Sei sulla pagina 1di 1

7

D of
HA555 EA-383129 P 3-1313003.03 4400004656 3 4 5 6 7
5 NOTES
REV. NO. SHEET NO. DRAWING NUMBER PLANT NO. INDEX JOB ORDER NO. CONTRACT NO.

OW NER.
1 2 115/13.8kV TRANSFORMER (T602) PROTN. SET-1 PANEL-1 +TRPA.21

TS
OF I
CONSENT
A A

SAS
IO BOX (SAS+SCP2)

TTEN
X115KV_BCU-B-IN
1X4S
COMMON

THE W RI
1 3

74/DC 1X4S
DC SUPPLY FAIL SET-1
1 3 2 4 LEGEND

THOUT
SHT.3/6E
DEVICE DESCRIPTION TYPE MAKE
F1
F1 2POLE, 6A MCB EP102UCC06 GE

WI
11 14 WITH AUX. CONTACTS

87T TRANSF. DIFFL. SEL487E SEL

DOCUMENT
12
PROTECTION RELAY
SHT.1/1E

74/86-1 SUPERVISION RELAY FOR LOCKOUT SPER 1C1 ABB


87T TRIP RELAY COIL
B B
A15 A16 74/DC DC SUPVN. RELAY MVAX12 ALSTOM
1X4S

S
RELAY FAULTY

THI
A14 3
SHT.7/2A

FROM
74/86-1

26 25

NED
1X4S
86-1 RLY. OPTD.
27

SHALL BE OBTAI
4
SHT.2/2D

DWG:ED-383632
SHT:28

PART
N
I
C C

FULL OR
SL.NO DESCRIPTION ROUTING SOURCE

1 115/13.8kV, TRANS. T602 (CB-A604) SET-1 DIFF (87T) SEL487E PH-A OPTD THROUGH IEC61850 SEL487E

N
I ON
2 115/13.8kV, TRANS. T602 (CB-A604)) SET-1 DIFF (87T) SEL487E PH-B OPTD THROUGH IEC61850 SEL487E

REPRODUCTI
3 115/13.8kV, TRANS. T602 (CB-A604) SET-1 DIFF (87T) SEL487E PH-C OPTD THROUGH IEC61850 SEL487E
REFERENCE DRAWINGS
4 115/13.8kV, TRANS. T602 (CB-A604) SET-1 74/DC-1 SUPVN OPTD THROUGH IEC61850 I/O BOX DRAWING TITLE DRAWING NO.

DRAWING CONTROL SHEET EE-383111


5 115/13.8kV, TRANS. T602 (CB-A604) SET-1 74/86-1 SUPVN OPTD THROUGH IEC61850 I/O BOX
RELAY & METERING ONE LINE DIAGRAM EA-382856

NO
6 115/13.8kV, TRANS. T602 (CB-A604) SET-1 74/87T DIFF PROT. FAULTY THROUGH IEC61850 I/O BOX

d SA
7 115/13.8kV, TRANS. T602 (CB-A604) SET-1 DIFF. CURRENT ALARM THROUGH IEC61850 SEL487E

onalGri
D D
8 115/13.8kV, TRANS. T602 (CB-A604) SET-1 86-1 LOCKOUT OPTD THROUGH IEC61850 SEL487E

OF Nati
9 115/13.8kV, TRANS. T602 (CB-A604) SET-1 HV WDG TEMP. HIGH TRIP THROUGH IEC61850 SEL487E

10 115/13.8kV, TRANS. T602 (CB-A604) SET-1 LV WDG. TEMP HIGH TRIP THROUGH IEC61850 SEL487E

11 115/13.8kV, TRANS. T602 (CB-A604) SET-1 MAIN TANK (63) BUCHHLOZ TRIP STG. OPTD THROUGH IEC61850 SEL487E

ARE THE SOLE PROPERTY


12 115/13.8kV, TRANS. T602 (CB-A604) SET-1 HV CHAMBER (63) OLTC PROTECTIVE RELAY TRIP THROUGH IEC61850 SEL487E

13 115/13.8kV, TRANS. T602 (CB-A604) SET-1 OLTC TANK 63 PRES. PROT. DEVICE TRIP THROUGH IEC61850 SEL487E

14 115/13.8kV, TRANS. T602 (CB-A604) SET-1 87T DIFF PROT. TRIP THROUGH IEC61850 SEL487E

15 115/13.8kV, TRANS. T602 (CB-A604) SET-1 HV WDG (87REF/HV) MFAC14 OPTD THROUGH IEC61850 SEL487E

16 115/13.8kV, TRANS. T602 (CB-A604) SET-1 LV WDG (87REF/LV) MFAC14 OPTD THROUGH IEC61850 SEL487E
AS-BUILT BY DATE

17 115/13.8kV, TRANS. T602 (CB-A604) SET-1 OLTC TANK 63 PRES. RELAY ALARM THROUGH IEC61850 SEL487E
D 2017-01-09 AES REVISED AS PER CONSULTANT COMMENTS KAM AS AS

N
HEREI
E 18 115/13.8kV, TRANS. T602 (CB-A604) SET-1 MAIN TANK (63) BUCHHLOZ ALARM THROUGH IEC61850 SEL487E E C 2016-11-24 AES AS MANUFACTURED KAM AS AS

B 2016-01-07 AES AS PER CUSTOMER REQUIREMENTS KAM AS AS


19 115/13.8kV, TRANS. T602 (CB-A604) SET-1 HV CHAMBER (63) BUCHHLOZ ALARM THROUGH IEC61850 SEL487E

NED
A 2015-10-12 AES ISSUED FOR DETAILED DESIGN KAM AS AS

CONTAI
20 115/13.8kV, TRANS. T602 (CB-A604) SET-1 49W/TS WDG TEMP ALARM HV WDG THROUGH IEC61850 SEL487E
REV. DATE BY CHKD. CERT. APPD.
DESCRIPTION
NO.
21 115/13.8kV, TRANS. T602 (CB-A604) SET-1 49W/TC WDG TEMP ALARM MV WDG THROUGH IEC61850 SEL487E
DRAWING COMPLETION CERTIFICATE (DCC):

ON
NFORMATI
THE I
DRAWN BY DINAKAR CHECKED BY KAMAL SCALE: NONE

2015-10-12
DATE STARTED DATE COMPLETED

AND
OPR'G. DEPT. ENG. DEPT.

F
F THIS DRAWING IS NOT TO BE USED FOR CERTIFIED

NG
CONSTRUCTION OR FOR ORDERING

DRAW I
MATERIAL UNTIL CERTIFIED AND DATED BY DATE

DC ELEMENTARY DIAGRAM +TRPA.21


115/13.8kV TRF.(T602) PROTN. SET-1 PANEL-1

S
THI
AL-UQAIR 115/13.8kV SUBSTATION-A
MANUFACTURER/VENDOR NAME
AL-UQAIR SAUDI ARABIA
ALFANAR ELECTRICAL SYSTEMS CONTRACT NO. JOB ORDER NO. INDEX PLANT NO. DRAWING NUMBER SHEET NO. REV. NO.
DRAWING NO. SHEET NO. REV. NO.
5
EA-383129 5 of 7 D 1 2 3 4 5 6 7
4400004656 3-1313003.03 P HA555 EA-383129 of
7 D
NG-A (2012/01)

DMS VECTOR NGA00