Sei sulla pagina 1di 1

3

D of
HA555 EA-383184 P 3-1313003.03 4400004656 3 4 5 6 7
02 NOTES
REV. NO. SHEET NO. DRAWING NUMBER PLANT NO. INDEX JOB ORDER NO. CONTRACT NO.

OW NER.
1 2

TS
13.8kV U/V LOAD SHEDDING PANEL-2 +UVLS.2

OF I
SL. DEVICE DEVICE OREDERING SL. DEVICE DEVICE OREDERING
DEVICE FUNCTION MODEL MAKE QUANTITY DEVICE FUNCTION MODEL MAKE QUANTITY
NO. LOCATION NUMBER DATA NO. LOCATION NUMBER DATA

CONSENT
A A

1 U6.01 94LS/B311 HIGH SPEED TRIP SELF RESET RELAY LOR S/R ELECTRO 10 7868FD 8 M1,M2 AC MINIATURE CIRCUIT BREAKER 2 POLE, 10A, C CURVE, 1 C/O CONTACT G62C10 GE 2 674635+672567
U6.02 94LS/B312 FOR U/V PROTECTION SWITCH +CAH
U10.01 94LS/B314 AUX. SUPPLY : 110-125 V DC,
U10.02 94LS/B315 NO. OF DECKS: 8 9 TH THERMOSTAT, 1NC, 0-60 C, 250V AC, 10A PTHT PLASTIM 1 PTHT

TTEN
U14.01 94LS/B316 CONTACTS : 16NO + 16NC
U14.02 94LS/B317 OPERATING COIL : F 1SFA 619 201 R1016
10 HS HEATER SWITCH C2SS2-10B ABB 1
U18.01 94LS/B318 SELF RESET COIL : D

THE W RI
U18.02 94LS/B319
11
U22.01 94LS/B320 DS DOOR SWITCH Z15G1307 HIGHLY 1 Z15G1307
U22.02 94LS/B321
12 IL FLOURESCENT LAMP (127V AC) FC416 MHM 1 FC416
2 U1.101 74/94LS/B311 TRIP RELAY SUPERVISION RELAY SPER 1C1 ABB 10 RS 485 002-AA LEGEND

THOUT
U1.301 74/94LS/B312 AUX. SUPPLY : 125 V DC, 13 SH SPACE HEATER 110-250V AC/DC, 50W PHT050 PLASTIM 1 PHT050
U1.107 74/94LS/B314 CONTACTS : 2C/O
U1.307 74/94LS/B315 SELF RESET

WI
14 X3.1 TERMINAL BLOCK FOR AC ILLUMINATION CIRCUIT WDU6SL WEIDMULLER 10 9537460000
U1.113 74/94LS/B316
U1.313 74/94LS/B317
XTJ TERMINAL BLOCK FOR TELEPHONE JACK WDU4SL WEIDMULLER 4 9537440000

DOCUMENT
15
U1.119 74/94LS/B318
U1.319 74/94LS/B319
U1.125 74/94LS/B320 16 2X3 TERMINAL BLOCK FOR DC AUX. CIRCUITS WDU6SL WEIDMULLER 5 9537460000
U1.325 74/94LS/B321
B B
17 2X5 TERMINAL BLOCK FOR DC CONTROL CIRCUITS WDU4SL WEIDMULLER 12 9537440000

S
THI
2X41 TERMINAL BLOCK FOR TC-1 CIRCUITS M10/10 RS ENTERLEC 46 115-320-27
18
3 TEST SWITCH
FT-19R ABB 3 FR2G 123 123 123

FROM
U28.01 TS4
U28.02 TS5 2X42 TERMINAL BLOCK FOR TC-2 CIRCUITS M10/10 RS ENTERLEC 46 115-320-27
U28.03 TS6 19
U31.01
TS7

NED
U31.02
TS8
U31.03 2X46 WDU4SL WEIDMULLER 46 9537440000

SHALL BE OBTAI
TS9 20 TERMINAL BLOCK FOR SPARE CONTACTS CIRCUITS
U34.01
U34.02 TS10
U34.03 TS11
21 2X4S 3
TS12 TERMINAL BLOCK FOR SAS CIRCUITS M4/6 SNTS ENTERLEC 1SNA115229R2000

4 U37.01 TS13 TEST SWITCH


FT-19R ABB 1 FR2G 123 000 000

PART
PO1
5 U40.01 POWER OUTLET DUPLEX (220/110V AC) EN11 ALF 1 EN11
PO2

N
I
C 6 U40.02 TJ TELEPHONE JACK B106 ALF 1 B106 C

FULL OR
N
I ON
REPRODUCTI
REFERENCE DRAWINGS
DRAWING TITLE DRAWING NO.

DRAWING CONTROL SHEET EE-383111

RELAYING & METERING ONE LINE DIAGRAM EA-382856

NO d SA
onalGri
D D

OF Nati
ARE THE SOLE PROPERTY
AS-BUILT BY DATE

D 2017-01-03 AES REVISED AS PER CONSULTANT COMMENTS KAM AS AS

N
HEREI
E E C 2016-11-24 AES AS MANUFACTURED KAM AS AS

B 2016-01-07 AES AS PER CUSTOMER REQUIREMENTS KAM AS AS

NED
A 2015-10-12 AES ISSUED FOR DETAILED DESIGN KAM AS AS

CONTAI
REV. DATE BY CHKD. CERT. APPD.
DESCRIPTION
NO.

DRAWING COMPLETION CERTIFICATE (DCC):

ON
NFORMATI
THE I
DRAWN BY DINAKAR CHECKED BY KAMAL SCALE: NONE

2015-10-12
DATE STARTED DATE COMPLETED

AND
OPR'G. DEPT. ENG. DEPT.

F
F THIS DRAWING IS NOT TO BE USED FOR CERTIFIED

NG
CONSTRUCTION OR FOR ORDERING

DRAW I
MATERIAL UNTIL CERTIFIED AND DATED BY DATE

LIST OF APPARATUS +UVLS.2


13.8kV U/V LOAD SHEDDING PANEL-2

S
THI
AL-UQAIR 115/13.8kV SUBSTATION-A
MANUFACTURER/VENDOR NAME
AL-UQAIR SAUDI ARABIA
ALFANAR ELECTRICAL SYSTEMS CONTRACT NO. JOB ORDER NO. INDEX PLANT NO. DRAWING NUMBER SHEET NO. REV. NO.
DRAWING NO. SHEET NO. REV. NO.
02
EA-383184 02 of 3 D 1 2 3 4 5 6 7
4400004656 3-1313003.03 P HA555 EA-383184 of
3 D
NG-A (2012/01)

DMS VECTOR NGA00