DATA U4

CITY MULTI®
CONTROLLER

1. MITSUBISHI ELECTRIC’S AIR-CONDITIONER NETWORK SYSTEM (MELANS) .............................................CNTR-2


1-1. Function table of controllers ........................................................................................................................CNTR-3

2. LOCAL REMOTE CONTROLLER .........................................................................................................................CNTR-4


2-1. Deluxe MA remote controller [PAR-21MAA] ................................................................................................CNTR-4
2-2. ME remote controller [PAR-F27MEA-US] ...................................................................................................CNTR-5
2-3. Simple MA remote controller [PAC-YT51CRB]............................................................................................CNTR-6
2-4. Wireless remote controller [PAR-FL32MA / PAR-FA32MA] .........................................................................CNTR-7
2-5. LOSSNAY M-NET remote controller [PZ-52SF] ..........................................................................................CNTR-8

3. SYSTEM CONTROLLER ......................................................................................................................................CNTR-9


3-1. System group controller [PAC-SF44SRA] ...................................................................................................CNTR-9
3-2. Schedule timer [PAC-YT34STA] ................................................................................................................CNTR-11
3-3. ON/OFF controller [PAC-YT40ANRA] .......................................................................................................CNTR-13
3-4. Central controller [G-50A] .........................................................................................................................CNTR-15
3-5. Central controller [GB-50A] .......................................................................................................................CNTR-23
3-6. Central controller [AG-150]........................................................................................................................CNTR-31
I
3-7. Central controller [GB-24] .........................................................................................................................CNTR-39
3-8. Power supply unit [PAC-SC50KUA] ...........................................................................................................CNTR-47
3-9. Power supply unit [PAC-SC51KUA] ...........................................................................................................CNTR-50
3-10. Integrated centralized control software [TG-2000A] ..................................................................................CNTR-53
3-11. Electric amount count software [PAC-YG11CDA] .....................................................................................CNTR-57
3-12. PLC software for general equipment [PAC-YG21CDA (SW-PLC-GE)] .....................................................CNTR-58
3-13. BACnet® interface [PAC-YG31CDA (SW-BACnet)] ...................................................................................CNTR-59
3-14. PLC software for demand input [PAC-YG41CDA] .....................................................................................CNTR-60
3-15. LONWORKS® interface [LMAP03U] ..............................................................................................................CNTR-62
3-16. DIDO Controller [PAC-YG66DCA] .............................................................................................................CNTR-64
3-17. AI Controller [PAC-YG63MCA] ..................................................................................................................CNTR-69
3-18. Transmission booster [PAC-SF46EPA] ......................................................................................................CNTR-74

4. SYSTEM COMPONENT .....................................................................................................................................CNTR-75

CONTROLLER
4-1. Y-, R2-, S-Series .......................................................................................................................................CNTR-78
4-2. Outdoor unit input/output connector (Y-, R2-, S-Series) ............................................................................CNTR-79
4-3. Indoor unit “-E” type input/output connector (Y-, R2-, S-Series) ................................................................CNTR-81

CONTROLLER (Feb. 2009) CNTR-1


1. MITSUBISHI ELECTRIC’S AIR-CONDITIONER NETWORK SYSTEM (MELANS) DATA U4

MELANS has a large line-up, including local remote controllers, timers, group controllers, central controllers,
integrated system software, PLC and its software, as well as BMS interface hardware and software. The
combination of the MELANS products can fulfill the requirements of small-scaled control system, middle-
scaled control system up to 2,000 indoor units, and/or large-scaled open systems affiliated with a BMS system.
Moreover, with central controller G-50A/GB-50A, PC browser and remote access (monitoring and operating) via
communication network is possible and easy.

All of the local remote controllers


feature liquid crystal LED displays
and are easy to operate.

Group

1 24

I/O
Controllers


CONTROLLER

(SW-BACnet)

This is a middle-scaled air


conditioning management
system, in which up to 2,000
indoor units can be centrally
controlled

MITSUBISHI ELECTRIC’s CITY MULTI® can be


easily connected to the building management
system through BACnet®.

CNTR-2 CONTROLLER (Feb. 2009)


1. MITSUBISHI ELECTRIC’S AIR-CONDITIONER NETWORK SYSTEM (MELANS) DATA U4

1-1. Function table of controllers


4
4 4
GB-24A Browser *4

CONTROLLER
/ / / /

LMAP03U: LonWorks® Interface


Controls up to 50 Groups/ 50 Indoor,
Details refer to its description.
PAC-YG31CDA: BACnet® Interface Software
(SW-BACnet)
Controls up to 500 Groups/ 500 Indoor,
For details, see its description.

CONTROLLER (Feb. 2009) CNTR-3


2. Local remote controller DATA U3
2. LOCAL REMOTE CONTROLLER DATA U4

2-1. Deluxe MA remote controller [PAR-21MAA]

Functions :Each unit :Each group :Each block


:Each floor :Collective :Not available
Item Description Operations Display
ON/OFF Run and stop operation for a single group
TIME SUN MON TUE WED THU FRI SAT
TIMER Hr ON
AFTER AFTER OFF Switches between Cool / Dry / Auto / Fan / Heat.
ERROR CODE FUNCTION
FILTER Operation mode Operation modes vary depending on the air conditioner unit.
WEEKLY
SIMPLE switching Auto mode is only for the CITY MULTI® R2- and WR2-Series.
ONLY1Hr. AUTO OFF

TEMP. ON/OFF Sets the temperature for a single group


Range of temperature setting
TEMP. Temperature Cool/Dry :
MENU ON/OFF FILTER setting Heat :
BACK MONITOR/SET DAY CHECK TEST
Auto :
( ) For PDFY/PEFY/PFFY by setting Dip SW 7-1 to ON and limits to HIGH fan speed only.
PAR-21MAA CLOCK OPERATION CLEAR
Models with 4 air flow speed settings: Hi/Mid-2/Mid-1/Low
Fan speed
Models with 3 air flow speed settings: Hi/Mid/Low
setting
Models with 2 air flow speed settings: Hi/Low

Air flow Air flow direction angles 100% - 80% - 60% - 40%, Swing,
direction Louver ON/OFF
setting Air flow direction settings vary depending on the model.
High-quality white color body and light-green display. ON/OFF/Temperature setting can be done up to 8 times one
Dot liquid-crystal display is applied. Weekly
day in the week.
Timer
Choose from Japanese, Chinese, English, Germany, The time can be set by the minute.
Spanish, Russian, Italian, French displays. Individually prohibit operation of each local remote control
Connectable to all CITY MULTI® indoor unit, and automati- function (Start/Stop, Change operation mode, Set
1
temperature, Reset filter).
cally adjust its function with the indoor unit connected. Permit / Prohibit
1: When the local remote controller inactivation command
local operation
Limiting temperature setting range is possible. is received from the master system controller,
Help to avoid over-cooling or over-heating. Save energy. " " is displayed.
Auto-stop timer is available.
By the setting from System Controller, the operation for the
Help to avoid forgetting to stop the air conditioner. Prohibition/permission
of specified mode following modes is prohibited.
Weekly timer is available. (Cooling prohibited At cooling prohibited : Cool, Dry, Auto,
ON/OFF/Temperature setting 8 times per day, 1 week /heating prohibited At heating prohibited : Heat, Auto,
scheduling. /cooling-heating prohibited) At cooling-heating prohibited : Cool, Heat, Dry, Auto
Grouping via cross-over wire directly. Indoor unit intake Measures the intake temperature of the indoor unit when
Usable as the local remote controller for system temperature the indoor unit is operating.
controller (MELANS)
When an error is currently occurring on an air conditioner
Combining ME remote controller and/or LOSSNAY Error
unit, the afflicted unit and the error code are displayed.
remote controller in a group is not possible.
Test run This operates air conditioner units in test run mode.

Up to 16 indoor units can be connected to an interlocked


Ventilation system that has one LOSSNAY. LOSSNAY items that can
equipment be set are "Hi" "Low" "Stop". Ventilation mode switching is
not available.

System example Function to limit The range of room temperature setting can be limited by the
the setting range initial setting.The lowest limit temperature can be made higher
of room ying, while the upper
temperature limit temperature lo
CONTROLLER

(Set temperature
range limit)

Easy-to-operate Setting/releasing of simplified locking for remote control


simplified locking switch can be performed.
function · Locking of all switches
(Auto lock function) · Locking of all switches except Start/Stop switch
Non-polarized
Non-polarized 2-wire
2-wire
MA MA
remote remote
controller controller

External dimension

(Front view) (Side view) (Rear view) Unit:mm[in.]


83.5 [3- 9 /32 ]
120 [4- 23 /32 ]

19
130 [5-1/8 ] [ 3/4 ] 46 [1-13/16]

CNTR-4 CONTROLLER (Feb. 2009)


2. Local remote controller DATA U3
2. LOCAL REMOTE CONTROLLER DATA U4
2-2. ME remote controller [PAR-F27MEA-US]
2-2. ME remote controller [PAR-27MEA-US]
Functions :Each unit :Each group :Each block
:Each floor :Collective :Not available
Item Description Operations Display
ON/OFF Run and stop operation for a single group
Switches between Cool / Dry / Auto / Fan / Heat.
Operation mode Operation modes vary depending on the air conditioner unit.
switching Auto mode is only for the CITY MULTI® R2- and WR2-Series.
Sets the temperature for a single group
SET TEMP. ON/OFF Range of temperature setting
SET TEMP. Temperature Cool/Dry :
setting Heat :
MODE TIMER CLOCK ON OFF FAN SPEED AIR DIRECTION FILTER
Auto :
( ) For PDFY/PEFY/PFFY by setting Dip SW 7-1 to ON and limits to HIGH fan speed only.
LOUVER VENTILATION CHECK TEST
Models with 4 air flow speed settings: Hi/Mid-2/Mid-1/Low
PAR-F27MEA-US TIMER SET Fan speed
Models with 3 air flow speed settings: Hi/Mid/Low
setting
Models with 2 air flow speed settings: Hi/Low
Air flow Air flow direction angles 100% - 80% - 60% - 40%, Swing,
direction Louver ON/OFF
setting Air flow direction settings vary depending on the model.

Three timer modes are available with its enhanced Individually prohibit operation of each local remote control
function (Start/Stop, Change operation mode, Set
timer function. Permit / Prohibit temperature, Reset filter). 1

The room temperature can be limited by the initial local operation 1: When the local remote controller inactivation command
is received from the master system controller, "-
setting. By setting the room temperature range CENTRALLY CONTROLLED -" is displayed.
narrower than usual setting, cooling/heating oper-
Indoor unit intake Measures the intake temperature of the indoor unit when
ation with excessive temperature can be prevent- temperature the indoor unit is operating.
ed and thus save energy. When an error is currently occurring on an air conditioner
Error
Allows for simple “button locking” function. unit, the afflicted unit and the error code are displayed.

Thanks to the three timer modes equipped, a proper mode


can be selected to meet the usage.
One day timer : ON/OFF setting of one time on one day can be applied.
Daily timer : ON/OFF setting by the One day timer can be repeated for
Timer operation everyday.
Auto OFF timer : OFF timer can be set in a range from 30 minutes to 4 hours.
Setting of Auto OFF timer automatically activates OFF timer at the next operation.
This function can be utilized to prevent the negligence of OFF setting.
Weekly schedule in only one patterns can be employed by connecting Program timer. 2

Test run This operates air conditioner units in test run mode.

Function to limit The range of room temperature setting can be limited by the
the setting range initial setting.The lowest limit temperature can be made higher
of room ying, while the upper
temperature limit temperature lo
(Set temperature When making the function to limit room temperature setting range
range limit) effective, the operation mode cannot be set to the auto mode.
System example
Easy-to-operate Setting/releasing of simplified locking for remote control
simplified locking switch can be performed.

CONTROLLER
function · Locking of all switches
(Auto lock function) · Locking of all switches except Start/Stop switch

ME ME
remote remote
controller controller

External dimension
(Front view) (Side view) (Rear view) Unit:mm[in.]
83.5 [3- 9 /32 ]
120 [4- 23 /32 ]

19
130 [5-1/8 ] [ 3/4 ] 46 [1-13/16]

CONTROLLER (Feb. 2009) CNTR-5


CONTROLLER Cntr- 5
2. LOCAL REMOTE CONTROLLER DATA U4

2-3. Simple MA remote :Each unit :Each group :Each block


controller [PAC-YT51CRB] :Each floor :Collective :Not available
Item Description Operations Display
ON/OFF Run and stop operation for a single group
Switches between Cool / Dry / Auto / Fan / Heat.
Operation mode
Operation modes vary depending on the air conditioner unit.
switching
Auto mode is the CITY MULTI® R2- and WR2-Series only.
Sets the temperature for a single group
Range of temperature setting
Temperature Cool/Dry :
setting Heat :
Auto :
( ) For PDFY/PEFY/PFFY by setting Dip SW 7-1 to ON and limits to
HIGH fan speed only.

Models with 4 air flow speed settings: Hi/Mid-2/Mid-1/Low


Fan speed setting Models with 3 air flow speed settings: Hi/Mid/Low
Models with 2 air flow speed settings: Hi/Low
Fan speed setting varies depending on the model.

Air flow direction Air flow direction angles (4-angle, Swing) Louver ON/OFF
setting Air flow direction settings vary depending on the model.

Control: START/STOP, room temperature, fan Timer operation Not available

speed, and operation mode selection Individually prohibit operation of each local remote control
The only wiring required is cross-over wiring based Permit / Prohibit function (Start/Stop, Set temperature). 1

local operation 1: When the local remote controller inactivation command is


on two-wire signal lines. received from the master system controller, "CENTRAL" is
Room temperature sensor is built in displayed.

LCD temperature setting and display in 1°C /1°F Indoor unit intake Measures the intake temperature of the indoor unit only when
temperature the indoor unit is operating.
unit.
Set temperature range limit Error
When an error is currently occurring on an air conditioner unit,
the afflicted unit and the error code are displayed.
Can operate all types of indoor units
If additional features are needed beyond Simple MA This operates air conditioner units in test run mode. 2
PAC-YT51CRB capabilities, use it in conjunction with Test run 2: The display for test run mode will be the same as for normal
Deluxe MA PAR-21MAA or Central Controllers AG-150A, start/stop (no display "test run").
G-50A, GB-50A or GB-24. Up to 16 indoor units can be connected to an interlocked system 3 3
Ventilation that has one LOSSNAY.
Using Simple MA PAC-YT51CRB in combination with equipment 3: The interlocked LOSSNAY will be enabled when the indoor
PAR-F27MEA-US M-NET Remote Controller is not unit(s) are enabled. LOSSNAY ON/OFF status is displayed
permitted inside a group. on the Simple MA PAC-YT51CRB. Fan speed and ventilation
mode switching are not available through the Simple MA.
Dimensions: 2-3/4 (W) x 4-3/4 (H) x 1-5/8 (D) in.
Function to limit The range of room temperature setting can be limited by the
the setting range initial setting.The lowest limit temperature can be made higher
of room temp. than the usual (67°F/19°C) at cooling/drying, while the upper
(Set temperature limit temperature lower than the usual (83°F/28°C) at heating.
range limit)
Prohibition/permission By the setting from System Controller, the operation for the
of specified mode following modes is prohibited.
/heating prohibited At cooling prohibited : Cool, Dry, Auto,
/cooling-heating At heating prohibited : Heat, Auto,
prohibited) At cooling-heating prohibited : Cool, Heat, Dry, Auto
CONTROLLER

CENTRALIZED CONTROLLER AG-150A

AG-150A

PAC-SC51KUA
Power supply

CNTR-6 CONTROLLER (Feb. 2009)


2. LOCAL REMOTE CONTROLLER DATA U4

2-4. Wireless remote controller


[PAR-FL32MA / PAR-FA32MA]
Functions :Each unit :Each group :Each block
:Each floor :Collective :Not available
Item Description Operations Display
ON/OFF Run and stop operation for a single group
Switches between Cool / Dry / Fan / Heat / Auto.
Operation mode
Operation modes vary depending on the air conditioner unit.
switching
Auto mode is only for the CITY MULTI® R2- and WR2-Series.
Sets the temperature for a single group
ON/OFF
Temperature Range of temperature setting
setting Cool/Dry :
Heat :
Auto :
Models with 4 air flow speed settings: Hi/Mid-2/Mid-1/Low
Fan speed setting
HEAT COOL
Models with 2 air flow speed settings: Hi/Low

Air flow direction Air flow direction angles 100% - 80% - 60% - 40%, Swing.
setting Air flow direction settings vary depending on the model.

Timer operation One ON/OFF setting can be set for one day.

PAR-FL32MA PAR-FA32MA Individually prohibit operation of each local remote control


Permit / Prohibit function (Start/Stop, Change operation mode, Set temperature,
(Signal receiving unit) local operation 1
Reset filter).
If operation is performed when the local remote controller
It can operate in a group system without requiring inactivation command is received from the main system
address settings. controller, a buzzer will ring and an LED will flash.

When operating, it displays LED lamps. When


Indoor unit intake Measures the intake temperature of the indoor unit when the
errors occur, the error code can be shown by the temperature indoor unit is operating.
LED flash count.
When an error occurs on the air conditioner unit, the operation
If an indoor unit with different functionality is operating inside the Error lamp on the signal receiving unit will flash.
same group, please note there may be cases when functionality
is partially disabled for batch control. Test run This operates air conditioner units in test run mode.
Wireless remote controllers can only be used for a single refrig-
erant system. Ventilation Up to 16 indoor units can be connected to an interlocked system
equipment that has one LOSSNAY.
If you use a system controller to centrally control a group, you
will need cross-wiring between indoor units when using a wire- Some models will have different display for the air flowdirection and fan speed.
less remote controller. Set the air flow direction and fan speed when performing initial setting.
Also ensure there is no difference between the group setting of
the main system controller and the cross wiring across indoor
units when wiring and setting cross wires.

System example

CONTROLLER
Non- Non-
Non-polarized polarized polarized
2-wire 2-wire 2-wire
Signal Signal Signal
receiving receiving receiving
unit unit unit

Wireless Wireless Wireless


remote remote remote
controller controller controller

External dimension
Unit:mm[in.]
PAR-FL32MA PAR-FA32MA
58[2-9/32] 19[3/4]

70[2-3/4] 22.5[7/8] 9.9[3/8]


CHECK TEST RUN
MODEL SELECT %C
4.8[3/16]
AMPM

AMPM
19[3/4]

NOT AVAILABLE

ON/OFF TEMP
ON/OFF
159[6-1/4]

83.5[3-9/32]
120[4-23/32]

35.2[1-3/8]

HEAT COOL
[3/16]
4.6

9.2[3/8]

CONTROLLER (Feb. 2009) CNTR-7


2. LOCAL REMOTE CONTROLLER DATA U4

2-5. LOSSNAY M-NET remote controller [PZ-52SF]


Functions :Each unit :Each group :Each block
:Each floor :Collective :Not available
Item Description Operations Display
ON/OFF Run and stop operation for a LOSSNAY unit
CENTRAL INTERLOCKED
HEAT EX.
BY-PASS Switches between automatic ventilation/ vent - heat
AUTO

CHECK
interchange/ normal ventilation
NOT AVAILABLE FILTER Note: Operation modes vary depending on the model.
Operation mode When connecting to only models without a damper,
switching these models cannot be used.("NOT AVAILABLE" will
ON/OFF appear in the display.)

Temperature
Not available
FILTER
setting
Models with 2 air flow speed settings: Hi/Low
Fan speed setting When only connected to single notch models, this function is
disabled.

Air flow direction Not available


setting
Timer operation Not available
Stand-alone LOSSNAY operation is possible by
Individually prohibit operation of each local remote control
commands from a central controller or LOSSNAY Permit / Prohibit function (Start/Stop, Reset filter). 1
local operation
remote controller. (AG-150A/G(B)-50A/GB-24A is a 1: When the local remote controller inactivation command is
received from a master system controller, " CENTRAL " is
central controller that supports LOSSNAY operation.) displayed.
The LOSSNAY remote controller is capable of Indoor unit intake Not available
changing the air flow and vent modes. temperature
All the wiring is cross-wiring that uses non-polar Error When an error occurs on the air conditioner unit, the operation
lamp on the signal receiving unit will flash.
two wire system signal cables.
: When setting up a LOSSNAY stand-alone system or when set- There is no test run switch for LOSSNAY remote controllers.
Test run 2
Set test run on a LOSSNAY by using the test run switch on the
ting up a LOSSNAY and central controller system, connect a LOSSNAY unit.
power supply unit for the signal cables. 2: Cancel by operating the start/stop switch after switching off
: It is impossible to use a LOSSNAY remote controller for LOSS- the LOSSNAY unit test run switch.
NAY unit that is interlocked other indoor unit (except for some
Ventilation Up to 16 indoor units can be connected to an interlocked system
models). equipment that has one LOSSNAY.

This is displayed to indicate it is being operated by an operation


Interlocked control unit's external control terminal for an interlocked system
operation that contains LOSSNAY units and indoor units.

System example External dimension


CONTROLLER

Unit:mm[in.]

LOSSNAY LOSSNAY LOSSNAY LOSSNAY ABS


unit unit unit unit

LOSSNAY remote LOSSNAY remote REMOTE CONTROLLER


controller controller MODEL
PZ-52S F-E

83.5[3-9/32 ]
78[3-1/16]

INPUT VOLTAGE DC30V


0.02A
120[ 4-23/32]

WEIGHT 0.15kg
SERIAL No.

MADE IN JAPAN KT79C117H01

ON/OFF

FILTER
LOSSNAY LOSSNAY LOSSNAY LOSSNAY PAC-SC51KUA
unit unit unit unit
Power supply
LOSSNAY remote LOSSNAY remote
controller controller 8
70[ 2-3/4 ] [5/16] 33[1-5/16 ]
(41[1- 5/8])

48[1-7/8 ]

CNTR-8 CONTROLLER (Feb. 2009)


3. SYSTEM CONTROLLER DATA U4

3-1. System group controller [PAC-SF44SRA]

Auto only supported for the CITY MULTI® R2- and WR2-Series.

( ) For PDFY/PEFY/PFFY by setting Dip SW 7-1 to ON and limits to HIGH fan speed only.

CONTROLLER

CONTROLLER (Feb. 2009) CNTR-9


3. SYSTEM CONTROLLER DATA U4

System example

System
remote
controller
PAC-SC51KUA
Power supply

MA remote MA remote
controller controller

LOSSNAY LOSSNAY LOSSNAY

LOSSNAY
LOSSNAY remote
remote controller controller

External dimension

Unit:mm[in.]
CONTROLLER

(Front view) (Side view)


18.5
130[5-1/8 ] 2[3/32 ] [23/32 ] (Rear view)

83.5[ 3-9/32 ]
120[ 4-23/32 ]

19
[ 3/4 ] 46[1-13/16]

CNTR-10 CONTROLLER (Feb. 2009)


&C=>18<18:>1/:9><:771< -.
3. SYSTEM CONTROLLER DATA U4

&/410?71>581<O#,' &'P
3-2. Schedule timer [PAC-YT34STA]
KD9J?EDI 79>KD?J 79>=HEKF 79>8BE9A
79><BEEH  HEKFEH9EBB;9J?L; 'EJ7L7?B78B;
('
( "J;C ;J7?BI (F;H7J?EDI ?IFB7O
&('"-(+
0$%2,-
)--+' ,KD &ED -K; 0;: ->K H? ,7J -"&+( .D?J9EDJHEB  KD?JI
 =HEKFI&7N?CKC KD?JI9EDD;9J;:?DED;=HEKF
(%%-"/
)+(! )+&"-
+(.) ,--&)
()+-"(' ('
(
('
&( ,9>;:KB;9EDJHEB (D;M;;A
( -&)
(' !$

('
(EF;H7J?EDI97D8;97HH?;:EKJ9EBB;9J?L;BOEH<EH;79>
('
( =HEKF
(F;H7J?ED
-?C;HH;I;J ->;J?C;HI;JJ?D=:;J7?BI97D8;:?I78B;:9EBB;9J?L;BO

('
(
,;JJ?D= ((%
!-
:;J7?BI
(F;H7J?EDFHE>?8?J('
(EF;H7J?EDCE:;I;JJ?D=J;CF;H7JKH;
,9>;:KB;
'KC8;HE<I;JJ?D=F7JJ;HDI-;DDEI;JJ?D=D?D;F7JJ;HDI
<KD9J?ED 'KC8;HE< (F;H7J?ED<EH7M;;A97D8;I;J8OI;B;9J?D=ED;E<J;D
I;JJ?D=I F7JJ;HDI<EH;79>:7O 
'KC8;HE<EF;H7J?EDI.FJE EF;H7J?EDI97D8;I;J?DED;F7JJ;HD

-?C;I;JJ?D=KD?J ->;?J;C97D8;I;J?D<?L;C?DKJ;KD?JI
->;M;;ABOI9>;:KB;E<KFJE =HEKFI
 KD?JI
KHH;DJJ?C;7D::7O
97D8;9EDJHEBB;:M?J>ED;I9>;:KB;J?C;H
?IFB7O HHEHIJ7J;
->;M;;ABOI9>;:KB;E<KFJEJ;DF7JJ;HDIDEI;J
J?D=D?D;F7JJ;HDI?I7L7?B78B;<EHI;JJ?D= .D?JEF;H7J?EDIJ7J;

Z('
(ZZ(F;H7J?ED)HE>?8?JZZ((%
!-Z ->;<EBBEM?D=97D8;?DFKJM?J>J>;B;L;BI?=D7BIEHFKBI;I?=D7BI
NJ;HD7B?DFKJ %;L;BI?=D7BZC;H=;D9OIJEF?DFKJZEHZEBB;9J?L;('
(Z
7D:Z,;J-;CF;H7JKH;Z97D8;I9>;:KB;:M?J>KF -?C;H9EDD;9J?ED )KBI;I?=D7BZEBB;9J?L;('
(ZEHZ%E97BH;CEJ;9EDJHEBB;H
JE I;JJ?D=I?DED;F7JJ;HD ;C;H=;D9OIJEF
?DFKJ;J9 
FHE>?8?J
F;HC?JZ
(D;?DFKJ97D8;I;B;9J;:<HECJ>EI;78EL;
"J97D8;9EDD;9J;:JEJ>;9;DJH7B9EDJHEBJH7DI
C?II?EDB?D;EHJEJ>;?D:EEH
EKJ:EEHJH7DIC?II?ED NJ;HD7BEKJFKJ
Z('
(Z7D:Z;HHEH
DEHC7BZ7H;EKJFKJM?J>J>;B;L;BI?=D7B
HHEHEKJFKJ
B?D;M?J>EKJJ>;FEM;HIKFFBOKD?J "J?IDEDFEB7H EF;H7J?EDEKJFKJ ->;EFJ?ED7BEKJFKJ978B;?IH;GK?H;:
M?H;
"J97D8;?DJ;HBE9A;:M?J>78K?B:?D=C7D7=;C;DJ "D:EEH
EKJ:EEHJH7DIC?II?EDB?D;EDD;9J78B;
EDD;9J?EDFEI?J?ED ;DJH7BIOIJ;CJH7DIC?II?EDB?D;EDD;9J78B;(FJ?ED7BFEM;H
IOIJ;CKI?D=J>;;NJ;HD7B?DFKJ
EKJFKJC7D7=?D= IKFFBOKD?J), $.?ID;;:;: 
<KD9J?ED
D;HHEHKD?J7::H;II7D:;HHEH9E:;7FF;7HED
J>;:?IFB7O?D97I;E<C7B<KD9J?ED>7FF;D?D=

CONTROLLER

CONTROLLER (Feb. 2009) CNTR-11


('-+(%%+ DJH
3. SYSTEM CONTROLLER DATA U4

System example

System
group
controller LOSSNAY
PAC-SC51KUA
Power supply

PAR-F27MEA-US

Schedule timer

PAR-21MAA PAC-YT51CRA

External dimension

Unit:mm[in.]
CONTROLLER

(Front view) (Side view)


18.5
130[5-1/8 ] 2[3/32 ] [23/32 ] (Rear view)

83.5[ 3-9/32 ]
120[ 4-23/32 ]

19 46[1-13/16]
[ 3/4 ]

CNTR-12 CONTROLLER (Feb. 2009)


&C=>18<18:>1/:9><:771<
3. SYSTEM CONTROLLER -.
DATA U4

 "!"<18:>1/:9><:771<O#,' !%P
3-3. ON/OFF controller [PAC-YT40ANRA]

KD9J?EDI 79>KD?J 79>=HEKF 79>8BE9A


79><BEEH  HEKFEH9EBB;9J?L; 'EJ7L7?B78B;
'-+%"3 ('
( "J;C ;I9H?FJ?ED (F;H7J?EDI ?IFB7O

('
( +KD7D:IJEFEF;H7J?ED<EHJ>;7?H9ED:?J?ED;HKD?JI

(F;H7J?EDCE:;
IM?J9>?D=
'EJ7L7?B78B;

-;CF;H7JKH;I;JJ?D= 'EJ7L7?B78B;

7DIF;;:I;JJ?D= 'EJ7L7?B78B;

?H<BEM:?H;9J?EDI;JJ?D= 'EJ7L7?B78B;

&7DK7BEF;H7J?ED
FHE>?8?J
F;HC?J ECF7J?8B;EDBOM?J>;NJ;HD7B?DFKJ
('
(EF;H7J?EDCE:;
I;JJ?D=J;CF;H7JKH;<?BJ;HH;I;J

,F;9?<?9CE:;
EF;H7J?EDFHE>?8?J
=HEKFI
 KD?JI97D8;9EDJHEBB;: 'EJ7L7?B78B;

EEB?D=FHE>?8?J>;7J?D=
FHE>?8?J9EEB?D=
>;7J?D=FHE>?8?J
.FJE =HEKFI
 KD?JI97D8;EF;H7J;:M?J>
ED;('
(H;CEJ;9EDJHEBB;H

+EECJ;CF;H7JKH;:?IFB7O 'EJ7L7?B78B;
=;D;H7BFKHFEI;?DJ;H<79;?I7L7?B78B;<EH9ED %<B7I>;I:KH?D=<7?BKH;
HHEH:?IFB7O
JHEBIE=;D;H7B:;L?9;I97D7BIE8;JKHD;:(' ->;;HHEH9E:;97D8;9ED<?HC;:8OH;CEL?D=J>;9EL;H 

7D:( ,9>;:KB;EF;H7J?ED 'EJ7L7?B78B;


#KIJFH;II7IM?J9>JEIJ7HJ
BBE<J>;KD?JI97D8;IJ7HJ;:7D:IJEFF;:8O
/;DJ?B7J?EDEF;H7J?ED
?D:;F;D:;DJ
HEKFEF;H7J?EDE<EDBO%(,,'2KD?JIFEII?8B;
(DBO('
(E<=HEKF
FH;II?D=J>;C7?DIM?J9>7D:;79>KD?J?DJ>; ->;%(,,'2M?BBHKD?D?DJ;HBE9AM?J>J>;EF;H7J?EDE<?D:EEH
=HEKF97D8;IJ7HJ;:7D:IJEFF;:M?J>?D:?L?:K7B /;DJ?B7J?EDEF;H7J?ED KD?J
?DJ;HBE9A;: ->;<7DH7J;7D:CE:;97DDEJ8;9>7D=;: ->;%M?BBJKHD
IM?J9>;I ('EDBO:KH?D=EF;H7J?ED7<J;H?DJ;HBE9A?D=
%<B7I>?D=:KH?D=<7?BKH;
"<7DO;HHEHI>EKB:E99KH?DJ>;7?H9ED:?J?ED;H?JI
NJ;HD7BEKJFKJ
HHEHEKJFKJ
EF;H7J?EDEKJFKJ
Z('
(Z7D:Z;HHEH
DEHC7BZ7H;EKJFKJM?J>J>;B;L;BI?=D7B
->;EFJ?ED7BEKJFKJ978B;?IH;GK?H;:
:;J7?BI97D8;9ED<?HC;:;7I?BOM?J>J>;<B7I>?D=
"D:EEH
EKJ:EEHJH7DIC?II?EDB?D;EDD;9J78B;
% ->;%7BIE?D:?97J;IM>;J>;H;79>=HEKF EDD;9J?EDFEI?J?ED ;DJH7BIOIJ;CJH7DIC?II?EDB?D;EDD;9J78B;)EM;HIKFFBO
?IHKDD?D=EHIJEFF;: KD?J), $.?ID;;:;: 

"DJ;HBE9AEF;H7J?EDM?J>;NJ;HD7BIOIJ;CFEII?8B;
● Interlock operation with external system possible.
▪ "J97D8;<B;N?8BO?DJ;HBE9A;:M?J>797H:H;7:;H
It can be flexibly interlocked with a card reader,
<?H;7B7HCIOIJ;CEH8K?B:?D=C7D7=;C;DJIOI
or building management system, etc., using the
J;C;J9 KI?D=J>;?D9EHFEH7J;:;NJ;HD7B
incorporated external input/output function.
?DFKJ
EKJFKJ<KD9J?ED
● Flexible group setting.
B;N?8B;=HEKFI;JJ?D=

CONTROLLER

▪ The groups can be easily configured, so the
->;=HEKFI97D8;;7I?BO9ED<?=KH;:IEJ>;
group pattern can be freely set according to the
=HEKFF7JJ;HD97D8;<H;;BOI;J799EH:?D=JEJ>;
layout.
B7OEKJ

▪ The ON/OFF controller can be connected
->;('
(H;CEJ;9EDJHEBB;H97D8;9EDD;9J;:
at the indoor/outdoor transmission line without
7JJ>;?D:EEH
EKJ:EEHJH7DIC?II?EDB?D;M?J>EKJ
the power supply unit.
J>;FEM;HIKFFBOKD?J

('-+(%%+
CONTROLLER (Feb. 2009) CNTR-13
DJH 
3. SYSTEM CONTROLLER DATA U4

System example

ON/OFF
remote
controller LOSSNAY
PAC-SC51KUA
Power supply
PZ-52SF
PAR-F27MEA-US

PAC-YT51CRB
PAR-21MAA

External dimension

Unit:mm[in.]
CONTROLLER

(Front view) (Side view)


18.1
[ 23/32 ]
130[ 5-1/8 ] (Rear view)

CENTRALIZED ON/OFF
120[4-23/32]

83.5 [3-9/32 ]

19
[ 3/4 ] 46[1-13/16 ]

CNTR-14 CONTROLLER (Feb. 2009)


3. SYSTEM CONTROLLER DATA U4

3-4. Central controller [G-50A]


Functions :Each unit :Each group :Each block
ON/OFF :Each floor :Collective :Not available
TEST RUN

1
ON/OFF MODE
2
FAN SPEED
3 GROUP Item Description Operations Display
SELECT

Run and stop operation for the air conditioner units


AIR

4 5
DIRECTION
6
BACK ON/OFF
73 ºF
SCREEN

Switches between Cool / Dry / Auto / Fan / Heat.


TEMP. CLOCK/
PATTERN VENTILATION
7 8 9 INS.
(Group of LOSSNAY unit : automatic ventilation/ vent - heat
CENTRAL CONTROLLER
REMOTE
PROHIBITION
TIMER
MODE RESET
ENTER
Operation mode interchange/ normal ventilation)
G-50A 0
switching
DEL.

Operation modes vary depending on the air conditioner unit.


Auto mode is only for the CITY MULTI® R2 and WR2 series.
Range of temperature setting
Cool/Dry :
Temperature Heat :
setting Auto :
( ) in case of PDFY/PEFY/PFFY-E indoor unit.
Range of temperature settings vary depending on model.
Models with 5 air flow speed settings: Hi/Mid-2/Mid-1/Low, Auto
Fan speed setting Models with 4 air flow speed settings: Hi/Mid/Low, Auto
Models with 2 air flow speed settings: Hi/Low
Fan speed setting (including Auto) varies depending on the model.
A. The central controller of G-50A combines Web Air flow direction angles, 4-angle, 5-angle Swing, Auto
Air flow direction 1
function (optional), which enable the air conditioner setting 1: Louver cannot be set.
Air flow direction settings vary depending on the model.
system management on a PC browser screen.
For one day, you can set start/stop three times and you can set
The management can even carried out remotely. Timer operation
enable/disable three times. 2
Microsoft® Internet explorer Ver. 5 or later by For a week's schedule, you can store three start/stop patterns
and one enable/disable pattern.
Microsoft Corporation is needed. Microsoft is a 2: When the timer is set, "Timer enabled" is shown on the
operation setting screen of the LCD.
registered trade mark of Microsoft Corporation in
the United States and other countries. Permit / Prohibit
Individually prohibit operation of each local remote control
function (Start/Stop, Change operation mode, Set temperature,
local operation
B. Together with integrated centralized control software Reset filter). 3
3: When the local remote controller inactivation command is
TG-2000A, and/or PLC, many optional functions like received from the master system controller, disabled mark
appears in inverted display on the operation screen.
"Charging", "Peak-cut", "Energy saving", "General
equipment management", "Scheduling" etc, can be Indoor unit intake Measures the intake temperature of the indoor unit only when
temperature the indoor unit is operating.
carried out. Details, please refer to sections of TG-
When an error is currently occurring on an air conditioner unit,
2000A and PLC software. the afflicted unit and the error code are displayed.
C. One G-50A can control maximum 50 Indoor units Error
4: When an error occurs, the LED flashes. The operation
monitor screen shows the abnormal unit by flashing it. The
4

(including Lossnay). The TG-2000A can manage error monitor screen shows the abnormal unit address,
error code and source of detection. The error log monitor
maximum 40 G-50As, therefore can manage screen shows the time and date, the abnormal unit
address, error code and source of detection.
maximum 2000 Indoor units (including Lossnay).
Test run This operates air conditioner units in test run mode.
D. Taking advantage of G-50A's Web functions, alarm-
The interlocked system settings can be performed by the master
ing E-mail containing address and error code can Ventilation
system controller.
equipment
be sent to appointed E-mail address upon any fault When setting the interlocked system, you can use the ventilation
switch to switch the free plan LOSSNAY settings between "Hi",
happen at the air conditioner system. This could "Low" and "Stop".
When setting a group of only free plan LOSSNAY units, you can
release standby personnel and save operation switch between "Normal ventilation", "Interchange ventilation"
cost. and "Automatic ventilation".

By using accessory cables you can set and monitor the

CONTROLLER
External following.
input/output Input
By level signal: "Batch start/stop", "Batch emergency stop"
5 5
By pulse signal: "Batch start/stop", "Enable/disable local
remote controller"
Output
"Start/stop", "Error/Normal"
5: Requires the external I/O cable (PAC-YG10HA-E) sold
External dimension separately.

300[11-13/16 ] Unit:mm[in.]
[31/32]
25

ON/OFF
120[ 4-3/4]

70[2-3/4 ]

CENTRAL CONTROLLER
G-50A

3[1/8] 57[2-1/4 ]
19[3/4]

46 34 Installation plate
[1-13/16 ] 220 [8-21/32] [1-5/16]
280[11 ] 288[11-11/32]
138[5-7/16]
47[1-27/32 ]

9 CN2 1 1 CN1 5 RS232C 12VDC GND S B A


106[4-3/16]

83.6[3- 9 / 32]
[13/16]

83.5[3-9/32]
21

POWER M-NET Ethernet


[1-1/8]

13 [1/2]
28

91[ 3-19/32] 47[1-27/32 ]

CONTROLLER (Feb. 2009) CNTR-15


3-4-1. Power supply to G-50A
3. SYSTEM CONTROLLER DATA U4
G-50A needs DC power supply of 24~30V and 12V; the former is for central control transmission use and the latter is for
G-50A's operating and LAN function use. G-50A can have power-supply at following 1,2,3 methods.

3-4-1-1. Power supply unit PAC-SC50KUA is the recommended power supplier for G-50A. The basic scheme is as follows. For
details, please refer to 3-6 Power supply unit PAC-SC50KUA.

LAN M-NET
M-MET

12V DC
Central controller
G-50A
UP

POWER SUPPLY UNIT

PAC-SC50KUA
MODE
L

POWER TING
RA

WEIGHT 2.11kg

SERIA
L No.

MITSUBIS HI ELECT RIC CORP ORATION

Power supply unit


PAC-SC50KUA
ME remote ME remote
controller controller

M-NET

LOSSNAY unit

ME remote LOSSNAY M-NET


remote controller
controller

Fig. 3-4-1 G-50A and PAC-SC50KUA basic scheme.


3-4-1-2. Power supply of DC 30V from connector of TB7 or TB3 of Outdoor unit and field supplied DC12V, which specified at
Table 3-4-1.

3-4-1-2-1. TB7 and field supplied DC 12V, 0.2A.


As shown at Fig. 3-4-2, G-50A receives power supply of DC 30V from the connector of TB7 at the R410A Outdoor unit
together with a field supplied DC12V, 0.2A. In the case, one of the Outdoor units should change its power supply switch of
CN41 to CN40.
R410A
Outdoor unit
Centralized control
transmission line Indoor/outdoor transmission line
CONTROLLER

CN41 CN40

Field supplied power


(DC12V 0.2A)

Indoor/outdoor transmission line

CN41

Fig. 3-4-2 G-50A, TB7 and field supplied DC12V scheme.

DC12V Power source should follow the specifications at Table 3-4-1, and the power cable to G-50A should not exceed 10m 32-3/4ft .

Table 3-4-1 DC12V power specifications


Source power DC12V 0.2A (Maximum loading)
Ripple noise Lower than 150mVp-p
Authorized or CE marked products.
Subject to regulations:
Compatible
IEC60950 (or EN60950)
specification
CISPR22/24 (or EN55022/24)
IEC61000-3-2/3-3 (or EN61000-3-2/3/3)

CNTR-16 CONTROLLER (Feb. 2009)


3. SYSTEM CONTROLLER DATA U4
3-4-1-2-2. TB3 and DC 12V, 0.2A
G-50A can also receive power supply from TB3 connector of the R410A or R407C, R22 Outdoor unit. Yet, Outdoor unit down
will lead down to G-50A too. The kind of connection is possible but not recommended air conditioner system of multiple
Outdoor units. The DC 12V 0.2A can be supplied at TB3 connector of PAC-SC50KUA, or a field supplier power complying
specification at Table 3-4-1.

Indoor/outdoor transmission line


TB3

CN41

Field supplied power


(DC12V 0.2A)

Fig.3-4-3 G-50A, TB3 and field supplied DC 12V scheme.

3-4-1-2-3. The effect on connectable quantity of Indoor unit when TB7 or TB3 is used to supply power to the G-50A.

As Indoor unit controller and system controllers share the power supply from the Outdoor unit, the total power consumption of
control use needs following considerations.

Taking the power consumption of the control board of Indoor unit as 1, the equivalent power consumption of the system con-
troller is as follows.

Table 3-4-2 The equivalent power consumption of controllers.

Other system controllers

Central controller System remote controller


Indoor unit ON/OFF remote controller (PAC-SF44SRA)
(G-50A) (PAC-YT40ANRA)
Schedule timer (PAC-YT34STA)

1 0.5 1 0.5

*In order to ensure the transmission quality in start-up of outdoor unit (or during communication traffic), the number of
system controllers which connected to indoor/outdoor transmission line in the same system, should not exceed3.

CONTROLLER
Any trouble caused by the failure of the field supplied DC12V power source is not responsible by Mitsubishi Electric Corporation.
When applying Charge and/or Peak-cut function on G-50A, Power Supply Unit (PAC-SC50KUA) is recommended to use. G-50A is possible to
receive power from the one of the Outdoor units, but there is a risk that the failure of power supply from the Outdoor unit will cause G-50A's
CAUTION function-down on the whole system.
At the air conditioner system of multiple Outdoor units, the connector of CN41 is changed to CN40 at only one of the Outdoor units when TB7 is
used to supply power. When the Outdoor unit failed, the connector at another unit can be changed from CN41 to CN40 to recover the power
supply, but remember to change the CN40 back to CN41 at the failed Outdoor unit.

CONTROLLER (Feb. 2009) CNTR-17


&C=>18<18:>1/:9><:771< -.
3. SYSTEM CONTROLLER DATA U4

 
 B>1<9-759;?>:?>;?>?=-31
 
 B>1<9-7=539-759;?>2?9/>5:9
NJ;HD7BI?=D7B?DFKJH;GK?H;IJ>;;NJ;HD7B"
(7:7FJ;H&E:;B)2 !IEB:I;F7H7J;BO
 NJ;HD7B?DFKJ
C;H=;D9OIJEF
DEHC7BHKD
IJEF7D:FHE>?8?J
;D78B;E<BE97BH;CEJ;9EDJHEBB;HEF;H7J?ED97D8;9EDJHEBB;:<EH7BB7?H
9ED:?J?ED;HI8;?D=9EDJHEBB;:8OKI?D=7LEBJ7=; /EH /9EDJ79JI?=D7B<HEC7D;NJ;HD7BIEKH9; 
,;B;9JM?J>J>;<KD9J?EDI;B;9JI;JJ?D=
KD9J?ED
'E NJ;HD7BI?=D7B?DFKJ<KD9J?ED +;C7HAI
'E  'E 
EDEJKI;;NJ;HD7B?DFKJI?=D7B ( (
<79JEHOI;JJ?D=
N;9KJ;;C;H=;D9OIJEF
DEHC7B ( (' ->;BE97BH;CEJ;9EDJHEBB;H('
(EF;H7J?EDI7D:J>;
M?J>B;L;BI?=D7B 9EDJHEBB;H('
(EF;H7J?ED7D:FHE>?8?J
;D78B;9>7D=;
EF;H7J?EDIM?BB8;FHE>?8?J;::KH?D=;C;H=;D9OIJEF
 );H<EHC('
(M?J>B;L;BI?=D7B (' ( ->;BE97BH;CEJ;9EDJHEBB;H('
(EF;H7J?EDI7D:J>;
9EDJHEBB;H('
(EF;H7J?EDI7D:FHE>?8?J
;D78B;9>7D=;
EF;H7J?EDIM?BB8;FHE>?8?J;:
 );H<EHC('
(FHE>?8?J
;D78B; (' (' ,;JJ>;FKBI;M?:J>M>?B;J>;9EDJ79J?I('JE JE I;9
M?J>FKBI;I?=D7BI
 %;L;BI?=D7B7D:FKBI;I?=D7B /EH /
%;L;BI?=D7B )KBI;I?=D7B
N7CFB;<EH('
(
EDJ79J('
JE I;9
EDJ79J(
EDJ79J('
,JEF +KD ,JEF ,?=D7B HKD
EDJ79J(

EDJ79J(' JE I;9


EDJ79J('
EDJ79J( ,?=D7B IJEF
'EHC7B C;H=;D9OIJEF 'EHC7B EDJ79J(
( (' (

->;FHE>?8?J
;D78B;?DFKJ?IJ>;I7C;
NJ;HD7B?DFKJIF;9?<?97J?EDI
' %;7:M?H; C;H=;D9OIJEF
DEHC7BB;L;BI?=D7B ('
(B;L;BI?=D7B ('
(FHE>?8?J
;D78B;FKBI;I?=D7B
CONTROLLER

'E  (H7D=; C;H=;D9OIJEF


DEHC7B?DFKJ ('
(?DFKJ ('?DFKJ
'E  2;BBEM 'EJKI;: 'EJKI;: (?DFKJ
%E97BH;CEJ;9EDJHEBB;HEF;H7J?ED
'E  BK; 'EJKI;: 'EJKI;:
FHE>?8?J?DFKJ
%E97BH;CEJ;9EDJHEBB;HEF;H7J?ED
'E  H7O 'EJKI;: 'EJKI;:
;D78B;?DFKJ
'E  +;: NJ;HD7BIEKH9;
EHB;L;BI?=D7B
0>;DJ>;;C;H=;D9OIJEF
DEHC7BI?=D7B?II;B;9J;:J>;IJ7JKIM?BB9>7D=;<HECDEHC7BJE;C;H=;D9OIJEFM>;DJ>;
;NJ;HD7B?DFKJI?=D7B9EDJ79J9>7D=;I<HEC(JE('7D:M?BB9>7D=;<HEC;C;H=;D9OIJEFJEDEHC7BM>;DJ>;
9EDJ79J9>7D=;I<HEC('JE( C;H=;D9OIJEFI?=D7BM?BB8H?D=J>;7?H9ED:?J?ED;HIJEIJEF7D:97D9;B?D=J>;
;C;H=;D9OIJEFM?BBDEJ7KJEC7J?97BBOH;I;JJ>;I;KD?JI -E=E879AJEJ>;FH;L?EKIEF;H7J?EDIJ7JKIJ>;OCKIJ8;
C7DK7BBOJKHD;:879AED
0>;DJ>;('
(I?=D7B?II;B;9J;:J>;IJ7JKIM?BB9>7D=;<HEC(JE('M>;DJ>;;NJ;HD7B?DFKJI?=D7B9EDJ79J
9>7D=;I<HEC(JE('7D:M?BB9>7D=;<HEC('JE(M>;DJ>;9EDJ79J9>7D=;I<HEC('JE(

EHFKBI;I?=D7B
L;D?<J>;('I?=D7B?I?DFKJ:KH?D=('J>;IJ7JKIM?BBH;C7?D('
"<J>;BE97BH;CEJ;9EDJHEBB;H?IFHE>?8?J;:J>;('
(EF;H7J?EDCE:;7D:J;CF;H7JKH;I;JJ?D=EF;H7J?EDI8OJ>;
BE97BH;CEJ;9EDJHEBB;HM?BB8;FHE>?8?J;:
,;JJ>;FKBI;M?:J>9EDJ79J('J?C;JE JE I;9

('-+(%%+ DJH 
CNTR-18 CONTROLLER (Feb. 2009)
&C=>18<18:>1/:9><:771< -.
3. SYSTEM CONTROLLER DATA U4

+;9ECC;D:;:9?H9K?J;N7CFB;

EHB;L;BI?=D7B

' ' )EM;HIKFFBO 


+;: +;:  /EH /
1
(H7D=; 1
+KD
IJEFEH (H7D=; 1
1 +KD
C;H=;D9OIJEF 2;BBEM 1 ,JEF
1
BK; 2 2 )HE>?8?J
)EM;HIKFFBO  )KHFB; 2 2
D78B;
&7N C  /EH / &7N C
 
<J  
<J
->?IKD?J ->?IKD?J

->;9EDJ79JH;B7OFEM;HIEKH9;;NJ;DI?ED978B;;J9 CKIJ8;FH;F7H;:I;F7H7J;BO7JJ>;I?J;
->;9EDD;9J?ED978B;97D8;; C  
<J .I;7 CC 40 5EHB7H=;HM?H; 
,JH?FJ>;;NJH7978B;D;7HJ>;9EDD;9JEH7D:I;9KH;BO?DIKB7J;J>;;NFEI;:I;9J?EDM?J>J7F;;J9

 

B>1<9-7=539-7:?>;?>2?9/>5:9
NJ;HD7BI?=D7BEKJFKJH;GK?H;IJ>;;NJ;HD7B"
O7:7FJ;H&E:;B)2 !IEB:I;F7H7J;BO
 NJ;HD7BEKJFKJ
0>;DED;EHCEH;7?H9ED:?J?ED;HI7H;HKDD?D=J>;Z('ZI?=D7BM?BB8;EKJFKJ7D:?<7C7B<KD9J?EDE99KHI?DED;EHCEH;7?H
9ED:?J?ED;HIJ>;Z&7B<KD9J?EDZI?=D7BM?BB8;I>EMD

 NJ;HD7BEKJFKJIF;9?<?97J?EDI
' %;7:M?H; ;J7?BIE<;79>J;HC?D7B Z('ZI?=D7B7D:Z&7B<KD9J?EDZI?=D7BM?BB
'E H;;D ECCEDNJ;HD7B=HEKD: 8EJ>8;EKJFKJ 

'E B79A ('


(
'E  HEMD &7B<KD9J?ED
DEHC7B

+;9ECC;D:;:9?H9K?J;N7CFB;

' ?E:;  .I;3 7D:3 H;B7OI>7L?D=J>;<EBBEM?D=IF;9?<?97J?EDI


3 (F;H7J?ED9E?B
B79A +7J;:LEBJ7=;  / /
HEMD )EM;HEDIKCFJ?ED  0EHB;II
 )H;F7H;7FEM;HIKFFBOI;F7H7J;BO799EH:?D=JEJ>;
3
H;B7O8;?D=KI;:  /EH /
 BM7OI?DI;HJ7:?E:;ED8EJ>;D:IE<J>;H;B7O9E?B
)EM;H 
,KFFBO
H;;D

CONTROLLER
&7N C
 
<J
% +KD:?IFB7OB7CF
% &7B<KD9J?ED:?IFB7OB7CF

79>;B;C;DJM?BBJKHDEDM>?B;('EF;H7J?EDEH7C7B<KD9J?EDE99KHI
->;9EDD;9J?ED978B;97D8;; C  
<J
->;H;B7OIB7CFI:?E:;I7D:;NJ;DI?ED978B;I;J9CKIJ8;FH;F7H;:I;F7H7J;BO7JJ>;I?J;

('"! );;BE<<J>;B78;B
0>;D9EDD;9J?D=J>;;NJ;HD7B?DFKJ
EKJFKJ978B;IJE9EDD;9JEH' EDJ>;9ED
JHEBB;HF;;BE<<J>;B78;BEDJ>;9EDJHEBB;H9EDD;9JEHI;9J?ED

J>;HD;J &'- )(0+

  , / ' +,   '  ' 

('-+(%%+ DJH
CNTR-19
CONTROLLER (Feb. 2009)
&C=>18<18:>1/:9><:771< -.
3. SYSTEM CONTROLLER DATA U4

   !/:991/>5:92?9/>5:9
0>;DKI?D=J>;%'9EDD;9J?ED<KD9J?ED9EDD;9JJ>;%'978B;JEJ>;J>;HD;J9EDD;9JEHE<J>?I:;L?9;
)HE9KH;J>;%'978B;7JJ>;I?J;7D:KI;7D;D>7D9;:97J;=EHO.-)978B;
EH7:;I9H?FJ?EDE<J>;")7::H;III;JJ?D=C;J>E:H;<;HJE"DIJ7BB7J?ED&7DK7B
%'?I ,-,F;9?<?97J?ED

J>;HD;J &'- )(0+

  , / ' +,   '  ' 

!"'
);H<EHCJ>;%'M?H?D=8;<EH;?DIJ7BB7J?ED7D:M?H;KFJEJ>;8E:O8OJ>;I7C;C;J>E:7IM?H?D=J>;&
'-JH7DIC?II?EDB?D;
0>;D7%'?I7BH;7:O9EDD;9J;::;9?:;J>;")7::H;II8O9EDIKBJ7J?EDM?J>J>;IOIJ;C7:C?D?IJH7JEH7D:
9EDD;9JJEJ>;%'8E:O7<J;H9>7D=?D=J>;")7::H;II
0>;D9EDD;9J?D=7D%'9EDD;9JEHIF79;<EHJ>;9EDD;9JEH7D:M?H?D=?IH;GK?H;: )HEL?:;J>?IIF79;7J
J>?IKD?J7D:J>;H;7HE<J>;;B;9JH?98EN +;<;HJE"DIJ7BB7J?ED&7DK7B
0>;DJ>;  9EL;H?IEF;D;:J>;%'IJ7JKIB7CF7D:%'9>7D=;EL;HIM?J9>7H;799;II;: EH:;
J7?B;:?D<EHC7J?EDH;<;HJE"DIJHK9J?EDEEA
CONTROLLER

('-+(%%+ DJH
CNTR-20 CONTROLLER (Feb. 2009)
3. SYSTEM CONTROLLER DATA U4

3-4-4. Browser screens of G-50A

81 °F 81 °F 81 °F 79 °F

81 °F 82 °F 81 °F 81 °F

81 °F 82 °F 81 °F 79 °F

81 °F 81 °F -- °F -- °F

Condition List (Overview) Condition List (Block)

81 °F

CONTROLLER
Operation Malfunction List

79 ˚F

79 ˚F

82 ˚F

Malfunction Log Weekly Schedule

CONTROLLER (Feb. 2009) CNTR-21


3. SYSTEM CONTROLLER DATA U4

Operation (DIDO Controller) Measurement status monitor (temperature


sensor/humidity sensor /measurement meter)

Trend Graph (temperature/humidity)


CONTROLLER

CNTR-22 CONTROLLER (Feb. 2009)


3. SYSTEM CONTROLLER
3-5. Central controller [GB-50A] DATA U4

3-5. Central controller [GB-50A]


Functions :Each unit :Each group :Each block
N623
:Each floor :Collective :Not available
CENTRAL CONTROLLER
Description Operations Display
MODEL
SERVICE REF. GB-50A-E Item
INPUT VOLTAGE DC30/24V;0.13/0.15A
(M-NET)
WEIGHT
SERIAL No.
1.1kg / 2 1
/ 2 lb
ON/OFF Run and stop operation for the air conditioner units
Switches between Cool / Dry / Auto / Fan / Heat.
MADE IN JAPAN

This device complies with Part15 of the FCCRules.Operation is (Group of LOSSNAY unit : automatic ventilation/ vent - heat
subject to the following two conditions:(1)this device may not cause
harmful interference,and(2)this device must accept any interference
Operation mode interchange/ normal ventilation)
received,including interference that may cause undesired operation. switching Operation modes vary depending on the air conditioner unit.

Range of temperature setting


Cool/Dry :
Temperature Heat :
setting Auto :
( ) in case of PDFY/PEFY/PFFY-E indoor unit.
Range of temperature settings vary depending on model.
Models with 5 air flow speed settings: Hi/Mid-2/Mid-1/Low, Auto
A. The central controller of GB-50A combines with Web Fan speed setting Models with 4 air flow speed settings: Hi/Mid/Low, Auto
Models with 2 air flow speed settings: Hi/Low
function, which enables the air conditioner system to be Fan speed setting (including Auto) varies depending on the model.

managed via PC browser screen. *1. Air flow direction


Air flow direction angles, 4-angle or 5-angle, Swing, Auto
1: Louver cannot be set.
1

The management can even carried out remotely. setting Air flow direction settings vary depending on the model.
*1 Microsoft® Internet explorer Ver. 5 or later by Individually prohibit operation of each local remote control
Permit / Prohibit function (Start/Stop, Change operation mode, Set temperature,
Microsoft Corporation is needed. Java executing local operation Reset filter). 3

environment is needed.(Microsoft VM Ver. 5.0 or 3: When the local remote controller inactivation command is
received from the master system controller, disabled mark
later, or SUN Microsystems’ Java plug-in Ver. 1.4.2 or appears in inverted display on the operation screen.
later) Microsoft is a registered trademark of Indoor unit intake Measures the intake temperature of the indoor unit only when
Microsoft Corporation in the United States and other temperature the indoor unit is operating.
countries. When an error is currently occurring on an air conditioner unit,
the afflicted unit and the error code are displayed.
B. Together with integrated centralized control software 4: When an error occurs, the LED flashes. The operation 4
Error monitor screen shows the abnormal unit by flashing it. The
TG-2000A and/or PLC, many optional functions like error monitor screen shows the abnormal unit address,
“Charging”, “Peak-cut”, “Energy saving”, “General error code and source of detection. The error log monitor
screen shows the time and date, the abnormal unit
equipment management”, “Scheduling” etc, can be address, error code and source of detection.
performed. For details, please refer to sections of TG- Ventilation
The interlocked system settings can be performed by the master
2000A and PLC software. equipment
system controller.
When setting the interlocked system, you can use the ventilation
C. One GB-50A can control a maximum of 50 Indoor units switch to switch the free plan LOSSNAY settings between "Hi",
"Low" and "Stop".
(including Lossnay). The TG-2000A can manage a When setting a group of only free plan LOSSNAY units, you can
switch between "Normal ventilation", "Interchange ventilation"
maximum of 40 GB-50As, and therefore, can manage and "Automatic ventilation".
a maximum 2,000 Indoor units (including Lossnay). By using accessory cables you can set and monitor the
External
D. Taking advantage of GB-50A’s Web functions, input/output
following.
Input
an notification e-mail containing address and error code By level signal: "Batch start/stop", "Batch emergency stop"
5 5
can be sent to appointed e-mail address if any error By pulse signal: "Batch start/stop", "Enable/disable local
remote controller"
occurs at the air conditioner system. Output
"Start/stop", "Error/Normal"
5: Requires the external I/O cable (PAC-YG10HA-E) sold
separately.

CONTROLLER
GB-50A needs a PC(field supplied) connected together to monitor and operate the air conditioner system.

External dimension

Unit:mm[in.]
20[25/32] 250[9-7/8] 20[25/32] 10
[13/32]
L-shape metal
20[25/32] (included)
20[25/32]

20[25/32]

250[9-7/8 ] 38[1-1/2]

N623

CENTRAL CONTROLLER
MODEL
SERVICE REF. GB-50A-E

INPUT VOLTAGE DC30/24V;0.13/0.15A


(M-NET)
WEIGHT 1.1kg / 2 1
/ 2 lb
130[5-1/ 8]

SERIAL No.

MADE IN JAPAN

Mounting with L-shape metal


This device complies with Part15 of the FCCRules.Operation is
subject to the following two conditions:(1)this device may not cause
harmful interference,and(2)this device must accept any interference
received,including interference that may cause undesired operation.
290[11-13/32]
310[12-7/32 ]

35[1-3/8"] DIN Rail


Attachment for DIN Rail (included)

20[25/32] Mounting with DIN Rail

CONTROLLER (Feb. 2009) CNTR-23


3. SYSTEM CONTROLLER DATA U4

3-5-1. Power supply to GB-50A


GB-50A needs DC power supply of 24~30V for central control transmission use, operating and LAN function use. GB-50A can
have power supply at following 1,2,3 methods.

3-5-1-1. Power supply unit PAC-SC51KUA or PAC-SC50KUA are the recommended power supplies for GB-50A. See below for
basic system. For details, please refer to Power supply unit PAC-SC51KUA.

LAN M-NET
M-MET

Central controller
GB-50A

Power supply unit


PAC-SC51KUA or
PAC-SC50KUA
ME remote ME remote
controller controller

M-NET

LOSSNAY unit

ME remote LOSSNAY remote


controller controller

Fig. 3-5-1 GB-50A and PAC-SC51KUA basic system.

3-5-1-2. Power supply of DC 30V from connector of TB7 or TB3 of Outdoor unit.

3-5-1-2-1. TB7 of Outdoor unit.


As shown at Fig. 3-5-2, GB-50A receives power supply of DC 30V from the connector of TB7 at the R410A Outdoor unit.
In the case, one of the Outdoor units should change its power supply switch of CN41 to CN40.

R410A
CONTROLLER

Outdoor unit
Central control
transmission line Indoor/outdoor transmission line

CN41 CN40

Indoor/outdoor transmission line

CN41

Fig. 3-5-2 GB-50A, TB7 power supply

CNTR-24 CONTROLLER (Feb. 2009)


3. SYSTEM CONTROLLER DATA U4

3-5-1-2-2. TB3 of Outdoor unit.


GB-50A can also receive power supply from TB3 connector of the R410A or R407C, R22 Outdoor unit. However, if the Outdoor
unit shuts down, G-50A will also automatically shuts down. Therefore, this connection is not recommended for air conditioner
system consisting multiple Outdoor units.

Indoor/outdoor transmission line


TB3

CN41

Fig.3-5-3 GB-50A, TB3 power supply

3-5-1-2-3. The effect on connectable quantity of Indoor unit when TB7 or TB3 is used to supply power to the GB-50A.
As Indoor unit controller and system controllers share the power supply from the Outdoor unit, the total power consumption of
control use needs following considerations.
Taking the power consumption index of Indoor unit sized P06-P54 as 1, the equivalent power consumption index and supply
capability index of others are listed at Table 3-5-1 and Table 3-5-2.
Table 3-5-1 The equivalent power consumption index by Indoor units, LOSSNAY, controllers
Indoor, OA unit Indoor unit BC controller MA RC. LOSSNAY ME Remote Contr. Timers, System Contr. ON/OFF Contr.

Sized P06-P54 Sized P72,P96 CMB PAR-21MAA PAR-F27MEA PAC-SF44SRA GB-50A PAC-YT40ANRA
PAC-YT51CRA(B) PZ-52SF PAC-YT34STA
PAR-FA32MA G-50A
LGH-RX-E
AG-150A
1 2 2 0 1/4 1/2 3 1
In order to ensure the transmission quality in start-up of outdoor unit (or during communication traffic), the number of system controllers that connect to
indoor/outdoor transmission line in the same system, should not exceed three.
*RC : Remote Controller
Table 3-5-2 The equivalent power supply capability index of Trans.Booster, Power supply unit, Connector TB3, TB7 of Outdoor unit.
Transmission Booster Power supply unit Outdoor unit Outdoor unit
PAC-SF46EPA PAC-SC50KUA PAC-SC51KUA Connector TB3 and TB7 total * Connector TB7 only
25 6 5 32 6
*If PAC-SC50(51)KUA is used to supply power at TB7 side, no power supply need from Outdoor unit at TB7, Connector TB3 itself will therefore have 32.
*Connector TB3 of PUMY gives equivalent power only 12. TB7 of PUMY should not be used to supply power, and power supply unit should be used.

Mitsubishi Electric Corporation is not responsible for any problems caused by the failure of the field supplied 12VDC power source.
When applying Charge and/or Peak-cut function on GB-50A, using a Power Supply Unit (PAC-SC50KUA or PAC-SC51KUA) is recommended.
GB-50A has the ability to receive power from the one of the Outdoor units, but there is a risk that a failure of the power supply from the

CAUTION Outdoor unit will cause GB-50A to shut down the whole system.
On a multiple Outdoor unit system, the connector of CN41 is changed to CN40 at only one of the Outdoor units when TB7 is used to supply
power. If that Outdoor unit fails, the connector at another unit can be changed from CN41 to CN40 to recover the power supply, but remember
to change the CN40 back to CN41 at the failed Outdoor unit.

With the equivalent power consumption values in Table 3-5-1 and Table 3-5-2, PAC-SF46EPA can be designed into the air-
conditioner system to ensure proper system communication according to 3-5-2-A, B, C.
3-5-2-A) Firstly, count from TB3 at TB3 side the total quantity of Indoor units and ME remote controller, Timers and System controllers.

CONTROLLER
If the total quantity reaches 40, a PAC-SF46EPA should be set. In this case, Indoor unit sized P72, 96 is counted as 2 Indoor
units, but MA remote controller(s), LOSSNAY is NOT counted.
3-5-2-B) Secondly, count from TB7 side to TB3 side the total transmission power consumption index. If the total power consumption reaches 32,
a PAC-SF46EPA should be set. Yet, if a PAC-SC50(51)KUA is used to supply power at TB7 side, count from index TB3 side only.
3-5-2-C) Thirdly, count from TB7 at TB7 side the total transmission power consumption index, If the total power consumption reaches 6,
a PAC-SF46EPA should be set.
System example

TB7 TB3
UP

TRANSMISSION BOOSTER
MODEL
PAC-SF46EPA

POWER RATING 220-240V:0.7A ~/N

50

WEIGHT 3.4kg

MADE IN JAPAN

01 02 Transmission
booster
PAC-SF96EPA
(No.1)
ME remote ME remote
controller controller
TB7 TB3 N1 N2
Outdoor unit Transmission booster (No.1) should be used, Within N2, conditions 1,2 should be followed.
if the total quantity of Indoor units and ME remote controllers 1.The total quantity of Indoor units and ME remote
reaches 40, (Indoor unit sized P72,96 is counted as 2); controller should not exceed 40.
or if the total equivalent transmission power consumption reaches 32. *Indoor unit sized P72,96 is counted as 2 units.
2.The total equivalent transmission power consumption
UP
should not exceed 25.

TRANSMISSION BOOSTER
MODEL
PAC-SF46EPA

220-240V:0.7A ~/N
POWER RATING
50

WEIGHT 3.4kg

MADE IN JAPAN

Transmission
LOSSNAY booster LOSSNAY
M-NET Central controller
(24VDC) unit PAC-SF46EPA unit
(GB-50A) (No.2)
PZ-52SF PZ-52SF
Power supply unit
PAC-SC51KUA or
PAC-SC50KUA
N3 N4
Transmission booster (No.2) should be used, Within N4, the total equivalent transmission
if the total equivalent transmission power consumption reaches 6. power consumption should not exceed 25.

CONTROLLER (Feb. 2009) CNTR-25


&C=>18<18:>1/:9><:771< -.
3. SYSTEM CONTROLLER DATA U4

 
B>1<9-759;?>:?>;?>?=-31

'
 
 B>1<9-7=539-759;?>2?9/>5:9
NJ;HD7BI?=D7B?DFKJH;GK?H;IJ>;;NJ;HD7B"
(7:7FJ;H&E:;B)2 !IEB:I;F7H7J;BO
 NJ;HD7B?DFKJ
C;H=;D9OIJEF
DEHC7BHKD
IJEF7D:FHE>?8?J
;D78B;E<BE97BH;CEJ;9EDJHEBB;HEF;H7J?ED97D8;9EDJHEBB;:<EH7BB7?H
9ED:?J?ED;HI8;?D=9EDJHEBB;:8OKI?D=7LEBJ7=; /EH /9EDJ79JI?=D7B<HEC7D;NJ;HD7BIEKH9; 
,;B;9JJ>;<KD9J?EDEDJ>;"D?J?7B,;JJ?D=0;8EHJ>;"D?J?7B,;JJ?D=-EEB

'E NJ;HD7BI?=D7B?DFKJ<KD9J?ED +;C7HAI

EDEJKI;;NJ;HD7B?DFKJI?=D7B
<79JEHOI;JJ?D=
N;9KJ;;C;H=;D9OIJEF
DEHC7B ->;BE97BH;CEJ;9EDJHEBB;H('
(EF;H7J?EDI7D:J>;
M?J>B;L;BI?=D7B 9EDJHEBB;H('
(EF;H7J?ED7D:FHE>?8?J
;D78B;9>7D=;
EF;H7J?EDIM?BB8;FHE>?8?J;::KH?D=;C;H=;D9OIJEF
 );H<EHC('
(M?J>B;L;BI?=D7B ->;BE97BH;CEJ;9EDJHEBB;H('
(EF;H7J?EDI7D:J>;
9EDJHEBB;H('
(EF;H7J?EDI7D:FHE>?8?J
;D78B;9>7D=;
EF;H7J?EDIM?BB8;FHE>?8?J;:
 );H<EHC('
(FHE>?8?J
;D78B; ,;JJ>;FKBI;M?:J>M>?B;J>;9EDJ79J?I('JE JE I;9
M?J>FKBI;I?=D7BI
 %;L;BI?=D7B7D:FKBI;I?=D7B /EH /
%;L;BI?=D7B )KBI;I?=D7B
N7CFB;<EH('
(
EDJ79J('
JE I;9
EDJ79J(
EDJ79J('
,JEF +KD ,JEF ,?=D7B HKD
EDJ79J(

EDJ79J(' JE I;9


EDJ79J('
EDJ79J( ,?=D7B IJEF
'EHC7B C;H=;D9OIJEF 'EHC7B EDJ79J(
CONTROLLER

( (' (

->;FHE>?8?J
;D78B;?DFKJ?IJ>;I7C;
NJ;HD7B?DFKJIF;9?<?97J?EDI
' %;7:M?H; C;H=;D9OIJEF
DEHC7BB;L;BI?=D7B ('
(B;L;BI?=D7B ('
(FHE>?8?J
;D78B;FKBI;I?=D7B
'E  (H7D=; C;H=;D9OIJEF
DEHC7B?DFKJ ('
(?DFKJ ('?DFKJ
'E  2;BBEM 'EJKI;: 'EJKI;: (?DFKJ
%E97BH;CEJ;9EDJHEBB;HEF;H7J?ED
'E  BK; 'EJKI;: 'EJKI;:
FHE>?8?J?DFKJ
%E97BH;CEJ;9EDJHEBB;HEF;H7J?ED
'E  H7O 'EJKI;: 'EJKI;:
;D78B;?DFKJ
'E  +;: NJ;HD7BIEKH9;
EHB;L;BI?=D7B
0>;DJ>;;C;H=;D9OIJEF
DEHC7BI?=D7B?II;B;9J;:J>;IJ7JKIM?BB9>7D=;<HECDEHC7BJE;C;H=;D9OIJEFM>;DJ>;
;NJ;HD7B?DFKJI?=D7B9EDJ79J9>7D=;I<HEC(JE('7D:M?BB9>7D=;<HEC;C;H=;D9OIJEFJEDEHC7BM>;DJ>;
9EDJ79J9>7D=;I<HEC('JE( C;H=;D9OIJEFI?=D7BM?BB8H?D=J>;7?H9ED:?J?ED;HIJEIJEF7D:97D9;B?D=J>;
;C;H=;D9OIJEFM?BBDEJ7KJEC7J?97BBOH;I;JJ>;I;KD?JI -E=E879AJEJ>;FH;L?EKIEF;H7J?EDIJ7JKIJ>;OCKIJ8;
C7DK7BBOJKHD;:879AED
0>;DJ>;('
(I?=D7B?II;B;9J;:J>;IJ7JKIM?BB9>7D=;<HEC(JE('M>;DJ>;;NJ;HD7B?DFKJI?=D7B9EDJ79J
9>7D=;I<HEC(JE('7D:M?BB9>7D=;<HEC('JE(M>;DJ>;9EDJ79J9>7D=;I<HEC('JE(

EHFKBI;I?=D7B
L;D?<J>;('I?=D7B?I?DFKJ:KH?D=('J>;IJ7JKIM?BBH;C7?D('
"<J>;BE97BH;CEJ;9EDJHEBB;H?IFHE>?8?J;:J>;('
(EF;H7J?EDCE:;7D:J;CF;H7JKH;I;JJ?D=EF;H7J?EDI8OJ>;
BE97BH;CEJ;9EDJHEBB;HM?BB8;FHE>?8?J;:
,;JJ>;FKBI;M?:J>9EDJ79J('J?C;JE JE I;9

CNTR-26 CONTROLLER (Feb. 2009)


('-+(%%+ DJH 
&C=>18<18:>1/:9><:771< -.
3. SYSTEM CONTROLLER DATA U4

 
 B>1<9-7=539-759;?>2?9/>5:9
+;9ECC;D:;:9?H9K?J;N7CFB;

EHB;L;BI?=D7B

' ' )EM;HIKFFBO 


+;:
  +;:  /EH /
1
(H7D=; 1
 +KD
IJEFEH  (H7D=; 1 1 +KD
 C;H=;D9OIJEF  2;BBEM 1 ,JEF
1
  BK; 2 2 )HE>?8?J
 )EM;HIKFFBO   )KHFB; 2 D78B;
2
&7N C  /EH / &7N C
 
<J  
<J
->?IKD?J ->?IKD?J

->;9EDJ79JH;B7OFEM;HIEKH9;;NJ;DI?ED978B;;J9 CKIJ8;FH;F7H;:I;F7H7J;BO7JJ>;I?J;
->;9EDD;9J?ED978B;97D8;;NJ;D:;:KFJE C .I;7 CC40
 
<J
5EHJ>?9A;HM?H; 
,JH?FJ>;;NJH7978B;D;7HJ>;9EDD;9JEH7D:I;9KH;BO?DIKB7J;J>;;NFEI;:I;9J?EDM?J>J7F;;J9

 

B>1<9-7=539-7:?>;?>2?9/>5:9
NJ;HD7BI?=D7BEKJFKJH;GK?H;IJ>;;NJ;HD7B"
O7:7FJ;H&E:;B)2 !IEB:I;F7H7J;BO
 NJ;HD7BEKJFKJ
0>;DED;EHCEH;7?H9ED:?J?ED;HI7H;HKDD?D=J>;^('`I?=D7BM?BB8;EKJFKJ7D:?<7C7B<KD9J?EDE99KHI?DED;EHCEH;7?H
9ED:?J?ED;HIJ>;^&7B<KD9J?ED`I?=D7BM?BB8;I>EMD

 NJ;HD7BEKJFKJIF;9?<?97J?EDI
' %;7:M?H; ;J7?BIE<;79>J;HC?D7B Z('ZI?=D7B7D:Z&7B<KD9J?EDZI?=D7BM?BB
'E H;;D ECCEDNJ;HD7B=HEKD: 8EJ>8;EKJFKJ 

'E B79A ('


(
'E  HEMD &7B<KD9J?ED
DEHC7B

+;9ECC;D:;:9?H9K?J;N7CFB;

' ?E:;  .I;3 7D:3 H;B7OI>7L?D=J>;<EBBEM?D=IF;9?<?97J?EDI


3 (F;H7J?ED9E?B
B79A +7J;:LEBJ7=;  / /
HEMD )EM;HEDIKCFJ?ED  0EHB;II

CONTROLLER
 )H;F7H;7FEM;HIKFFBOI;F7H7J;BO799EH:?D=JEJ>;
3
H;B7O8;?D=KI;:  /EH /
 BM7OI?DI;HJ7:?E:;ED8EJ>;D:IE<J>;H;B7O9E?B
)EM;H 
,KFFBO
H;;D
&7N C
 
<J
% +KD:?IFB7OB7CF
% &7B<KD9J?ED:?IFB7OB7CF

79>;B;C;DJM?BBJKHDEDM>?B;('EF;H7J?EDEH7C7B<KD9J?EDE99KHI
->;9EDD;9J?ED978B;97D8;;NJ;D:;:KFJE C  
<J
->;H;B7OIB7CFI:?E:;I7D:;NJ;DI?ED978B;I;J9CKIJ8;FH;F7H;:I;F7H7J;BO7JJ>;I?J;

CONTROLLER (Feb. 2009) CNTR-27


&C=>18<18:>1/:9><:771< -.
3. SYSTEM CONTROLLER DATA U4

  !/:991/>5:92?9/>5:9
EDD;9JJ>;%'978B;JEJ>;%' 9EDD;9JEHE<J>?I:;L?9;
)HE9KH;J>;%'978B;7JJ>;I?J;7D:KI;7D;D>7D9;:97J;=EHO.-)978B;
EH7:;I9H?FJ?EDE<J>;")7::H;III;JJ?D=C;J>E:H;<;HJE"DIJ7BB7J?ED&7DK7B
%'?I ,-,F;9?<?97J?ED
->;C7N?CKCM?H?D=B;D=J><HEC!.JE  ?I C4 <J5
 ?I9EDD;9J;:JEJ>;CED?JEH?D=)L?7!.

!"'
);H<EHCJ>;%'M?H?D=8;<EH;?DIJ7BB7J?ED7D:M?H;KFJEJ>;8E:O8OJ>;I7C;C;J>E:7IM?H?D=J>;&
'-JH7DIC?II?EDB?D;
0>;D7%'?I7BH;7:O9EDD;9J;::;9?:;J>;")7::H;II8O9EDIKBJ7J?EDM?J>J>;IOIJ;C7:C?D?IJH7JEH7D:
9EDD;9JJEJ>;%'8E:O7<J;H9>7D=?D=J>;")7::H;II
,F79;<EHJ>;9EDD;9JEH7D:M?H?D=?IH;GK?H;: +;<;HJE"DIJ7BB7J?ED&7DK7B
CONTROLLER

CNTR-28 ('-+(%%+
CONTROLLER (Feb. 2009) DJH 
3. SYSTEM CONTROLLER DATA U4

3-5-4. Browser screens of GB-50A

81 °F 81 °F 81 °F 79 °F

81 °F 82 °F 81 °F 81 °F

81 °F 82 °F 81 °F 79 °F

81 °F 81 °F -- °F -- °F

Condition List (Overview) Condition List (Block)

81 °F

CONTROLLER
Operation Malfunction List

79 ˚F

79 ˚F

82 ˚F

Malfunction Log Weekly Schedule

CONTROLLER (Feb. 2009) CNTR-29


3. SYSTEM CONTROLLER DATA U4

Operation (DIDO Controller) Measurement status monitor (temperature


sensor/humidity sensor /measurement meter)

Trend Graph (temperature/humidity)


CONTROLLER

CNTR-30 CONTROLLER (Feb. 2009)


3. SYSTEM CONTROLLER DATA U4

3-6. Central controller [AG-150A]

Functions :Each unit :Each group :Each block


:Each floor :Collective :Not available
Item Description Operations Display

ON/OFF Run and stop operation for the air conditioner units

Switches between Cool / Dry / Auto / Fan / Heat. (Group of


LOSSNAY unit : automatic ventilation/ vent - heat interchange/
Operation mode
normal ventilation)
switching
Operation modes vary depending on the air conditioner unit.
Auto mode is the City Multi R2 and WR2 series only.
Range of temperature setting
Cool/Dry :
Temperature Heat :
setting Auto :
( ) when using middle-temperature on PDFY, PEFY-NMSU/NMHU-by setting DipSW7-1
to ON.

A. The centralized controller of AG-150A combines Web Range of temperature settings vary depending on model.
Models with 5 air flow speed settings: Hi/Mid-2/Mid-1/Low, Auto
function (optional), which enable the air conditioner Fan speed setting
Models with 4 air flow speed settings: Hi/Mid/Low, Auto
system management on a PC browser screen. Models with 2 air flow speed settings: Hi/Low
Fan speed setting (including Auto) varies depending on the model.
*1The management can even carried out remotely.
Air flow direction Air flow direction angles, 4-angle or 5-angle Swing, Auto 1
Microsoft® Internet explorer Ver. 6 or later by Microsoft Corporation is needed. 1: Louver cannot be set.
setting
(Note: You must have "Sun Microsystems Java".) Air flow direction settings vary depending on the model.
Microsoft® Internet explorer is a registered trade mark of Microsoft Weekly schedule can be set for each group of air conditioning units.
Corporation US in the USA and other countries. Schedule 2 By registering a license for AG-150A, weekly (2 types), annual, and current day
scheduling function become available.
Note: Connect AG-150A to a private network. operation The system follows either the current day, annual schedule, or weekly, which are
2
in the descending order of overriding priority.
B. Together with integrated centralized control software Twenty-four events can be scheduled per day, including Start/Stop, Mode,
Temperature Setting, Operation Prohibition, Vane Direction, and Fan Speed.
TG-2000A, and/or PLC, many optional functions like Two types of weekly schedule (Summer/Winter) can be set.
Settable items dependant on the indoor unit model.
"Charging", "Peak-cut", "Energy saving", "General
equipment management", "Scheduling" etc, can be Permit / Prohibit
Individually prohibit operation of each local remote control
function (Start/Stop, Change operation mode, Set temperature,
local operation
carried out. Details, please refer to sections of Reset filter). 3

3: When the local remote controller inactivation command is


TG-2000A and PLC software. received from the master system controller,
"Disabled"appears in inverted display on the operation setting screen.
C. One AG-150A can control maximum 50 Indoor units
Indoor unit intake Measures the intake temperature of the indoor unit only when
(including LOSSNAY). The integrated centralized temperature the indoor unit is operating.
control software TG-2000A can manage maximum
When an error is currently occurring on an air conditioner unit,
40 AG-150As, therefore can manage maximum the afflicted unit and the error code are displayed.
4: When an error occurs, the "ON/OFF" LED flashes. The 4
2000 Indoor units (including LOSSNAY). Error operation monitor screen shows the abnormal unit by flashing
D. Taking advantage of AG-150A's Web functions, it. The error monitor screen shows the abnormal unit address,
error code and source of detection. The error log monitor
alarming E-mail containing address and error code screen shows the time and date, the abnormal unit address,
error code and source of detection.
can be sent to appointed E-mail address upon any Test run This operates air conditioner units in test run mode.
fault happen at the air conditioner system. The interlocked system settings can be performed by the master
Ventilation
E. AG-150A features a 9"-wide color LCD touch panel. equipment system controller.
When setting the interlocked system, you can use the ventilation
The settings for air conditioning units can be switch to switch the free plan LOSSNAY settings between "Hi",
changed by touching the corresponding icons on "Low" and "Stop".
When setting a group of only free plan LOSSNAY units, you can

CONTROLLER
the display. switch between "Normal ventilation", "Interchange ventilation"
and "Automatic ventilation".
By using accessory cables you can set and monitor the following.
External Input: By level signal: "Batch start/stop", "Batch emergency stop"
input/output By pulse signal: "Batch start/stop", "Enable/disable local remote
controller" 5 5
Output: "Start/stop", "Error/Normal"
5: Requires the external I/O cable (PAC-YG10HA-E) sold
separately.
External dimension
25.6 44.7
(1-1/16)(1-13/16)
300 (11-13/16) Unit:mm[in.]

Installation plate
185 (7-5/16)

290.8(11-1/2)
273(10-3/4)
250(9-7/8)
200(7-7/8)

CENTRALIZED CONTROLLER AG-150A


175.8(6-15/16)
163.4(6-7/16)
147(5-13/16)

167(6-5/8)

272 (10-3/4)
Back View
272 (10-3/4)
250 (9-7/8)
261(10-5/16)
146 (5-3/4)

167 (6-5/8)

CONTROLLER (Feb. 2009) CNTR-31


3. SYSTEM CONTROLLER DATA U4

3-6-1. Power supply to AG-150A


AG-150A needs DC power supply of 24~30V (M-NET) and 24V; the former is for centralized control transmission use and the
latter is for AG-150A's operating and LAN function use. AG-150A can have power-supply at following 1,2 methods.

3-6-1-1. Power supply unit PAC-SC51KUA is the recommended power supply for AG-150A. The basic scheme is as follows.
For details, please refer to Power supply unit PAC-SC51KUA.

M-NET M-NET

CENTRALIZED CONTROLLER AG-150A

Centralized controller
AG-150A 24VDC TB2

PAC-SC51KUA ME remote ME remote


(TB2 and TB3 used) controller controller

M-NET

LOSSNAY unit

ME remote PZ-52SF
controller

Fig. 3-6-1 AG-150A and PAC-SC51KUA basic scheme.

3-6-1-2. Power supply of 30VDC (M-NET) from connector of TB3 of Outdoor unit and PAC-SC51KUA.
AG-150A can also receive power supply from TB3 connector of the R410A or R407C, R22 Outdoor unit.Yet, Outdoor
unit down will lead down to AG-150A too. The kind of connection is possible but not recommended air conditioner
system of multiple Outdoor units. The 24VDC can be supplied at TB3 connector of PAC-SC51KUA.
CONTROLLER

Indoor/outdoor transmission line


TB3

CN41

PAC-SC51KUA
(TB3 24VDC used)
CENTRALIZED CONTROLLER AG-150A

Centralized controller
AG-150A

Fig. 3-6-2 AG-150A, TB3 and PAC-SC51KUA scheme.

When applying Charge and/or Peak-cut function on AG-150A, Power Supply Unit (PAC-SC51KUA) is recommended to use. AG-150A is
possible to receive power from the one of the Outdoor units, but there is a risk that the failure of power supply from the Outdoor unit will

CAUTION cause AG-150A's function-down on the whole system.


At the air conditioner system of multiple Outdoor units, the connector of CN41 is changed to CN40 at only one of the Outdoor units when
TB7 is used to supply power. When the Outdoor unit failed, the connector at another unit can be changed from CN41 to CN40 to recover
the power supply, but remember to change the CN40 back to CN41 at the failed Outdoor unit.

CNTR-32 CONTROLLER (Feb. 2009)


3. SYSTEM CONTROLLER DATA U4

3-6-2. External input/output usage


3-6-2-1. External signal input function
External signal input requires the external I/O adapter (Model: PAC-YG10HA-E) sold separately.
(1) External input
Emergency stop/normal, run/stop and prohibit/permit of local remote controller operation can be controlled for all air
conditioners being controlled by using a voltage (12VDC or 24VDC) contact signal from an external source.
(Select with the function select setting.)

No Function External signal input function Remarks


name
Do not use external input signal
1 Not in use
(factory setting)
Execute emergency stop/normal The local remote controller ON/OFF operations, and the
Emergency with level signal controller ON/OFF operation and prohibit/permit change
2 stop
operations will be prohibited during emergency stop.
(Level signal)
Timer operation will also be prohibited.
Perform ON/OFF with level signal The local remote controller ON/OFF operations, and the
ON/OFF controller ON/OFF operations and prohibit/permit change
3 operations will be prohibited.
(Level signal)
Timer operation will also be prohibited.
ON/OFF Perform ON/OFF, prohibit/permit Set the pulse width while the contact is ON to 0.5 to 1 sec.
4 prohibit/permit with pulse signals.
(Pulse signal)

(2) Level signal and pulse signal (12VDC or 24VDC)


(A) Level signal (B) Pulse signal
(Example) for ON/OFF
Contact ON
Signal 1 (run) 0.5 to 1 sec
Contact OFF Contact ON
Stop Run Stop
Contact OFF

Contact ON Signal 2 (stop) 0.5 to 1 sec


Contact ON
Contact OFF
Normal Emergency stop Normal Contact OFF

CONTROLLER
OFF ON OFF

*The prohibit/permit input is the same.


(3)External input specifications
CN5 Lead wire Emergency stop/normal level signal ON/OFF, level signal ON/OFF, prohibit/enable pulse signal
No.5 Orange Emergency stop/normal input ON/OFF input ON input
No.6 Yellow Not used Not used OFF input
Local remote controller operation
No.7 Blue Not used Not used prohibit input
Local remote controller operation
No.8 Gray Not used Not used enable input
No.9 Red External DC source “+ 12VDC” or “+ 24VDC”
(A) For level signal
When the emergency stop/normal signal is selected, the status will change from normal to emergency stop when the
external input signal contact changes from OFF to ON, and will change from emergency stop to normal when the
contact changes from ON to OFF. Air conditioning units that came to an emergency stop will remain stopped after
the emergency stop is cancelled. Manually start up each unit to restore the previous operation.
When the ON/OFF signal is selected, the status will change from OFF to ON when the external input signal contact
changes from OFF to ON, and will change from ON to OFF when the contact changes from ON to OFF.

(B) For pulse signal


Even if the ON signal is input during ON, the status will remain ON.
If the local remote controller is prohibited, the ON/OFF operation mode and temperature setting operations by the
local remote controller will be prohibited.
Set the pulse width (contact ON time) to 0.5 to 1 sec.

CONTROLLER (Feb. 2009) CNTR-33


3. SYSTEM CONTROLLER DATA U4

3-6-2-1. External signal input function


(4) Recommended circuit example

(A) For level signal


CN5
Red
X1

Run/stop or
Emergency stop

Orange X1
Power supply(*1)
(12VDC or 24VDC) Use relays X1, X2, Y1, and Y2 that meet the
Max.10m following specifications.
(32 ft)
This unit Contact rating
Rated voltage >= 12VDC
(B) For pulse signal Rated current >= 0.1A
Power supply(*1) Minimum applicable load =< 1mA at DC
CN5
Red (12VDC or 24VDC)

Gray Y2
Blue Y1 X1 X2 Y1 Y2
Yellow X2
Orange X1

Run Stop Prohibit Enable


Max.10m
(32 ft)
This unit

The contact relay, DC power source, extension cable, etc., must be prepared separately at the site.
The connection cable can be extended up to 10m (32 ft). (Use a 0.3mm2 (AWG 22) or larger wire.)
Strip the extra cable near the connector, and securely insulate the exposed section with tape, etc.

3-6-2-2. External signal output function


* External signal output requires the external I/O adapter (Model: PAC-YG10HA-E) sold separately.
(1)External output
When one or more air conditioners are running, the " ON " signal will be output and if a malfunction occurs in one or more air
conditioners, the " Malfunction " signal will be output.

(2)External output specifications


CN5 Lead wire Details of each terminal The " ON" signal is output even while the " Malfunction"
No.1 Green Common (External ground) signal is being output.

No.2 Black ON/OFF


CONTROLLER

No.3 Brown Malfunction/normal

(3)Recommended circuit example

CN5

Use Z1 and Z2 relays that meet the following specifications.


Diode(*2)
Z1 L1 Operation coil
Brown
Black (*2) Rated voltage : 12VDC, 24VDC
Z2
(*2) Power Consumption: 0.9W or less
Z1 L2
Z2 (*1) Prepare a power supply separately according to the relay
Power (*1)
Green Supply being used. (12VDC or 24VDC)
Max.10m (*2) Always insert a diode on both ends of the relay coil.
This unit (32 ft) L1: Run display lamp
L2: Malfunction display lamp

Each element will turn on while ON operation or a malfunction occurs.


The connection cable can be extended up to 10m (32 ft).
The relays, lamps, diodes and extension cables, etc, must be prepared separately at the site.

Punch out the knockout hole


NOTE
* When connecting the external input/output cables to connector CN5
on the controller, punch out the knockout hole.

CNTR-34 CONTROLLER (Feb. 2009)


3. SYSTEM CONTROLLER DATA U4

3-6-3. LAN connection function


When using the LAN connection function, connect the LAN cable to the
LAN connector of this device.
Procure the LAN cable at the site, and use 100 BASE-TX Straight cable.
For a description of the IP address setting method, refer to Instruction Book.
LAN is 100 BASE-TX Specification.

LAN

NOTE
Perform the LAN wiring before installation, and wire up to the body by the same method as wiring the M-NET
transmission line.
When a LAN is already connected, decide the IP address by consultation with the system administrator and
connect to the LAN body after changing the IP address.
Connect AG-150A to a private network.

CONTROLLER

CONTROLLER (Feb. 2009) CNTR-35


3. SYSTEM CONTROLLER DATA U4

3-6-4. Browser screens of AG-150A

Condition List (Overview) Condition List (Block)

°F
CONTROLLER

Operation Malfunction List

Malfunction Log Weekly Schedule

CNTR-36 CONTROLLER (Feb. 2009)


3. SYSTEM CONTROLLER DATA U4

Operation (DIDO Controller) Measurement status monitor (temperature


sensor/humidity sensor /measurement meter)

Trend Graph (temperature/humidity)

CONTROLLER

CONTROLLER (Feb. 2009) CNTR-37


3. SYSTEM CONTROLLER DATA U4

3-6-5. Liquid crystal displays of AG-150A

Floor layout screen Weekly schedule setting screen

Floor layout screen Annual schedule setting screen


CONTROLLER

Block display screen Operation screen

Error status screen Error history display screen

CNTR-38 CONTROLLER (Feb. 2009)


3. SYSTEM CONTROLLER DATA U4

3-7. Central controller [GB-24A]


Functions :Each unit :Each group :Each block
:Each floor :Collective :Not available
Item Description Operations Display

ON/OFF Run and stop operation for the air conditioning units
130 (51/8) Switches between Cool / Dry / Auto / Fan / Heat / Setback.
Operation mode (Group of LOSSNAY unit : automatic ventilation/ vent - heat
switching interchange/ normal ventilation)
*Operation modes vary depending on the air conditioner unit.
Range of temperature setting
Cool/Dry : 19°C - 30°C(14°C - 30°C) / 67°F - 87°F(57°F - 87°F)
Temperature Heat : 17°C - 28°C(17°C - 28°C) / 63°F - 83°F(63°F - 83°F)
setting Auto : 19°C - 28°C(17°C - 28°C) / 67°F - 83°F(63°F - 83°F)
Setback : Upper limit : 21°C - 30°C(21°C - 30°C) / 69°F - 87°F(69°F - 87°F)
Lower limit : 17°C - 26°C(17°C - 26°C) / 63°F - 79°F(63°F - 79°F)
250 (97/8) ( ) in case of using middle-temperature on PDFY, PEFY by setting DipSW7-1 to ON.
*Range of temperature settings vary depending on model.
Models with 5 air flow speed settings: Hi/Mid-2/Mid-1/Low, Auto
A. The centralized controller GB-24A combines Web Fan speed setting Models with 4 air flow speed settings: Hi/Mid/Low, Auto
Models with 2 air flow speed settings: Hi/Low
function, which enable the air conditioner system *Fan speed settings vary depending on the model.
management through a PC browser screen. Air flow direction 4-angle or 5-angle, Swing, Auto *1
*1 The management can even be carried out remotely. Air flow direction
setting
*1: Louver cannot be set.
*1 Microsoft ® Internet explorer Ver. 6 or later by Microsoft Corporation is *Air flow direction settings vary depending on the model.
needed. (Note: You must have “Sun Microsystems Java”; plug-in Ver.1.4.2 Today /weekly /annual schedule can be set in groups from the units.
or later). Microsoft is a registered trademark of Microsoft Corporation in the Schedule Schedule will be prioritized and performed in orders of Today *2
United States and other countries. operation annual weekly. Schedules (ON/OFF, mode, set temp,
permit/prohibit) can be changed up to 12 times per day.
Note: Connect GB-24A to a private network. *2: Schedule operation setting vary depending on the model.
B. One GB-24A can control maximum of 24 units Individually prohibit operation of each local remote control function
(including indoor units/LOSSNAY/DIDO*2/AI/PI controller). Permit / Prohibit
(ON/OFF, Operation mode switching, Temperature setting, Reset filter).
*3: When the local remote controller inactivation command is
*3

*2 The maximum number of the controllable units varies depending on the local operation
received from the main system controller, "Disabled"appears in
indoor unit or DIDO controller (the number of contacts used). inverted display on the operation setting screen.
Hold Prohibits the scheduled operation from being executed.
C. Using GB-24A's web functions, an error notification
email containing the address and error code can be Indoor unit intake
temperature
Measures the intake temperature of the indoor unit only when the indoor
unit is in operation.
sent to the appointed email address if any problem
When an error is currently occurring on an air conditioning unit, the
occurs in the air conditioning system. afflicted unit and the error code are displayed.
*4: When an error occurs, the "Error" LED flashes. The operation *4
D. Set back mode enables the indoor temperature Error monitor screen shows the abnormal unit by flashing. The error monitor
to be controlled within the setting range (°C/°F screen shows the abnormal unit's address, error code and source of
detection. The error log monitor screen shows the time, date, abnormal
°C/°F). unit's address, error code and source of detection.
Test run This operates air conditioning units in test run mode.
E. Hold operation is a priority function and when it is
effective, local remote controller operation The interlocked system settings can be performed by the master system
controller. When setting the interlocked system, you can use the ventilation
(ON/OFF,Mode,set temp) and schedule setting will Ventilation switch to switch the free plan LOSSNAY settings between "Hi", "Low"
be prohibited. equipment and "Stop". When setting a group of only free plan LOSSNAY units, you
can switch between "Normal ventilation", "Interchange ventilation" and
Hold operation will maintain even after electric power failure. Use the
"Automatic ventilation".
Automatic restoration after power failure function on the air conditioning units.
By using accessory cables you can set and monitor the following.
Input: By level signal: "Batch start/stop", "Batch emergency stop" *5 *5
External
By pulse signal: "Batch start/stop", "Enable/disable local remote controller"
input/output
Output: "Start/stop", "Error/Normal"
*5: Requires the external I/O cable (PAC-YG11HA) sold separately.

CONTROLLER
External dimension
Unit:mm[in.]

CONTROLLER (Feb. 2009) CNTR-39


3. SYSTEM CONTROLLER DATA U4

3-7-1. Power supply to GB-24A


GB-24A needs DC power supply of M-NET (24~32VDC) for centralized control transmission use, operation and LAN function use.
(1). Power supply of M-NET from power supply unit PAC-SC51(50)KUA.
Power supply unit PAC-SC51(50)KUA is recommended for GB-24A. See the diagram below ; for details, please refer to
the IM of Power supply unit PAC-SC51(50)KUA

LAN M-NET
M-NET

Centralized controller
GB-24A
Outdoor unit Indoor unit Indoor unit

Power supply unit


PAC-SC51(50)KUA
ME remote ME remote
controller controller

M-NET

Outdoor unit LOSSNAY unit


Indoor unit

ME remote LOSSNAY M-NET


controller remote controller

Mr.Slim
Outdoor unit

M-NET Indoor unit


adapter MA: MA remote controller

MA MA

Fig. 1 Basic structure of GB-24A and PAC-SC51(50)KUA

(2). Power supply of M-NET from outdoor unit connector TB7.


CONTROLLER

As shown on Fig. 2, GB-24A receives power supply of M-NET from R410A outdoor unit connector TB7.
In case one of the outdoor units should change its power supply, switch CN41 to CN40.
*NOTE: This method applies to R410A CITY MULTI outdoor unit except PUMY (S series)

R410A
Outdoor unit

Centralized control
transmission line Indoor/outdoor transmission line

Centralized controller
GB-24A
CN41 CN40

TB7

Indoor/outdoor transmission line

CN41
TB7

Fig. 2 GB-24A, TB7 scheme

CNTR-40 CONTROLLER (Feb. 2009)


3. SYSTEM CONTROLLER DATA U4

(3) Power supply of M-NET from outdoor unit connector TB3.


GB-24A can also receive power supply from R410A/R407C/ R22 outdoor unit connector TB3. However, if the
outdoor unit shuts down, GB-24A will also automatically shut down. Therefore, this scheme is not recommended
for air conditioning system consisting of multiple outdoor units.

Indoor/outdoor transmission line


TB3

CN41

ME remote
cotroller

Centralized controller
GB-24A
Fig. 3 GB-24A, TB3 scheme.

CONTROLLER

CONTROLLER (Feb. 2009) CNTR-41


3. SYSTEM CONTROLLER DATA U4

3-7-2. External input/output usage

CN2
(1). External signal input function
External signal input requires the external I/O adapter (Model: PAC-YG10HA) sold separately.
1). External input
Emergency stop/normal, run/stop and prohibit/enable of local remote controller operation can be controlled for all air
conditioners being controlled by using a voltage (12VDC or 24VDC) contact signal from an external source.
(Select the function on the Initial Setting Web or the Initial Setting Tool)

No External signal input function Remarks

1 Do not use external input signal


(factory setting)
2 Execute emergency stop/normal The local remote controller ON/OFF operations, and the
with level signal controller ON/OFF operation and prohibit/enable change
operations will be prohibited during emergency stop.
3 Perform ON/OFF with level signal The local remote controller ON/OFF operations, and the
controller ON/OFF operations and prohibit/enable change
operations will be prohibited.
4 Perform ON/OFF, prohibit/enable Set the pulse width while the contact is ON to 0.5 to 1 sec.
with pulse signals.
2). Level signal and pulse signal (12VDC or 24VDC)
(A) Level signal (B) Pulse signal
(Example) for ON/OFF
Contact ON
0.5 to 1 sec
Contact OFF
Contact ON
Stop Run Stop Signal 1 (run)
Contact OFF

Contact ON 0.5 to 1 sec


Contact ON
Contact OFF Signal 2 (stop)
Normal Emergency stop Normal Contact OFF
CONTROLLER

OFF ON OFF

The prohibit/enable input is the same.


3). External input specifications
CN2 Lead wire Emergency stop/normal level signal ON/OFF, level signal ON/OFF, prohibit/enable pulse signal
No.5 Orange Emergency stop/normal input ON/OFF input ON input
No.6 Yellow Not used Not used OFF input
Local remote controller operation
No.7 Blue Not used Not used
prohibit input
Local remote controller operation
No.8 Gray Not used Not used
enable input
No.9 Red External DC source
(A) For level signal
When the emergency stop/normal signal is selected, the status will change from normal to emergency stop when the
external input signal contact changes from OFF to ON, and will change from emergency stop to normal when the
contact changes from ON to OFF. Emergency stop signal will bring the air conditioners to stop, and canceling the
emergency stop will not automatically reset these units. To go back to the previous operation status, they must be
manually turned back on.
When the ON/OFF signal is selected, the status will change from OFF to ON when the external input signal contact
changes from OFF to ON, and will change from ON to OFF when the contact changes from ON to OFF.

(B) For pulse signal


Even if the ON signal is input during ON, the status will remain ON.
If the local remote controller is prohibited, the ON/OFF operation mode and temperature setting operations by the
local remote controller will be prohibited.
Set the pulse width (contact ON time) to 0.5 to 1 sec.

CNTR-42 CONTROLLER (Feb. 2009)


3. SYSTEM CONTROLLER DATA U4

4). Recommended circuit example


(A) For level signal
CN2
Red
9 X1

Run/stop or
8
Emergency stop
7
6
Orange X1
5 Power supply
(12VDC or 24VDC) Use relays X1, X2, Y1, and Y2 that meet the
1
Max.10m following specifications.
(32 ft) Contact rating
This unit
Rated voltage >= 12VDC
(B) For pulse signal Rated current >= 0.1A
Minimum applicable load =< 1mA at DC
CN2 Power supply
Red (12VDC or 24VDC)
9

Gray Y2
8
Blue Y1
7 X1 X2 Y1 Y2
Yellow X2
6
Orange X1
5
Run Stop Prohibit Enable
1
Max.10m
(32 ft)
This unit

The contact relay, DC power source, extension cable, etc., must be prepared separately at the site.
The connection cable can be extended up to 10m (32 ft). (Use a 0.3mm2 (AWG 22) or larger wire.)
Strip the extra cable near the connector, and securely insulate the exposed section with tape, etc.

(2). External signal output function


External signal output requires the external I/o adapter (Model: PAC-YG10HA) sold separately.
1). External output
When one or more air conditioners are running, the “ON” signal will be output and if a malfunction occurs in one or more air
conditioners, the “Malfunction” signal will be shown.

2). External output specifications


CN 2 Lead wire Details of each terminal " ON" signal and " Malfunction" signal will

CONTROLLER
No.1 Green Common (External ground) both be output.

No.2 Black ON/OFF


No.3 Brown Malfunction/normal

3). Recommended circuit example

CN2
Use Z1 and Z2 relays having the following specifications.
9
Operation coil
Diode(*2) Rated voltage :12VDC,24VDC
4 Z1 L1
Brown Power Consumption : 0.9W or less
3
2 Black (*2) ( 1)Prepare a power supply separately according to the
(*2) Z2
relay being used. (12VDC or 24VDC)
Z1 L2 ( 2)Always insert a diode on both ends of the relay coil.
Z2
Power (*1)
Green Supply
1
Max.10m
This unit (32 ft) L1: Run display lamp
L2: Malfunction display lamp

Each element will turn on while ON operation or a malfunction occurs.


The connection cable can be extended up to 10m (32ft).
The relays, lamps, diodes and extension cables, etc, must be prepared separately at the site.

CONTROLLER (Feb. 2009) CNTR-43


3. SYSTEM CONTROLLER DATA U4

3-7-3. LAN connection function


Connect the LAN cable to the LAN connector of this device.
Procure the LAN cable at the site, and use an enhanced category 5 UTP cable.
For a description of the IP address setting method, refer to Installation Manual.
LAN is 10 BASE-T Specification.
The maximum wiring length from HUB to GB-24A is 100m [328ft].
GB-24A is connected to the monitoring PC via HUB.

NOTE
Perform the LAN wiring before installation, and wire up to the body by the same method as wiring the M-
NET transmission line.
When a LAN is already connected, decide the IP address by consultation with the system administrator and
connect to the LAN body after changing the IP address.
Space f or the connector and wiring is required. Refer to Installation Manual.
Connect GB-24A to a private network.
Use a security device such as a VPN router when connecting the GB-24A to the Internet to prevent
unauthorized access.
(If no security devices are installed, the operation settings may be changed by an unauthorized person
without the knowledge of the user.)
CONTROLLER

CNTR-44 CONTROLLER (Feb. 2009)


3. SYSTEM CONTROLLER DATA U4

3-7-4. Browser screens of GB-24A

Condition List (Overview) Condition List (Block)

CONTROLLER
Operation (with Setback) Operation (without Setback)

Malfunction Log Malfunction List

CONTROLLER (Feb. 2009) CNTR-45


3. SYSTEM CONTROLLER DATA U4

Operation (DIDO Controller) Measurement status monitor (temperature


sensor/humidity sensor /measurement meter)
CONTROLLER

Trend Graph (temperature/humidity) Weekly Schedule

CNTR-46 CONTROLLER (Feb. 2009)


3. SYSTEM CONTROLLER DATA U4

3-8. Power supply unit [PAC-SC50KUA]


PAC-SC50KUA supplies DC powers of 24V and 12V at TB2 and TB3 respectively; the former is for central control transmission
use and the latter is for G-50A operation and LAN function use.

3-8-1. When using PAC-SC50KUA as the power supplier for system controller, the capacity for system controller is considered
as follows.

Main SC Central control


transmission line Indoor/outdoor transmission line

TB7
Add : 000
(DC12V) CN41
TB3

TB2
(DC24V)
Indoor/outdoor transmission line
Power supply unit TB7
PAC-SC50KUA

Sub SC CN41

Add : 201

SC : System Controller
Lossnay

Lossnay can have its own Lossnay remote


controller, but the total quantity of the controllers
is limited.
Fig. 3-8-1 Equivalent power consumption of controllers
In this case, pay attention to leave the power supply switch connector on CN41 of the Outdoor unit as the factory setting
before shipment.

Taking the power consumption of the control board of Indoor unit as 1, the power consumption of various controllers is rated at
Table 3-8-1.
Table 3-8-1 Equivalent power consumption of controllers
Central controllers Other system controllers Remote controllers
ON/OFF remote controller System remote controller ME remote controller

CONTROLLER
(PAC-YT40ANRA) (PAC-SF44SRA) (PAR-F27MEA)
G-50A GB-50A GB-24A Schedule timer LOSSNAY remote controller
(PAC-YT34STA) (PZ-52SF)
0.5 3 1 1 0.5 0.25

PAC-SC50KUA is capable to supply equivalent power up to 6, therefore the maximum connectable number of system con-
trollers is as follows.
Note: AG-150A cannot be connected to PAC-SC50KUA. Use PAC-SC51KUA to connect to AG-150A.

Table 3-8-2 Max. connectable quantity of controller when using PAC-SC50KUA


Central controller Other system controllers Remote controllers
System remote controller ME remote controller
ON/OFF remote controller
(PAC-SF44SRA) (PAR-F27MEA)
G-50A GB-50A GB-24A (PAC-YT40ANRA) Schedule timer LOSSNAY remote controller
(PAC-YT34STA) (PZ-52SF)
2 units
(Note 1) 2 units 1 unit 6 units 12 units 24 units

(Note 1) Due to its current limit of DC12V supplying, the PAC-SC50KUA can supply power for maximum 2 G-50As.
Note: AG-150A cannot be connected to PAC-SC50KUA. Use PAC-SC51KUA to connect to AG-150A.

As the air conditioner control system may combine all kinds of system controllers, the total power consumption of system con-
trollers need to count with Table 3-8-1.
For example, the controller system contain 1 G-50A, 2 ON/OFF remote controllers (PAC-YT40ANRA), 1 schedule timer (PAC-
YT34STA), 6 Lossnay remote controllers connected at centralized control communication line.
then the total power consumption is
1x0.5+2x1+1x0.5 +6x0.25 = 4.5 6.
One PAC-SC50KUA is therefore enough. The total power consumption should not exceed 6.

CONTROLLER (Feb. 2009) CNTR-47


&C=>18<18:>1/:9><:771<
3. SYSTEM CONTROLLER -.
DATA U4

8 0>;DIKFFBOFEM;HJE   J>;), $.97DIKFFBOFEM;HJEEJ>;HIOIJ;C9EDJHEBB;HI7I<EBBEMI

-78B;8EDD;9J78B;DKC8;HE<IOIJ;C9EDJHEBB;HM>;D   ?IKI;:
/EDD;9J78B;
-EJ7BDKC8;HE<('
(H;CEJ;9EDJHEBB;H'
   
 / / / / /
/ / / / / /
/ / / / /
 / / / / /
-EJ7BDKC8;HE<  / / / /
,OIJ;CH;CEJ;9EDJHEBB;H  / / / /
,9>;:KB;J?C;H
 / / /
 / / /
 / /
 / /
/
/

0>;D7FFBO?D=>7H=;7D:
EH);7A9KJ<KD9J?EDED  )EM;H,KFFBO.D?J), $.?IH;9ECC;D:;:JEKI;   ?IFEII?8B;JE
('"! H;9;?L;FEM;H<HECED;E<J>;(KJ:EEHKD?JI8KJJ>;H;?I7H?IAJ>7JJ>;<7?BKH;E<FEM;HIKFFBO<HECJ>;(KJ:EEHKD?JM?BB97KI;  I<KD9J?ED
:EMDEDJ>;M>EB;IOIJ;C

8 0>;DIKFFBOFEM;HJE   J>;), $.97DIKFFBOFEM;HJEEJ>;HIOIJ;C9EDJHEBB;HI7I<EBBEMI 

-78B;8EDD;9J78B;DKC8;HE<IOIJ;C9EDJHEBB;HM>;D   ?IKI;: 


/EDD;9J78B;
CONTROLLER

-EJ7BDKC8;HE<('
(H;CEJ;9EDJHEBB;H'
   
 / / /
/ / /
/ / /
 / /
-EJ7BDKC8;HE<  / /
,OIJ;CH;CEJ;9EDJHEBB;H  /
,9>;:KB;J?C;H
 /





0>;D7FFBO?D=>7H=;7D:
EH);7A9KJ<KD9J?EDED  )EM;H,KFFBO.D?J), $.?IH;9ECC;D:;:JEKI;   ?IFEII?8B;JE
('"! H;9;?L;FEM;H<HECED;E<J>;(KJ:EEHKD?JI8KJJ>;H;?I7H?IAJ>7JJ>;<7?BKH;E<FEM;HIKFFBO<HECJ>;(KJ:EEHKD?JM?BB97KI;  I<KD9J?ED
:EMDEDJ>;M>EB;IOIJ;C

CNTR-48 CONTROLLER (Feb. 2009)

('-+(%%+ DJH
3. SYSTEM CONTROLLER DATA U4

External dimension

Unit:mm[in.]
265[10-7/16 ]
59.2[ 2-11/32 ]
150[ 5-29/32]

225 [8-27/32 ]
240 [9-7/16]
TB3

TB2

Cable fixture Cable fixture


TB1

CONTROLLER

CONTROLLER (Feb. 2009) CNTR-49


3. SYSTEM CONTROLLER DATA U4

3-9. Power supply unit [PAC-SC51KUA]


PAC-SC51KUA supplies DC power of 22-30V and 24V at TB2 and TB3 respectively; the former is for centralized transmission use
and the latter is for AG-150A operation and LAN function use.

3-9-1. When using PAC-SC51KUA as the power supplier for system controller, the capacity for system controller is
considered as follows.

Main SC Centralized control


transmission line Indoor/outdoor transmission line
CENTRALIZED CONTROLLER AG-150A

TB7
Add : 000
(24VDC) CN41
TB3

TB2
(30VDC) M-NET
Indoor/outdoor transmission line
Power supply unit TB7
PAC-SC51KUA

Sub SC CN41

Add : 201

SC : System Controller
LOSSNAY

Lossnay can have its own Lossnay remote


controller, but the total quantity of the controllers
is limited.
Fig. 3-9-1 Equivalent power consumption of controllers
In this case, pay attention to leave the power supply switch connector on CN41 of the Outdoor unit as the factory setting
before shipment.
Taking the power consumption of the control board of Indoor unit as 1, the power consumption of various controllers is rated
at Table 3-9-1.
Table 3-9-1 Equivalent power consumption of controllers
Centralized controller *1 Other system controllers Remote controllers
System remote controller ME remote controller
CONTROLLER

ON/OFF remote controller (PAC-44SRA) (PAR-F27MEA)


AG-150A GB-50A GB-24A
(PAC-YT40ANRA) Schedule timer LOSSNAY remote controller
( PAC-YT34STA) (PZ-52SF)

0.5 3 1 1 0.5 0.25

*1: G-50A cannot be connected to PAC-SC51KUA. Use PAC-SC50KUA to connect G-50A.

PAC-SC51KUA is capable to supply eqovalent power up to 5, therefore the maximum connectable number of system controller
is as follows.
Table 3-9-2 Max. connectable quianity of controller when using PAC-SC51KUA

Centralized controller *1 Other system controllers Remote controllers


System remote controller ME remote controller
ON/OFF remote controller (PAC-44SRA) (PAR-F27MEA)
AG-150A GB-50A GB-24A (PAC-YT40ANRA) Schedule timer LOSSNAY remote controller
( PAC-YT34STA) (PZ-52SF)

1 unit 1 unit 1 unit 5 units 10 units 20 units

*1: G-50A cannot be connected to PAC-SC51KUA. Use PAC-SC50KUA to connect G-50A.

As the air conditioner control system may combine all kinds of system controllers, the total power
consumption of system controllers need to count with Table 3-9-2.
For example, the controller system contain 1 AG-150A, 2 ON/OFF remote controllers (PAC-YT40ANRA),
1 schedule timer (PAC-TY34STA), 6 Lossnay remote controllers connected at centralized control
communication line.
Then the total power consumption is
1 x 0.5+2 x 1+1 x 0.5+6 x 0.25 = 4.5 < 5.
One PAC-SC51KUA is therefore enough. The total power consumption should not exceed 5.
CNTR-50 CONTROLLER (Feb. 2009)
3. SYSTEM CONTROLLER DATA U4

3-9-2. When supply power to 1 AG-150A, the PAC-SC51KUA can supply power to other system controllers as follows.
Table 3-9-3 Connectable number of system controller when 1 AG-150A is used.
V : Connectable
Total number of ON/OFF remote controller(AN)
0 1 2 3 4 5
0 V V V V V
1 V V V V V
2 V V V V
3 V V V V
Total number of 4 V V V
System remote controller(SR) 5 V V V
Schedule timer(ST)
6 V V
7 V V
8 V
9 V
10

When applying Charge and/or Peak-cut function on AG-150A, Power Supply Unit (PAC-SC51KUA) is recommended to use.
CAUTION AG-150A is possible to receive power from one of the Outdoor units, but there is a risk that the failure of power supply from
the Outdoor unit will cause AG-150A's functiondown on the whole system.

3-9-3. When supply power to 1 GB-50A, the PAC-SC51KUA can supply power to other system controllers as follows.
Table 3-9-4 Connectable number of system controller when 1 GB-50A is used.
V : Connectable
Total number of ON/OFF remote controller(AN)
0 1 2 3 4 5

CONTROLLER
0 V V V
1 V V
2 V V
3 V
Total number of 4 V
System remote controller(SR) 5
Schedule timer(ST)
6
7
8
9
10

When applying Charge and/or Peak-cut function on GB-50A, Power Supply Unit (PAC-SC51KUA) is recommended to use.
CAUTION GB-50A is possible to receive power from one of the Outdoor units, but there is a risk that the failure of power supply from
the Outdoor unit will cause AG-150A's functiondown on the whole system.

CONTROLLER (Feb. 2009) CNTR-51


3. SYSTEM CONTROLLER DATA U4

External dimension

Unit:mm[in.]

271(10-1116) 72(2-7 8)
90(3-916)

!$!%"  ""

#!  "!
!#"""%"%"! "!$&"#!
 #"  "!$#!""&"  
$#"  ""&#!#!  "

169(6-11 16)


130(5-1 8)

155(6-1 8)


TB2,TB3 TB1
CONTROLLER

CNTR-52 CONTROLLER (Feb. 2009)


3. SYSTEM CONTROLLER DATA U4

3-10. Integrated centralized control software [TG-2000A]


3-10-1. Example of Basic System Configuration.
Single-phase 208/230V
M-NET
Charge
CENTRALIZED CONTROLLER AG-150A

Input AG-150A
license

Web
24VDC
monitor
license Single-phase 208/230V

Schedule Power supply unit


license PAC-SC51KUA
Compatible with TG-2000A Ver. 4.10 and higher
Indoor unit system The electric amount count software or separately
3-phase 208/230V watt-hour meter procured parts must be used with the designated PLC.
(3-wire)
Indoor unit power source
watt-hour meter Indoor unit system
watt-hour meter
Outdoor unit system
watt-hour meter Indoor unit
watt-hour meter

USB or RS-485 Outdoor unit system


watt-hour meter
RS-232C
Converter
PLC (with electric amount count
Uninterruptive Central controller software)
power supply (UPS) personal computer
TG-2000A Central control
Uninterruptible
power supply (UPS) personal computer
TG-2000A

TG-2000
Integrated Integrated centralized control
centralized control software installation
software installation

The TG-2000A can realize the following functions


using the AG-150A/G(B)-50A option (license).
Operation/monitor
Annual/weekly schedule

CONTROLLER
Charge
Energy saving 1
Peak cut 1
1: Compatible with TG-2000A Ver. 4.10 and
CENTRALIZED CONTROLLER AG-150A

higher, G-50A Ver. 2.51 or later.


Main features of TG-2000A
1 Up to 2000 indoor units (40 AG-150, G-50A, GB-24 or GB-50A units) can be operated and monitored . simultaneously
2 The air-conditioner layout can be displayed on the screen, making control and operation easier.
3 The annual and weekly schedules can be set. Two schedules, such as the summer master and winter master, can be
saved in the weekly schedule.
4 Air-conditioning charges can be calculated based on the multiple air-conditioner usage results. The power apportionment
percentage data and apportioned power rate can be calculated for each indoor unit using the power apportionment
function, and can be output as a CSV format file. Power apportionment charging is not possible with the old model, A control or K control.
Charging without WHM : The user manually inputs the power rate to calculate the air-conditioning charges. (Using a tool)
RS-485 WHM charging : The RS-485 WHM value is automatically tabulated to calculate the air-conditioning charges.
PLC + pulse WHM charging : The pulse output WHM value is automatically tabulated by the PLC to calculate the air-
conditioning charges.
5 Energy saving operation is possible using the "ON/OFF", "set temperature change", "fan operation changeover" and
"performance save operation (60% to 90%)" functions.
Energy saving operation matching the amount of power in use is possible by using the PLC's electric amount count
software.
6 Night Set-Back function operation is possible with schedule settings. 1,4
7 General equipment can be operated and monitored. 2
8 General equipment can be schedule-controlled when using PAC-YG21CDA with PLC.
For details of PLC refer to Installation Manual of PAC-YG21CDA. 3
1: Compatible with TG-2000A Ver. 4.10 or later, G-50A Ver. 2.51 or later.
2: Compatible with TG-2000A Ver. 4.30 or later, G-50A Ver. 2.51 or later.
3: Compatible with TG-2000A Ver. 4.60 or later, G-50A Ver. 2.70 or later.
4: With Night Set-Back function, the CITY MULTI system can run at heating mode with target temperature set to 54 12 under
schedule control. This function can protect the room from dropping down to extremely low temperature at mid-night.
Note: AG-150A (Ver. 1XX Series) will be compatible with TG-2000 Ver. 5.5 or later. Depending on the versions of TG-2000 and
G(B)-50A, some functions may not be available.

CONTROLLER (Feb. 2009) CNTR-53


3. SYSTEM CONTROLLER DATA U4

3-10-2. List of TG-2000A functions


The data for each G-50A/GB-50A can be grouped and used to control the operation of up to 2000 units in floor or block units, etc.,
from the personal computer screen. By using a PLC or a watt-hour meter, the power rate can be apportioned, energy saving
control can be executed, and other general equipment can be controlled.

List of integral software functions


G-50A/GB-50A license

Web monitor

Charge

Schedule

Energy saving

(peak cut)
Energy saving

general equipment
PLC for
Item Details

ON/OFF The units can be turned ON and OFF for all floors or in block, floor or group units. V
The general equipment can be turned ON and OFF.
V
( A PLC and the general equipment control PLC software required.) 2

Operation modes The operation mode can be switched between COOL, DRY, FAN, AUTO and
HEAT for all floors or in block, floor or group units. V

Temperature setting The room temperature can be set for all floors or in block, floor or group units.
Set temperature range COOL / DR
HEAT V
AUTO
Depend on unit type
Fan speed The fan speed can be set to four stages for all floors or in block, floor or group units. V
Air direction The air direction can be set in four vertical directions or to swing for all floors or in block,
V
floor or group units.(The selectable air direction dif fers according to the model.)

Interlocked unit ON/OFF If there is an interlocked unit (LOSSNAY), the unit can be turned ON (strong/weak) or OFF for all floors
V
(LOSSNAY) or in block, floor or group units. (Note that the ventilation mode cannot be selected for interlocked units.)

Local operation The items for which operation with the local remote controller are to be prohibited can be selected for
prohibit all floors or in block, floor or group units. (The items that can be prohibited are ON/OFF, operation mode, V
set temperature and filter sign reset.)

Annual / weekly The annual/weekly schedule function can be used by registering the license.
V V
schedule Two settings, such as seasonal settings for summer and winter, can be saved.

Power rate By registering the G-50A unit license number, the power rate apportionment percentage data for
apportionment charging each indoor unit can be output in CSV format. The power rate for each tenant can be easily V V
(power rate manual input) calculated by having each user input the power rate manually.

Power rate An RS-485 watt-hour meter is connected to calculate the air-conditioning charges based on the
apportionment charging amount each tenant's air-conditioner has operated. Two charging rates can be applied per day.
CONTROLLER

By using a PLC (with electric amount count software) and a watt-hour meter with pulse transmitter, V V
the air-conditioning charges can be calculated based on the amount each tenant's air-conditioner has
operated.Up to five charging rates can be applied per day. 1

History Up to 3000 items for the error history and up to 10000 items for operation history can be saved.
Each history file can be output as a daily report or monthly report in CSV format. V
The operation history consists only of the operations carried out with the TG-2000A, and is limited to some limited operation items.

Operation time monitor The cumulative operation time of each indoor unit can be viewed or output as a CSV format file.
V V
(This function is valid only when the charging function license is registered.)

Filter sign display Automatic display of the filter sign can be disabled. (System batch.)
V
mask In this case, the filter sign state is confirmed with manual operations .
Energy saving Energy saving operation is possible using the "ON/OFF", "set temperature change", "fan operation
V V
control 1 changeover" and "performance save operation" functions.

Energy saving Energy saving operation matching the amount of power in use is possible.
V V
(peak cut) 1 (PLC (with electric amount count software) and watt-hour meter with pulse transmitter are required.)

Night Set-Back function 1,4 V V


Set temperature The set temperature lower limit can be set for cooling and the upper limit for heating.
limit 1 (Valid only when PAR-F27MEA is used.) V

Control other general It is possible to control other general equipment on ON/OFF operation / monitoring / Alarm /
equipment scheduling, if TG-2000A combines PLC installed with PLC software PAC-YG21CDA. 2 V

Setting inter-lock with CITY MULTI indoor units is possible.


(Table setting tool for input/output definition is needed.) 3 V V

The ON/OFF status of the connected general equipment and the error status can be V
changed or monitored from the DIDO (PAC-YG66DCA).
1: Compatible with TG-2000A Ver. 4.10 or later, G-50A Ver. 2.51 or later.
2: Compatible with TG-2000A Ver. 4.30 or later, G-50A Ver. 2.51 or later.
3: Compatible with TG-2000A Ver. 4.60 or later, G-50A Ver. 2.70 or later.
4: With Night Set-Back function, the CITY MULTI system can run at heating mode with target temperature set to 54 12 under schedule control.
This function can protect the room from dropping down to extremely low temperature at midnight.
Note: Depending on the versions of TG-2000 and G(B)-50A, some of the functions may not be available for use.

CNTR-54 CONTROLLER (Feb. 2009)


&C=>18<18:>1/:9><:771<
3. SYSTEM CONTROLLER -.
DATA U4

10 <:A=1<=/<119=:2'


0;;ABOI9>;:KB;I9H;;D

BEEHI9H;;D

DDK7BI9>;:KB;I9H;;D

BE9AI9H;;D

BB<BEEHI9H;;D (F;H7J?EDI;JJ?D=I9H;;D CONTROLLER

?H9ED:?J?ED?D=9>7H=;I9H;;D

('-+(%%+
CONTROLLER (Feb. 2009) CNTR-55
DJH
3. SYSTEM CONTROLLER DATA U4

3-10-4. Requirements (system recommendations)


We recommend the following software and hardware when using this application (TG-2000A).
Item Requirement Recommended
PC PC/AT interchangeable machine Operation check completed, using IBM, and DELL

CPU Within 1000 indoor units : Pentium 4 2.8GHz or faster


Pentium 4 1.8GHz or faster
1001 indoor units or over :
Pentium 4 1.8GHz or faster
(Case of temp, trend use : 2.8GHz or faster.)
Memory 128MB or more (In Windows XP : 256MB or more) 512MB or more
HDD 6GB or more (2GB or more of C drive free 4GB or more of C drive free space necessary
space necessary) When using the trend function, the drive used for au-
tomatic output must have the following free space ac-
cording to the number of groups.
200 groups = 2GB, 500 groups = 5GB,
1000 groups = 10GB, 2000 groups = 20GB
Storage device FDD, CD-ROM drive Devices other than those shown at the left may also
be installed.
Resolution 1024 768 or higher, 65536 colors or more
Serial port 1 port or more Required when using RS-485 communication WHM
LAN Internal LAN (10/100 Mbps) 1
OS Windows XP Professional English version only
Windows 2000 Professional Personal computer must support each OS.
Service Pack 2 and above
Other Computer must be dedicated for this use
(TG-2000A).
1 Purchase the option, or use the equipment recommended for the personal computer when purchasing the personal computer.

3-10-5. Compatible Units


The TG-2000A has two main functions: centralized control of air conditioners and cost accounting. However, not all
functions are available with all air conditioners. (TG-2000A Ver.4.80 or later)
CONTROLLER

Table: Compatible units and function list ( : supported, : Certain restrictions apply, : Not supported)

Function Control/
Charging (Billing) with WHM
Model Maintenance

Y-Series 1
R2-Series 1
WR2-Series 1
WY-Series 1
S-Series 1
Indoor unit 2
LOSSNAY 4
OA processing unit 1
"A" control type 3 1
(Adapter required)
"K" control type 3 1
(Converter required)
1 : Can be calculated for each charging block. May not be available with some older models.
2 : Indoor unit models before Free Plan models do not support a charge apportioning billing method based on
the “capacity save”. The existence of even a single unit of those types in the system requires that the
method of charge apportioning billing be set to either “Thermo on time” or “Fan operation time”.
3 : Not all of the A-control and K-control units support these functions. The calculation of the charge for the
auxiliary heater may not be handled by these units.
4 : LOSSNAY groups to which the remote controller is connected support the charging system.

CNTR-56 CONTROLLER (Feb. 2009)


3. SYSTEM
3. System remote controller
CONTROLLER DATA
DATA U3
U4

3-11. Electric
3-11. amount
Electronic count count
amount software [PAC-YG11CDA]
software [PAC-YG11CDA]
MITSUBISHI ELECTRIC offers charging function for the air conditioner system. Detailed output of every indoor on electricity
consumption of air-conditioning is available. The electricity consumption of air-conditioner is counted based on the refrigerant
consumption of every indoor unit, which makes the proportion of electricity consumption precise.

System example

Single-phase 208/230V

Charge
Input
CENTRALIZED CONTROLLER AG-150A

license AG-150A

DC12V

Single-phase 208/230V

Power supply unit


PAC-SC51KUA
3-phase 208/230V
(3-wire)

Outdoor unit system


watt-hour meter Indoor unit system watt-hour meter

Indoor unit system watt-hour meter

PLC (Pulse counting software installed)

Uninterrupted
power source (UPS) PC for TG-2000A

Install TG-2000A software

CONTROLLER
Necessary parts for the system

Name (Model name) Manufacturer Remarks


PC for central control PC/AT convertible unit Confirmed operation of IBM, DELL, Hp Compaq.
For details, refer to G-50A Technical Manual.
TG-2000A MITSUBISHI ELECTRIC
Charge license MITSUBISHI ELECTRIC Requires for each AG-150A/G-50A/GB-50A.
Web monitor license MITSUBISHI ELECTRIC Requires for each AG-150A/G-50A/GB-50A.
PLC MITSUBISHI ELECTRIC PLC for pulse counting connects maximum 5 sets.
For details, refer to Installation Manual of PAC-YG11CDA.
PAC-YG11CDA MITSUBISHI ELECTRIC For details, refer to G-50A Technical Manual.
Watt-hour meter with pulse oscillator MITSUBISHI ELECTRIC For the specification of the watt-hour meter, refer to G-50A
Technical Manual.
Uninterrupted power source (UPS) Field supplied.

CONTROLLER (Feb. 2009) CNTR-57


CONTROLLER Cntr- 37
3. SYSTEM CONTROLLER DATA U4

3-12.PLC
3-12. PLCsoftware
softwarefor for general
general equipment
equipment [PAC-YG21CDA]
[PAC-YG21CDA (SW-PLC-GE])
(SW-PLC-GE)]
MITSUBISHI ELECTRIC's Air Conditioner control system can combine control of general equipment like lighting, air condition-
ers from others, and so on.
Functions on general equipment : On/Off operation, alarm, monitoring, scheduling.

System example

LAN M-NET *1

CENTRALIZED CONTROLLER AG-150A

AG-150A
license Input

*1.MITSUBISHI ELECTRIC Air Conditioner network.

M-NET *1

PAC-SC51KUA
Power supply unit

Free contact
CENTRALIZED CONTROLLER AG-150A

(input and output signal)


AG-150A

Pulse or Level output

Lighting
Level input
PLC

PC for TG-2000A Other manufacturer's packaged


air-conditioning units

TG-2000A installed.
PLC software for general equipment
PAC-YG21CDA [SW-PLC-GE] Other manufacturer's fan coil units

Chiller/heat source
machine
CONTROLLER

Necessary parts for the system

Materials (model names) Maker Remarks


PC for central control PC/AT compatible Confirmed operation of IBM, DELL, Hp Compaq.
For details, refer to G-50A Technical Manual.
TG-2000A MITSUBISHI ELECTRIC Use Ver.4.60 or later (Use G-50A's Ver. 2.70 or later)
Web monitor license MITSUBISHI ELECTRIC Requires for each AG-150A/G-50A/GB-50A.
PLC for general equipments license MITSUBISHI ELECTRIC Table-setting of input/output is necessary.
PLC MITSUBISHI ELECTRIC Make sure DI board and DO board are mounted.
PAC-YG21CDA [SW-PLC-GE] MITSUBISHI ELECTRIC For details, refer to G-50A Technical Manual.

CNTR-58 CONTROLLER (Feb. 2009)


CONTROLLER Cntr- 38
3. SYSTEM CONTROLLER DATA U4

3-13. BACnet® ®interface


3-13. BACnet interface [PAC-YG31CDA
[PAC-YG31CDA] (SW-BACnet)]
[SW-BACnet]
CITY MULTI® can easily combine into a Building Management System (BMS) via the BACnet® interface software and a PC.
BACnet® is an opened transmission protocol widely used at BMS, and related equipment control. CITY MULTI® is therefore
compatible with large-scaled BMS management via BACnet®.

One BACnet® interface software and PC serves up to 10 AG-150A/G-50As/GB-50As.


System example

Central BMS
monitor
®
BACnet

LAN M-NET
CENTRALIZED CONTROLLER AG-150A

AG-150A

BACnet® interface software


PAC-YG31CDA (SW-BACnet)

M-NET

PAC-SC51KUA
Power supply unit

CENTRALIZED CONTROLLER AG-150A

AG-150A

Web
Browser TG-2000A
(Optional) (Optional)

CONTROLLER
Communication items at BACnet® Interface Software PAC-YG31CDA (SW-BACnet)
On/Off On/Off
Mode Mode
Fan speed Fan speed
Air direction Air direction
Set temp. Set temp.
Filter sign reset Filter sign
Indoor temperature
State
Operation Prohibit local On/Off Prohibit local On/Off
Monitoring
Prohibit local Mode Prohibit local Mode
Prohibit local Filter sign reset Prohibit local Filter sign reset
Prohibit local Set temp. Prohibit local Set temp.

Forced Off Alarm signal


Error code
Communication state
Use a dedicated PC with the BACnet® interface software (PAC-YG31CDA).

CONTROLLER (Feb. 2009) CNTR-59


3. SYSTEM CONTROLLER DATA U4

3-14.PLC
3-14. PLCsoftware
softwarefor for demand
demand inputinput [PAC-YG41CDA]
[PAC-YG41CDA]
MITSUBISHI ELECTRIC's CITY MULTI® has its intelligent way to carry out peak-cut control while maximizing the air condition-
ing effect.

System example

The registration of
- Energy saving setting
License energy saving control
- Set temperature control ( .
- Monitoring of current energy saving - Fan (thermostat OFF) control
state or peak cut control is
necessary. - Stopping control

CENTRALIZED CONTROLLER AG-150A

AG-150A
PC for TG-2000A

Collects current - Capacity saving control


daily consumption (60/70/80/90%)
(every per minute)
Collects daily
power
consumption

Watt-hour
meter
PLC PAC-YG11CDA
(Pulse counting
software installed) Counts for electric power pulse
or
Requires to execute the peak cut control.
Either method should be used.These methods cannot be used together.

Demand
controller
PLC
(PLC software
for demand input) Contact input (4 levels max.)

If the quantity of G-50A exceeds 11 sets, one set of PLC is required


for each 10 sets of PLC.
CONTROLLER

Necessary parts for the system

Name (Model name) Maker Remarks


PC for central control PC/AT convertible unit Confirmed operation of IBM, DELL, Hp Compaq.
For details, refer to G-50A Technical Manual.
TG-2000A MITSUBISHI ELECTRIC Use Ver.4.6 or later.
G-50A/GB-50A MITSUBISHI ELECTRIC Use Ver.2.6 or later.
Energy saving control (peak cut) license MITSUBISHI ELECTRIC Requires for each AG-150A/G-50A/GB-50A.
Web monitor license MITSUBISHI ELECTRIC Requires for each AG-150A/G-50A/GB-50A.

CNTR-60 CONTROLLER (Feb. 2009)


3. System remote controller DATA U3
3. SYSTEM CONTROLLER DATA U4

Applying the energy saving setting from the integrated centralized control software TG-2000A or Initial setting Web allows
conducting the energy saving control by the indoor/outdoor units or peak-cut control by using PLC.

Item Content
Energy saving Indoor unit control The TG-2000A or Initial setting Web sets the f ollowing energy saving items and energy saving
control time to G-50A/GB-50A per operation block. G-50A/GB-50A conducts energy saving operation to
the indoor units with the set detail.
Temperature control ( .
Fan control (Thermostat ON)
Stopping control
For the block with temperature difference between set and inlet temperature exceeding the set,
the energy saving control set at level 0 is not applied.
Outdoor unit The TG-2000A or Initial setting Web sets the following energy saving items and energy saving
control 2 time to G-50A/GB-50A per outdoor unit and the set G-50A/GB-50A conducts the energy saving
operation for the outdoor unit.
Peak cut control Power consumption Connecting the watt-hour meter (PLC) allows conducting energy saving operation meeting the
monitoring method power consumption. The control object and detail are same as that of the energy saving rotated
control. One set of the watt-hour meter can be set for each G-50A/GB-50A.
Demand controller Energy-saving control that is appropriate to the current demand level is performed by receiving
method the demand level contact signal from the demand controller using the PLC.
An installation of demand input PLC software is necessary to use the PLC.
Control targets and control content of this method are the same as those of the energy-saving control.
Each PLC unit can control up to ten G-50A units to be on the energy-saving control.
Monitoring of Control status During the energy saving control, the energy saving mark is displayed on the air conditioner
energy saving group icon of Web, integrated software.
control Daily report Daily power consumption and control level can be monitored by the integrated software. G-50A/GB-50A
status/history1 can hold the data for 3 days max. including that of today, yesterday and the day before yesterday.
Monthly report Monthly power consumption can be monitored by the integrated software (for 62 days max.).
The integrated software monitors from PLC for display and storing.
1; Daily Report and Monthly Report are functions that are enabled only when registering the "Energy-saving peak cut control license."TG-
2000A must always be kept in operation to gather data on energy-saving control status and the operation history. The auto-output CSV
files in the Daily Report and Monthly Report can be saved for two years in the appropriate folders.
2; For Mr. Slim units, apply Outdoor Unit Control function only to Inverter type units.

CONTROLLER

CONTROLLER Cntr- 41
CNTR-61
CONTROLLER (Feb. 2009)
3. SYSTEM CONTROLLER DATA U4

3-15. LonWorks
3-15. LonWorks® ® interface [LMAP03U]
interface [LMAP03U]
CITY MULTI® can easily combine into a Building Management System (BMS) via the LONWORKS and M-NET adapter
®

LMAP03U. LONWORKS is an opened transmission protocol widely used at BMS and related equipment control.
®

CITY MULTI® is therefore compatible with large-scaled BMS management via LONWORKS . ®

One LMAP03U serves up to 50 indoor units. (CITY MULTI , Mr. Slim , and LOSSNAY .)
® ® ®

System example

LMAP

Building management system

Protocol : LONWORKS ®

LMAP

Lighting

Elevator
CONTROLLER

Communication items at LONWORKS ®


and M-NET Adapter LMAP03U
On/Off On/Off
Mode Mode
Set point from network (Set temp.) Set point from network (Set temp.)
Fan speed Fan speed

Thermo On/Off
State Indoor temperature
Operation Monitoring Alarm signal

Prohibit local On/Off Prohibit local On/Off


Prohibit local Mode Prohibit local Mode
Prohibit local Set temp. Prohibit local Set temp.

Batch Off

CNTR-62 CONTROLLER (Feb. 2009)


&C=>18<18:>1/:9><:771<
3. SYSTEM CONTROLLER
-.
DATA U4

DL?HEDC;DJIF;9?<?97J?ED

"J;C ;I9H?FJ?ED

EDD;9J;:GK?FC;DJ &"-,.",!"%-+" &KBJ?FB;IFB?JJOF;7?H9ED:?J?ED;HI "-2&.%-" ®


,FB?JJOF;7?H9ED:?J?ED;HI &H ,%"& ®
!;7JH;9EL;HOL;DJ?B7JEHI %(,,'2®
 EH:;J7?BIE<J>;9EDD;9J78B;CE:;BIFB;7I;9EDJ79JJ>;:;7B;H 
'KC8;HE<.D?JI (Including LOSSNAY®)
%&)97D9EDJHEB ?D:EEHKD?JI?D9BK:?D=%(,,'2
';KHED!") -&)'   &!P
';JMEHA-H7DI9;?L;H -- H;;-EFEBE=OA8FI
L;H7=;9ECCKD?97J?ED97F79?JO ?DFKJI
I;9ED:
);H<EHC7D9;
);7A9ECCKD?97J?ED97F79?JO  ?DFKJI
I;9ED:<EHED;I;9ED:
->;FHEF;H9ECCKD?97J?ED?IDEJE8J7?D78B;M>;D9ECCKD?97J?ED?DJ;HL7BI;N9;;:?JIF;H<EHC7D9;7IIKH;IK<<?9?;DJ?DJ;HL7BI
$,;HL?9;?IH;9ECC;D:;:<EHJ>;D;JMEHAI;HL?9;
;J7?B;:IF;9?<?97J?EDI<EHJ>;%('0(+$,D;JMEHA97D8;<EKD:?DZ-- H;;-EFEBE=O-H7DI9;?L;H.I;HI K?:;Z8O9>;BEDEHFEH7J?ED

 # (!1>A:<6)-<5-.71=

';JMEHA/7H?78B;I

+;GK;IJ(D
(<< DL D DL?(D(<<6D DL D DLE(D(<<6D (D
(<<IJ7J;

+;GK;IJ&E:; DLD DL?&E:;6D DLD DLE&E:;6D &E:;IJ7J;

,;JFE?DJ<HECD;JMEHA ,;JFE?DJIJ7J;
DLD DL?,;J)E?DJ6D DLD DLE,;J)E?DJ6D
I;JJ;CF  I;JJ;CF 

+;GK;IJ7DIF;;: DLD DL?7D,F;;:6D DLD DLE7D,F;;:6D 7D,F;;:IJ7J;

DL D DLE->;HCE6D ->;HCE(D
(<<IJ7J;

DL D DLE,F79;-;CF6D "D:EEH-;CF;H7JKH;IJ7J;

DL D DLEB7HC6D B7HCI?=D7B

+;GK;IJFHE>?8?J DL D DL?)HE(D(<<6D DL D DLE)HE(D(<<6D )HE>?8?JBE97B DEJ;


DEJ; BE97B(D
(<< (D
(<<IJ7J;

+;GK;IJFHE>?8?J DL D DL?)HE&E:;6D DL D DL?)HE&E:;6D )HE>?8?JBE97B DEJ;


DEJ; BE97B&E:; &E:;IJ7J;

+;GK;IJFHE>?8?J DL D DL?)HE,;J)E?DJ6D )HE>?8?JBE97B


DEJ; BE97B,;JFE?DJ DL D DL?)HE,;J)E?DJ6D ,;JFE?DJIJ7J; DEJ;

CONTROLLER
DEJ; ->;97I;E<"-2&.%-"®-&?I?D:?97J;:
DEJ; ->;H;?I797I;M>?9>97DDEJ8;KI;:M?J>J>;IOIJ;C9ED<?=KH7J?EDE<J>;7?H9ED:?J?ED;HIKD?JI
DEJ;ZDZE<J>;D;JMEHAL7H?78B;I>EMI?D:EEHKD?J7::H;II&'-
DEJ;"J?IFEII?8B;JEKI;M>;DJ>;Z&ZH;CEJ;9EDJHEBB;H

NJ;HD7B:?C;DI?ED


 45
.D?JCC4?D 5
 

 45  45

 45



 45



"J;C ;I9H?FJ?ED
 !N 0N 
?C;DI?EDI
4  
!N 
0N 
 5
';J0;?=>J  A=
B8
)EM;H,EKH9; Q   / !P
KHH;DJEDIKCFJ?ED  C&7N?CKC
 45
 

 45



(F;H7J?D=+7D=;
(F;H7J?ED -;CF;H7JKH;
,JEH7=;+7D=;
DL?HEDC;DJ
!KC?:?JO  JE+!'E9ED:;DI7J?ED
"DIJ7BB7J?EDDL?HEDC;DJ "DJ>;9EDJHEB8EN

;J7?BE<I;9J?ED
 45


45



+
 45




4 

 5

('-+(%%+
CONTROLLER (Feb. 2009) DJH
CNTR-63
3. SYSTEM CONTROLLER DATA U4

3-16. DIDO controller [PAC-YG66DCA]


The DIDO controller is used in combination with a(n) AG-150A/G(B)-50A/GB-24A to operate general-purpose equipment, as well as to
monitor operating and error status. It is equipped with two sets of standard terminal s (Channels 1 and 2), and four sets of expansion
connectors for the input/output terminals. Expansion cable is optional.
Other devices can only be controlled from AG-150A, AG-150A/G(B)-50A/GB-24A Web browser and TG-2000A. Operation cannot be
monitored or performed from the G-50A LCD.
In addition, this device includes a function that interlocks M-NET devices such as indoor units, general equipment, etc.

External Dimensions

26 (11/32)
111 (43/8)

200 (77/8) 45 (125/32)


150 (529/32)
52 (21/16) 46.5 (127/32) 4.5 9 (3/8)
(3/16)

DIDO controller
PAC-YG66DCA

[ OUTPUT ] Transistor Output 24 VDC [ OUTPUT ] Non-voltage Contact Output


[ Junction Terminal ] Ch1 Ch2 Ch1 Ch2
ON/OFF,(ON) (OFF) ON/OFF,(ON) (OFF) ON/OFF,(ON) (OFF) ON/OFF,(ON) (OFF)

[ Output LEDs ]
Ch1 Ch2
ON/OFF (OFF) ON/OFF (OFF)
(ON) (ON)
107.6 (41/4)

110 (411/32)
N623

120 (43/4)
DIDO controller
MODEL
PAC-YG66DCA
SERVICE REF. PAC-YG66MCA-J
INPUT VOLTAGE DC24V;0.2A
This device complies with Part15 of the FCC Rules.Operation is
WEIGHT 0.6 kg / 13/ 8 lb
subject to the following two conditions: (1)this device may not cause
SERIAL No.
harmful interference, and (2)this device must accept any interference
received, including interference that may cause undesired operation. MADE IN JAPAN

[ INPUT ] [ 24 VDC Power Supply]


[ Expansion I/O ]
Ch1 Ch2
Ch5,Ch6 Ch3,Ch4 ON/OFF Error ON/OFF Error

26 (11/32) 83.5 (35/16) 27 (13/32)

Unit: mm (in)
26 (11/32)
15 (19/32)
CONTROLLER

Usage Restrictions
>,768%,6+,/(&75,&'2(61277$.(),1$1&,$/5(63216,%,/,7<)25'$0$*(6&$86('%<,668(6%(<21'285&21752/25
special circumstances (predicable or unpredictable); and secondary or accidental damages, and damages to
other objects. We also do not take financial responsibility for opportunities lost as a result of device failure, or
electrical power failure at the end-user site.
CAUTION Mitsubishi Electric does not take financial responsibility caused by end-users' requests including, but not
limited to, device testing, startup, readjustment, and replacement.
>212786(7+,6'(9,&(,1',6$67(535(9(17,216(&85,7y, or "critical to life" applications.
>It is recommended to provide an external switch for general-purpose equipment in case of a failure of the
DIDO controller or a peripheral part.

CNTR-64 CONTROLLER (Feb. 2009)


3. SYSTEM CONTROLLER DATA U4

3-16-1. Specifications

3-16-1-1. Device Specifications

Item Rating and Specification


Screw terminal block
Power Supply 24 VDC 10%: 5 W (*1) (M3) (*8)
Screw terminal block
M-NET communication 17 to 30 VDC (*2)
(M3) (*8)
Applied load
MAX: 24 VDC, 5 W
Non-voltage Relay contact (2) MIN: 5 VDC, 2 mW Screw terminal block
ON/OFF, (M3.5) (*8)
(ON) * AC loads cannot be
(*4) connected.

Transistor (2) 24 VDC 40 mA or less Screwless terminal


Output (*5) block
Standard

(*3) Applied load


MAX: 24 VDC, 5 W
Non-voltage Relay contact (2) MIN: 5 VDC, 2 mW Screw terminal block
(OFF) * AC loads cannot be (M3.5) (*8)
(*4) connected.
Interface 24 VDC 40 mA or less Screwless terminal
Transistor (2) (*5) block
ON/OFF Non-voltage a contact 24 VDC 1 mA or less Screwless terminal
Input (2 each) (*6) block
Error/Normal
ON/OFF, (ON)
24 VDC 40 mA or less
Expansion

Output (*4) Transistor (4 each) 9 pin connector


(*5)
(OFF) (*4)
ON/OFF 24 VDC 1 mA or less
Input 24 VDC input (4 each) 9 pin connector
Error/Normal (*7)

1s 30 ms
Output Pulse Width 1s 30 ms

Interlock
Function Interlock M-NET devices and output contacts according to status of input contacts. (*8)

Operating temperature range 0 to 40 [32 to 104 ]


Environment Temperature
Conditions Storage temperature range -20 to 60 [-4 to 140 ]

CONTROLLER
Humidity 30 to 90%RH (no condensation)
Dimensions 200 (W) × 120 (H) × 45 (D) mm / 77/8 (W) × 43/4 (H) × 125/32 (D) in
Weight 0.6 kg / 13/8 lb
Time Backup
In the event of power failure or shut-off, the internal capacitor will continue to track time for approximately one week.
During Power
(The internal capacitor takes about 24 hours to fully charge; a replacement battery is not necessary.)
Failure
Installation Inside a control panel (indoors)
Environment * Use this product in a hotel, a business office environment or similar environment.

*1: For details, refer to "3-16-1-2. Parts Purchased Separately".


*2: Supply electric power from a power unit for the transmission line or an outdoor unit.
Furthermore, the power consumption factor of the M-NET circuitry of this device is "1/4" (equivalent to one ME Remote Controller).
*3: Non-voltage Relay contact or transistor is available for output. Only one can be used at a time.
*4: ( ) is in the case of a pulse.
*5: The output is open collector type. Power must be supplied from an external power source to the output circuit of this device.
*6: Power is supplied from this device to the external contacts.
*7: Power must be supplied from an external power source.
*8: M3 and M3.5 are sizes of the screw on the terminal block (ISO metric screw thread).
The number indicates the screw diameter (mm).

CONTROLLER (Feb. 2009) CNTR-65


3. SYSTEM CONTROLLER DATA U4

3-16-1. Specifications

3-16-1-1. Device Specifications

Centralized control line


Power supply unit
PAC-SC51KUA
M-NET M-NET Indoor control line

DIDO controller 24 VDC


LAN
CENTRALIZED CONTROLLER AG-150A

AG-150A Power supply


or G(B)-50A *1 CITY MULTI
(a) (b) (c) (d)

Ventilation fan,
lighting, etc. × up to 6 units

DIDO control
24 VDC
(a) (b) Power supply
(c) (d)

Ventilation fan, (a) ON/OFF, (ON) output


AG-150A/G(B)-50A lighting, etc. × up to 6 units
Web or TG-2000A*2 (b) (OFF) output
(c) ON/OFF input
(d) Error/Normal input
* This figure omits the power supply line and only shows the transmission line.
Standard: Terminal block (for 2 units)
>6(49054544,*:589-58 ;40:9)
*1: The DIDO controller can be connected to G(B)-50A with Ver.3.20 or later.
Total: 6 units
*2: The DIDO controller can be connected to TG-2000A with Ver.5.10 or later.
<Restrictions>
Maximum of 50 units (50 channels) per AG-150A/G(B)-50A, 24 units (24 channels) per GB-24A.
However, the number of units that can be connected to a(n) AG-150A/G(B)-50A is up to 50 (24 for the GB-24A) including the number of
contacts used on this device, an indoor unit, LOSSNAY unit, etc.
Up to 6 contacts can be connected to the DIDO controller (1 M-NET address per contact). One contact connected to this device is
calculated as the equivalent of one indoor unit connected to AG-150A/G(B)-50A/GB-24A.
For example, 5 contacts connected to the DIDO controller are calculated as the equivalent of 5 indoor units connected to
AG-150A/G(B)-50A.

A58:/,9/0,2+.85;4+5-:/,#*,4:8(20@,+*54:852204,;9,904.2,6504:.85;4+04.(::/,65wer unit for


the transmission line.
CONTROLLER

However, when supplying electric power to the M-NET*,4:8(20@,+*54:852204,-853:/,!


A series outdoor
unit without using a power supply unit for the transmission line, use single-point grounding at the TB7 of that
outdoor unit.
Furthermore, when connecting this device to the M-NET indoor control line, use grounding at the TB3 for each
outdoor unit system.
A-:/,#:8(493099054204,5-:/09+,<0*,09*544,*:,+:5:/,#0ndoor control line and the outdoor
NOTE unit is down because, for example, the power supply is interrupted for servicing or there is a failure, the DIDO
controller cannot be controlled from the system controller.
A54:852204.:/,9?stem remote controller, ON/OFF remote controller, and schedule timer is only possible with
channel 1 of a standard terminal block.
A *54:8522,8*(4542? be monitored or performed from AG-150A, AG-150A/G(B)-50A/GB-24A Web
browser, and TG-2000A. Operation cannot be monitored or performed from the G-50A 
AWhen AG-150A/G(B)-50A/GB-24A is connected, monitoring control can only be performed from AG-150A,
AG-150A/G(B)-50A/GB-24A Web or TG-2000A. Monitoring control cannot be performed from the system
remote controller (ON/OFF remote controller or schedule timer).

CNTR-66 CONTROLLER (Feb. 2009)


3. SYSTEM CONTROLLER DATA U4

3-16-1. Specifications

3-16-1-2. Parts Purchased Separately

Prepare the following parts to install this device.

Required Part Specification


Unit fixing screws M4 screw 4 (*M4: ISO metric screw thread)
Commercially available power source: 24 VDC 10% 0.2 A (Minimum loading), SELV circuit, power line with
grounding terminal
Ripple noise: Lower than 200 mVp-p
Compatible specification
Authorized or CE marked products
Subject to regulations: - IEC60950 (or EN60950)
Power supply for this
- CISPR22/24 (or EN55022/24)
device
- IEC61000-3-2/3-3 (or EN61000-3-2/3-3)
When using transistor output (including extension output) for the 24 VDC output of this device, increase
the capacity to match the number used.
G1 set used: 0.3 ADC (Minimum) G2 sets used: 0.4 ADC (Minimum) G 3 sets used: 0.5 ADC (Minimum)
G4 sets used: 0.6 ADC (Minimum) G5 sets used: 0.7 ADC (Minimum) G 6 sets used: 0.8 ADC (Minimum)
* The increase of the power supply capacity is 0.1 ADC for every set.
Power line Use a sheathed vinyl cord or cable. At least 0.75 mm2 (AWG18)
Type of the cable: Sheathed vinyl cords or cable which comply with the following specifications or
equivalent.
G"' 1.2 mm to 88G''$ 882 to 2 mm2 (AWG 16)
M-NET transmission * CPEV: PE insulated PVC jacketed shielded communication cable
line * CVVS: PVC insulated PVC jacketed shielded control cable
PE: Polyethylene PVC: Polyvinyl choloride
Power needs to be supplied to the M-NET circuitry of this device. Use an outdoor unit or a separately
purchased power supply unit for the transmission line.
Use electric wire of an appropriate size for the terminal block of this device.
Electric wire size ···· (1) Solid wire: 0.65 mm (AWG21) - 1.2 mm (AWG16)
Signal lines (2) Stranded wire: 0.75 mm2 (AWG18) - 1.25 mm2 (AWG16)
Single strand: At least 0.18 mm
To use an expansion input/output, use a separa tely purchased external input/output adapter.
[Parts to be Purchased Separately]
Name Model Application Remark

CONTROLLER
This is not required when power is to be
PAC-SC50KUA Power supply to the M-NET transmission line
supplied from an outdoor unit.
Power supply unit
This is not required when power is to be
PAC-SC51KUA Power supply to the M-NET transmission line
supplied from an outdoor unit.

Connection adapter for using an expansion This is required when an expansion input/
External I/O adapter PAC-YG10HA
input/output output is used.
[Commercially available parts]
Name Application Remark
External 24 VDC Supplies power when to use the DIDO controller or Refer to "Power supply for this device" in "Required
power source transistor output. Part" above for the power supply capacity.
Requires commercially available relay device
Relay device depending on the electric specifications with an
external device.

CONTROLLER (Feb. 2009) CNTR-67


3. SYSTEM CONTROLLER DATA U4

3-16-3. Interlock control

The DIDO controller (PAC-YG66DCA) has an interlock control function, which enables operation or set temperature change on the
M-NET devices such as indoor units and also enables signal output to the contacts on the DIDO controller.
Interlock control covers the units connected to the DIDO controller with M-NET system. AG-150A/G(B)-50A/GB-24A must be connected
to use the function. Ask your dealer for interlock control setting. The setting requires special tool support.

Before using the interlock control, you must agree to the following.
1.This feature must not be used for disaster prevention or security purpose.
(Not designed to be used in situations that are life-threatening)
2.No functions must be added that allow the malfunctioning unit to run by defeating the safety features, such as
an external ON/OFF switch or a short-circuit.
CAUTION 3.Those settings for the function that are not supported by the interlocked units must not be made. All the
settings must be made within the specified range.
(Failure to observe these precautions may result in malfunctions and failures.)
4.Perform a test run for interlock control, and confirm the correct settings and normal operation.
5.The system must be configured in the way that integrates the operation of the interlocked fire and emergency
control systems.

Item Content Remarks


Number of events 24 events 1 event interlock with 1 unit
Determinant condition for At input contact change 7-#/1',+'+-21
interlock control 7//,/'+-21//,/,/*)
Interlock control contents 1 action for 1 condition ,2$0*-") "-,20-* "-4$01 2'$ 3,(21 "-,,$"2$# 2-
(to be output) 7F operation of indoor units "-,20-**$01wi2'1712$+
7-#/1',+*,"#!&+%#,$'+",,/2+'1s 
7Temperature setting of indoor units 
"-,20-**$0(21$*%-0-2'$0"-,20-**$01
8-,2 "2-32.322-"-,20-**$0
 (,2'$1 +$1712$+
2'$0 ,2$0*-")"-,20-*.0-'(!(2(-,%3,"2(-,(1 
$, !*$# 2$+$0&$,"712-.%0-+
 
   A



 CENTRALIZED CONTROLLER AG-150A

Indoor unit
AG-150A Operation ON/OFF
CONTROLLER


Outdoor unit

 Interlock with M-NET devices

 DIDO Controller Lights


 ON/OFF
Interlock with contact output

Card key
 ON/OFF


,2$0*-")"-,20-*-%"-,20-**$0$6 +.*$

CNTR-68 CONTROLLER (Feb. 2009)


3. SYSTEM CONTROLLER DATA U4

3-17. AI controller [PAC-YG63MCA]


The AI controller measures temperature and humidity; it also has an alarm capability if the measurement data exceeds defined setpoints.
Historical measurement data can be displayed via only the AG-150A, AG-150/G(B)-50A/GB-24A Web browser and TG-2000A.
Temperature and humidity cannot be displayed on the G-50A LCD.
Furthermore, an alarm can be output if measurement data exceeds a preset upper or lower limit.
The AI controller also features a function that interlocks M-NET devices for indoor units, etc.

External Dimensions

(11/32)
26
46 (113/16)

200 (77/8) 45 (125/32)


150 (529/32) 9 (3/8)
4.5
(3/16)
Al controller
PAC-YG63MCA

[ OUTPUT ] Non-voltage Contact Output


Ch1 Ch2
Alarm Alarm

[ Output LEDs ]
Ch1 Ch2
Alarm Alarm

N623

110 (411/32)
120 (43/4)
Al controller
MODEL
PAC-YG63MCA
SERVICE REF. PAC-YG60MCA-J
INPUT VOLTAGE DC24V;0.2A
This device complies with Part15 of the FCC Rules.Operation is
WEIGHT 0.6 kg / 13/ 8 lb
subject to the following two conditions: (1)this device may not cause
SERIAL No.
harmful interference, and (2)this device must accept any interference
received, including interference that may cause undesired operation. MADE IN JAPAN

[ INPUT ]
[ 24 VDC Power Supply]
Ch1 Ch2
Pt100 4 to 20 mA / 1 to 5 V / 0 to 10 V 4 to 20 mA / 1 to 5 V / 0 to 10 V

26 (11/32) 83.5 (35/16) 27 (13/32)

(11/32) Unit: mm (in)


26
(19/32)
15

Usage Restrictions
9'213 '1&'*#!20'!"-#1,-22)#$',,!'*0#1.-,1' '*'27$-0"+%#1!31#" 7'113#1 #7-,"-30!-,20-*-0

CONTROLLER
special circumstances (predicable or unpredictable); and secondary or accidental damages, and damages to
other objects. We also do not take financial responsibility for opportunities lost as a result of device failure, or
CAUTION electrical power failure at the end-user site.
Mitsubishi Electric does not take financial responsibility caused by end-users' requests including, but not
limited to, device testing, startup, readjustment and replacement.
9-,-231#2&'1"#4'!#',"'112#0.0#4#,2'-,1#!30'27-0!0'2'!*2-*'$#..*'!2'-,1

CONTROLLER (Feb. 2009) CNTR-69


3. SYSTEM CONTROLLER DATA U4

3-17-1. Specifications

3-17-1-1. Device Specifications

Item Description
Power 24 VDC 10%: 5 W Screw terminal
Supply block (M3) (*5)
Screw terminal
M-NET communication 17 to 30 VDC (*1) block (M3) (*5)
Measurement Measurement External
Ch Sensor target range Measurement error connection method
0.3%FS 0.1 (0.18 )
Pt100 Temperature -30 to 60 (*3) Screwless terminal
(3-wire system) [-22 to 140 ] [at 25 (77 )] block (3 poles)
Ch1 4 to 20 mADC 0.5%FS 0.1 (0.18 )
Analog

Temperature/ (Set by system (*3) Screwless terminal


Input

Interface 1 to 5 VDC
humidity controller) 0.5%FS 0.1%RH block (2 poles)
0 to 10 VDC [at 25 (77 )]
4 to 20 mADC 0.5%FS 0.1 (0.18 )
Analog

Temperature/ (Set by system (*3) Screwless terminal


Ch2 1 to 5 VDC
humidity controller) 0.5%FS 0.1%RH block (2 poles)
(*2) 0 to 10 VDC [at 25 (77 )]
Applied load
Upper/lower limit
Output

MAX: 24 VDC, 5 W Screw terminal


alarm interlock output MIN: 5 VDC, 2 mW block (M3.5) (*5)
(non-voltage contact) * AC loads cannot be connected.
Interlock
Function Interlock M-NET devices according to measurement data values. (*4)
Operating temperature range 0 to 40 [32 to 104 ]
Environment Temperature
Storage temperature range -20 to 60 [-4 to 140 ]
Conditions
Humidity 30 to 90%RH (no condensation)
Dimensions 200 (W) × 120 (H) × 45 (D) mm / 77/8 (W) × 43/4 (H) × 125/32 (D) in
Weight 0.6 kg / 13/8 lb
Time Backup
During Power In the event of power failure or shut-off, the internal capacitor will continue to track time for approximately one week.
Failure (The internal capacitor takes about 24 hours to fully charge; a replacement battery is not necessary.)
Installation Inside a control panel (indoors)
Environment * Use this product in a hotel, a business office environment or similar environment.

*1: Supply electric power from a power supply unit for the transmission line or an outdoor unit. Furthermore, the power consumption
factor of the MNET circuitry of this unit is "1/4" (equivalent to one ME Remote Controller).
*2: Configure the dip switch settings for the analog input method to use.
*3: The measurement error for the system includes the measurement error for this unit, sensor, and wiring.
CONTROLLER

a%FS (full scale) = a% × ([measurement range's upper limit value] - [lower limit value])
*4: Settings for the interlock function are performed from the Maintenance Tool. For details, refer to the operation manual for the
Maintenance Tool.
*5: M3 and M3.5 are sizes of the screw on the terminal block (ISO metric screw thread). The number indicates the screw diameter
(mm).

CNTR-70 CONTROLLER (Feb. 2009)


3. SYSTEM CONTROLLER DATA U4

3-17-1. Specifications

3-17-1-1. Device Specifications

Centralized control line


Power supply unit
PAC-SC51KUA
M-NET M-NET Indoor control line
CENTRALIZED CONTROLLER AG-150A

TB7 TB3
AG-150A or 24 VDC Power
LAN AI controller Supply
or G(B)-50A *1
CITY MULTI
(3) (4)
(1) (2)
AI controller 24 VDC Power
Supply Temperature sensor, Upper/lower limit
humidity sensor, alarm interlock
AG-150A/ (3) (4) etc. devices, etc.
G(B)-50A Web (1) (2)
or TG-2000A *2
Temperature sensor, Upper/lower limit (1) Channel 1 temperature or humidity sensor input
humidity sensor, alarm interlock (2) Channel 2 temperature or humidity sensor input
etc. devices, etc. (3) Channel 1 upper/lower limit alarm output
(4) Channel 2 upper/lower limit alarm output
* This figure omits the power supply line and only shows the transmission line.

*1: The AI controller can be connected to G(B)-50A with Ver.3.20 or later.


*2: The AI controller can be connected to TG-2000A with Ver.5.10 or later.
<Restrictions>
Maximum of 50 units per AG-150A/ G(B)-50A, 24 units per GB-24A.
However, the number of units that can be connected to an AG-150A/G(B)-50A is up to 50 (to 24 with the GB-24A) including this device,
an indoor unit, LOSSNAY unit, etc.

=246-*5-.*/),4271)2+6-*"(*164&/.<*)(21642//.1*75*5.1,/*32.16,4271).1,&66-*32 wer unit for


the transmission line.
However, when supplying electric powe4626-*T (*164&/.<*)(21642//.1*+4206-*
A series outdoor
unit without using a power supply unit for the transmission line, use single-point grounding at the TB7 of that
outdoor unit.
746-*4024*9-*1(211*(6.1,6-*"64&150.55.21/.1*2+6-.5)*8.(*to6-*".1)224(21642//.1*
NOTE use grounding at the TB3 for each outdoor unit system.

CONTROLLER
=+6-*"64&150.55.21/.1*2+6-.5)*8.(*.5(211*(6*)62&1".1)224(21642//.1*&1)6-*276)224
unit is down because, for example, the power supply is interrupted for servicing or there is a failure, the AI
controller cannot be set and monitored from the system controller.
=The sensor connected to the AI controller can only be monitored from AG-150A, AG-150/G(B)-50A/GB-24A
Web browser and TG-2000A. The sensor cannot be monitored from the G-50A LCD.

CONTROLLER (Feb. 2009) CNTR-71


3. SYSTEM CONTROLLER DATA U4

3-17-1. Specifications

3-17-1-2. Parts Purchased Separately

Prepare the following parts to install this device.

Required Part Specification


Unit fixing screws M4 screw 4 (* M4: ISO metric screw thread)
Commercially available power source: 24 VDC 10% 0.2 A (Minimum loading), SELV circuit, power line with
grounding terminal
Ripple noise: Lower than 200 mVp-p
Power supply for this Compatible specification
device Authorized or CE marked products.
Subject to regulations: - IEC60950 (or EN60950)
- CISPR22/24 (or EN55022/24)
- IEC61000-3-2/3-3 (or EN61000-3-2/3-3)
A separate power supply for sensors may be required.
Power supply for
In the case of 24 VDC voltage, the capacity of the power supply for this unit can be increased so that the
sensors
power supply can be shared.
Use a sheathed vinyl cord or cable.
Power line
At least 0.75 mm2 (AWG18)
Type of the cable: Sheathed vinyl cords or cable which comply with the following specifications or
equivalent.
F"' 77>9 77F''$ 77>9 77WG 16)
M-NET transmission * CPEV: PE insulated PVC jacketed shielded communication cable
line * CVVS: PVC insulated PVC jacketed shielded control cable
PE: Polyethylene PVC: Polyvinyl chloride
Power needs to be supplied to the M-NET circuitry of this device. Use an outdoor unit or a separately
purchased power supply unit for the transmission line.
Shows the size of the electric wire (copper wire) that is adapted to the terminal block of this device. Refer
to the usage and cautionary items of the sensor when performing settings. However, use a line with shielded
Signal lines line.
(Sensor input lines) Electric wire size ···· (1)Solid wire: 0.65 mm (AWG21) - 1.2 mm (AWG16)
(2)Stranded wire: 0.75 mm (AWG18) - 1.25 mm (AWG16)
Single strand: At least 0.18 mm
[Parts to be Purchased Separately]
Name Model Application Remark
CONTROLLER

This is not required when power is to be


PAC-SC50KUA Power supply to the M-NET transmission line
supplied from an outdoor unit.
Power supply unit
This is not required when power is to be
PAC-SC51KUA Power supply to the M-NET transmission line
supplied from an outdoor unit.

[Commercially available parts]


Part Use Remark
External 24 VDC Supplies power to the AI controller. Refer to "Power supply for this device" and "Power
power source supply for sensors" in "Required Part" above for the
capacity of the power supply.
Sensor Measures temperature and humidity. Temperature sensor (PAC-SE40TSA) cannot be
connected.

CNTR-72 CONTROLLER (Feb. 2009)


3. SYSTEM CONTROLLER DATA U4

3-17-2. Interlock control

AI controller (PAC-YG63MCA) has an interlock control function, which enables operation or set temperature change on the M-NET devices
such as indoor units.
Interlock control covers the units connected to the AI controller with M-NET system. AG-150A/G(B)-50A /GB-24A must be connected to
use the function. Ask your dealer for interlock control setting. The setting requires special tool support.

Before using the interlock control, you must agree to the following.
1.This feature must not be used for disaster prevention or security purpose.
(Not designed to be used in situations that are life-threatening)
2.No functions must be added that allow the malfunctioning unit to run by defeating the safety features, such as
an external ON/OFF switch or a short-circuit.
CAUTION 3.Those settings for the function that are not supported by the interlocked units must not be made. All the
settings must be made within the specified range.
(Failure to observe these precautions may result in malfunctions and failures.)
4.Perform a test run for interlock control, and confirm the correct settings and normal operation.
5.The system must be configured in the way that integrates the operation of the interlocked fire and emergency
control systems.

Item Content Remarks


Number of events 24 events 1 event interlock with 1 unit
Determinant condition for Measurement value 75!##"'+%*#02/#*#+13)2#'+0#11'+%/+%#
interlock control Measurement interval is 1 to 7200 seconds. 75!##"'+%2--#/),4#/)'*'1)/*"#1#!1',+
value and cancellation value
Interlock control contents 1 action for 1 condition .4&2,/$+ $/.42/, $/6&23 4)& 5.*43 $/..&$4&% 4/
(to be output) 7FF operation of indoor units $/.42/,,&237*4)sy34&-
:0&2"4*/.-/%&$)".(&/'*.%//25.*43 
:&-0&2"452&3&44*.(/'*.%//25.*43
:/.4"$4/540544/$/.42/,,&2
4)&2 .4&2,/$+$/.42/,02/)*#*4*/.'5.$4*/.*3 
&."#,&%"4&-&2(&.$934/0'2/- /
  
A




!AG A

.%//25.*4 

CONTROLLER
AG  0&2"4*/.

54%//25.*4

 .4&2,/$+7*4)%&6*$&3
 //,*.(/0&2"4*/.7)&.4)&4&-0&2"452&*3
 /2"#/6&
/.42/,,&2 5./0&2"4*/.7)&.4)&4&-0&2"452&*3,/7&24)".



&-0&2"452&3&.3/2

.4&2,/$+$/.42/,/'$/.42/,,&2&8"-0,&

CONTROLLER (Feb. 2009) CNTR-73


3. SYSTEM CONTROLLER DATA U4

3-18. Transmission booster [PAC-SF46EPA]


The Outdoor unit supplies transmission power 30VDC for the indoor-outdoor transmission line at its connector TB3 and TB7.
The power is consumed by the Indoor unit, ME remote controller, Timers and System controllers.When the total quantity of
Indoor units, and ME remote controller, Timers and System controllers is over 40, or when transmission power supply is not
enough, the transmission booster PAC-SF46EPA should be designed into the air-conditioner system to ensure the system
communication.Indoor unit sized P72, 96 is counted as 2 units.

3-18-1. Designing PAC-SF46EPA into an air-conditioner system.


Taking the power consumption of Indoor unit sized P06-P54 as 1, the equivalent power consumption or supply of others are
listed at Table 3-18-1 and Table 3-18-2.

Table 3-18-1 The equivalent power consumption by Indoor units, LOSSNAY, controllers
Indoor Indoor unit BC controller MA RC. LOSSNAY ME Remote Contr. Timers, System Contr. ON/OFF Contr.

PAR-21MAA
Sized P06-P54 Sized P72-P96 CMB PAR-F27MEA-US PAC-SF44SRA GB-50A PAC-YT40ANRA
PAC-YT51CRB
PZ-52SF PAC-YT34STA GB-24A
PAR-FA32MA
LGH-RX-E G-50A
PZ-41SLB AG-150A
1 2 2 0 1/4 1/2 3 1
*RC : Remote Controller

Table 3-18-2 The equivalent power supply of Trans. Booster, Power supply unit, Connector TB3, TB7 of Outdoor unit.
Transmission Booster Power supply unit Outdoor unit Outdoor unit
PAC-SF46EPA PAC-SC50KUA PAC-SC51KUA Connector TB3 and TB7 total * Connector TB7 only
25 6 5 32 6
*If PAC-SC50KUA or PAC-SC51KUA is used to supply power at TB7 side, no power supply need from Outdoor unit at TB7, Connector TB3 itself will therefore have 32.

Transmission booster PAC-SF46EPA has equivalent transmission power 25.

With the equivalent power consumption values in Table 3-18-1 and Table 3-18-2, PAC-SF46EPA can be designed into the air-
conditioner system to ensure proper system communication according to 3-18-1-A, B, C.

3-18-1-A) Firstly, count from TB3 at TB3 side the total quantity of Indoor units and ME remote controller, Timers and System
controllers.If the total quantity reaches 40, a PAC-SF46EPA should be set.In this case, Indoor unit sized P72, 96
is counted as 2 Indoor units, but MA remote controller(s), LOSSNAY is NOT counted.

3-18-1-B) Secondly, count from TB7 side to TB3 side the total transmission power consumption. If the total power consumption
CONTROLLER

reaches 32, a PAC-SF46EPA should be set.Yet, if a PAC-SC50KUA or PAC-SC51KUA is used to supply power at TB7
side, count from TB3 side only.

3-18-1-C) Thirdly, count from TB7 at TB7 side the total transmission power consumption, If the total power consumption reach-
es 6, a PAC-SF46EPA should be set.

External dimension
Unit:mm [in.]
360[14-3/16]
240[9-15/32]

UP
165[6-1/2]
300[11-13/16]

340[13-13/32]
160[6-5/16]

CNTR-74 CONTROLLER (Feb. 2009)


4. SYSTEM COMPONENT DATA U4

In a multi air conditioner system that is a free plan direct-expansion type, a connector for inputting and outputting signals
to/from the outside is fitted as standard on the control board of the indoor and outdoor units. Use this when you want
each unit to input/output signals individually. (Note: When there are many control units it is recommended that you use
MELANS. This would enable you to save on labor.) In order to have an input output signal from each connector, you must
have a dedicated adapter (sold separately) and a relay circuit (on-site arrangements).
Note : See next page for actual examples of use.

Types of control that uses connectors for the outdoor unit / water-source unit input output signal
(connection for each type of option).
Connector
Category Application Function
Y, WY R2, WR2
Method of disabling cool and heat operation (thermo Comp ON/OFF CN3D
CN3D
off) by input from the outside to the outdoor unit.
The low noise operation of the indoor unit can be
commenced by the external input to the outdoor
unit (water-source unit).
Night mode CN3D CN3D
(The night mode can be adapted only under

Input less f or heating)


You can switch the operation mode between cooling
and heating by input from the outside to the outdoor Autochangeover CN3N
unit.
Forces the heat source unit to stop operation by Pump Interlock
TB8 TB8
receiving contact signals from the pump interlock signal input
(level) (W-Series) (W-Series)
circuit
Forces outdoor unit to perform a fan operation by Snow sensor CN3S CN3S
receiving signals from the snow sensor. (note 10) signal input (Y-Series) (R2-Series)
Compressor is
run state
Method of receiving a signal from the outdoor unit
CN51 CN51
(water-source unit) to the outside. Error state or
Output Can be used as a device that displays the oper- frost prevention
ation state. output (note 8)
Can be used as an interlocked control with ex-
ternal equipment. Operation ON
TB8 TB8

CONTROLLER
signal (note 9)

Types of control that uses connectors for the indoor unit input output signal (connection for each type of option)

Category Application Function Connector

Method of ON/OFF control by turning on and off switches or con- Distant/local


tacts from an outside to each indoor unit group. switching (note 1)
CN32
Input Can be used as a timer adapter (Note 1)
(Note 2,3) Can be used as a "forget to switch off prevention" or "forced stop". ON/OFF (level)

Method of ON/OFF control by inverting start/stop using external


ON/OFF (pulse) CN51
pulse (a-contact) for each indoor unit group.

Method of sending signals to outside for each indoor unit group. Operation state
CN51
It can be used as a device to display operation states. Error state
It can be used as an interlocked control with the external equip-
ment. Operation mode
(heat) state
Output
Operation mode CN52
(cool, dry) state
Thermo ON
(fan) state

CONTROLLER (Feb. 2009) CNTR-75


4. SYSTEM COMPONENT DATA U4

Note 1: Connect the signal input only to the principal unit in a group.
(However, the demand input is required to enter into indoor units individually.)
Note 2: When using star t/stop input at group operation, Local remote controller is necessary.
(MA remote controller or M-NET remote controller)
Note 3: When setting to Remote, operation can not be performed from Local remote controller.
The remote controller displa Y CONTR
Note 4: When using start/stop input at group oper utomatic address star ormed.
Note 5: When CN51 or CN52 is commonly used as an output signal, be sure to use the remote display kit.
Note 6: The remote display kit can be used for the input signal of CN51 and CN52.
Note 7: Connect to the pr ation mode (Heating/Cooling-
Dry) of signal output. mostat ON
(or f
Note 8: The error state of the heat source unit can be output when Dip SW3-3 is OFF.
When Dip SW3-3 is ON, the signal is output only when the heat source unit is stopped and the water
temperature (TH6) is 5°C[41°F] or lower.
Note 9: When Dip SW2-7 is OFF, the operation ON signal is output only when the compressor is in operation.
When Dip SW2-7 is ON, the signal is output when cooling or heating operation signal from the controller is
received. (The signal is kept active even if the compressor stops due to thermo OFF.)
Note 10: When multiple outdoor units exist in one refrigerant circuit, settings on every outdoor unit (signal input)
are required.
CONTROLLER

CNTR-76 CONTROLLER (Feb. 2009)


4. SYSTEM COMPONENT DATA U4

It is possible to have ON/OFF control by turning the indoor unit power on and off. You can select functions by set-
ting the DipSW1-9 and 1-10 on the indoor unit.
Types of ON/OFF control (indoor unit settings)
It is possible to have ON/OFF control for each indoor unit (or group) by dip switches 9 and 10 (SW1-9, SW1-10)
of the indoor unit.
Setting SW 2 (note 1)
Function Operation when indoor unit recovers
9 10
All auto All indoor units will always restart regardless of the state that was be-
OFF ON
restart fore the power was turned off (POWER OFF) (after 5 minutes).
Auto Indoor units which are operated before the power was turned off
recovery (POWER OFF) will restart (after 5 minutes). ON OFF

Operation stays stopped regardless of the state that was before the
All OFF OFF OFF
power was turned off.

Note 1. The dip switch setting for all units in the indoor unit group is required.
Note 2. Do not cut-off the power to the outdoor unit. If you do, it will disconnect the power to the crank-
case heater of the outdoor unit and that could cause damage to the compressor.
Note 3. This cannot be applied to the power ON/OFF of the drain pump and humidifier equipment.

Description of when using distant/local switching (CN32)

SW1 SW2
State Remote controller display/operation
Local switching ON/OFF
OFF OFF Local / Permit The operation permit
It displays "CENTRALLY CONTROLLED", while
ON OFF Distant / Stop the state is distant.
It prohibits ON/OFF operation of remote
ON ON Distant / Operate controller.

System example
Outdoor unit

Outdoor unit
power supply

CONTROLLER
Indoor unit

Indoor unit
power supply Local
Switch remote
controller

When the power to the outdoor unit is cut-off for a long time, the crankcase heater for the compressor also stops. If the
compressor is started soon after the power is restored, there is a chance that a fault will occur in the compressor.
When using the above function, make sure the power to the outdoor units will not be cut-off.

Limitations to combining system controls

Control combining
Description Pulse ON/OFF Power ON/OFF Automatic recover
distant/local
1 Control combining distant/local CN32 1 1 1
2 Pulse ON/OFF CN51

3 HA ON/OFF (JEMA) CN51

4 Power ON/OFF -

5 Automatic recover -

1: Pulse ON/OFF, Power ON/OFF and automatic recover can only be used when the distant/local setting
(CN32) is set to local. Therefore, always avoid this function when combining control.

CONTROLLER (Feb. 2009) CNTR-77


4. SYSTEM COMPONENT DATA U4

4-1. Y-, R2-, S-Series


1) SW4-4: OFF (Compressor ON/OFF, Low sound mode)
CN3D 1-3P 2-level of on-Demand *1
Open 100%(No Demand)
Short-circuit 0%

CN3D 1-2P Low sound mode *2


Open OFF
Short-circuit ON
*1 When SW4-4 on the outdoor unit in one refrigerant circuit system is set to ON (4 levels or 8 levels or 12 levels of on- DEMAND), this function cannot be used.
*2 This function and the 4 levels or 8 levels on-DEMAND function can be used together. Input the order to CN3D 1-2P on the outdoor unit whose SW4-4 is set to OFF.
2) When SW4-4 on one outdoor unit in one refrigerant circuit system is set to ON (4 levels of on-DEMAND) (*3)
CN3D 1-2P
CN3D 1-3P Open Short-circuit
Open 100% (No DEMAND) 75%
Short-circuit 0% 50%
Note the following steps to be taken when using STEP DEMAND. If the demand settings are switched in the wrong order listed as the wrong
Example: When switching from 100% to 50% example above, the unit may go into thermo OFF mode.
The percentage of the DEMAND listed in the table above is an
Steps in DEMAND <WRONG> 100% NO
0% 50%
approximate value based on the compressor volume and does not
level setting <CORRECT> 100% OK
75% 50% necessarily correspond with the capacity.
This function and the Low sound mode function cannot be used together.
3) When SW4-4 on the two outdoor units in one refrigerant circuit system is set to ON (8 levels of on-DEMAND) (*3,*4)
8 levels of on-DEMAND No.2 CN3D
1-2P Open Short-circuit
No.1 CN3D 1-2P 1-3P Open Short-circuit Open Short-circuit
Open Open 100% (No DEMAND) 50% 88% 75%
Short-circuit 50% 0% 38% 25%
Short-circuit Open 88% 38% 75% 63%
Short-circuit 75% 25% 63% 50%
4) When SW4-4 on the all outdoor units in one refrigerant circuit system is set to ON (12 levels of on-DEMAND) (*4)
12 levels of No.2 CN3D 1-2P Open
on-DEMAND 1-3P Open Short-circuit
No.3 CN3D 1-2P Open Short-circuit Open Short-circuit
No.1 CN3D 1-2P 1-3P Open Short-circuit Open Short-circuit Open Short-circuit Open Short-circuit
Open Open 100% 67% 92% 84% 67% 34% 59% 50%
Short-circuit 67% 34% 59% 50% 34% 0% 25% 17%
Short-circuit Open 92% 59% 84% 75% 59% 25% 50% 42%
Short-circuit 84% 50% 75% 67% 50% 17% 42% 34%

12 levels of No.2 CN3D 1-2P Short-circuit


on-DEMAND 1-3P Open Short-circuit
CONTROLLER

No.3 CN3D 1-2P Open Short-circuit Open Short-circuit


No.1 CN3D 1-2P 1-3P Open Short-circuit Open Short-circuit Open Short-circuit Open Short-circuit
Open Open 92% 59% 84% 75% 84% 50% 75% 67%
Short-circuit 59% 25% 50% 42% 50% 17% 42% 34%
Short-circuit Open 84% 50% 75% 67% 75% 42% 67% 59%
Short-circuit 75% 42% 67% 59% 67% 34% 59% 50%
*3 Input the order to CN3D on the outdoor unit whose SW4-4 is set to ON.
*4 CN3D of No. 1, 2, 3 can be selected arbitrary with the outdoor unit whose SW4-4 is set to ON.

CNTR-78 CONTROLLER (Feb. 2009)


4. SYSTEM COMPONENT DATA U4

4-2. Outdoor unit input/output connector (Y-, R2-, S-Series)


1.Wiring should be covered by insulation tube with supplementary insulation.
Caution: 2.Use relays or switches with IEC or equivalent standard.
3.The electric strength between accessible parts and control circuit should have 2750V or more.

4-2-1. Output
=!7'7+ 
Distant control
board Relay circuit Adapter *1 Outdoor unit L1 : Outdoor unit error display lamp
L1 X control board L2 : Compressor operation lamp (compressor running state)
Lamp power source

Y X, Y : Relay (coil =<0.9W : 12VDC)


X Y 5 CN51
L2 4
*1. Optional part : PAC-725AD or field supply.
3

Preparations
in the field Maximum cable
length is 10m

4-2-2. Input
Y-, R2-Series
 !7+4*+1'2*'2*!/0+2713*+ (2) Silent mode (Night mode)
(Night mode) (CN3D) (CN3D + DipSW4-4 OFF)
Outdoor unit
For details, refer to "Table 4-1". Relay circuit Adapter *2 control board
Outdoor unit
Relay circuit Adapter *2 control board CN3D
X 1
CN3D 2
X 1
2 3
Y 3
Preparations
Preparations in the field
in the field Maximum cable
Maximum cable length is 10m
X : Relay Contact rating voltage >= 15VDC
length is 10m Contact rating current >= 0.1A
%!/0+2713*+35*+1'2* Minimum applicable load =< 1mA at DC
Y : Demand *2. Optional part : PAC-715AD or field supply.
X,Y : Relay Contact rating voltage >= 15VDC
Contact rating current >= 0.1A Silent mode : The sound pressure level is reduced by controlling
Minimum appicable load =< 1mA at DC (Night mode) the maximum fan frequency and compressor frequency.
*2. Optional part : PAC-715AD or field supply.

CONTROLLER
-Note-
The sound pressure level cannot be reduced, when neither
the fan frequency nor the compressor frequency are maximum.

(3) System changeover (CN3N)


!23:6+2635 !
Relay circuit Adapter *2 Outdoor unit
control board Outdoor unit
Relay circuit Adapter *2 control board
X 1 CN3N
2 CN3S
X 1
Y 3 2
3

Preparations Preparations
in the field Maximum cable
in the field
length is 10m
Maximum cable
X : Cooling / Heating
length is 10m
Y : Validity / Invalidity of X
X : Relay Contact rating voltage >= 15VDC
X,Y : Relay Contact rating voltage >= 15VDC
Contact rating current >= 0.1A Contact rating current >= 0.1A
Minimum applicable load =< 1mA at DC Minimum applicable load =< 1mA at DC
*2. Optional part : PAC-715AD or field supply. *2. Optional part : PAC-715AD or field supply.
!23:6+2635The outdoor fan runs when X is closed
X in stop mode or thermostat mode.
OFF ON
OFF Normal
Y
ON Cooling Heating

CONTROLLER (Feb. 2009) CNTR-79


4. SYSTEM COMPONENT DATA U4

S-Series
(1) Step demand and Silent mode (Night mode) (CN3D) (2) Silent mode (Night mode) (CN3D + DipSW8-1 OFF)
Outdoor unit Outdoor unit
Relay circuit Adapter *2 control board Relay circuit Adapter *2 control board

CN3D CN3D
X 1 X 1
2 2
Y 3 3

Preparations Preparations
in the field in the field
Maximum cable Maximum cable
length is 10m length is 10m
X,Y : Relay Contact rating voltage >= 15VDC X : Relay Contact rating voltage >= 15VDC
Contact rating current >= 0.1A Contact rating current >= 0.1A
Minimum appicable load =< 1mA at DC Minimum applicable load =< 1mA at DC
*2. Optional part : PAC715AD or field supply. *2. Optional part : PAC-715AD or field supply.
DipSW8-1 ON (Step demand only)
Silent mode : The sound pressure level is reduced by controlling
X (Night mode) the maximum fan frequency and compressor frequency.
OFF ON -Note-
OFF 100% 75% The sound pressure level cannot be reduced, when neither the
Y fan frequency nor the compressor frequency are maximum.
ON 0% 50%
*They are rough values.
DipSW8-1 OFF (Compressor ON/OFF and Silent mode [Night mode)

Compressor
Y ON/OFF X Low noise mode

OPEN ON OPEN OFF


SHORT OFF SHORT ON

(3) System changeover (CN3N)

Relay circuit Adapter *2


Outdoor unit
control board
X 1 CN3N
2

Y 3

Preparations
CONTROLLER

in the field Maximum cable


length is 10m
SW1 : Cooling / Heating
SW2 : Validity / Invalidity of X
X, Y : Relay Contact rating voltage >= 15VDC
Contact rating current >= 0.1A
Minimum applicable load =< 1mA at DC
*2. Optional part : PAC-715AD or field supply.
X
OFF ON
OFF Normal
Y
ON Cooling Heating

CNTR-80 CONTROLLER (Feb. 2009)


4. SYSTEM COMPONENT DATA U4

4-3. Indoor unit “-E” type input/output connector (Y-, R2-, S-Series)
1.Wiring should be covered by insulation tube with supplementary insulation.
Caution: 2.Use relays or switches with IEC or equivalent standard.
3.The electric strength between accessible parts and control circuit should have 2750V or more.

ON/OFF (Pulse) input specification


Item Description
Input signal Pulse sign (a connect)

Standard of pulse

200msec or more

Input Output

CN51 CN52
Distant control board Relay circuit Adapter 1 Distant control board Relay circuit Adapter 1 Indoor unit
Indoor unit
control board
control board 1
SW 1
Power supply Power supply
X L1 CN52
of relay X 2 CN51 of relay X Z Y X
2
L2
3 Y
3
L1
Y Z Y L3
4 Z 4
L2
Z 5

Maximum cable
Maximum cable length is 10m[32ft.]
L1 : Status lamp
SW : Distant ON/OFF switch length is 10m[32ft.] Fan motor output (SW1-5 OFF)
L1 : Status lamp Every time the SW is pushed Thermostat ON (SW1-5 ON)
L2 : Error lamp (the pulse is inputted), it L2 : Cooling/Dry status lamp
X : Relay (a point of contact, fixed DC1mA) reacts against ON/OFF. L3 : Heating status lamp
Y, Z : Relay Contact rating voltage >= 15VDC X, Y, Z : Relay (Coil with fixed 12VDC, a power consumption of 0.9W or less)
Contact rating current >= 0.1A
Minimum applicable load =< 1mA at DC

CN32
Distant control board Relay circuit Adapter 2 Indoor unit
control board
1
Power supply CN32

CONTROLLER
X Y
of relay
SW1 X 2

SW2 Y 3

Maximum cable
length is 10m[32ft.]
SW1 : Distant/Local switching SW2 is available when SW1
SW2 : ON/OFF switch is ON.
X, Y : Relay Contact rating voltage >= 15VDC
Contact rating current >= 0.1A
Minimum applicable load =< 1mA at DC

CN52
Distant control board Relay circuit Adapter 1 Indoor unit
control board

Power supply 1
CN52
of relay
X

SW1 X 5

Maximum cable
length is 10m[32ft.]
SW1 : Demand switch
X : Relay (coil <=0.9W,12VDC)

SW1 Indoor unit


ON Forced thermo-OFF
1. Optional part : PAC-725AD or field supply
OFF Normal running 2. Optional part : PAC-715AD or field supply

CONTROLLER (Feb. 2009) CNTR-81