www.tyco-fire.com
Contacts
NOTICE DEFLECTOR
Do not use the Series RFII in (DROPPED
applications where the air pressure DEFLECTOR POSITION)
above the ceiling is greater than
that below. Down drafts through the
SPRINKLER/SUPPORT CUP
Sprinkler/Support Cup Assembly
ASSEMBLY
can delay sprinkler operation in a fire
situation.
THREAD INTO RETAINER
Operation SUPPORT
CUP UNTIL
WITH THREAD
DIMPLES
MOUNTING
When exposed to heat from a fire, the SURFACE IS EJECTION
Cover Plate, normally soldered to the FLUSH WITH SPRING
Retainer at three points, falls away to CEILING
expose the Sprinkler/Support Cup
Assembly.
The Deflector - supported by the
Guide Pins - then drops down to its
operational position. SOLDER COVER
The glass bulb contains a fluid that TABS (3) COVER PLATE/RETAINER PLATE
expands when exposed to heat. When ASSEMBLY
the rated temperature is reached, the FIGURE 1
fluid expands sufficiently to shatter the SERIES RFII CONCEALED SPRINKLER
glass bulb, activating the sprinkler and
allowing water to flow.
RESPONSE MINIMUM
SPACING
Installation
RATING FLOW/PRESSURE
16’ x 16’ 26.0 GPM / 21.6 PSI
QUICK
The TYCO Series RFII, 5.6 K-factor, (4,9 m x 4,9 m) (98,4 LPM / 1,49 BAR)
Royal Flush Concealed Pendent Sprin- 18’ x 18’ 33.0 GPM / 34.7 PSI
klers, (TY3532) must be installed in QUICK (5,5 m x 5,5 m) (124,9 LPM / 2,39 BAR)
accordance with this section.
20’ x 20’ 40.0 GPM / 51 PSI
General Instructions QUICK (6,1 m x 6,1 m) (151,4 LPM / 3,52 BAR)
Do not install any bulb-type sprinkler
if the bulb is cracked or there is a loss TABLE A
of liquid from the bulb. With the sprin- SERIES RFII (TY3532)
kler held horizontally, a small air bubble 155°F (68°C) AND 200°F (93°C) CONCEALED SPRINKLER
should be present. The diameter of the HYDRAULIC DESIGN CRITERIA
air bubble is approximately 1/16 inch
(1,6 mm) for the 155°F (68°C) and 3/32 Do not attempt to compensate for Step 2. Remove the Protective Cap.
inch (2,4 mm) for the 200°F (93°C) tem- insufficient adjustment in the Sprinkler Step 3. With pipe thread sealant
perature ratings. by under- or over-tightening the Sprin- applied to the pipe threads, hand-
Obtain a 1/2 inch NPT sprinkler joint kler/Support Cup Assembly. Re-adjust tighten the sprinkler into the sprinkler
by applying a minimum to maximum the position of the sprinkler fitting to fitting.
torque of 7 to 14 ft.-lbs. (9,5 to 19,0 suit.
Step 4. Wrench-tighten the sprinkler
Nm). Higher levels of torque can distort Step 1. Install the sprinkler only in the using only the RFII Sprinkler Wrench
the sprinkler Inlet with consequent pendent position with the centerline shown in Figure 3. Apply the RFII Sprin-
leakage or impairment of the sprinkler. of the sprinkler perpendicular to the kler Wrench to the Sprinkler as shown
mounting surface. in the figure.
TFP260
Page 3 of 4
SPRINKLER
SUPPORT CUP
ASSEMBLY
FACE
OF CEILING,
RETAINING RING
MOUNTING
SURFACE FIGURE 4
DISPOSABLE PROTECTIVE CAP
Sprinkler Wrench
Specify: RFII Sprinkler Wrench,
P/N 56-000-1-075