kW] 2.5 3.4 5.0 5.7 6.8 9.5 12.0 13.4 20.0 24.1
Heating capacity [kW] 3.2 4.0 6.0 7.0 7.5 10.8 13.5 15.5 23.0 26.4